How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Major Defect
Correction likely involves a significant expense
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Minor Defect
Correction likely involves only a minor expense
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Serviceable
Item or component is in serviceable condition
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open
1) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo 1-1 Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
2) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo 2-1 Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood fiber, Brick veneer
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade
Foundation/stem wall material: Poured in place concrete
3) Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-1 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-2 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-3 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-4 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-5 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-6 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-7 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-8 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-9 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-10 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-11 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-12 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-13 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-14 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 3-15 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary. Photo 3-16 Many sections of siding and/or trim were loose, warped, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
4) One or more exhaust duct end caps were damaged. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
Photo 4-1 One or more exhaust duct end caps were damaged. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary. Photo 4-2 One or more exhaust duct end caps were damaged. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
5) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo 5-1 One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
6) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo 6-1 One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
7) "Honeycombing" was found in one or more sections of the concrete foundation. This occurs when aggregate and sand in the concrete mixture bunches into clusters and fails to mix with the cement paste. This can be caused because the concrete mix was too stiff, by inadequate consolidation (insufficient use of a mechanical concrete vibrator) and/or pouring the concrete from too high of an elevation. In many cases honeycombing is only a cosmetic issue, but it does make concrete susceptible to water infiltration. Where honeycombing is accessible, recommend that a qualified person fill voids with an approved material such as hydraulic cement or non-shrinking grout.
When honeycombing is visible, it may also exist in hidden areas. Honeycombing can result in mold growth in absorbent flooring materials (e.g. carpeting and mortar joints), and can cause rigid flooring materials to warp and buckle.
Photo 7-1 "Honeycombing" was found in one or more sections of the concrete foundation. This occurs when aggregate and sand in the concrete mixture bunches into clusters and fails to mix with the cement paste. This can be caused because the concrete mix was too stiff, by inadequate consolidation (insufficient use of a mechanical concrete vibrator) and/or pouring the concrete from too high of an elevation. In many cases honeycombing is only a cosmetic issue, but it does make concrete susceptible to water infiltration. Where honeycombing is accessible, recommend that a qualified person fill voids with an approved material such as hydraulic cement or non-shrinking grout.
8) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo 8-1 Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
9) Caulk was missing in some areas. For example, at siding butt joints. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit: http://www.reporthost.com/?CAULK
Photo 9-1 Caulk was missing in some areas. For example, at siding butt joints. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Inspected with drone
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
10) Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo 10-1 Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
11) One or more downspouts were incomplete. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo 11-1 One or more downspouts were incomplete. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
12) The roof covering appeared serviceable at the time of inspection. No significant deficiencies affecting the overall function of the roof system were observed at the time of the inspection; however, roofs are exposed to ongoing weathering and deterioration over time, and continued routine maintenance and monitoring are recommended to help preserve serviceability.
Photo 12-1 The roof covering appeared serviceable at the time of inspection. No significant deficiencies affecting the overall function of the roof system were observed at the time of the inspection; however, roofs are exposed to ongoing weathering and deterioration over time, and continued routine maintenance and monitoring are recommended to help preserve serviceability. Photo 12-2 The roof covering appeared serviceable at the time of inspection. No significant deficiencies affecting the overall function of the roof system were observed at the time of the inspection; however, roofs are exposed to ongoing weathering and deterioration over time, and continued routine maintenance and monitoring are recommended to help preserve serviceability.
Photo 12-3 The roof covering appeared serviceable at the time of inspection. No significant deficiencies affecting the overall function of the roof system were observed at the time of the inspection; however, roofs are exposed to ongoing weathering and deterioration over time, and continued routine maintenance and monitoring are recommended to help preserve serviceability.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Vapor retarder: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s)
13) The pull-down attic ladder was observed to be missing the two lower steps at the time of inspection. This condition is a safety hazard because the ladder cannot be used as intended for safe access to the attic and may increase the risk of a fall or injury. Recommend repair or replacement by a qualified contractor to restore safe and proper access to the attic.
Photo 13-1 The pull-down attic ladder was observed to be missing the two lower steps at the time of inspection. This condition is a safety hazard because the ladder cannot be used as intended for safe access to the attic and may increase the risk of a fall or injury. Recommend repair or replacement by a qualified contractor to restore safe and proper access to the attic.
14) One or more attic framing members were observed to be split at the connection point near the upper portion of the framing assembly. The visible separation in the wood at this location may reduce the structural integrity of the affected member and suggests possible installation stress, fastener-related splitting, or loading concerns. Recommend further evaluation and repair as needed by a qualified contractor to ensure the framing is properly supported and performing as intended.
Photo 14-1 One or more attic framing members were observed to be split at the connection point near the upper portion of the framing assembly. The visible separation in the wood at this location may reduce the structural integrity of the affected member and suggests possible installation stress, fastener-related splitting, or loading concerns. Recommend further evaluation and repair as needed by a qualified contractor to ensure the framing is properly supported and performing as intended.
15) One or more attic framing members were observed to have an open joint/gap at a nailed connection, with the adjoining boards not fully bearing tightly against one another at the time of inspection. This type of loose or improperly seated framing connection may reduce the stability and intended support of the assembly. Recommend further evaluation and correction by a qualified contractor to ensure the framing connection is properly secured and supported.
Photo 15-1 One or more attic framing members were observed to have an open joint/gap at a nailed connection, with the adjoining boards not fully bearing tightly against one another at the time of inspection. This type of loose or improperly seated framing connection may reduce the stability and intended support of the assembly. Recommend further evaluation and correction by a qualified contractor to ensure the framing connection is properly secured and supported.
16) H-clips were not observed at one or more roof sheathing panel edges in the attic where such intermediate edge support is commonly installed to help reinforce panel joints between framing members. The absence of panel edge clips may allow for reduced edge support and can contribute to deflection or movement of the roof sheathing under load. Recommend further evaluation by a qualified contractor and correction as needed.
Photo 16-1 H-clips were not observed at one or more roof sheathing panel edges in the attic where such intermediate edge support is commonly installed to help reinforce panel joints between framing members. The absence of panel edge clips may allow for reduced edge support and can contribute to deflection or movement of the roof sheathing under load. Recommend further evaluation by a qualified contractor and correction as needed. Photo 16-2 H-clips were not observed at one or more roof sheathing panel edges in the attic where such intermediate edge support is commonly installed to help reinforce panel joints between framing members. The absence of panel edge clips may allow for reduced edge support and can contribute to deflection or movement of the roof sheathing under load. Recommend further evaluation by a qualified contractor and correction as needed.
17) The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
Photo 17-1 The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
18) One or more attic access hatches or doors had no weatherstripping, or the weatherstripping was substandard. Weatherstripping should be installed around hatches or doors as necessary to prevent heated interior air from entering the attic. For more information, visit: http://www.reporthost.com/?ATTACC
Photo 18-1 One or more attic access hatches or doors had no weatherstripping, or the weatherstripping was substandard. Weatherstripping should be installed around hatches or doors as necessary to prevent heated interior air from entering the attic. Photo 18-2 One or more attic access hatches or doors had no weatherstripping, or the weatherstripping was substandard. Weatherstripping should be installed around hatches or doors as necessary to prevent heated interior air from entering the attic.
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Required repair, replacement and/or evaluation (see comments below)
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
Type of garage vehicle door: Sliding
Number of vehicle doors: 2
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): No
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
19) The door between the garage and the house did not appear to be fire resistant, or the inspector was unable to verify that it was via a label. This is a potential safety hazard. House to garage doors, to prevent fire and fumes from spreading from the garage into interior living space, should be constructed of fire-resistant materials. Doors, generally considered to be suitable for the purpose, are solid core wood, steel, honeycomb steel or a door that has been factory labeled as fire rated. Recommend that a qualified contractor replace or repair the door and, at that time, make any other corrections that might be required to provide suitable fire resistance between the garage and the dwelling per standard building practices. For more information, visit: http://www.reporthost.com/?AGFR
Photo 19-1 The door between the garage and the house did not appear to be fire resistant, or the inspector was unable to verify that it was via a label. This is a potential safety hazard. House to garage doors, to prevent fire and fumes from spreading from the garage into interior living space, should be constructed of fire-resistant materials. Doors, generally considered to be suitable for the purpose, are solid core wood, steel, honeycomb steel or a door that has been factory labeled as fire rated. Recommend that a qualified contractor replace or repair the door and, at that time, make any other corrections that might be required to provide suitable fire resistance between the garage and the dwelling per standard building practices.
20) Weatherstripping around or at the base of the door between the garage and the house was missing. House to garage doors should prevent fire and fumes from spreading from the garage to the house. Weatherstripping should form a seal around this door. This is a potential safety hazard. Recommend that a qualified person replace or install weatherstripping as necessary.
Photo 20-1 Weatherstripping around or at the base of the door between the garage and the house was missing. House to garage doors should prevent fire and fumes from spreading from the garage to the house. Weatherstripping should form a seal around this door. This is a potential safety hazard. Recommend that a qualified person replace or install weatherstripping as necessary.
21) One or more garage door opener photoelectric safety sensors were observed to be damaged and/or missing at the time of inspection. This condition is a significant safety concern because the automatic reverse safety system may not function properly to detect an obstruction in the path of the closing door, which increases the risk of injury or property damage. Current safety standards require automatic garage door openers to be equipped with a functional entrapment protection device, including photoelectric sensors installed in accordance with the manufacturer’s instructions and applicable safety requirements under UL 325. Recommend evaluation and repair by a qualified garage door contractor to restore proper and safe operation. For more information on garage door safety issues, visit: http://www.reporthost.com/?GDPES
Photo 21-1 One or more garage door opener photoelectric safety sensors were observed to be damaged and/or missing at the time of inspection. This condition is a significant safety concern because the automatic reverse safety system may not function properly to detect an obstruction in the path of the closing door, which increases the risk of injury or property damage. Current safety standards require automatic garage door openers to be equipped with a functional entrapment protection device, including photoelectric sensors installed in accordance with the manufacturer’s instructions and applicable safety requirements under UL 325. Recommend evaluation and repair by a qualified garage door contractor to restore proper and safe operation. Photo 21-2 One or more garage door opener photoelectric safety sensors were observed to be damaged and/or missing at the time of inspection. This condition is a significant safety concern because the automatic reverse safety system may not function properly to detect an obstruction in the path of the closing door, which increases the risk of injury or property damage. Current safety standards require automatic garage door openers to be equipped with a functional entrapment protection device, including photoelectric sensors installed in accordance with the manufacturer’s instructions and applicable safety requirements under UL 325. Recommend evaluation and repair by a qualified garage door contractor to restore proper and safe operation.
Photo 21-3 One or more garage door opener photoelectric safety sensors were observed to be damaged and/or missing at the time of inspection. This condition is a significant safety concern because the automatic reverse safety system may not function properly to detect an obstruction in the path of the closing door, which increases the risk of injury or property damage. Current safety standards require automatic garage door openers to be equipped with a functional entrapment protection device, including photoelectric sensors installed in accordance with the manufacturer’s instructions and applicable safety requirements under UL 325. Recommend evaluation and repair by a qualified garage door contractor to restore proper and safe operation.
22) Rust corrosion was observed along the lower section of the garage door at the time of inspection. This condition appears consistent with prolonged moisture exposure and may lead to continued deterioration of the door material, reduced service life, and possible impairment of proper operation if not addressed. Recommend repair or replacement of the affected components as needed by a qualified contractor and continued monitoring for sources of moisture exposure.
Photo 22-1 Rust corrosion was observed along the lower section of the garage door at the time of inspection. This condition appears consistent with prolonged moisture exposure and may lead to continued deterioration of the door material, reduced service life, and possible impairment of proper operation if not addressed. Recommend repair or replacement of the affected components as needed by a qualified contractor and continued monitoring for sources of moisture exposure. Photo 22-2 Rust corrosion was observed along the lower section of the garage door at the time of inspection. This condition appears consistent with prolonged moisture exposure and may lead to continued deterioration of the door material, reduced service life, and possible impairment of proper operation if not addressed. Recommend repair or replacement of the affected components as needed by a qualified contractor and continued monitoring for sources of moisture exposure.
Photo 22-3 Rust corrosion was observed along the lower section of the garage door at the time of inspection. This condition appears consistent with prolonged moisture exposure and may lead to continued deterioration of the door material, reduced service life, and possible impairment of proper operation if not addressed. Recommend repair or replacement of the affected components as needed by a qualified contractor and continued monitoring for sources of moisture exposure.
23) One or more automatic vehicle door openers were inoperable. Recommend that a qualified contractor evaluate and repair or replace opener(s) as necessary.
Photo 23-1 One or more automatic vehicle door openers were inoperable. Recommend that a qualified contractor evaluate and repair or replace opener(s) as necessary. Photo 23-2 One or more automatic vehicle door openers were inoperable. Recommend that a qualified contractor evaluate and repair or replace opener(s) as necessary.
24) One or more automatic door openers were not plugged in or had no power. The inspector was unable to fully evaluate the automatic opener(s).
Photo 24-1 One or more automatic door openers were not plugged in or had no power. The inspector was unable to fully evaluate the automatic opener(s).
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 125
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum, Stranded copper
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: At main disconnect panel outside
Carbon monoxide alarms installed: No, recommend install
25) One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the kitchen wouldn't reset when tripped. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo 25-1 One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the kitchen wouldn't reset when tripped. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary. Photo 25-2 One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the kitchen wouldn't reset when tripped. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo 25-3 One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the kitchen wouldn't reset when tripped. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
26) One or more electric receptacles at the bathroom(s) had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
Outdoors (since 1973)
Bathrooms (since 1975)
Garages (since 1978)
Kitchens (since 1987)
Crawl spaces and unfinished basements (since 1990)
Photo 26-1 One or more electric receptacles at the bathroom(s) had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices.
27) Non-metallic sheathed wiring was loose, unsupported, or inadequately supported at one or more locations. Such wiring should be trimmed to length if necessary and attached to runners or to solid backing with fasteners at intervals of 4 1/2 feet or less. Fasteners should be installed within 12 inches of all enclosures. Recommend that a qualified electrician repair per standard building practices.
Photo 27-1 Non-metallic sheathed wiring was loose, unsupported, or inadequately supported at one or more locations. Such wiring should be trimmed to length if necessary and attached to runners or to solid backing with fasteners at intervals of 4 1/2 feet or less. Fasteners should be installed within 12 inches of all enclosures. Recommend that a qualified electrician repair per standard building practices.
28) One or more receptacles were worn. Worn receptacles can work intermittently or when the plug is wiggled. They can overheat or arc and spark due to loose connections. This is a potential fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.
Photo 28-1 One or more receptacles were worn. Worn receptacles can work intermittently or when the plug is wiggled. They can overheat or arc and spark due to loose connections. This is a potential fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.
29) One or more electric receptacles and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
Photo 29-1 One or more electric receptacles and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
30) One or more electric receptacles were incorrectly wired with an open neutral. Recommend that a qualified electrician repair as necessary.
Photo 30-1 One or more electric receptacles were incorrectly wired with an open neutral. Recommend that a qualified electrician repair as necessary. Photo 30-2 One or more electric receptacles were incorrectly wired with an open neutral. Recommend that a qualified electrician repair as necessary.
31) One or more light fixtures installed outside were loose and/or substandard. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair as necessary.
Photo 31-1 One or more light fixtures installed outside were loose and/or substandard. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair as necessary.
32) One or more smoke alarms were missing, damaged, or missing components. Smoke alarms should be replaced as necessary. For more information, visit: http://www.reporthost.com/?SMKALRM
Photo 32-1 One or more smoke alarms were missing, damaged, or missing components. Smoke alarms should be replaced as necessary.
33) Carbon monoxide alarms were missing on one or more levels. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit: http://www.reporthost.com/?COALRM
Photo 33-1 Carbon monoxide alarms were missing on one or more levels. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards.
34) One or more electrical outlets were observed to have no power at the time of inspection, and the associated GFCI device was not found to be tripped. This condition may indicate a disconnected outlet, an open circuit, a wiring defect, or another electrical fault that was not readily visible during the inspection. Because the outlet was not functioning as intended, its safety and proper operation could not be confirmed. Recommend further evaluation and repair as needed by a qualified electrician.
Photo 34-1 One or more electrical outlets were observed to have no power at the time of inspection, and the associated GFCI device was not found to be tripped. This condition may indicate a disconnected outlet, an open circuit, a wiring defect, or another electrical fault that was not readily visible during the inspection. Because the outlet was not functioning as intended, its safety and proper operation could not be confirmed. Recommend further evaluation and repair as needed by a qualified electrician.
35) The exterior doorbell button was missing at the time of inspection, with wiring/components visibly exposed at the mounting location. This condition leaves the doorbell system incomplete and may allow moisture intrusion or damage to the exposed components. Recommend repair or replacement by a qualified contractor.
Photo 35-1 The exterior doorbell button was missing at the time of inspection, with wiring/components visibly exposed at the mounting location. This condition leaves the doorbell system incomplete and may allow moisture intrusion or damage to the exposed components. Recommend repair or replacement by a qualified contractor.
36) A loose wire/cable was observed extending across the floor at the time of inspection. This condition appears unfinished and creates a trip hazard, and the exposed cable may be subject to damage from foot traffic or routine use of the room. Recommend evaluation and proper securing, termination, or removal by a qualified contractor as needed.
Photo 36-1 A loose wire/cable was observed extending across the floor at the time of inspection. This condition appears unfinished and creates a trip hazard, and the exposed cable may be subject to damage from foot traffic or routine use of the room. Recommend evaluation and proper securing, termination, or removal by a qualified contractor as needed.
37) The switch cover plate was observed to be missing a mounting screw at the time of inspection. This condition is a minor deficiency, but loose or incompletely secured cover plates may shift out of place and leave the switch assembly less securely protected. Recommend installation of the missing screw to properly secure the cover plate.
Photo 37-1 The switch cover plate was observed to be missing a mounting screw at the time of inspection. This condition is a minor deficiency, but loose or incompletely secured cover plates may shift out of place and leave the switch assembly less securely protected. Recommend installation of the missing screw to properly secure the cover plate.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 77 PSI
Location of main water shut-off: Under bathroom sink
Condition of supply lines: Appeared serviceable
Supply pipe material: PVC plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
38) No expansion tank was installed for the water supply system. Expansion tanks are recommended when a property is on a public water supply system and the property's water system is "closed" via a pressure reducing valve (PRV), check valve, or backflow preventer. No room for expansion of water exists in this type of system. Thermal expansion occurs when water is heated during non-use periods. In a closed system with no provision for expansion, its effects can include:
Backflow into the water main
Damage to water heater connections, gas water heater flue tubes and pumps serving washers and dishwashers
Leaking faucets
"Weeping" of water through the water heater temperature-pressure relief (TPR) valve
Noisy water hammer in the pipes
Expansion tanks can eliminate these problems by giving water a place to go when thermal expansion occurs. When a water heating cycle ends, or when any fixture is opened within the system, the impact of thermal expansion is reduced, and water drains out of the expansion tank back into the system. Recommend that a qualified plumber install an expansion tank per standard building practices.
Photo 38-1 No expansion tank was installed for the water supply system. Expansion tanks are recommended when a property is on a public water supply system and the property's water system is "closed" via a pressure reducing valve (PRV), check valve, or backflow preventer. No room for expansion of water exists in this type of system. Thermal expansion occurs when water is heated during non-use periods.
39) The exterior hose bib was observed to be damaged and incomplete at the time of inspection, with the operating handle missing. This condition may prevent proper operation of the fixture and can make it difficult to fully control water flow or shut the fixture off as intended. Recommend repair or replacement by a qualified contractor.
Photo 39-1 The exterior hose bib was observed to be damaged and incomplete at the time of inspection, with the operating handle missing. This condition may prevent proper operation of the fixture and can make it difficult to fully control water flow or shut the fixture off as intended. Recommend repair or replacement by a qualified contractor.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Required repair, replacement and/or evaluation (see comments below)
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Garage
Hot water temperature tested: Yes
40) The water heater was observed to be producing no hot water at the time of inspection and also exhibited visible signs of tampering, including removed or open access areas exposing internal components. This condition indicates the unit was not functioning as intended and raises concern that prior unauthorized adjustment, disassembly, or incomplete repair may have affected safe and proper operation. Because the system was not producing hot water and appeared to have been altered, the water heater could not be confirmed as serviceable at the time of inspection. Recommend prompt evaluation and repair or replacement as needed by a qualified plumber.
Photo 40-1 The water heater was observed to be producing no hot water at the time of inspection and also exhibited visible signs of tampering, including removed or open access areas exposing internal components. This condition indicates the unit was not functioning as intended and raises concern that prior unauthorized adjustment, disassembly, or incomplete repair may have affected safe and proper operation. Because the system was not producing hot water and appeared to have been altered, the water heater could not be confirmed as serviceable at the time of inspection. Recommend prompt evaluation and repair or replacement as needed by a qualified plumber. Photo 40-2 The water heater was observed to be producing no hot water at the time of inspection and also exhibited visible signs of tampering, including removed or open access areas exposing internal components. This condition indicates the unit was not functioning as intended and raises concern that prior unauthorized adjustment, disassembly, or incomplete repair may have affected safe and proper operation. Because the system was not producing hot water and appeared to have been altered, the water heater could not be confirmed as serviceable at the time of inspection. Recommend prompt evaluation and repair or replacement as needed by a qualified plumber.
Photo 40-3 The water heater was observed to be producing no hot water at the time of inspection and also exhibited visible signs of tampering, including removed or open access areas exposing internal components. This condition indicates the unit was not functioning as intended and raises concern that prior unauthorized adjustment, disassembly, or incomplete repair may have affected safe and proper operation. Because the system was not producing hot water and appeared to have been altered, the water heater could not be confirmed as serviceable at the time of inspection. Recommend prompt evaluation and repair or replacement as needed by a qualified plumber. Photo 40-4 The water heater was observed to be producing no hot water at the time of inspection and also exhibited visible signs of tampering, including removed or open access areas exposing internal components. This condition indicates the unit was not functioning as intended and raises concern that prior unauthorized adjustment, disassembly, or incomplete repair may have affected safe and proper operation. Because the system was not producing hot water and appeared to have been altered, the water heater could not be confirmed as serviceable at the time of inspection. Recommend prompt evaluation and repair or replacement as needed by a qualified plumber.
41) Insulation was missing from one or more accessible hot water supply lines at the water heater at the time of inspection. Missing insulation can contribute to heat loss, reduced energy efficiency, and delayed hot water delivery at plumbing fixtures. Recommend installation of proper pipe insulation by a qualified contractor.
Photo 41-1 Insulation was missing from one or more accessible hot water supply lines at the water heater at the time of inspection. Missing insulation can contribute to heat loss, reduced energy efficiency, and delayed hot water delivery at plumbing fixtures. Recommend installation of proper pipe insulation by a qualified contractor.
42) Significant corrosion or rust was found on the water heater tank casing. This is an indication that the water heater is near or at the end of its service life. At a minimum, monitor this water heater and budget for a replacement in the near future. Consider replacing the water heater now before any leaks occur. Significant flooding can occur if the water heater does fail.
Photo 42-1 Significant corrosion or rust was found on the water heater tank casing. This is an indication that the water heater is near or at the end of its service life. At a minimum, monitor this water heater and budget for a replacement in the near future. Consider replacing the water heater now before any leaks occur. Significant flooding can occur if the water heater does fail.
43) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo 43-1 The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Location of forced air furnace: Attic
Condition of furnace filters: Required replacement
Location for forced air filter(s): None visible
Condition of forced air ducts and registers: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior
Type: Split system
Condition of controls: Required repair, replacement and/or evaluation (see comments below)
44) The gas furnace flue vent connector was observed to be improperly installed at the furnace connection point, with an open gap present around the flue penetration at the top of the unit at the time of inspection. This condition is a safety concern because improper venting can allow combustion gases, including carbon monoxide, to escape from the venting system rather than being safely discharged to the exterior. Recommend prompt evaluation and correction by a qualified HVAC contractor to ensure the flue is properly secured and venting as intended.
Photo 44-1 The gas furnace flue vent connector was observed to be improperly installed at the furnace connection point, with an open gap present around the flue penetration at the top of the unit at the time of inspection. This condition is a safety concern because improper venting can allow combustion gases, including carbon monoxide, to escape from the venting system rather than being safely discharged to the exterior. Recommend prompt evaluation and correction by a qualified HVAC contractor to ensure the flue is properly secured and venting as intended.
45) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo 45-1 The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future. Photo 45-2 The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
46) One or more heating or cooling air supply registers had a weak air flow, or no apparent flow. This may result in an inadequate air supply to some rooms. Adjustable damper(s) in ducts may exist and be adjusted to improve the flow. Adjusting register controls may also help to improve the flow. If such adjustments don't result in a balanced flow to registers, have a qualified HVAC contractor evaluate and repair or make modifications as necessary.
Photo 46-1 One or more heating or cooling air supply registers had a weak air flow, or no apparent flow. This may result in an inadequate air supply to some rooms. Adjustable damper(s) in ducts may exist and be adjusted to improve the flow. Adjusting register controls may also help to improve the flow. If such adjustments don't result in a balanced flow to registers, have a qualified HVAC contractor evaluate and repair or make modifications as necessary.
47) One or more HVAC ceiling supply registers were observed to be inoperable and would not open at the time of inspection. This condition may restrict proper air distribution into the affected area and can reduce overall system performance and comfort. Recommend evaluation and repair or replacement as needed by a qualified HVAC contractor.
Photo 47-1 One or more HVAC ceiling supply registers were observed to be inoperable and would not open at the time of inspection. This condition may restrict proper air distribution into the affected area and can reduce overall system performance and comfort. Recommend evaluation and repair or replacement as needed by a qualified HVAC contractor.
48) One or more condensate drain lines were observed to terminate at or immediately adjacent to the exterior wall of the home at the time of inspection. This discharge location is substandard because condensate moisture may repeatedly wet the exterior cladding and surrounding components, which can contribute to staining, material deterioration, and possible moisture intrusion over time. Recommend correction by a qualified HVAC contractor to extend the condensate discharge to an appropriate termination point away from the structure.
Photo 48-1 One or more condensate drain lines were observed to terminate at or immediately adjacent to the exterior wall of the home at the time of inspection. This discharge location is substandard because condensate moisture may repeatedly wet the exterior cladding and surrounding components, which can contribute to staining, material deterioration, and possible moisture intrusion over time. Recommend correction by a qualified HVAC contractor to extend the condensate discharge to an appropriate termination point away from the structure.
49) Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.
Photo 49-1 Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.
50) The digital display on the thermostat was dim or displayed readings in a substandard way. This may be caused by a low or dead battery. The batteries should be replaced. If this condition persists after replacing the batteries, then recommend that a qualified HVAC contractor evaluate and repair or replace as necessary.
Photo 50-1 The digital display on the thermostat was dim or displayed readings in a substandard way. This may be caused by a low or dead battery. The batteries should be replaced. If this condition persists after replacing the batteries, then recommend that a qualified HVAC contractor evaluate and repair or replace as necessary.
51) Rust corrosion was observed on the exterior HVAC condenser fan guard and surrounding metal components at the time of inspection. Corrosion can contribute to ongoing deterioration of the affected components and may eventually impact the durability and proper protection of the condenser fan assembly. Recommend evaluation and repair or replacement of corroded components as needed by a qualified HVAC contractor.
Photo 51-1 Rust corrosion was observed on the exterior HVAC condenser fan guard and surrounding metal components at the time of inspection. Corrosion can contribute to ongoing deterioration of the affected components and may eventually impact the durability and proper protection of the condenser fan assembly. Recommend evaluation and repair or replacement of corroded components as needed by a qualified HVAC contractor.
52) One or more condensate drain lines in the attic were observed to have improper slope at the time of inspection. Condensate drain lines are intended to maintain continuous downward pitch to promote proper drainage, and improper slope may allow water to collect within the line, increasing the risk of slow drainage, overflow, leakage, or secondary moisture-related damage. Recommend evaluation and correction by a qualified HVAC contractor to ensure proper drainage.
Photo 52-1 One or more condensate drain lines in the attic were observed to have improper slope at the time of inspection. Condensate drain lines are intended to maintain continuous downward pitch to promote proper drainage, and improper slope may allow water to collect within the line, increasing the risk of slow drainage, overflow, leakage, or secondary moisture-related damage. Recommend evaluation and correction by a qualified HVAC contractor to ensure proper drainage. Photo 52-2 One or more condensate drain lines in the attic were observed to have improper slope at the time of inspection. Condensate drain lines are intended to maintain continuous downward pitch to promote proper drainage, and improper slope may allow water to collect within the line, increasing the risk of slow drainage, overflow, leakage, or secondary moisture-related damage. Recommend evaluation and correction by a qualified HVAC contractor to ensure proper drainage.
53) Air filters for the heating and/or cooling system were missing at one or more locations where they should have been installed. Indoor air quality will be reduced as a result. Recommend installing good quality filters at intended locations (e.g. in or at the air handler, behind return air grills). Filters should be sized correctly to minimize air gaps. Many types of filters are available. Recommend installing pleated filters or better rather than the cheapest disposable kind. For more information, visit: http://www.reporthost.com/?FLTRTPS
54) The HVAC system was observed to produce both hot and cold air at the time of inspection, and the accessible air supply components appeared serviceable under the operating conditions present at the time of the inspection.
Photo 54-1 The HVAC system was observed to produce both hot and cold air at the time of inspection, and the accessible air supply components appeared serviceable under the operating conditions present at the time of the inspection. Photo 54-2 The HVAC system was observed to produce both hot and cold air at the time of inspection, and the accessible air supply components appeared serviceable under the operating conditions present at the time of the inspection.
Photo 54-3 The HVAC system was observed to produce both hot and cold air at the time of inspection, and the accessible air supply components appeared serviceable under the operating conditions present at the time of the inspection. Photo 54-4 The HVAC system was observed to produce both hot and cold air at the time of inspection, and the accessible air supply components appeared serviceable under the operating conditions present at the time of the inspection.
Photo 54-5 The HVAC system was observed to produce both hot and cold air at the time of inspection, and the accessible air supply components appeared serviceable under the operating conditions present at the time of the inspection. Photo 54-6 The HVAC system was observed to produce both hot and cold air at the time of inspection, and the accessible air supply components appeared serviceable under the operating conditions present at the time of the inspection.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Gas fireplace or stove type: Insert
55) Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit: http://www.reporthost.com/?ANGFINSP
Photo 55-1 Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Required repair, replacement and/or evaluation (see comments below)
Condition of dishwasher: Required repair, replacement and/or evaluation (see comments below)
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Natural gas
Type of ventilation: Microwave
Condition of refrigerator: Required repair, replacement and/or evaluation (see comments below)
Condition of built-in microwave oven: Appeared serviceable
56) The dishwasher was inoperable. Recommend that a qualified specialist evaluate and repair or replace as necessary.
Photo 56-1 The dishwasher was inoperable. Recommend that a qualified specialist evaluate and repair or replace as necessary.
57) One or more cabinets, drawers and/or cabinet doors were difficult to open. Recommend that a qualified person repair or replace as necessary.
Photo 57-1 One or more cabinets, drawers and/or cabinet doors were difficult to open. Recommend that a qualified person repair or replace as necessary.
58) The under-sink food disposal was jammed. Recommend that a qualified contractor repair or replace as necessary.
Photo 58-1 The under-sink food disposal was jammed. Recommend that a qualified contractor repair or replace as necessary.
59) The refrigerator was not properly cooling. Appears the cooling components froze up. Recommend that a qualified person repair as necessary. The refrigerator may need replacing.
Photo 59-1 The refrigerator was not properly cooling. Appears the cooling components froze up. Recommend that a qualified person repair as necessary. The refrigerator may need replacing. Photo 59-2 The refrigerator was not properly cooling. Appears the cooling components froze up. Recommend that a qualified person repair as necessary. The refrigerator may need replacing.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Central exhaust fan
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes
60) The master bathroom toilet was observed with the water supply shut off at the time of inspection, and a board had been affixed to the ceiling area directly below this fixture. These conditions are suspicious for a prior or active plumbing leak and prevented confirmation of proper toilet operation and the condition of concealed components. The covered ceiling area below may be concealing moisture-related damage or previous repair activity associated with leakage from the toilet, water supply connection, drain, or wax seal. Recommend prompt evaluation by a qualified plumber and further evaluation of the concealed ceiling area below by a qualified contractor, with repairs made as needed based on findings.
Photo 60-1 The master bathroom toilet was observed with the water supply shut off at the time of inspection, and a board had been affixed to the ceiling area directly below this fixture. These conditions are suspicious for a prior or active plumbing leak and prevented confirmation of proper toilet operation and the condition of concealed components. The covered ceiling area below may be concealing moisture-related damage or previous repair activity associated with leakage from the toilet, water supply connection, drain, or wax seal. Recommend prompt evaluation by a qualified plumber and further evaluation of the concealed ceiling area below by a qualified contractor, with repairs made as needed based on findings. Photo 60-2 The master bathroom toilet was observed with the water supply shut off at the time of inspection, and a board had been affixed to the ceiling area directly below this fixture. These conditions are suspicious for a prior or active plumbing leak and prevented confirmation of proper toilet operation and the condition of concealed components. The covered ceiling area below may be concealing moisture-related damage or previous repair activity associated with leakage from the toilet, water supply connection, drain, or wax seal. Recommend prompt evaluation by a qualified plumber and further evaluation of the concealed ceiling area below by a qualified contractor, with repairs made as needed based on findings.
61) Active leakage was observed at one or more bathroom vanity sink drain lines at the time of inspection. This condition is a plumbing defect that can result in ongoing moisture intrusion, deterioration of vanity cabinets and adjacent building materials, concealed damage, and conditions conducive to microbial growth if not promptly corrected. Continued leakage may also damage finishes and subfloor materials beneath the affected fixtures. Recommend prompt evaluation and repair by a qualified plumber.
Photo 61-1 Active leakage was observed at one or more bathroom vanity sink drain lines at the time of inspection. This condition is a plumbing defect that can result in ongoing moisture intrusion, deterioration of vanity cabinets and adjacent building materials, concealed damage, and conditions conducive to microbial growth if not promptly corrected. Continued leakage may also damage finishes and subfloor materials beneath the affected fixtures. Recommend prompt evaluation and repair by a qualified plumber. Photo 61-2 Active leakage was observed at one or more bathroom vanity sink drain lines at the time of inspection. This condition is a plumbing defect that can result in ongoing moisture intrusion, deterioration of vanity cabinets and adjacent building materials, concealed damage, and conditions conducive to microbial growth if not promptly corrected. Continued leakage may also damage finishes and subfloor materials beneath the affected fixtures. Recommend prompt evaluation and repair by a qualified plumber.
Photo 61-3 Active leakage was observed at one or more bathroom vanity sink drain lines at the time of inspection. This condition is a plumbing defect that can result in ongoing moisture intrusion, deterioration of vanity cabinets and adjacent building materials, concealed damage, and conditions conducive to microbial growth if not promptly corrected. Continued leakage may also damage finishes and subfloor materials beneath the affected fixtures. Recommend prompt evaluation and repair by a qualified plumber. Photo 61-4 Active leakage was observed at one or more bathroom vanity sink drain lines at the time of inspection. This condition is a plumbing defect that can result in ongoing moisture intrusion, deterioration of vanity cabinets and adjacent building materials, concealed damage, and conditions conducive to microbial growth if not promptly corrected. Continued leakage may also damage finishes and subfloor materials beneath the affected fixtures. Recommend prompt evaluation and repair by a qualified plumber.
Photo 61-5 Active leakage was observed at one or more bathroom vanity sink drain lines at the time of inspection. This condition is a plumbing defect that can result in ongoing moisture intrusion, deterioration of vanity cabinets and adjacent building materials, concealed damage, and conditions conducive to microbial growth if not promptly corrected. Continued leakage may also damage finishes and subfloor materials beneath the affected fixtures. Recommend prompt evaluation and repair by a qualified plumber. Photo 61-6 Active leakage was observed at one or more bathroom vanity sink drain lines at the time of inspection. This condition is a plumbing defect that can result in ongoing moisture intrusion, deterioration of vanity cabinets and adjacent building materials, concealed damage, and conditions conducive to microbial growth if not promptly corrected. Continued leakage may also damage finishes and subfloor materials beneath the affected fixtures. Recommend prompt evaluation and repair by a qualified plumber.
62) The bathtub was observed to be missing the overflow drain cover and the tub stopper assembly at the time of inspection. Missing drain components leave the fixture incomplete and may allow improper operation of the tub drain and overflow system, while also leaving openings that are not properly finished or protected. Recommend repair or replacement of the missing components by a qualified contractor.
Photo 62-1 The bathtub was observed to be missing the overflow drain cover and the tub stopper assembly at the time of inspection. Missing drain components leave the fixture incomplete and may allow improper operation of the tub drain and overflow system, while also leaving openings that are not properly finished or protected. Recommend repair or replacement of the missing components by a qualified contractor. Photo 62-2 The bathtub was observed to be missing the overflow drain cover and the tub stopper assembly at the time of inspection. Missing drain components leave the fixture incomplete and may allow improper operation of the tub drain and overflow system, while also leaving openings that are not properly finished or protected. Recommend repair or replacement of the missing components by a qualified contractor.
Photo 62-3 The bathtub was observed to be missing the overflow drain cover and the tub stopper assembly at the time of inspection. Missing drain components leave the fixture incomplete and may allow improper operation of the tub drain and overflow system, while also leaving openings that are not properly finished or protected. Recommend repair or replacement of the missing components by a qualified contractor.
63) Caulk was missing around the tub spout at the time of inspection. Missing sealant at this location may allow water to enter the wall assembly during normal use, which can contribute to concealed moisture intrusion, deterioration of surrounding materials, and potential microbial growth over time. Recommend sealing the tub spout penetration properly with appropriate caulking by a qualified contractor.
Photo 63-1 Caulk was missing around the tub spout at the time of inspection. Missing sealant at this location may allow water to enter the wall assembly during normal use, which can contribute to concealed moisture intrusion, deterioration of surrounding materials, and potential microbial growth over time. Recommend sealing the tub spout penetration properly with appropriate caulking by a qualified contractor.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Glass panel
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Metal
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Laminate
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
64) Handrails at one or more flights of stairs were loose and/or wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo 64-1 Handrails at one or more flights of stairs were loose and/or wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary. Photo 64-2 Handrails at one or more flights of stairs were loose and/or wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
65) Guardrails at one or more locations with drop-offs higher than 30 inches were loose and/or wobbly, and pose a fall hazard. Recommend that a qualified person repair guardrails as necessary.
Photo 65-1 Guardrails at one or more locations with drop-offs higher than 30 inches were loose and/or wobbly, and pose a fall hazard. Recommend that a qualified person repair guardrails as necessary.
66) Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary. For more information, visit: http://www.reporthost.com/?SQUEAK
Photo 66-1 Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary. Photo 66-2 Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary.
Photo 66-3 Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary. Photo 66-4 Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary.
67) Some interior door hardware (door stoppers) were missing. Recommend that a qualified person repair or replace as necessary.
Photo 67-1 Some interior door hardware (door stoppers) were missing. Recommend that a qualified person repair or replace as necessary. Photo 67-2 Some interior door hardware (door stoppers) were missing. Recommend that a qualified person repair or replace as necessary.
Photo 67-3 Some interior door hardware (door stoppers) were missing. Recommend that a qualified person repair or replace as necessary.
68) One or more window screens were damaged or deteriorated. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.
Photo 68-1 One or more window screens were damaged or deteriorated. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary. Photo 68-2 One or more window screens were damaged or deteriorated. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.
69) Fixtures such as closet shelving were loose and/or damaged. Recommend that a qualified person repair or replace as necessary.
Photo 69-1 Fixtures such as closet shelving were loose and/or damaged. Recommend that a qualified person repair or replace as necessary. Photo 69-2 Fixtures such as closet shelving were loose and/or damaged. Recommend that a qualified person repair or replace as necessary.
Photo 69-3 Fixtures such as closet shelving were loose and/or damaged. Recommend that a qualified person repair or replace as necessary. Photo 69-4 Fixtures such as closet shelving were loose and/or damaged. Recommend that a qualified person repair or replace as necessary.
70) One or more guardrail balusters were observed to be substandard at the time of inspection. The spacing and/or installation of the balusters did not appear to provide the level of opening limitation generally intended for guard assemblies, which is a safety concern because openings in guards are not permitted to allow passage of a 4-inch sphere under 2021 IRC Section R312.1.3. Substandard guard balusters may increase the risk of a child passing through or becoming entrapped. Recommend evaluation and correction by a qualified contractor to ensure the guard assembly is properly installed and safely configured.
Photo 70-1 One or more guardrail balusters were observed to be substandard at the time of inspection. The spacing and/or installation of the balusters did not appear to provide the level of opening limitation generally intended for guard assemblies, which is a safety concern because openings in guards are not permitted to allow passage of a 4-inch sphere under 2021 IRC Section R312.1.3. Substandard guard balusters may increase the risk of a child passing through or becoming entrapped. Recommend evaluation and correction by a qualified contractor to ensure the guard assembly is properly installed and safely configured.
71) One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.
Photo 71-1 One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets. Photo 71-2 One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.
Photo 71-3 One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.
72) One or more interior door knobs were observed to be installed backwards, with the locking mechanism facing the exterior side of the room instead of the interior, at the time of inspection. This improper installation is a functional deficiency that may impair intended privacy and proper operation of the door hardware. Recommend correction by a qualified contractor to ensure the door hardware is installed in its intended orientation and functions properly.
Photo 72-1 One or more interior door knobs were observed to be installed backwards, with the locking mechanism facing the exterior side of the room instead of the interior, at the time of inspection. This improper installation is a functional deficiency that may impair intended privacy and proper operation of the door hardware. Recommend correction by a qualified contractor to ensure the door hardware is installed in its intended orientation and functions properly. Photo 72-2 One or more interior door knobs were observed to be installed backwards, with the locking mechanism facing the exterior side of the room instead of the interior, at the time of inspection. This improper installation is a functional deficiency that may impair intended privacy and proper operation of the door hardware. Recommend correction by a qualified contractor to ensure the door hardware is installed in its intended orientation and functions properly.
73) Lock mechanisms on one or more windows were missing. This can pose a security risk. Recommend that a qualified person repair as necessary.
Photo 73-1 Lock mechanisms on one or more windows were missing. This can pose a security risk. Recommend that a qualified person repair as necessary.
74) One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-1 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-2 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-3 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-4 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-5 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-6 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-7 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-8 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-9 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-10 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-11 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-12 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-13 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-14 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-15 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made. Photo 74-16 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
Photo 74-17 One or more walls and ceilings in the home exhibited visible blemishes, surface irregularities, nail pops, loose drywall tape, and/or substandard finishing at the time of inspection. In many cases, these conditions appear cosmetic in nature and may be consistent with normal settlement, incomplete finishing, or workmanship deficiencies; however, where staining or discoloration is present, a moisture-related cause cannot be fully ruled out without further evaluation. Any stained areas appeared dry at the time of inspection unless otherwise noted; however, concealed moisture intrusion may not always be visible during a limited visual inspection. Recommend repair of the visible finish deficiencies and further evaluation of any suspect stained areas to determine whether an underlying moisture source is present before cosmetic repairs are made.
75) Base/shoe molding was missing at one or more wall sections at the time of inspection. This condition is primarily a finish deficiency and leaves the wall-to-floor transition incomplete, which may detract from the overall fit and finish of the area. Recommend installation of the missing molding by a qualified contractor.
Photo 75-1 Base/shoe molding was missing at one or more wall sections at the time of inspection. This condition is primarily a finish deficiency and leaves the wall-to-floor transition incomplete, which may detract from the overall fit and finish of the area. Recommend installation of the missing molding by a qualified contractor. Photo 75-2 Base/shoe molding was missing at one or more wall sections at the time of inspection. This condition is primarily a finish deficiency and leaves the wall-to-floor transition incomplete, which may detract from the overall fit and finish of the area. Recommend installation of the missing molding by a qualified contractor.