Property Inspection Report

Client(s):  Mr. & Mrs. Jones
Property address:  1234 Sample CT # 2
Hamilton, MT 59840
Inspection date:  Tuesday, August 6, 2019

This report published on Tuesday, January 7, 2020 3:56:39 PM MST

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeDamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Attached Garage
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation, No Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary

General InformationTable of contents
Report number: jones20190806
Time started: 9:00 am
Time finished: 1:45 pm
Present during inspection: No one
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Warm and warming throughout the day
Payment method: Check
Buildings inspected: One house with attached garage
Number of residential units inspected: 1
Age of main building: 1995
Source for main building age: Realtor, Municipal records or property listing
Front of building faces: Southwest
Main entrance faces: Southwest
Occupied: No
1) Microbial growths were found at one or more locations in interior rooms. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit:
http://www.reporthost.com/?MOLDCDC
http://www.reporthost.com/?MOLDEPA
Photo
Photo 1-1 This is a living room window sill & trim
2) Some areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope, Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Asphalt, Poured in place concrete, Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open, Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood, Plastic fiber, Concrete
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Wood
3) Guardrails at one or more locations with drop-offs higher than 30 inches had gaps that were too large. This poses a safety hazard for children (e.g. falling, getting stuck in railing). Guardrails should not have gaps or voids that allow passage of a sphere equal to or greater than 4 inches in diameter, or 6 inches in diameter at triangular spaces between stair edges and guardrails. At a minimum, the client should be aware of this hazard. Recommend that a qualified contractor repair or replace guardrails per standard building practices.
Photo
Photo 3-1 
Photo
Photo 3-2 
4) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 4-1 
5) Conducive conditionsFlashing appeared to be missing from above one or more deck or porch ledger boards, or could not be verified. Missing flashing at this location can cause moisture to accumulate between the ledger boards and the building. Fungal rot may occur in this area and cause the ledger board fasteners to fail. Recommend contacting a qualified building contractor to further evaluated the installing of flashing above ledger boards per standard building practices. For more information, visit:
http://www.reporthost.com/?LB
http://www.reporthost.com/?SD
Photo
Photo 5-1 
Photo
Photo 5-2 
6) More than one connecting brackets and or fasteners for the deck, porch, such as joist hangers, support post/beam brackets and or fasteners were missing. Approved deck connecting brackets such as Simpson Strong Tie should be installed; along with fasteners such as Teco nails should be installed in every nail hole in hardware. Recommend that a qualified person install approved brackets & fasteners where necessary.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
7) Conducive conditionsSoil was in contact with one or more wooden deck, porch or balcony support posts. This is a conducive condition for wood destroying organisms. Even if posts are made of treated wood, the cut ends below soil may not have been field treated. Recommend grading soil or repairing as necessary to prevent wood-soil contact.
Photo
Photo 7-1 
8) Wooden deck or porch surfaces and/or railings were overdue for normal maintenance. Recommend that a qualified person clean and preserve as necessary. Where decks have been coated with a finish such as opaque stains or paint, it may be too difficult to strip the finish and apply anything but paint or opaque stain. Where transparent stain or penetrating oil has been applied in the past, recommend that a penetrating oil be used. For more information, visit:
http://www.reporthost.com/?PENOIL
http://www.reporthost.com/?DKMAIN
Photo
Photo 8-1 
Photo
Photo 8-2 
Photo
Photo 8-3 
Photo
Photo 8-4 
Photo
Photo 8-5 
Photo
Photo 8-6 
9) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the concrete driveway, but no trip hazards were found. The client may wish to have a qualified person apply the proper sealant to prevent water penetration.
Photo
Photo 9-1 
Photo
Photo 9-2 
10)  Surrounding grounds, driveway, sidewalks, porches, decks & covers.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
Photo
Photo 10-5 
Photo
Photo 10-6 
Photo
Photo 10-7 
Photo
Photo 10-8 
Photo
Photo 10-9 
Photo
Photo 10-10 
Photo
Photo 10-11 
Photo
Photo 10-12 
Photo
Photo 10-13 
Photo
Photo 10-14 
Photo
Photo 10-15 
Photo
Photo 10-16 
Photo
Photo 10-17 
Photo
Photo 10-18 
Photo
Photo 10-19 
Photo
Photo 10-20 
Photo
Photo 10-21 
Photo
Photo 10-22 
11)  Underneath side of decks
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 
Photo
Photo 11-6 
Photo
Photo 11-7 
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood fiber
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Finished basement
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
12) There were several basement window well covers was missing. This is a potential fall/trip hazard. Recommend having a qualified person install approved window well covers.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
13) DamageRot was found at one or more fascia edges or surfaces. Conducive conditions for rot should be corrected, properly priming & painting wood fiber siding & trim where needed. Refer to the wood-fiber section below. Recommend that a qualified contractor repair as necessary. All rotten wood should be replaced.
Photo
Photo 13-1 Where a gable end & eave edged trim meet, behind a rain gutter.
14) Some sections of siding or trim were loose or damaged, including trim on exterior door(s). Recommend that a qualified person repair, replace or install siding or trim as deemed necessary.
Photo
Photo 14-1 Garage entry door trim piece
Photo
Photo 14-2 Door trim
Photo
Photo 14-3 Door window plastic trim pieces
Photo
Photo 14-4 
Photo
Photo 14-5 Loose soffit/eave pieces
15) Conducive conditionsThis property was clad with composition wood-fiber siding. Various manufacturers (e.g. Louisiana Pacific, Weyerhaeuser and Masonite) have produced this type of siding, which is made from oriented strand board (OSB) or "hardboard." It is prone to deteriorate and/or fail prematurely due to moisture penetration, especially when the paint coating is substandard or has not been maintained. Failure is typically visible in the form of swelling, cracking, buckling, wafer pops, delamination and fungal growth.

Some areas of siding or trim on this structure showed symptoms described above and need replacement and/or maintenance. Some manufacturers (e.g. Louisiana Pacific) recommend a repair process for this siding where affected areas are sealed with Permanizer Plus, a flexible primer made by Pittsburgh Paint, followed by two coats of 100% acrylic latex paint. This sealant must be applied to the bottom edges using a brush. The face of the siding can be sprayed. The Permanizer Plus sealer isn't required for edges that aren't swollen, cracked or deteriorated, but the acrylic latex should still be brushed on these edges.

Recommend that a qualified contractor evaluate and replace any siding or trim as deemed necessary, and/or seal and repaint as necessary. Repairs should be made per the siding and/or sealant manufacturer's installation instructions, and per standard building practices.

For more information, visit:
http://www.reporthost.com/?PERMPLUS
http://www.reporthost.com/?COMPSDNG
Photo
Photo 15-1 
Photo
Photo 15-2 
Photo
Photo 15-3 
Photo
Photo 15-4 
Photo
Photo 15-5 
Photo
Photo 15-6 
Photo
Photo 15-7 
Photo
Photo 15-8 
16) Conducive conditionsOne or more windows or doors were installed with no "drip cap" or "Z" flashings installed above them. Better building practices call for such flashings, which greatly reduce the chance of leaks above windows and doors. Without this flashing, caulk and paint must be maintained or water can enter the wall structure and cause rot and possible structural damage. Depending on the exposure (e.g. roof overhang, height of exterior wall, direction of prevailing rain) this may or may not be an issue. The client should monitor these areas in the future and maintain caulk and paint as necessary. Consult with a qualified contractor about installing flashings where needed, and per standard building practices. Note that when trim or siding is removed to install flashing, damaged wood may be found and additional repairs may be needed.
Photo
Photo 16-1 
Photo
Photo 16-2 
17) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
Photo
Photo 17-5 
18) Conducive conditionsVegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
19) Conducive conditionsThe paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 19-1 
Photo
Photo 19-2 
Photo
Photo 19-3 Trim edges
Photo
Photo 19-4 
Photo
Photo 19-5 
Photo
Photo 19-6 
20) Conducive conditionsCaulk was missing and/or deteriorated in some areas. For example, around doors and/or at siding-trim junctions. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
Photo
Photo 20-4 
Photo
Photo 20-5 
Photo
Photo 20-6 
Photo
Photo 20-7 
Photo
Photo 20-8 
21)  Exterior
Photo
Photo 21-1 
Photo
Photo 21-2 
Photo
Photo 21-3 
Photo
Photo 21-4 
Photo
Photo 21-5 
Photo
Photo 21-6 
Photo
Photo 21-7 
Photo
Photo 21-8 
Photo
Photo 21-9 
22)  Foundation
Photo
Photo 22-1 
Photo
Photo 22-2 
Photo
Photo 22-3 
Photo
Photo 22-4 
Photo
Photo 22-5 
Photo
Photo 22-6 
Photo
Photo 22-7 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Exterior door material: None
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Bearing wall
Beam material: Not determined (inaccessible or obscured)
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
23)  Basement, mainly finished
Photo
Photo 23-1 
Photo
Photo 23-2 
Photo
Photo 23-3 
Photo
Photo 23-4 
Photo
Photo 23-5 
Photo
Photo 23-6 
Photo
Photo 23-7 
Photo
Photo 23-8 
Photo
Photo 23-9 
Photo
Photo 23-10 
Photo
Photo 23-11 
Photo
Photo 23-12 
Photo
Photo 23-13 
Photo
Photo 23-14 
Photo
Photo 23-15 
Photo
Photo 23-16 
Photo
Photo 23-17 
Photo
Photo 23-18 
Photo
Photo 23-19 
Photo
Photo 23-20 
24)  Mechanical room located in basement
Photo
Photo 24-1 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: Multiple
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
25) Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 25-1 
26) Conducive conditionsSignificant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 26-1 
Photo
Photo 26-2 
Photo
Photo 26-3 
Photo
Photo 26-4 
27) Conducive conditionsSignificant amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Photo
Photo 27-1 
Photo
Photo 27-2 
28) Nail heads were exposed on one or more ridge shingles. This could lead to water leaking. Recommend applying an approved sealant over exposed nail heads now and as necessary in the future to prevent leaks.
Photo
Photo 28-1 
Photo
Photo 28-2 
Photo
Photo 28-3 
29) This asphalt or fiberglass composition roof surface appeared to have two or more layers of shingles. Additional layers of composition shingles typically last only 80% of their rated life, and the shingle manufacturer's warranty may be voided. The client should be aware that all layers of roofing will need to be removed when this roof surface needs replacing.
Photo
Photo 29-1 
Photo
Photo 29-2 
30)  Roof
Photo
Photo 30-1 
Photo
Photo 30-2 
Photo
Photo 30-3 
Photo
Photo 30-4 
Photo
Photo 30-5 
Photo
Photo 30-6 
Photo
Photo 30-7 
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt, Cellulose loose fill
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Vapor retarder: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s), Enclosed soffit vents
31) One or more attic access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC
Photo
Photo 31-1 The attic sheetrock lid
32) The ceiling insulation installed in the attic appeared to have an approx. an R-30 rating, that's less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend considering contacting a qualified insulation contractor to further evaluate and install insulation for better energy efficiency and per standard building practices.
Photo
Photo 32-1 
Photo
Photo 32-2 
33)  Attic
Photo
Photo 33-1 Mst. bd. closet ceiling
Photo
Photo 33-2 Garage ceiling
Photo
Photo 33-3 
Photo
Photo 33-4 
Photo
Photo 33-5 
Photo
Photo 33-6 
Photo
Photo 33-7 
Photo
Photo 33-8 
Photo
Photo 33-9 
Photo
Photo 33-10 
Photo
Photo 33-11 
Photo
Photo 33-12 
34)  Ridge & soffit ventilation
Photo
Photo 34-1 
Photo
Photo 34-2 
Photo
Photo 34-3 
Attached GarageTable of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Hollow core, Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 2
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
35) One or more gaps, holes and/or areas with missing or substandard surface materials were found in the attached garage walls or ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit:
http://www.reporthost.com/?AGFR
Photo
Photo 35-1 Exposed wood framing
36) The photoelectric sensors that trigger the auto-reverse feature on one or more garage vehicle doors' automatic openers were located higher than 4-6 inches from the floor. This is a potential safety hazard. A qualified person should relocate sensors so they are 4-6 inches from the floor per standard building practices. For more information on garage door safety issues, visit:
http://www.reporthost.com/?GDPES
Photo
Photo 36-1 
37) The garage door(s) weather stripping was damaged or missing. This can allow moisture, wind and cold/warm air into the garage area. Recommend a qualified person install weather stripping where needed.
Photo
Photo 37-1 
Photo
Photo 37-2 
Photo
Photo 37-3 
38) Minor cracks and wear were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Photo
Photo 38-1 
Photo
Photo 38-2 
Photo
Photo 38-3 
Photo
Photo 38-4 
39) The inside of the garage was sheetrock, but was not completely fire tapped. Although it may not be required, the client may wish to have the walls & ceiling fire taped for further protection.
Photo
Photo 39-1 
Photo
Photo 39-2 
Photo
Photo 39-3 
Photo
Photo 39-4 
40)  Garage
Photo
Photo 40-1 
Photo
Photo 40-2 
Photo
Photo 40-3 
Photo
Photo 40-4 
Photo
Photo 40-5 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Not determined, not readily apparent
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: No, recommend install
41) One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the full bath and/or basement wouldn't trip when tested. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 41-1 
42) One or more electric receptacles at the exterior had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 42-1 
43) Bare wire ends, or wires with a substandard termination, were found at one or more locations. This is a potential shock hazard. Recommend that a qualified electrician repair as necessary. For example, by cutting wires to length and terminating with wire nuts in a permanently mounted, covered junction box.
Photo
Photo 43-1 In the attic above the mst. bd.
44) Several electric receptacles in the basement were incorrectly wired with an open neutral. This is a potential shock hazard. Recommend that a qualified electrician repair as deemed necessary.
Photo
Photo 44-1 
Photo
Photo 44-2 
Photo
Photo 44-3 
45) One cover plates for switches, receptacles or junction boxes were missing or broken in the garage. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 45-1 
46) Carbon monoxide alarms were missing on one or more levels. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit:
http://www.reporthost.com/?COALRM
47) One or more globes or covers for light fixtures were missing or damaged. Recommend replacing as necessary to avoid exposed bulbs. With closet lighting or where flammable stored objects are near light fixtures, missing or broken covers can be a fire hazard.
Photo
Photo 47-1 
Photo
Photo 47-2 
48) One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 48-1 
Photo
Photo 48-2 
49) Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 49-1 
50) The inspector does not verify that the legend for circuit breakers in panel(s) #A is accurate, complete, legible or may be confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend that a qualified person verify the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.
Photo
Photo 50-1 
51)  Electric service panel & 200 amp shut off breaker
Photo
Photo 51-1 
Photo
Photo 51-2 
52)  Electrical meter pedestal & an outside 200 amp shut off breaker
Photo
Photo 52-1 
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Basement, In mechanical room
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, Galvanized steel
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: Yes
Condition of sump pump: Required repairs, replacement and/or evaluation (see comments below)
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: propane tank
Location of main fuel shut-off valve: At propane tank
53) Based on visible equipment or information provided to the inspector, this property appeared to have a yard irrigation (sprinkler) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. When this system is operated, recommend verifying that water is not directed at building exteriors, or directed so water accumulates around building foundations. Sprinkler heads may need to be adjusted, replaced or disabled. Consider having a qualified plumber verify that a backflow prevention device is installed per standard building practices to prevent cross-contamination of potable water. Recommend that a qualified specialist evaluate the irrigation system for other defects (e.g. leaks, damaged or malfunctioning sprinkler heads) and repair if necessary.
54) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC
55) Based on visible equipment or information provided to the inspector, the water supply to this property appeared to be from a private well. Private well water supplies are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible and accessible components are evaluated. Recommend the following:
  • That a qualified well contractor fully evaluate the well, including a pump/flow test
  • That the well water be tested per the client's concerns (coliforms, pH, contaminants, etc.)
  • Research the well's history (how/when constructed, how/when maintained or repaired, past performance, past health issues)
  • Document the current well capacity and water quality for future reference
For more information, visit:
http://www.reporthost.com/?WELL
56) A water softener system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Water softeners typically work by removing unwanted minerals (e.g. calcium, magnesium) from the water supply. They prevent build-up of scale inside water supply pipes, improve lathering while washing, and prevent spots on dishes. Recommend consulting with the property owner about this system to determine its condition, required maintenance, age, expected remaining life, etc. For more information, visit:
http://www.reporthost.com/?WTRSFT
http://www.reporthost.com/?HRDWTR
Photo
Photo 56-1 
57) A sump pump was installed in the basement. These are specialty systems and only a limited evaluation was performed as part of this inspection. The inspector does not determine the adequacy of sump pumps and their associated drainage systems. The presence of a sump pump may indicate that water routinely accumulates below or inside the structure. Recommend asking the property owner how often the sump pump operates and for how long at different times of the year. The client should be aware that the service life of most sump pumps is 5-7 years, and that the pump may need replacing soon depending on its age and how often it operates.
Photo
Photo 57-1 
58)  Plumbing
Photo
Photo 58-1 
Photo
Photo 58-2 
Photo
Photo 58-3 
Photo
Photo 58-4 
Photo
Photo 58-5 
Photo
Photo 58-6 
Photo
Photo 58-7 
Photo
Photo 58-8 
Photo
Photo 58-9 
Photo
Photo 58-10 
Photo
Photo 58-11 Main water shut off valve
Photo
Photo 58-12 Water pressure gauge....normal water pressure is 40 to 60 psi
59)  Propane tank
Photo
Photo 59-1 
Photo
Photo 59-2 Propane regulator & shut off valve on side of house
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Boiler Mate
Capacity (in gallons): 41
Temperature-pressure relief valve installed: Yes
Location of water heater: Mechanical room, Basement
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 166.6
Age of water heater;: Not determined, the manufacture's serial number did not easily determine the age
60) The estimated useful life for most standard steel water heaters is 8-12 years. The inspector was unable to determine the age of the water heater due to the manufacturer's label or serial number not clearly indicating the age or unable to easily look it up. The client should be aware that this water heater may be near, at or beyond its useful life and may need replacing at any time. Recommend attempting to determine the water heater's age by possibly contacting the manufacture itself with the serial number.

If found to be near, at or beyond its useful lifespan, recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater does fail. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.

Amtrol Boiler Mate 41 gal.
Ser.# BM 174850 BZ
Mod.# WH-7L
Photo
Photo 60-1 
Photo
Photo 60-2 
Photo
Photo 60-3 
Heating, Ventilation, No Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Radiant, Wood-burning fireplace or stove
General heating distribution type(s): Pipes and wall mounted radiators
Source for last service date of primary heat source: Unknown
Condition of hydronic system: Appeared serviceable, requires further evaluation and servicing (see recommendations below)
Type of hydronic or steam heat: Hydronic (hot water), Circulating pump, Radiators
Hydronic or steam heat fuel type: Propane
Condition of burners: Appeared serviceable
Type of combustion air supply: Vented door
Condition of venting system: Appeared serviceable
Condition of controls: Appeared serviceable
61) The estimated useful life for most cast iron boilers is 30 years. This boiler appeared to be approx. 26 yrs. old. Recommend contacting a qualified HVAC contractor to service and further evaluate and make any repairs deemed necessary in the heating system now and annually in the future.

Weil-McLain HE 11 propane boiler
Ser.# CP 2521151
Mod.# HE 11-5
BTU heat cap. 109,000
Manuf. 08/25/1993 approx. 26 yrs old.
Photo
Photo 61-1 
Photo
Photo 61-2 
Photo
Photo 61-3 
Photo
Photo 61-4 
Photo
Photo 61-5 
62) There was a free standing electric heater unplugged in the upstairs living room. This is a plug-in appliance and the inspector does not evaluate or operate removable plug-in appliances like heater, a/c units, microwaves, etc. This heater is exempt from the report. Recommend asking the current owner about the operation of the unit.
Photo
Photo 62-1 
63)  Wall mounted radiant heaters, pumped into the boiler heating system, with wall mounted zone thermostats.
Photo
Photo 63-1 
Photo
Photo 63-2 
Photo
Photo 63-3 
Photo
Photo 63-4 
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning stove type: Freestanding
Condition of chimneys and flues: Appeared serviceable, Near, at or beyond service life
Wood-burning chimney type: Masonry, Metal, Cinder block
64) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 64-1 
Photo
Photo 64-2 
65) Screws were missing from one or more single-wall metal stove pipe joints and the elbow was pushed inside the pipe coming off the stove. The elbow should have been placed over the pipe coming off the stove.This is a safety hazard due to the risk of the pipe coming apart and smoke or co gas leaking out at the joint into the living area. Three screws should be installed at each joint, at the flue collar and at chimney ends. Recommend that a qualified person repair per standard building practices before use.
Photo
Photo 65-1 
66) One or more metal B-vent flues for gas-fired appliances were significantly corroded and cracked. Water may enter the building structure or reach the gas-fired appliance. Excessive heat may also be emitted from corroded areas. Recommend that a qualified contractor replace corroded flue sections as necessary.
Photo
Photo 66-1 
Photo
Photo 66-2 Cracked vent pipe
Photo
Photo 66-3 
67)  Chimney
Photo
Photo 67-1 
Photo
Photo 67-2 
Photo
Photo 67-3 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Propane, Electronic ignition
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: N/A (none installed)
68) The range could tip forward. An anti-tip bracket may not be installed. This is a potential safety hazard since the range can tip forward when weight is applied to the open door, such as when a small child climbs on it or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free-standing ranges since 1985. Recommend installing an anti-tip bracket to eliminate this safety hazard. For more information, visit:
http://www.reporthost.com/?ATB
Photo
Photo 68-1 
69) The exhaust fan over the range recirculated the exhaust air back into the kitchen. This may be due to no duct being installed, baffles not being installed, or problems with duct work. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. Recommend that a qualified contractor evaluate and repair as necessary so exhaust air is ducted outdoors.
Photo
Photo 69-1 
70)  Kitchen
Photo
Photo 70-1 
Photo
Photo 70-2 
Photo
Photo 70-3 
Photo
Photo 70-4 
Photo
Photo 70-5 
Photo
Photo 70-6 
Photo
Photo 70-7 
Photo
Photo 70-8 
Photo
Photo 70-9 
Photo
Photo 70-10 
Photo
Photo 70-11 
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Full bath, Master bath, first floor
Location #C: Full bath, basement
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
71) The clothes dryer was equipped with a vinyl or mylar, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. They can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow and cause overheating. Recommend that such ducts be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. For more information, visit:
http://www.reporthost.com/?DRYER
Photo
Photo 71-1 
72) Conducive conditionsGaps, no caulk, or substandard caulking were found between the shower enclosure and the floor and/or walls at location(s) #A and B. Water can penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 72-1 
Photo
Photo 72-2 
73) Caulk around the base of the toilet at location(s) #A and B was missing, substandard and/or deteriorated. Modern standards require caulk to be installed around the entire toilet base where it meets the floor for sanitary reasons. Without it, soiled water can soak into flooring and sub-floor materials if the toilet overflows. Condensation from the toilet can also soak into the flooring. Recommend that a qualified person caulk around toilet bases per standard building practices.
Photo
Photo 73-1 
74)  Bath/laundry rooms
Photo
Photo 74-1 
Photo
Photo 74-2 
Photo
Photo 74-3 
Photo
Photo 74-4 
Photo
Photo 74-5 
Photo
Photo 74-6 
Photo
Photo 74-7 
Photo
Photo 74-8 
Photo
Photo 74-9 
Photo
Photo 74-10 
Photo
Photo 74-11 
Photo
Photo 74-12 
Photo
Photo 74-13 
Photo
Photo 74-14 
Photo
Photo 74-15 
Photo
Photo 74-16 
Photo
Photo 74-17 
Photo
Photo 74-18 
Photo
Photo 74-19 
Photo
Photo 74-20 
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Fiberglass or vinyl, Glass panel, Sliding glass
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Wood, Metal, Multi-pane, Casement, Fixed, Jalousie
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall, Wallpaper, Masonry, Wood
Ceiling type or covering: Drywall, Wood & beam
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
75) Carpeting in one or more areas was loose. Recommend that a qualified contractor repair as necessary. For example, by stretching or replacing carpeting.
Photo
Photo 75-1 
Photo
Photo 75-2 
76) Conducive conditionsThere appeared to be moisture, fungal or mold growth or damage to one or more of the interior window wood sills. Recommend a qualified person properly treat the area affected by any fungal growth before any repairs are made to the window sills.
Photo
Photo 76-1 Discolored areas
Photo
Photo 76-2 
77) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.reporthost.com/?ECC
Photo
Photo 77-1 
78) Screens were missing from some windows or siding glass doors. These windows may not provide ventilation during months when insects are active.
Photo
Photo 78-1 
79)  Interior
Photo
Photo 79-1 
Photo
Photo 79-2 
Photo
Photo 79-3 
Photo
Photo 79-4 
Photo
Photo 79-5 
Photo
Photo 79-6 
Photo
Photo 79-7 
Photo
Photo 79-8 
Photo
Photo 79-9 
Photo
Photo 79-10 
Photo
Photo 79-11 
Photo
Photo 79-12 
Photo
Photo 79-13 
Photo
Photo 79-14 
Photo
Photo 79-15 
Photo
Photo 79-16 
Photo
Photo 79-17 

Scope of the Inspection:

The scope of the inspection is strictly limited as set forth in the Pre-Inspection Agreement. The parties understand and agree BEFORE any inspection takes place that the inspection will be of readily accessible areas of the building to be inspected and is limited to visual observations of apparent conditions existing at the time of the inspection only. Latent and concealed defects and deficiencies, including but not limited to, basement flooring, basement seepage and roof leakage, inaccessible attic spaces do to a verity of reasons, are Excluded from the inspection. The parties agree in advance that the American Society of Home Inspectors (ASHI) Standards of Practice, most current edition, shall define the standard duty and the conditions, limitations, and exclusions of the inspection and are incorporated by reference herein. Refer to the signed Pre-Inspection Agreement for further limitations, exclusions and liabilities.

You are encouraged to read the entire report, not just summery sections. The whole and complete report is all pertinent information in the inspection. Please read and carefully consider all the information comprised in the Final Report.

I sincerely hope that the information in this report is useful and helpful to you, in giving a more in depth awareness of the current condition of the property that has just been inspected.

Again, Thank-You for choosing HHI-Hews Home Inspection, its been a pleasure serving you.