Inspector: Leon Jaworowski, P.E.
NYS License No. 16000093216

Property Inspection Report

Client(s):  Benjamin Riordan
Property address:  211 East Farmingdale Street
Islip Terrace, NY 11752
Inspection date:  Saturday, June 8, 2019

This report published on Wednesday, June 12, 2019 6:27:41 AM EDT

Thank you for using ALLIANCE Inspections Inc. for your inspection needs. We appreciate your business and are confident you will be satisfied with the services we provided. Please read through the entire report and review the photographs with any commentary.
If you have any questions regarding the report, or conditions of the residence please feel free to contact us.
The report is confidential and the exclusive property of the Inspector as an instrument of service. It is provided to the Client listed in the report title only for general information on the overall apparent visual condition of the inspected systems and components of the structure identified in the report at the time of the inspection. In addition, the report may have been prepared for client's specific requirements or restrictions, and may also be unreliable to others due to the potential for variable inspection circumstances and the potential for rapidly changing conditions.
Use or duplication of this report by any unauthorized persons without the express written permission of the inspector is strictly prohibited, and may be a violation of copyright laws.

ITEMS ADDITIONALLY EXCLUDED FROM THIS INSPECTION: Sewage disposal systems, below grade drainage systems, site features not identified, irrigation and sprinkler systems, pools, pest inspection, radon testing, security systems, appliances, and thru-wall air conditioners. See Inspection agreement for further limitations and details.

GENERAL NOTES ABOUT THE INSPECTION-The Inspection and this report only apply to the conditions at the time of the Inspection. The information contained in this report may be unreliable for other seasonal or environmental conditions, such as changes in the weather (e.g. rain, snow, temperature, etc.) or groundwater, and may not be applicable beyond the date of the Inspection as conditions sometimes change or become worse within a short period of time. If the Client has any concerns, or any conditions not addressed in this report become apparent, the Client shall notify Alliance Inspections, Inc. and provide an opportunity to re-inspect conditions. If repair or replacement is done without giving Alliance Inspections, Inc. notice and the opportunity to re-inspect conditions Alliance Inspections, Inc. shall have no liability.

Alliance Inspections Inc. are GENERALIST INSPECTORS performing an overall visual inspection and visual assessment of readily accessible systems and components of the building, and can not practically inspect hidden or inaccessible items, or be specialists with expertise in every field related to building construction and maintenance. Alliance Inspections, Inc. can also not inspect, evaluate, or report conditions on concealed systems or components or those that require disassembly or damage to finishes in order to facilitate inspection. Inspections are additionally limited to what can be observed given time restrictions of the inspection as well as cost limitations to the Client, and given it is only a visual inspection of readily accessible systems and components without the use of specialized tools or equipment.

Sometimes specialists in various fields are referred to for maintenance and repairs, or for further evaluations due to the limitations of an Inspection. Occasionally specialists will find additional defects or problems upon further evaluation or dissassembly of components. It is beyond the scope of an Inspection to perform evaluations in specialty fields or dissassemble components or systems, so discovery of additional defects after further evaluation by a specialist is possible, particularly if some time has passed since the Inspection.

In addition specialists sometimes disagree with the general findings and recommendations from an Inspection, and sometimes prefer replacement over repairs due to liability concerns. It is recommended that any such specialist who disagree with opinions or recommendations contained in this report put their findings in writing on company letterhead, signed by a person in responsible charge. Otherwise the Client must decide how much weight to give each opinion.

SEE THE INSPECTION AGREEMENT FOR ADDITIONAL PROVISIONS AND RESTRICTIONS

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Major defectCorrection likely involves a significant expense
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior
Foundation
Basement
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas
Structural Pest Findings

General Information
Table of contents
Report number: 2019-006
Time started: 10:00 AM
Time finished: 12:45 PM
Inspector: Leon Jaworowski, PE, LEED, AP
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions: Clear
Temperature: Warm
Ground condition: Dry
Payment method: Check
Type of building: Single family
Buildings inspected: ! Residential Building with Attached Garage
Number of residential units inspected: 1
Age of building(s): 58 Yrs.
Source for building age: Property listing
Front of building faces: South
Main entrance faces: South
Occupied: No
1) Safety, Comment - Structures built prior to 1980 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.epa.gov
http://www.cpsc.gov
http://www.cdc.gov
2) Evaluate, Comment - Based on construction observed, to this property may have been made without the owner having attained permits or inspections from the municipality. Work may have been performed by someone other than a qualified contractor or person. The client should consult with the property owner about this, and if necessary research permits.

At worst case, if substantial work was performed without permits, this knowledge must be disclosed when the building is sold in the future. This can adversely affect future sales. Also, the local municipality could require costly alterations to bring the building into legal compliance or even require that the additions or modifications be removed.
3) - We appreciate the opportunity to conduct this inspection for you! Please carefully read your entire Inspection Report. Call us 631-241-4038 after you have reviewed your report, so we can go over any questions you may have. Remember, when the inspection is completed and the report is delivered, we are still available to you for any questions you may have, throughout the entire closing process.

Properties being inspected do not "Pass" or "Fail. The following report is based on an inspection of the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFCI outlets may not be installed; this report will focus on safety and function, not current code. This report identifies specific non-code, non-cosmetic concerns that the inspector feels may need further investigation or repair.

For your safety and liability purposes, we recommend that licensed contractors evaluate and repair any critical concerns and defects. Note that this report is a snapshot in time. We recommend that you carry out a final walk-through inspection immediately before closing to check the condition of the property, using this report as a guide. We offer a Final Walk Through Inspection as one of our services. We provide this service at a discounted rate to former clients.

Please note the link for this report expires within 120 days so please print a copy of this report for your records as soon as possible.
4) - The residential dwelling unit appears to be part of a complex that is managed, and maintained by a "Home Owners" or "Condo" association. This inspection is limited to a visual evaluation of the systems and components that are located within the dwelling unit inspected. The current condition of "Common Elements" are excluded from this inspection. Such elements include, but are not limited to:
  • The building site condition, structural stability, drainage systems and insulation
  • All exterior surfaces, materials and structure
  • All roof surfaces, materials and structure
  • All attic spaces
  • The building foundation, floor substructure and all spaces below, such as basements and/or crawl spaces
  • All stairs, landings, porches, hallways, walks and balconies, elevators, utility metering, parking stalls/ports
  • All decks, patios, pools, spas, recreational areas/equipment
  • All common areas on the property

Any comments regarding these items in this report have been made as a courtesy only. The client should consult with the Home Owner's or Condo Association regarding these items.
Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wood
Site profile: Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Condition of deck, patio and/or porch covers: Required repairs, replacement and/or evaluation (see comments below)
Deck, patio, porch cover material and type: Open
5) Safety, Repair/Replace - Some covers were obscured by and couldn't be fully evaluated.

The concrete patio adjacent to side door entrance is severely deteriorated and should be removed and/or replaced. Tripping hazards exist from the displaced sections of concrete.
Photo
Photo 5-1 This concrete patio is severely deteriorated and should be/removed and replaced. it contains tripping hazards.
6) Repair/Replace, Evaluate - Most or all of the fencing was damaged or deteriorated. A qualified contractor should evaluate and replace or repair sections as necessary.
Photo
Photo 6-1 The existing stockade fence should be repaired and/or replaced.
Photo
Photo 6-2 There are major sections of the stockade fence that are deteriorated and/or missing. The fencing should be replaced.
7) Repair/Replace, Evaluate - One or more trip hazards were found in the driveway due to cracks, settlement, heaving and/or deterioration. A qualified contractor should evaluate and repair or replace driveway sections as necessary to eliminate trip hazards.
Photo
Photo 7-1 There are sections of the concrete driveway that are cracked and displaced causing tripping hazards. these locations should be removed and replaced.
8) Repair/Replace - One or more fence gates were difficult to open and close and/or difficult to latch. A qualified person should repair as necessary.
9) - Grading and drainage are probably the most significant aspects of a property, simply because of the direct and indirect damage that moisture can have on structures. More damage has probably resulted from moisture and expansive soils than from most natural disasters. Also, there should be gutters and downspouts with splash blocks that discharge away from the building. We have discovered evidence of moisture intrusion inside structures when it was raining that would not have been apparent otherwise.

In addition, we recommend that downspouts do not terminate over paved areas such as walks or driveways, as they can contribute to icy slip and fall hazards in winter.

Minor settlement or hairline cracks in drives, walks or even foundations are normal to properties of any age. They should, however, be monitored for expansion and sealed as necessary.

Vegetation too close to the home can contribute to damage through root damage to the foundation, branches abrading the roof and siding, and leaves providing a pathway for moisture and insects into the home.

Although rails are not required around drop-offs less than 30 inches, consider your own personal needs and those of your family and guests. By today's standards, spindles at decks and steps should be spaced no more than 4 inches apart for the safety of children.

An egress ladder and window should also be installed within the well or basement wall, especially where below-grade bedrooms exist and no basement access door exists.
Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Cement fiber, Vinyl, Brick veneer
Window/Door Frames and Trim Conditions: Area where vinyl j channel meets frame of window needs caulkin
SOFFIT (Underhang section right below roof, sticks out from top of wall): Vinyl soffit (underhang) with venting holes for attic ventilation.
FASCIA (Board right below roof edge): Wooden fascia (boards behind gutters and at top of side walls) covered with metal
Condition of exterior stairs: Required repairs, replacement and/or evaluation (see comments below)
Condition of handrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Concrete
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full
Condition of chimneys: Required repair, replacement and/or evaluation (see comments below)
Chimney type: Masonry
10) Safety, Major defect, Repair/Replace, Evaluate - No metal liner was installed in the masonry chimney at location #A, and one or more gas appliances use the chimney for a flue. Standard building practices require that a metal liner be installed in masonry chimneys used to vent gas appliances such as furnaces and water heaters. The purpose of the metal liner is to ensure a correct draft, and to prevent damage to the masonry flue from corrosive exhaust deposits and moisture in the exhaust gases. A qualified chimney service contractor should evaluate and install a metal liner as necessary. For more information search for "gas liner" at:
http://www.csia.org/
11) Safety, Repair/Replace - No spark screen or rain cap was installed for the chimney flue at location #. Spark screens prevent the following:
  • Fire hazard from wood fire sparks and embers exiting flues
  • Wildlife (birds, rodents, raccoons, etc.) entering flues

  • Rain caps prevent the following:
  • Rainwater entering flues and mixing with combustion deposits, creating caustic chemicals which can corrode flues
  • Rainwater entering flues and causing damage to masonry from freeze-thaw cycles

A qualified person should install screening and rain caps as per standard building practices.
Photo
Photo 11-1 No rain cap or spark screen is located on the chimney. Additionally, the concrete crown contains a crack that should be evaluated and repaired by a qualified person.
12) Safety, Comment - Based on the appearance of the siding and the age of this structure, some, most or all of the exterior siding material may contain asbestos. The product is known as asbestos-cement siding. The client should be aware of this when considering repairs to or replacement of this siding, and consult with qualified testing labs and/or abatement contractors as necessary. For more information on asbestos in the home, visit http://www.cpsc.gov/cpscpub/pubs/453.html
13) Repair/Replace, Evaluate, Monitor - The masonry chimney crown at location #A was cracked. The crown is meant to keep water off of the chimney structure. The chimney can be damaged by wet masonry going through freeze-thaw cycles. A properly constructed chimney crown should:
  • Be constructed using either pre-cast concrete slabs, cast-in-place steel reinforced concrete, solid stone, or metal
  • Be sloped down from the flue a minimum of 3 inches of fall per foot of run
  • Extend a minimum of 2-1/2 inches beyond the face of the chimney on all sides
  • Not directly contact the flue liner (if installed), and this gap should be filled with flexible caulk
  • Have flashing installed between the bottom of the crown and the top of the brick chimney

A qualified chimney service contractor or mason should evaluate and repair or replace the crown as necessary.
14) Repair/Replace, Evaluate - Extensions such as splash blocks or drain pipes for some downspouts were missing. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair, replace or install as necessary
Photo
Photo 14-1 there are no splash blocks located at many of the downspouts. This will allow water to sit adjacent to the concrete foundation and permit water to potentially leak into the basement.
15) Repair/Maintain, Evaluate, Comment - There are several venting systems from th basement venting below the kitchen casement window that do not appear to be in use. these openings shown in the picture below should be evaluated to make sure the systems are no longer in use. if not in use they should be capped off to avoid any heat loss.
Photo
Photo 15-1 These two openings may have been vents a some point in time, but appear not to be in use now. they should be evaluated.
16) Repair/Maintain, Evaluate - Exterior stairs were deteriorated. A qualified person should evaluate and repair or replace as necessary.

Both the front and side door concrete stairs showed cracked concrete on the stairs and/or along the sides. These conditions should be repaired to prevent further deterioration from trapped water and freeze thaw cycles.
Photo
Photo 16-1 These significant cracks in the side door entrance stairs should be sealed to prevent further damage from water and the freeze thaw cycles.
Photo
Photo 16-2 This crack in the front door stairs should be sealed to prevent further damage.
17) Repair/Maintain, Evaluate - Handrails at one or more flights of stairs were loose. This is a safety hazard. A qualified person should repair or replace as necessary and as per standard building practices.

The left front door handrail was loose and should be repaired by a qualified person.
Photo
Photo 17-1 This stair post handrail is loose and needs to be repaired.
18) Repair/Maintain, Monitor, Comment - Some exterior wall sections were obscured by vegetation and couldn't be fully evaluated.

Vegetation should be trimmed to provide a space of approximately 12 inches between the vegetation and the walls of the structure.
Photo
Photo 18-1 The vegetation is to close to the house and should be trimmed back to prevent insects and termites from entering the wall structure.
19) Repair/Maintain - Caulk was deteriorated in some areas. For example, around windows, around doors and/or at siding-trim junctions. A qualified person should repair or replace as necessary. For more information, visit:
https://www.reporthost.com/_docs/FPL_Caulking_Ins_Outs.pdf
Photo
Photo 19-1 The caulking around certain windows is in need of replacement around several of the windows and doors as shown by these two photos.
Photo
Photo 19-2 
20) Comment - It should be noted that there were no exterior electrical outlets on the home. The client should consider adding a few to accommodate future outdoor activities.
21) - Certain asbestos-cement shingles were cracked and/or displaced. These sections need to be corrected.
Photo
Photo 21-1 Certain sections of asbestos-cement singles were cracked and need to be repaired and/or replaced.
Foundation
Table of contents
Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of foundation and footings: Appeared serviceable
Foundation type: Basement (See Basement Section)
Foundation material: Poured in place concrete
Footing material: Below Grade - Not deternined
Anchor bolts for seismic reinforcement: Not determined
Condition of floor substructure: Appeared serviceable
Main Beam material: Built up wood
Main Beam Column Supports: Layout in basement and coverings over colums prevented a through inspection of the column type.
Floor structure: Solid wood joists
Insulation: None Visible
Condition of concrete slab floor(s): Appeared serviceable
Insulation material underneath floor above: None visible
22) Repair/Maintain, Evaluate, Monitor - One or more minor exterior & interior cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including hydraulic cement, resilient caulks and epoxy sealants.
Photo
Photo 22-1 Cracks on the interior and exterior foundation wall are in need of sealing by a qualified person.
Photo
Photo 22-2 An exterior crack in the foundation that needs to be sealed by a qualified person.
23) Repair/Maintain, Evaluate, Comment - Some foundation and/or footings sections were obscured by vegetation and couldn't be fully evaluated.

The vegetation should be pruned back so that these areas can be monitored.
Photo
Photo 23-1 The vegetation is to close to the house and should be trimmed back to prevent insects and termites from entering the wall structure.
24) Monitor, Comment - Signs of efflorescence found. Efflorescence is white chaulk-like coating found on concrete caused by water picking up salts as it migrates through concrete, then leaving the salt on the surface as it evaporates. This condition was observed on the interior of the concrete foundation.
25) Comment - Foundation
A foundation provides a stable, rigid base to support a home. The foundation supports the frame and structure and protects it from moisture and contact with the soil. The foundation must rest on firm soil and be protected from water entry or excessive dampness. The majority of homes are built on foundations that form a crawl space or full basement. The basement rests on a footing that supports the home's weight. Foundation walls are constructed of brick, concrete block, poured concrete, clay tile, stone, or similar materials. The basement floor usually consists of poured concrete. Crawl spaces can either have a dirt or concrete floor.

Full-depth basements are the most complicated type of foundation because of potential water problems and the pressure of soil outside the basement walls. While full-depth basements require the most maintenance, crawl spaces and slab foundations must also be protected from excessive moisture.

Proper grading around the house is your best protection against seepage into the basement that may cause expensive damage. When a home is built, workers dig the excavation several feet larger than the basement walls to allow for construction clearances. At the base of the hole, near the footing, they install a drain tile system and cover it with a small amount of gravel. They also apply a damp-proof coating to the walls and the hole is filled. Most of the hole around the basement is filled with soil from the site. This may contain gravel, rock, wood, paper, and unfortunately almost anything no longer useful to home construction. For the next 20 years, this soil and "stuff" settles around your basement walls. It settles quickly for the first few years and more slowly after that.

To divert surface water the soil should pitch away from the home with a 1 inch pitch per foot for about 6 feet beyond the foundation. All downspouts from the roof drainage system should be at least 3 feet away from the foundation. Open window wells should have either grates or, preferably, a weatherproof shield over them. This will keep the rain and snow from building up inside the well and possibly leaking into the home.
26) Comment - Many sections of the floor substructure were not fully evaluated due lack of access from ceiling types located in the basement..
27) Comment - All concrete slab floor sections were obscured by flooring and couldn't be fully evaluated.
Condition of the basement: Appeared serviceable
Type: Finished Basement (framed walls with wall coverings)
Miscellaneous Items 1:: Wood Framing with no insulation
Miscellaneous Items 2: The basement is heated with hot water baseboard., eparate heating thermostat in basement, The basement contains a utility room
Floor Material: Vinyl Tile over Concrete
Ceiling type or covering: CeilingTiles, Drop Ceiling
Condition of ceilings: Appeared serviceable
Wall type or covering: Paneling, The paneling is notty pine.
Condition of walls: Appeared serviceable
Type: Wood Windows, Jalousie window
Condition: Windows appear to be original single pane units, budget for replacement - See Pictures
28) Safety, Repair/Replace, Evaluate - electric receptacles had reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
Photo
Photo 28-1 The hot and neutral in this receptacle is reversed and should be corrected by a licensed electrician.
29) Safety, Repair/Replace, Evaluate - One or more electric receptacles at the laundry room and/or basement had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
30) Safety, Evaluate, Comment - Some ceiling areas in this structure had tiles possibly installed prior to 1980. This material may contain asbestos, which is a known carcinogen and poses a health hazard. Laws were passed in the United States in 1978 prohibiting use of asbestos in residential structures, but stocks of existing materials have been known to be used for some time thereafter. The client may wish to have this ceiling material tested by a qualified lab to determine if it does contain asbestos.

In most cases, when the material is intact and in good condition, keeping it encapsulated with paint and not disturbing it may reduce or effectively eliminate the health hazard. If the client wishes to remove the material, or plans to disturb it through remodeling, they should have it tested by a qualified lab and/or consult with a qualified industrial hygienist or asbestos abatement specialist. For more information, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/453.html
31) Maintain, Monitor, Comment - Wood paneling or any material that will absorb water is not a good product to use in a basement, which tends to be moist. Excess water will result in mold and mildew. Use a dehumidifier to remove excess water.
32) Maintain, Monitor, Comment - Dampness noted - Any material that will absorb water is not a good product to use in a basement, which tends to be moist. Mold and/or mildew can result from this moisture condition. Recommend using a dehumidifier to remove excess water.
33) Evaluate, Monitor, Comment - Signs of efflorescence found. Efflorescence is white chaulk-like coating found on concrete caused by water picking up salts as it migrates through concrete, then leaving the salt on the surface as it evaporates.
34) Comment - If any part of basement area is used as a bedroom at least 1 window should be egress. The windows in basement do not qualify as Egress size (5.7 sq. ft, aprox. size 29 inches by 41 inches). Egress is a size that is deemed appropriate for the average person to use as a hatch to climb through. We recommend installing at least 1 egress window in any finished basement with a bedroom.
35) - The basement windows are old and do not offer any thermopane qualities. As the basement is heated, replacement of these windows will make the home more energy efficient.
Photo
Photo 35-1 This is and old wood frame basement window that should be replaced.
Photo
Photo 35-2 This old single pane window has an air space that will let cold air into the basement during the winter season. These type of basement windows should be removed and replaced by a qualified person.
Photo
Photo 35-3 The basement also had jalousie windows that are also not energy efficient.
Roof / Attic
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Appeared serviceable
Roof type: Hipped
Roof inspection method: Viewed from ground with binoculars
Condition of shingle and/or shake roof surface materials: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles (15 year life)
Apparent number of layers of roof surface material: One layer of Roofing was observed
Condition of exposed flashings: Appeared serviceable
Condition of attic: Appeared serviceable
Attic inspection method: Viewed from hatch(es)
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Ceiling insulation material: Fiberglass roll or batt
Approx. Depth: 1 - 4 inches
Vapor retarder: Not determined
Attic ventilation: Appears serviceable
36) Repair/Replace, Evaluate - Some "rubber boot" flashings were deteriorated. Leaks may occur as a result. A qualified contractor should replace flashings where necessary.

The boot flashing over the electrical service post is in poor condition and should be replaced by qualified person.
Photo
Photo 36-1 
37) Repair/Maintain, Maintain, Comment - The ceiling insulation's depth (R rating) was significantly less than what's recommended for this area. Recommend having a qualified contractor install additional insulation as per standard building practices for better energy efficiency. For more information, visit:
http://www.eere.energy.gov/consumer/tips/insulation.html
38) Monitor, Comment - The roofing material appeared weathered and aged. This condition requires monitoring and/or maintenance repairs.
Photo
Photo 38-1 Several roof sections showed signs of extensive wear. The entire roof area should be monitored in the future to make sure that no leaks develop. This may require entering the attic area to see if the roof sheathing is showing signs of leaks,
39) - Roofing
All roofs have structural framing of joists or trusses that support a wood deck that is either plywood, solid 3/4 inch wood planking or oriented strand board. In general, the two basic styles are sloped and low-sloped (or flat) roofs.
Asphalt fiberglass shingles (3-tab or architectural) are the most common type of sloped roofing material. A typical asphalt shingle can last from 15-40 years. Asphalt fiberglass shingles come in many shapes and sizes. Other materials used for sloped roofs include wood shakes, wood shingles, cement asbestos, tile, slate, metal, and cement tile.

Low-slope or flat roofs require a special roofing material to seal against moisture. Since the slope is low, water does not easily run from the surface. Materials used include single-ply rubber, roll roofing, torch down (modified bitumen), metal, and built-up roofing. On occasion it may be acceptable to use a sloped shingle on a flat roof if an ice membrane is used. A flat roof should have a slight slope to prevent puddling of water. Flat roof material is not made to walk on.

Roof Ventilation
Ventilation is necessary to remove moisture from the attic. This is achieved through a various combinations of roof vents, soffit vents, gable wall vents, ridge vents, static vents, and ventilation fans. Good attic ventilation lowers air conditioning costs. Bathroom and kitchen exhaust fans are needed to remove excessive moisture, but they must be routed to the exterior and not into the attic. Excessive moisture causes mildew and mold.

Gutters and Downspouts
When it rains, your roof sheds a tremendous quantity of water that must be moved away from the foundation to protect the basement or crawlspace. Always have downspouts drain at least 3 feet away from the foundation. Always make sure your gutters are cleaned and flowing correctly. If downspouts are draining underground always monitor during heavy rain to make sure there is no back up of water.

Adequate attic ventilation, solar / wind exposure, and organic debris all affect the life expectancy of a roof (see www.gaf.com for roof info).  Always ask the seller about the age and history of the roof.  Metal roofs in snow areas often do not have gutters and downspouts, as there is a concern that snow or ice cascading off the roof may tear gutters from the house.  Likewise, be advised that such cascading may cause personal injury or even death.  If this house has a metal roof, consult with qualified roofers or contractors regarding the advisability of installing a damming feature which may limit the size and amount of snow / ice sliding from the roof.  
Garage / Carport
Table of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
Type: Attached
Condition of detached garage or carport structure: Appeared serviceable
Condition of garage: Appeared serviceable
Condition of garage vehicle door(s): Appeared serviceable
Garage vehicle door type: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Floor Material: Concrete
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Not determined
40) Safety, Repair/Replace, Evaluate - One or more electric receptacles at the garage had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
41) Safety, Repair/Replace - No "photo eye" sensors were installed for one or more vehicle door's electric door opener. They've been required on all automatic door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit:
http://www.cpsc.gov/cpscpub/pubs/523.html
http://www.ohdstl.com/safety.html
42) Repair/Replace, Repair/Maintain, Evaluate - One or more automatic door openers were installed in a substandard way. A qualified contractor should evaluate and repair or replace opener(s) as necessary.
Photo
Photo 42-1 The garage door opener was not installed in its own dedicated outlet. A licensed electrician should make the correct connection for this device.
43) Repair/Maintain, Evaluate, Comment - One or more automatic vehicle door openers couldn't be fully evaluated because they were disconnected.
Photo
Photo 43-1 The automatic garage door opener was disconnected from the door. The operating condition of this device could not be evaluated. It should be evaluated by a qualified person.
44) Comment - Garage doors are made of hundreds of possible combinations of materials, rollers, tracks, operators, springs, locks, and other options. Garage doors are normally found to be made of either wood, steel or plastic. Most newer doors have some type of insulation within the door. Wooden garage doors need to be properly maintained and sealed because water causes damage to wood. The bottom of the garage door will come in contact with water the most often and needs to be water resistance. The bottom of a garage door should have a vinyl or rubber weatherstripping that comes in contact with the ground.

Garage openers should be equipped with a force reversal mechanism as well as a laser mechanism that will not allow the door to close if the laser beam is broken. The garage door should open and close freely and not get hung up.
If there is a door from the garage to the inside of the house it should be fire rated, self-closing, and should open to the inside of the house.
Electric outlets in a garage should have a GFCI circuit.
Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Overhead
Number of service conductors: 2
Service voltage (volts): 120
Service amperage (amps): 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Copper
Main disconnect rating (amps): 100
System ground: Cold water supply pipes
Condition of main service panel: Appeared serviceable
Condition of sub: Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A: Garage
Location of sub-panel #B: Basement
Location of main disconnect: Breaker at top of main service panel
Branch circuit wiring type: Non-metallic sheathed
Condition of branch circuit wiring: Serviceable
Condition of smoke detectors: Appeared serviceable
Smoke detectors present: Yes
Carbon monoxide detectors present: No
Smoke detector power source: Battery
45) Safety, Major defect, Repair/Replace, Evaluate - Panel #B used older style, screw-in fuses. This type of fuse allows anyone to install incorrectly rated fuses, possibly resulting in damage to wiring. Based on the age and/or appearance of the panel(s) using fuses, and/or deterioration of the panels or components inside, recommend having a qualified electrician replace this panel with a modern panel and circuit breakers. If the panel isn't replaced, then a qualified electrician should evaluate and make repairs as necessary.
Photo
Photo 45-1 This fuse box located in the basement as a sub-panel contains fuses rated for 20 & 30 amps. The garage contains a new main panel for the home. A licensed electrician should be hired to evaluate the need to maintain this panel. if not necessary, it should be removed.
46) Safety, Repair/Replace, Evaluate - Wire splices were exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.
Photo
Photo 46-1 This electrical splice should be located in a junction box. A licensed should be contacted to install the box.
47) Safety, Repair/Replace, Evaluate - Two-pronged electric receptacles rather than three-pronged, grounded receptacles were installed in bedroom areas. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:
  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

This list is not exhaustive. A qualified electrician should evaluate and install grounded receptacles as per the client's needs and standard building practices.
48) Safety, Repair/Replace, Evaluate - Some open ground, three-pronged electric receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. For example, replacing receptacles or correcting wiring circuits.

Grounding type receptacles began being required in residential structures during the 1960s. Based on the age of this structure and the presence of 2-pronged receptacles in some areas of this structure, an acceptable repair may be to simply replace the ungrounded 3-pronged receptacles with 2-pronged receptacles. However the following appliances require grounding type receptacles:
  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

This list is not exhaustive. Grounded circuits and receptacles should be installed in locations where such appliances will be used.
49) Safety, Repair/Replace, Evaluate - One or more electric receptacles at the kitchen, bathroom(s), laundry room, garage, exterior and/or basement had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
50) Safety, Repair/Replace - This property had one or more fuel burning appliances and/or an attached garage, and no carbon monoxide detectors were visible. This is a safety hazard. Recommend installing one or more carbon monoxide detectors as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
51) Safety, Evaluate - Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Centigrade. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950 may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Centigrade. Connecting older, 60 degree-rated wiring to such newer fixtures is a potential safety hazard due to the risk of fire. Repairs for such conditions often involve replacing the last few feet of wiring to newer fixtures with new 90 degree-rated wire. This often requires installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware that this safety hazard may be present in this building. Recommend consulting with the property owner to determine if and when newer fixtures were installed, and/or to have a qualified electrician evaluate and repair as per standard building practices.
52) Repair/Replace, Evaluate, Monitor, Comment - The electric service to this property appeared to be rated at substantially less than 200 amps, and may be inadequate for the client's needs. Recommend consulting with a qualified electrician about upgrading to a 200 amp service.
53) Comment - The electrical supply to your home begins outside, either from your electric company's overhead or underground line. The main electric panel, which is usually located in the basement or garage, is divided into circuits through individual breakers or fuses and is fed through the wiring system, outlets and cords to various electrical devices.
Any home that has a Bulldog Pushmatic, Zinsco, Sylvania Zinsco or Federal Pacific main electric panel should have it evaluated by a licensed electrician, as these are older types of panels and breakers that have been known to overheat and cause house fires.
Most modern homes have 220-volt systems with a minimum of 100 amps of power. Older houses may have fuses and can have 60 amp systems. Main panels can have sub-panels that are fed by the main panel. These sub-panels can range in size from 30 amps on up. On most main panels you will find one breaker marked "main." This breaker will be near the top of the box and will be 100, 150, or 200 amp. If you switch this breaker off, all power in your home will be disconnected.
Distribution wiring is what routes electrical power to lights, outlets and appliances. Most of this wiring is buried in walls and attics, but some will be visible near the main service panel and in basements and crawl spaces. Since the 1970's, plastic shielded wiring (Romex is a common brand name) has been used in residential construction. Older homes may have cloth shielded wiring, BX or flexible metal-shielded wiring, or even conduit (metal pipe). The composition of the wire used is normally copper but during the 1950's a tin coating was used for a short period of time to cover the copper and in the 1970's solid 1 strand aluminum was briefly used. Any type of single strand aluminum wiring has been proven to be a fire hazard and if found will be noted on our report and should be evaluated by a licensed electrician.
A ground fault circuit interrupter GFCI is a valuable safety device that should be installed in bathrooms, kitchens, sink locations, unfinished basements, laundry rooms, garages and exterior outlets. GFCI outlets or circuits provide a high level of safety against shock. A tiny imbalance in the power and neutral lines will trip a GFCI meaning that the electric is instantly shut off. The imbalance indicates potential current leakage that could deliver a shock.
Some baths may have non-GFCI outlets which are protected by a GFCI outlet in a remote area (garage, another bath, etc.). 
Electricity requires at least 2 wires: it pushes through the live or positive wire (usually black in color) and returns through the neutral wire (usually white in color). This is why all electrical devices have plugs with at least two prongs. Modern systems add a third (ground) wire for safety.
Also, note that most electricians agree that smoke detectors are good for about 5 years, and the breakers in your panel box have an expected life of about 20 years.  Therefore, if this home was built before 1991, consider having the panel box and breakers evaluated by a licensed electrician, as an overheated breaker can result in a structural fire.  
If your home does not have a carbon monoxide detector, it is now required to have them in New York State, we recommend making that investment.
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: Basement
Location of main water shut: Basement
Water service: Public
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Cast iron, Lead
Condition of fuel system: Appeared serviceable
Location of main fuel shut: Basement
54) Safety, Comment - Copper water supply pipes in buildings built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:
  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

For more information visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
http://www.epa.gov/safewater/lead/index.html
55) Safety, Comment - The client was advised by the sellers agent that the house originally was heated by an oil fired hot air furnace and then converted to gas. The client was advised that the oil tank was legally abandoned. If the oil tank(s) has been removed and/or legally decommissioned, the client should obtain the certificate(s) for his files prior to closing.
56) Repair/Replace, Evaluate, Monitor - Stains were found in one or more sections of waste lines. This may indicate that past leaks have occurred. Recommend consulting with the property owner about this, and either monitoring these areas in the future for leaks or having a qualified plumber evaluate and repair as necessary.
57) Repair/Replace, Evaluate - Moderate corrosion was found in some water supply valves. Leaks may occur as a result. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 57-1 This corroded valve handled should be evaluated and replaced, as required by a licensed plumber.
Water Heater
Table of contents
Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Required repair, replacement and/or evaluation (see comments below)
Type: Tank
Estimated age: Under 5 Years
Energy source: Natural gas
Capacity (in gallons): 40
Manufacturer: A.O. Smith
Model: GCV 40 301
Location of water heater: Basement utility room
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
58) Safety, Repair/Replace - No drain line was installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.
Photo
Photo 58-1 The PRV valve is missing a copper pipe overflow tube. this should be added to the system by a licensed plumber.
59) - A water heating system for drinking and bathing water can come in many shapes and sizes. The most conventional type of water heating system is the stand alone type that includes its own tank and heating system. This type of system can use either oil, natural gas, propane or electric to heat water.

Another type of water heating system found is a tankless system where the water is heated through the heating system, in most cases this heating system is a hot water or hydronic heating system. One drawback to this type of system is that if the home needs a large amount of hot water at a specific time this system may not be able to keep up with the demand.

There are also other combination systems available, for example; there is a system available where the water is heated through the heating system but stored in a separate tank.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Appeared serviceable
Location of heating system: Utility room, Basement
Heating type: Baseboard
Fuel type: Natural gas
Manufacturer: Weil-McLain
Model: Gold CGa
Source for last service date: Label on heater
Last service date: 12/15
60) - The heating, ventilation, and air conditioning/cooling system (often referred to as HVAC) is the climate control system for the structure. The goal of these systems is to keep the occupants at a comfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs at a minimum. The HVAC system is usually powered by electricity and/or natural gas, but can also be powered by other sources such as butane, oil, propane, solar panels, or wood.

Most homes are heated with either a warm air furnace that uses ducts and ceiling/wall registers or a hydronic (warm water) system that uses radiators, baseboard (convector) elements, or heating pipes buried in walls or floors.
Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type: Natural gas
Condition of refrigerator: Appeared serviceable
Condition of built: Appeared serviceable
61) Comment - The estimated useful life for most kitchen appliances is 10 to 15 years. One or more appliances (dishwasher) appeared to be near, at or beyond their service life. Recommend budgeting for replacements in the near future.
62) - The kitchen is used for food preparation and often for entertainment. Kitchens typically include a stove, dishwasher, sink and other appliances. We try to test all appliances but in some cases (dishes in the dishwasher, food in the oven, etc.) we are not able to.
We test the cabinets to make sure they operate correctly as well as note the condition of the counter top. We check for plumbing leaks in the sink as well as dishwasher. The electric outlets near the sink should all have a GFCI circuit.
Bathrooms / Laundry / Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Basement -Full
Location #B: 1st Floor -Full
Condition of counters: Appeared serviceable
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
Location: Basement
Condition of laundry facilities: Required repair, replacement and/or evaluation (see comments below)
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Not determined
63) Safety, Repair/Replace - The clothes dryer was equipped with a vinyl, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
Photo
Photo 63-1 Accordion vinyl exhaust lines for dryers are no longer acceptable. It should be replaced with a metal exhaust system by a qualified person.
64) Major defect, Repair/Replace, Evaluate - Major moisture damage was found in areas by the shower at location #A. A qualified person should evaluate and repair as necessary.

This shower stall has significant wall damage from water leaking through the grout or severe usage. A complete evaluation was not possible as the shower head was missing and the line capped.
Photo
Photo 64-1 The shower stall in the basement is not functional due to severe wall damage. This damage must be repaired by a qualified person or the shower cannot be used. A shower head must also be installed in order to further evaluate the complete shower system.
65) Repair/Replace, Evaluate - The sink drain stopper mechanism at location #A and B was inoperable and/or difficult to operate. A qualified person should repair or replace as necessary.
Photo
Photo 65-1 Both bathrooms contain inoperable drain stoppers that must be repaired by a licensed plumber.
66) Repair/Replace, Evaluate - Moderate deterioration was found at the bathtub at location #B. The client(s) should consider replacing the bathtub.
67) Repair/Replace, Evaluate - The bathtub drain stopper mechanism at location #B was inoperable. A qualified person should repair or replace as necessary.
68) Repair/Replace, Evaluate - The bathroom with a shower at location #B didn't have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
69) Repair/Replace - Hardware such as hinges, latches or pulls were loose and/or missing at one or more cabinets at location #B. A qualified person should repair as necessary.

A pull knob was missing in the 1st floor sink cabinet.
70) Repair/Replace - The shower head at location #A was missing. A qualified person should repair or replace as necessary.
71) Repair/Maintain - Caulk around the tub's plumbing fixtures (faucets, spouts, escutcheon plates, etc.) at location #B was deteriorated. A qualified person should repair as necessary.
Interior Rooms / Areas
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
Bedroom Locations within the home: There are three bedrooms on the 1st floor.
Exterior door material: Wood, Metal
Condition of interior doors: Appeared serviceable
Type of windows: Aluminum, Single pane, Sliding, Thermopane Casement Andersen window in kitchen.
Condition of windows: Appeared serviceable
Wall type or covering: Drywall
Condition of walls: Appeared serviceable
Ceiling type or covering: Drywall (Sheetrock)
Condition of ceilings: Appeared serviceable
Flooring type or covering: Linoleum, Wood, Tile
Condition of flooring: Appeared serviceable
72) Repair/Replace, Evaluate - Screens in some windows are damaged. A qualified person should evaluate and repair or replace as necessary.
73) Evaluate, Monitor, Comment - Many windows used single-pane glass. Single-pane windows are one of the largest sources of heat loss in winter and heat gain in the summer due to their low insulating ability and high air leakage rates. They're estimated to be responsible for 25 to 50 percent of the energy used to heat and cool homes. The client should consider replacing single-pane windows with new, multi-pane windows.

The single pane windows did have storm windows but the system will not be energy efficient.
74) Comment - The structural frame of the home rests on the foundation walls and holds up the floors, interior walls, and roof. Most homes in the US are framed with wood, but a few are built with a brick or block support. Recently homes are starting to be framed with metal. Once the frame and structure are properly designed and installed, little maintenance is needed except to protect the structure from water and insects.

The exterior walls are framed to support the structure, allow for window and door openings, and protect the structure from the elements. Most exterior walls are framed with 2 by 4 studs spaced 16 inches on center. The studs are braced in the corners and doubled around window and door openings. Special "headers" are placed over openings to support the weight above the opening. Exterior wall framing allows space for electrical, cable, telephone, heat distribution components and plumbing supply and waste lines. The framing also supports exterior siding or cladding and includes space for insulation.

Interior areas consist of bedrooms, baths, kitchen, laundry, hallways, foyer, and other open areas.   All exposed walls, ceilings and floors will be inspected.  Doors and windows will also be investigated for damage and normal operation. Although excluded from inspection requirements, we will inform you of obvious broken gas seals in windows.  Please realize that they are not always visible, due to temperature, humidity, window coverings, light source, etc. Your inspection will report visible damage, wear and tear, and moisture problems if seen. Personal items in the structure may prevent the inspector from viewing all areas, as the inspector will not move personal items.

An inspection does not include the identification of, or research for, appliances and other items that may have been recalled or have had a consumer safety alert issued about it. Any comments made in the report are regarding well known notices and are provided as a courtesy only. Product recalls and consumer product safety alerts are added almost daily by the Consumer Product Safety Commission. We recommend visiting the following Internet site if recalls are a concern to you: http://www.cpsc.gov.
Structural Pest Findings
Table of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than five feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood destroying organisms may infest, reinfest or become active at anytime. No warranty is provided as part of this inspection.
Visible evidence of active wood destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood destroying insects: No
Visible evidence of damage by wood decay fungi: No
75) - There are termite traps located along some of the perimeter points around the home. The selling agent stated they are active baited locations. The client should get documented verification of this statement as well as to ask the company about whether there had been a previous infestation of termites or were the traps a preventative measure.
Photo
Photo 75-1 Another termite trap located along the outer perimeter of the home. The selling agent indicated that all traps are currently baited. the client should get documented evidence of this information.
Photo
Photo 75-2 One of few termite traps located along the outer perimeter of the home.