Inspector: William Corbett

Summary Page

Property Inspection Report
Client(s): Sample Report
Property address: xxxx XXXX Drive Birmingham, AL 35242
Inspection date: Saturday, August 23, 2008

This summary page published on 5/19/2009 6:19:53 PM CDT

Return to report

Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection only involves a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 
 
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

1) General Information:   - Hornet, bee and/or wasp nests were found in one or more areas, including the exterior. These can pose a safety hazard. Nests should be removed as necessary.

2) General Information:   - Evidence of rodent infestation was found in the form of feces, poison in one or more areas including the attic. Recommend consulting with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.cdc.gov/rodents/prevent_rodents/seal_up.htm
http://www.cdc.gov/rodents/prevent_rodents/trap_up.htm
http://www.cdc.gov/rodents/prevent_rodents/clean_up.htm

4) Grounds:   - Exterior stairs were substandard. A qualified person should evaluate and repair or replace as necessary.

5) Grounds:   - One or more sets of stairs were unstable due to lack of bracing. A qualified contractor should evaluate and repair as necessary. For example, by installing additional bracing or supports.

6) Grounds: - Flashing was missing from above one or more deck ledger boards. This can cause moisture to accumulate between the ledger board(s) and the building. Rot may result in this area and cause the ledger board fasteners to fail. The deck may separate from the building in this event and poses a significant safety hazard. A qualified contractor should install flashing above ledger board(s) where necessary. For more information on installing deck ledger boards visit:
http://www.hometime.com/Howto/projects/decks/deck_4.htm

And for more information on building safe decks in general, visit: http://www.thisoldhouse.com/toh/knowhow/exteriors/article/0,16417,212625,00.html

7) Grounds:   - Guardrails in one or more areas were damaged, loose. This is a safety hazard. A qualified person should repair or replace as necessary, and as per standard building practices.

8) Grounds:   - Handrails at one or more flights of stairs were wobbly, substandard. This is a safety hazard. Standard building practices require that handrails be:

  • Installed at stairs with three or more risers
  • Sized and shaped so your hand can encircle them
  • Permanently and securely attached, and able to withstand a 200 pound force in any direction at any point
  • Continuous and extend for the entire flight of the stairs
  • Located between 30 and 38 inches above the leading edge of the stair treads

    A qualified person should repair, replace or install as necessary and as per standard building practices.
    9) Grounds:   - One or more retaining walls higher than three feet were found on this property and guardrails or barriers were missing. This is a safety hazard due to the risk of falling. At a minimum, the client should be aware of this hazard, especially when children are present. Ideally a qualified contractor should install adequate guardrails or make modifications to existing barriers as necessary above retaining walls higher than 3 feet to eliminate fall hazards. Dense shrubbery or vegetation may be acceptable as a barrier, but only when mature enough to be effective.

    10) Grounds:   - One or more decks, porches and/or balconies were with loose fasteners or decking boards. A qualified person should evaluate and repair or replace as necessary.

    11) Grounds: - One or more large tree stumps were close to the building exterior. Wood destroying insects such as carpenter ants nest in such stumps and are more likely to infest the building as a result. Recommend having large tree stumps within a few feet from the building removed, by a qualified tree service contractor if necessary.

    12) Grounds:   - Minor cracks and/or deterioration were found in one or more retaining walls. Recommend repairing cracks with mortar, elastomeric sealant, or other suitable material to prevent water intrusion and further deterioration. The client should monitor such walls in the future for continued deterioration (cracking, leaning, bowing, etc.). Repairs and/or replacement by a qualified contractor may be necessary in the future.

    13) Grounds: - Vegetation such as trees, shrubs and/or vines was in contact with or less than one foot from the building exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the building exterior.

    14) Grounds:   - Vegetation was overgrown around equipment for one or more utilities, such as gas or electric meters. Vegetation should be pruned or removed as necessary to allow unobstructed access.

    15) Grounds:   - One or more significantly sized diseased or dead trees were found on the property grounds. The client may wish to have them removed, or to have them evaluated by a qualified arborist.

    18) Exterior / Foundation:   - Some sections of siding and/or trim were damaged by wood boring bees. A qualified person should evaluate and repair, replace or install as necessary.

    19) Exterior / Foundation:   - Minor cracks or deterioration were found in one or more sections of brick veneer. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.

    20) Exterior / Foundation:   - Wooden support posts were not securely fastened to beams above. This is a safety hazard since they can separate during a seismic event. A qualified contractor should evaluate and make repairs as necessary, such as installing metal ties, bracing with lumber and/or plywood gussets as per standard building practices.

    21) Exterior / Foundation:   - Gaps existed at one or more openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and entry by vermin.

    22) Exterior / Foundation: - Caulk was missing, deteriorated around windows, around doors, at siding butt joints, at siding-trim junctions, at wall penetrations. A qualified person should repair or replace as necessary. For more information, visit:
    http://www.reporthost.com/_docs/FPL_Caulking_Ins_Outs.pdf

    24) Roof / Attic:   - One or more downspouts or downspout extensions drained onto walkways. This may result in ice or moss forming on walkways, and may pose a fall hazard. A qualified person should evaluate and install or modify extensions as necessary so rainwater isn't directed onto walkways.

    25) Roof / Attic:   - Recessed "can" lights that are not rated for contact with insulation were installed in the ceiling below the attic. One or more of these lights are in contact with insulation. This is a fire hazard. Insulation should be moved, and wells or barriers should be installed or repaired as necessary to keep the insulation away from these lights as per the manufacturer's installation instructions.

    26) Roof / Attic: - Roof repairs were needed because some composition shingles had the following conditions: lifting, damage. Leaks may occur as a result. A qualified contractor should evaluate and repair as necessary.

    27) Roof / Attic: - Extensions such as splashblocks or drain pipes for some downspouts were substandard. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair, replace or install as necessary

    28) Roof / Attic:   - Some downspouts were substandard. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair as necessary.

    29) Roof / Attic: - The siding on one or more exterior walls above lower roof sections was in contact with or had less than a one inch gap between it and the roof surface below. A gap of at least one inch is recommended so water isn't wicked up into the siding from the shingles below, and also to provide room for additional layers of roofing materials when the current roof surface fails. Recommend having a qualified contractor make repairs as necessary, such as trimming siding, so at least a one inch gap exists between the siding and the roofing below where necessary.

    30) Roof / Attic: - Paper facing on batt insulation was oriented towards open spaces, rather than against interior space surfaces. The paper facing acts as a vapor barrier, and if located away from the interior surfaces, can trap moisture from condensation in the cavity between the paper facing and the interior spaces. This is a conducive condition for wood destroying insects. The inspector was unable to evaluate the structure obscured by the insulation. The insulation should be reinstalled or replaced by a qualified person, and as per the manufacturer's instructions.

    31) Roof / Attic:   - The ceiling insulation in some areas of the attic was uneven. This may result in increased heating or cooling costs due to decreased energy efficiency. A qualified person should repair, replace or install insulation as necessary. For more information, visit:
    http://www.eere.energy.gov/consumer/tips/insulation.html

    32) Roof / Attic:   - No weatherstrip was installed around the attic access hatch. Weatherstrip should be installed around the hatch to prevent heated interior air from entering attic. For more information, visit:
    http://www.reporthost.com/_docs/atticaccess.pdf

    33) Roof / Attic: - Debris had accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the building exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

    34) Roof / Attic: - One or more downspouts are clogged with debris. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the building exterior or make water accumulate around the foundation. Downspouts should be cleared now and as necessary in the future.

    38) Garage / Carport:   - The auto-reverse mechanism on the vehicle door opener needs adjustment. This is a safety hazard, especially for small children. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
    http://www.cpsc.gov/cpscpub/pubs/523.html
    http://www.ohdstl.com/safety.html

    39) Garage / Carport:   - Weatherstrip around or at the base of the garage-dwelling door was missing. A qualified person should repair or replace as necessary to prevent vehicle fumes from entering living spaces.

    41) Electric:   - One or more kitchen electric receptacles and/or the boxes they are installed in were loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.

    42) Electric:   - Some light fixtures were loose. A qualified person should evaluate and repair or replace as necessary.

    43) Electric:   - Lamp holders or light fixtures with fully or partially exposed bulbs were installed in one or more closets or attic spaces. This is a safety hazard due to the risk of fire. Flammable stored items may come into contact with hot bulbs, and hot fragments from broken bulbs may fall on combustible materials. Standard building practices require closet lighting to use fluorescent light fixtures, or to use fully enclosed incandescent fixtures. Installing a compact fluorescent lamp in a lamp holder is not an acceptable practice. A qualified electrician should replace closet lights as necessary and as per standard building practices.

    44) Electric:   - This property had one or more fuel burning appliances and/or an attached garage, and no carbon monoxide detectors were visible. This is a safety hazard. Recommend installing one or more carbon monoxide detectors as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

    45) Electric:   - One or more wall-mounted exterior light fixtures had wiring that's subject to water intrusion due to caulk not being installed around the light fixture's back plate. Caulk should be applied around the perimeter of back plates where missing. A gap should be left at the bottom for condensation to drain out.

    46) Electric:   - Some light fixtures were inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner. Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.

    48) Plumbing / Fuel Systems:   - All water supply pipes in the attic, basement were uninsulated. Recommend insulating pipes as per standard building practices for better energy efficiency and to prevent water pipes from freezing.

    50) Water Heater:   - This water heater was not fully evaluated because the following condition(s) existed: gas supply turned off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the appliance is operable. Note that as per the standards of practice for NACHI (http://www.nachi.org) and ASHI (www.ashi.org), the inspector is not required to operate shut-off valves, pilot lights or overcurrent protection devices, or any controls other than "normal controls".

    51) Heating:   - The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit: http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

    52) Heating:   - One or more air filters were dirty. A qualified person should replace filter(s) as necessary. Filters should be checked monthly and maintained as necessary in the future.

    53) Heating:   - This heating system was not fully evaluated because the following condition(s) existed for the furnace: gas supply turned off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that as per the standards of practice for NACHI (http://www.nachi.org) and ASHI (www.ashi.org), the inspector is not required to operate shut-off valves, pilot lights or overcurrent protection devices, or any controls other than "normal controls".

    54) Heating 2:   - The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit: http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

    55) Heating 2:   - One or more air filters were dirty. A qualified person should replace filter(s) as necessary. Filters should be checked monthly and maintained as necessary in the future.

    56) Heating 2:   - This heating system was not fully evaluated because the following condition(s) existed for the furnace: gas supply turned off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that as per the standards of practice for NACHI (http://www.nachi.org) and ASHI (www.ashi.org), the inspector is not required to operate shut-off valves, pilot lights or overcurrent protection devices, or any controls other than "normal controls".

    57) Cooling / Heat Pump:   - The cooling fins at the heat pump were dirty. A qualified person should clean fins as necessary.

    58) Cooling / Heat Pump:   - The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.

    59) Cooling / Heat Pump:   - One or more air filters were dirty. A qualified person should replace filter(s) as necessary. Filters should be checked monthly and maintained as necessary in the future.

    60) Cooling / Heat Pump 2:   - The cooling fins at the heat pump were dirty. A qualified person should clean fins as necessary.

    61) Cooling / Heat Pump 2:   - The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.

    62) Cooling / Heat Pump 2:   - One or more air filters were dirty. A qualified person should replace filter(s) as necessary. Filters should be checked monthly and maintained as necessary in the future.

    64) Kitchen:   - Caulk was deteriorated where counters meet backsplashes. A qualified person should repair as necessary.

    65) Bathrooms / Laundry / Sinks:   - The clothes dryer exhaust duct was damaged. Air flow will be restricted as a result. This is a safety hazard due to the risk of fire. A qualified person should evaluate and replace or repair as necessary. For more information, visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
    http://chimneykeepers.com/dryerclean.html

    66) Bathrooms / Laundry / Sinks: - The toilet at location #D was loose. A qualified contractor should remove the toilet(s) for further evaluation and repairs if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.

    67) Bathrooms / Laundry / Sinks: - Moderate deterioration or damage was found in the tiled shower enclosure, including cracked, missing grout. A qualified contractor should evaluate and repair as necessary. Note that damage to the wall or other structures behind this tile may be found upon further evaluation, and additional repairs may be needed.

    68) Bathrooms / Laundry / Sinks:   - Water damage was found in the shelving or cabinet components below one or more sinks at location #C, D. A qualified contractor should evaluate and make repairs as necessary.

    69) Bathrooms / Laundry / Sinks:   - The shower head at location #A was missing. A qualified person should repair or replace as necessary.

    70) Bathrooms / Laundry / Sinks: - Caulk was missing by the floor, wall, fixtures at the bathtub at location #A, C, D, E. A qualified person should repair as necessary.

    71) Bathrooms / Laundry / Sinks:   - Caulk was deteriorated at the counter backsplash at location #A, C, D, E. A qualified person should repair as necessary.

    73) Interior Rooms / Areas: - Stains and elevated levels of moisture were found in one or more ceiling areas. The stain(s) appear to be due to roof leaks. A qualified contractor should evaluate and repair as necessary.

    74) Interior Rooms / Areas:   - Some interior doors wouldn't latch. A qualified person should evaluate and repair as necessary.

    75) Interior Rooms / Areas:   - Some windows that were built to open were difficult to open and close. A qualified person should evaluate and repair as necessary.

    76) Interior Rooms / Areas:   - Some windows were damaged. A qualified person should evaluate and repair or replace as necessary.

    77) Interior Rooms / Areas:   - Water stains or evidence of leaking were found at some basement windows. A qualified person should evaluate and repair as necessary.

    78) Interior Rooms / Areas:   - The sash spring mechanisms in some windows were broken or loose. A qualified contractor or service technician should evaluate and make repairs as necessary so the window operate as intended (open easily, stay open without support, close easily, etc.).

    79) Interior Rooms / Areas:   - One or more exterior doors had minor damage. A qualified person should repair or replace as necessary.

    80) Interior Rooms / Areas:   - The weatherstrip around one or more exterior doors was deteriorated, missing. A qualified person should repair or replace as necessary.

    81) Interior Rooms / Areas:   - Thresholds at one or more exterior doors are deteriorated. A qualified person should repair, replace or install as necessary.

    82) Interior Rooms / Areas:   - Deadbolts on one or more exterior doors were difficult to operate. A qualified person should repair as necessary.

    83) Interior Rooms / Areas:   - Crank handles at some windows were missing. A qualified person should repair or replace as necessary.

    84) Interior Rooms / Areas:   - Lock mechanisms on some windows were missing. A qualified person should repair as necessary.

    85) Interior Rooms / Areas:   - Glass in some windows was cracked or broken. A qualified contractor should replace glass where necessary.

    86) Interior Rooms / Areas:   - Trim was missing in some areas. A qualified person should repair as necessary.

    87) Interior Rooms / Areas:   - Fixtures such as closet shelving were loose, damaged. A qualified person should repair or replace as necessary.

    88) Interior Rooms / Areas:   - Significant damage (holes, etc.) were found in one or more ceiling sections. A qualified person should repair as necessary.

    89) Interior Rooms / Areas:   - Minor cracks and/or holes were found in walls in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.

    90) Interior Rooms / Areas:   - Minor cracks and/or holes were found in ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.