Inspector: Steven Waterman
NACHI #06092992

Sample Single Family

Client(s):  R&P K
Property address: 
Paradise, Ca. 95969
Inspection date:  Thursday, September 13, 2018

This report published on Friday, October 19, 2018 4:24:01 PM PDT

NOTE:

The findings and recommendations contained in this report are based on the newest and most up to date construction and safety standards in the industry. Some deficiencies may not have been recognized as such at the time the structure was built or remodeled. Other deficiencies are aimed at energy efficiency or air quality, and are not required building restrictions or practices.

Look 1st Inspections LLC is not a specialist in code compliance or zoning restrictions, and no part of the report should be considered as required repair and/or replacement.


This report will be available for viewing for 120 days from date of publication. For viewing after 120 days please contact Look 1st Inspections LLC.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeEnergy EfficiencyCorrection will likely save on energy costs
Concern typeCommentFor your information
Concern typeDamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating
Cooling / Heat Pump
Fireplaces / Stoves / Chimneys
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas

View summary

General Information
Table of contents
Report number: 2238
Time started: 9:35 am
Time finished: 12:10 pm
Client present for discussion at end of inspection: No
Weather conditions: Clear
Temperature: Warm
Ground condition: Dry
Type of building: Single family
Age of building(s): 30 years
Source for building age: Property listing
Front of building faces: North
1) Some wall and floor surfaces were obscured by furniture and/or stored items and couldn't be fully evaluated.
Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wood
Condition of retaining walls: Required repairs, replacement and/or evaluation (see comments below)
Retaining wall material: Wood
Site profile: Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete, Paving stones
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Condition of guardrails: Appeared serviceable
Deck, porch and/or balcony material: Composite
Condition of exterior stairs: Appeared serviceable
Condition of handrails: Appeared serviceable
Exterior stair material: Composite
2) DamageWood in one or more retaining walls were rotten or damaged by wood destroying insects. A qualified person should evaluate and repair or replace sections as necessary.
Photo
Photo 2-1 West side garage
Photo
Photo 2-2 West side garage
3) DamageOne or more wood spacers in the driveway were rotten or damaged by unspecified wood destroying insects. These spacers typically fill expansion joints that are meant to prevent the concrete slabs from breaking. Recommend replacing wood spacers as necessary with a rot and insect resistant material that compresses and expands, such as treated wood.
Photo
Photo 3-1 Driveway by front entry
4) Fences were damaged or deteriorated in some areas. A qualified person should repair or replace sections as necessary.
Photo
Photo 4-1 East side
5) Conducive conditionsFirewood was stored so that it was either in contact with the building or very close to it. This is a conducive condition for wood destroying insects. Recommend storing firewood outdoors in an open area, as far away from the building as practical, to keep away insects. For more information visit http://ohioline.osu.edu/hyg-fact/2000/2065.html
Photo
Photo 5-1 Deck
6) Minor cracks, settlement, heaving and/or deterioration were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Photo
Photo 6-1 Driveway
Exterior / Foundation
Table of contents
Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Foundation type: Crawlspace
Foundation material: Poured in place concrete
Footing material: Poured in place concrete
Anchor bolts for seismic reinforcement: Installed
Anchor bolts for seismic reinforcement were observed at: Crawl space
Condition of floor substructure: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of crawl space: Appeared serviceable
Crawl space inspection method: Traversed
Insulation material underneath floor above: Fiberglass roll or batt
Ventilation: Appears serviceable
Vapor barrier present: No
7) Conducive conditionsCaulk was missing at wall penetrations. A qualified person should repair or replace as necessary. For more information, visit:
http://www.reporthost.com/_docs/FPL_Caulking_Ins_Outs.pdf
Photo
Photo 7-1 NE corner
Roof / Attic
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Appeared serviceable
Roof type: Gable
Roof inspection method: Traversed
Condition of shingle and/or shake roof surface materials: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Condition of attic: Appeared serviceable
Attic inspection method: Traversed
Roof structure type: Rafters
Ceiling insulation material: Fiberglass loose fill, Fiberglass roll or batt
Ceiling insulation rating: R19 to R30
Vapor retarder: Installed
Roof ventilation: Appears serviceable
8) No weatherstrip was installed around the attic access hatch. Weatherstrip should be installed around the hatch to prevent heated interior air from entering attic. For more information, visit:
http://www.reporthost.com/_docs/atticaccess.pdf
Photo
Photo 8-1 Attic access
9) One or more downspouts or downspout extensions drained onto walkways. This may result in ice or moss forming on walkways, and may pose a fall hazard. Client(s) may wish to consider having a qualified person evaluate, and install or modify extensions as necessary or desired so rainwater isn't directed onto walkways.
Photo
Photo 9-1 NW corner garage
Garage / Carport
Table of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
Type: Attached
Condition of garage dwelling door: Required repair, replacement and/or evaluation (see comments below)
Type of garage dwelling door: Solid core
Condition of garage vehicle door(s): Appeared serviceable
Garage vehicle door type: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
10) The self-closing device on the garage-dwelling door needs adjustment repair or replacing. This door is intended to prevent vehicle fumes from entering living spaces and to slow the spread of fire from the garage to living spaces. A qualified person should evaluate and make repairs as necessary.
Photo
Photo 10-1 Garage dwelling door
11) No "photo eye" sensors were installed for one or more vehicle door's electric door opener. They've been required on all automatic door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit:
http://www.cpsc.gov/cpscpub/pubs/523.html
http://www.ohdstl.com/safety.html
Photo
Photo 11-1 
Photo
Photo 11-2 
Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120/240
Service amperage (amps): 200
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 200
System ground: Concrete encased electrode
Condition of main service panel: Appeared serviceable
Condition of sub: Appeared serviceable
Location of main service panel #A: Building exterior, NW corner garage
Location of sub panel #B: Garage interior
Branch circuit wiring type: Nonmetallic sheathed
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Solid strand aluminum branch circuit wiring present: None visible
Condition of smoke detectors: Required repair, replacement and/or evaluation (see comments below)
Smoke detectors present: Yes
Carbon monoxide detectors present: Yes
12) Some open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.
Photo
Photo 12-1 Crawl space, SE corner
13) Some cover plates on receptacle boxes were missing. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. A qualified person should repair as necessary.
Photo
Photo 13-1 Crawl space, SE corner
14) One or more wall-mounted exterior light fixtures had wiring that's subject to water intrusion due to caulk not being installed around the light fixture's back plate. Caulk should be applied around the perimeter of back plates where missing. A gap should be left at the bottom for condensation to drain out.
Photo
Photo 14-1 Garage
Photo
Photo 14-2 Front entry
15) Smoke detectors were missing from hallways leading to bedrooms. Additional smoke detectors should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, in each bedroom, and one each level of the building. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
Photo
Photo 15-1 Outside NW bedroom
16) One or more electric receptacles at the following "wet" locations appeared to have no ground fault circuit interrupter (GFCI) protection: kitchen and/or crawl space. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
Photo
Photo 16-1 Kitchen
Photo
Photo 16-2 Kitchen
Photo
Photo 16-3 Kitchen
Photo
Photo 16-4 
17) The service drop wires were in contact with trees or vegetation. The utility company should prune or remove trees as necessary to prevent straining or abrading the service drop wires.
Photo
Photo 17-1 North side street
18) Some electric receptacles were not evaluated because of furniture and/or stored items.
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Required repair, replacement and/or evaluation (see comments below)
Location of main water meter: Not determined
Location of main water shut: North side
Water service: Public
Service pipe material: Copper
Condition of supply lines: Required repair, replacement and/or evaluation (see comments below)
Supply pipe material: Copper
Condition of waste lines: Required repair, replacement and/or evaluation (see comments below)
Condition of fuel system: Required repair, replacement and/or evaluation (see comments below)
Location of main fuel shut: NE corner
19) One or more flexible gas supply connectors were routed through a metal cabinet. Standard building practices require that solid iron pipe be used where gas supply lines are routed through holes in metal cabinets. Continued vibration from this equipment may cause the edge of the metal cabinet to wear through the flexible connector, resulting in gas leaks. This is a safety hazard. A qualified heating and cooling contractor should evaluate and make repairs and/or modifications as necessary.
Photo
Photo 19-1 East side at HVAC unit
20) Conducive conditionsLeaks were found in one or more waste pipes and/or fittings. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 20-1 Hall bathroom toilet waste line
Photo
Photo 20-2 Under hall bathroom toilet waste line
Photo
Photo 20-3 Hall bathroom toilet waste line
21) Conducive conditionsLeaks were found in one or more water supply valves. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 21-1 South side under deck
22) The main shut-off valve was leaking. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 22-1 North side
23) Water supply lines were routed outside and are subject to freezing. Pipe wrap or foam sleeves are inexpensive and easily installed. Recommend insulating pipes as necessary to prevent pipes from freezing and bursting.
Photo
Photo 23-1 North side
24) The inspector was not able to find the water meter. Recommend that the client attempt to find the water meter by consulting with the property owner, searching for it themselves, or consulting with the local water municipality. It is especially important to find the meter if no main shut-off valve is found because the meter may be the only way to turn off the water supply in the event of an emergency, such as when a supply pipe bursts.
25) One or more outside faucets were missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the building. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

Client(s) may wish to consider installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
Photo
Photo 25-1 North side
Water Heater
Table of contents
Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Required repair, replacement and/or evaluation (see comments below)
Type: Tank
Estimated age: 30 years
Energy source: Natural gas
Capacity (in gallons): 40
Manufacturer: Rheem
Model: 21VR40-7 / ser#0287A49252
Location of water heater: Garage
Condition of burners: Required repair, replacement and/or evaluation (see comments below)
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
26) The water heater's seismic straps or struts were substandard. For example, they may allow significant movement or use improper fasteners. This is a potential safety hazard. Leaks may also occur in water supply pipes. A qualified person should evaluate and either repair existing straps or install new straps or struts as necessary and as per standard building practices.

NOTE: Need back bracing.
Photo
Photo 26-1 
Photo
Photo 26-2 
27) The following conditions were found in the burner chamber: rust and/or deterioration. A qualified contractor should evaluate, and repair if/as necessary.
Photo
Photo 27-1 
Photo
Photo 27-2 
28) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be beyond this age and/or its useful lifespan and may need replacing at any time.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Appeared serviceable
Location of heating system: Exterior, East side
Heating type: Forced air
Fuel type: Natural gas
Approximate BTUs: Not determined
Manufacturer: Ruud
Model: Label illegible
Condition of burners: Not evaluated (no access), excluded
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Condition of distribution system: Appeared serviceable
Distribution system: Ducts and registers
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: Behind return air grill
29) Filters should be checked monthly and maintained as necessary in the future.
30) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appeared to be beyond this age and may need replacing or significant repairs at any time.
Cooling / Heat Pump
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Appeared serviceable
Location: Exterior, East side
Type: Packaged unit
Estimated age: 30 years
Approximate tonnage: Not determined
Manufacturer: Ruud
Condition of distribution system: See Heating
Condition of controls: See Heating
Condition of air filters: See Heating
31) The estimated useful life for most cooling systems and heat pumps is 10 to 15 years. This system appears to be this age and may need replacing or significant repairs at any time.
Fireplaces / Stoves / Chimneys
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
Condition of fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Location #A: Living room
Stove type: Freestanding
Fuel type: Wood
Condition of chimneys: Appeared serviceable
Chimney type: Metal
32) Firebricks lining the woodstove at location #A are cracked. A qualified person should replace firebricks as necessary.
Photo
Photo 32-1 
33) All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of garbage disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type: Natural gas
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave / range hood: Appeared serviceable
34) Grout was deteriorated around the sink. A qualified person should repair as necessary.
Photo
Photo 34-1 
Photo
Photo 34-2 
35) The dishwasher drain line was not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The client should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

Also, no "air gap" was installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client should consult with a qualified contractor to determine if an air gap should be installed.
Photo
Photo 35-1 
36) Some counters showed minor damage.
Photo
Photo 36-1 
37) No duct was installed for the cooktop exhaust fan. Ventilation may be inadequate and moisture may accumulate indoors. Client(s) may wish to consider having a qualified contractor install a duct so the exhaust fan vents outdoors.
Photo
Photo 37-1 
Bathrooms / Laundry / Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Hall
Location #B: Master
Location #C: Garage
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of laundry facilities: Appeared serviceable
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes
38) Conducive conditionsCaulk and/or Grout was deteriorated by the floor and/or wall at the bathtub at location #A. A qualified person should repair as necessary.
Photo
Photo 38-1 Hall bathroom
Photo
Photo 38-2 Hall bathroom
39) Conducive conditionsCaulk and/or Grout was deteriorated around the shower floor and/or walls at location #B . A qualified person should repair as necessary.
Photo
Photo 39-1 Master bathroom
Photo
Photo 39-2 Master bathroom
Photo
Photo 39-3 Master bathroom
Photo
Photo 39-4 Master bathroom
40) Conducive conditionsThe toilet at location #B was loose. A qualified contractor should remove the toilet(s) for further evaluation and repairs if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 40-1 Master bathroom
41) The bathtub drain stopper mechanism at location #A was loose. A qualified person should repair or replace as necessary.
Photo
Photo 41-1 Hall bathroom
42) The bathroom with a shower at location #A and B didn't have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. Client(s) may wish to consider having a qualified contractor install exhaust fans as per standard building practices where missing in bathrooms with showers.
Interior Rooms / Areas
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
Exterior door material: Wood, Sliding glass
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Condition of interior doors: Appeared serviceable
Type of windows: Aluminum
Condition of windows: Appeared serviceable
Wall type or covering: Drywall
Condition of walls: Appeared serviceable
Ceiling type or covering: Drywall, Wood and beam
Condition of ceilings: Appeared serviceable
Flooring type or covering: Carpet, Vinyl, Tile
43) One or more exterior doors had minor deterioration.
Photo
Photo 43-1 Garage entry door
44) Minor cracks and/or holes were found in walls and ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.Look First Inspections requires an inspection agreement to be signed by Client prior to performing an inspection. If you were not present at the inspection and did not sign the Inspection Agreement you, by accepting, paying for, and/or using the inspection report you acknowledge and agree to be bound by the terms and conditions of the inspection agreement and further agree that the Inspection Agreement will form part of the inspection report.