This report published on Thursday, January 30, 2025 2:11:16 PM EST
Thank you for choosing Hane Home Inspections, LLC. Please note that every home inspection report is going to include numerous items that may not have been immediately apparent during walkthroughs earlier in the buying process. It is not unusual to have a lengthy report on houses that are in good condition. If you have questions regarding the severity of issues reported below, feel free to contact us via email, text, or phone call. We are more than happy to go over any concerns with the report that you might have. Questions are always welcome.
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Minor Defect
Correction likely involves only a minor expense
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Serviceable
Item or component is in serviceable condition
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: 30s
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Source for main building age: Municipal records or property listing
Occupied: Yes
1) Some areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Driveway material: Asphalt
Sidewalk material: Poured in place concrete
2) Damage was found in sidewalk. Recommend that qualified contractor repair as necessary.
Photo 2-1
3) The soil or grading was flat and/or sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. It can be a conducive condition for wood-destroying organisms. Recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo 3-1 Photo 3-2
Photo 3-3
4) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios. The client may wish to have repairs made for cosmetic reasons and to help prevent further deterioration.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Apparent wall structure: Wood frame
Wall covering: Vinyl
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Poured in place concrete
6) One crack observed that client disclosed had moisture present in the past. This crack was observed on both the interior and exterior of the home. Recommend evaluation and sealing by a qualified contractor.
Photo 6-1
7) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo 7-1 Photo 7-2
Photo 7-3 Photo 7-4
Photo 7-5 Photo 7-6
Photo 7-7 Photo 7-8
Photo 7-9 Photo 7-10
Photo 7-11 Photo 7-12
Photo 7-13 Photo 7-14
Photo 7-15
8) Window well covers were missing for below grade or partially below grade windows. Consider installing to prevent buildup of debris and to help direct water away from the foundation.
9) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo 9-1 Photo 9-2
Photo 9-3 Photo 9-4
10) Caulk was missing and/or deteriorated in some areas. For example, at wall penetrations. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit: http://www.reporthost.com/?CAULK
Photo 10-1 Photo 10-2
Photo 10-3
11) 4 rain drains were leaking. Recommend sealing.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Pier or support post material: Steel
Beam material: Steel
Floor structure above: Engineered wood joists
Insulation material underneath floor above: Fiberglass roll or batt
12) One or more joists were cracked or damaged. Recommend repair.
Photo 12-1
13) Basement stairs were not secure. Recommend improving.
Photo 13-1
14) Minor cracks observed in the concrete floor. These are common in basements and do not appear to present a structural concern. However, the client may wish to seal these cracks to prevent soil gases from entering the home, especially if radon is a concern.
Photo 14-1
15) No backup system was present for the sump pump in the case of a power failure. Sump pumps frequently run during and immediately after heavy storms, during which power outages are more likely. Consider installing a battery backup or equivalent system to ensure that the pump can operate when needed.
Note that it is common to be without a backup system, and backup systems are not required.
16) The sump pump was on a GFCI-protected outlet. These outlets are known to trip at times, sometimes without clear cause. If power is lost without the home owner being aware, water may accumulate in the sump pit and ultimately in the basement. Consider installing a water alarm or other alert system to ensure that if the outlet trips it will be made known.
Note that GFCI protection is required for sump pumps in some areas.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Attic inspection method: Viewed from hatch(es)
Roof structure type: Trusses
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): >R-38
Roof inspection method: Drone
Estimated Roof Age: 1-5 years
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
18) Scraped or damaged shingles were observed. The useful life of the roof covering may be reduced by such damage. Recommend evaluation and repair of any damaged shingles as necessary by a qualified roofer.
Photo 18-1 Photo 18-2
Photo 18-3 Photo 18-4
Photo 18-5
19) The ceiling insulation in one or more areas of the attic was compacted or uneven. Heating and cooling costs may be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).
Photo 19-1 Photo 19-2
Photo 19-3 Photo 19-4
20) Gusset/truss plate was loose. Recommend securing.
Photo 20-1
21) The attic structure was in good condition.
Photo 21-1 Photo 21-2
22) Some attic areas were inaccessible due to low height, depth of insulation, unconnected attic spaces, or lack of permanently installed walkways. These areas are necessarily excluded from the inspection.
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
23) One or more holes were found in the attached garage walls or ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit: http://www.reporthost.com/?AGFR
Significant energy will also be lost as a result of the gap at the foundation/basement
Photo 23-1 Photo 23-2
Photo 23-3
24) Moisture intrusion observed in the garage. This can be the result of poor site drainage, downspout/gutter issues, or holes/gaps on the exterior. Recommend evaluation and repairs as needed.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Underground
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Location of main service panel: Garage
Location of main disconnect: Breaker at top of main service panel
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. . Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Water service: Public
Service Pipe Material: Copper
Location of main water shut-off: Basement
Supply pipe material: PEX plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
Vent pipe material: Plastic
240 volt receptacle for laundry equipment present: Yes
26) Gaps, no caulk, or substandard caulking were found between countertops and backsplashes. Water can penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing or replacing caulk.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Type: Tank
Energy source: Electricity
Estimated age: 2023
Capacity (in gallons): 50
Location of water heater: Basement
Water Heater Brand: A.O. Smith
28) Wiring for the water heater's power supply was exposed and subject to damage. Standard building practices call for non-metallic sheathed wiring to be protected with BX armored conduit to prevent damage. This is a potential safety hazard for shock. Recommend that a qualified contractor repair per standard building practices.
Photo 28-1
29) The electric water heater operated. Note that it is beyond the scope of the inspection to test the water temperature.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
HVAC Brand: Lennox
Location of Thermostat(s): 1st Floor Hall
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2023
Location of forced air furnace: Basement
Location for forced air filter(s): At end of air handler
Cooling system and/or heat pump fuel type: Electric
Estimated AC Age: 2023
Location of heat pump or air conditioning unit: Building exterior
Type: Split system
31) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit: http://www.reporthost.com/?ANFURINSP
32) Areas of the home had significantly different temperatures at time of inspection. The HVAC system may require balancing. Recommend consulting with a qualified technician to determine the most effective way of balancing temperatures throughout the home.
33) Recommend that home buyers replace or clean HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or cleaning them as necessary. How frequently they need replacing or cleaning depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
34) The flames on the furnace looked good.
Photo 34-1
35) The outdoor air temperature was below 65 degrees Fahrenheit during the inspection. Air conditioning systems can be damaged if operated during such low temperatures. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
37) Counter(s) were loose in area(s). Recommend securing to prevent damage or injury.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
38) One or more doors were missing from interior spaces. Recommend replacing.
Coat closet
39) Thermal scans indicated anomalies that appear to be the result of missing, uneven, or out of place insulation. Recommend improving insulation for greater energy efficiency.
Location: loft
Photo 39-1 Photo 39-2
40) Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary. For more information, visit: http://www.reporthost.com/?SQUEAK
2nd floor landing
41) Window lock(s) were not aligned well. This can prevent the window from being tightly sealed when closed, in addition to posing a security risk if located on the first floor or over an accessible deck. Recommend adjustments as needed to ensure that the locks can be properly operated to seal the window and prevent energy loss.
Loft right window
42) Floor covering was deteriorated in area(s). Recommend repair for aesthetic purposes and to help protect the subfloor.
2nd floor hall bath
Photo 42-1
43) Tack strip could be felt at the edges of carpeting. Recommend evaluation and improvements by a qualified flooring contractor.
44) Minor cracks, nail pops, and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product: http://www.reporthost.com/?ECC
45) Paint was incomplete, blemished, damaged, or otherwise substandard in areas. Recommend improving for aesthetic purposes.
Owner bedroom door, owner bedroom
Photo 45-1 Photo 45-2
46) Cracks existed around the windows. Consider sealing with caulking.
47) Stains were found in one or more wall areas. However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks.Consult with the property owner and monitor the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, then recommend that a qualified contractor evaluate and repair as necessary.
Loft baseboard
Photo 47-1 Photo 47-2
Thank you for choosing Hane Home Inspections, LLC. Please note that every home inspection report is going to include numerous items that may not have been immediately apparent during walkthroughs earlier in the buying process. It is not unusual to have a lengthy report on houses that are in good condition. If you have questions regarding the severity of issues reported above, feel free to contact us via email, text, or phone call. We are more than happy to go over any concerns with the report that you might have. Questions are always welcome.