This is an actual home inspection report published in 20 minutes, starting from the time the report was uploaded from the ReportHost Pro software to the ReportHost website.  The 20 minute time included resizing and uploading digital pictures, spell checking and publishing.

An example of a report that took 10 minutes can be found here.


Website: http://www.allpointinspections.com/
Phone: (XXX) XXX-XXXX
XXXXXXXXX 
Poulsbo, WA 98370
Inspector: Jim Gallant

 

Full General Home Inspection and Structural Pest Inspection
WA State Dept. Agriculture ICN# XXXXXXXXX
Client(s): XXXX XXXXXXX
Property address: XXXX XXXXXXX XX
XXXXXX, XX
Inspection date: XX/XX/XXXX
This report published on XX/XX/XXXX XX:XX:XX PM PDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

WAC 16-228-2045 requires that a diagram be prepared for WDO (Wood Destroying Organism) inspection reports. A copy is available upon request.

For information on follow-up inspections, please see the bottom section of this report.


Thank you for choosing All Point Home Inspections. We've made every effort to provide you with a thorough, high quality inspection, and hope that the information in this report proves to be valuable in your consideration of this property. If for any reason you are unsatisfied with this report, or have questions after reviewing it, please don't hesitate to call us. If you are satisfied, please tell your friends about us.

This inspection complies with the American Society of Home Inspectors' (ASHI) Standards of Practice and the National Association of Home Inspectors' (NAHI) Standards of Practice. This report is intended to identify major defects within a structure that significantly affect its habitability or that cost in excess of $500 to repair, although minor defects may be noted in the report. Cosmetic items such as damaged molding, trim, doors, cabinets, interior paint or carpet are generally excluded from this report.

Home inspection reports by nature focus on defects and may seem negative in tone. Some features of this property may be in excellent condition and of high quality but have not been mentioned, or been deemed adequate in the report. This is not meant to downplay this property's assets, but to focus on alerting you to potentially expensive problems. Bear in mind that all homes, regardless of their age, have some number of defects.

Areas of the property that are excluded due to lack of access are vulnerable to infestation and damage from wood destroying insects and organisms.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Safety Poses a risk of injury or death 
Major defect Correction likely involves a significant expense 
Repair/Replace Recommend repairing or replacing 
Repair/Maintain Recommend repair and/or maintenance 
Minor defect Correction only involves a minor expense 
Maintain Recommend ongoing maintenance 
Evaluate Recommend evaluation by a specialist 
Monitor Recommend monitoring in the future 
Comment For your information 

Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
WDO/WDI Infestation Evidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI Damage Damage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating
Fireplaces / Stoves / Chimneys
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas
Structural Pest Findings
 
General Information Return to table of contents
Report number: xxxxxx
Time started: 9:00 AM
Time finished: 11:00 AM
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions: Partly cloudy
Temperature: Cool
Ground condition: Damp
Inspection fee: $XXX
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Age of building(s): XXXX
Source for building age: Client
Front of building faces: East
Main entrance faces: East
Occupied: Yes


1)   Structures built prior to 1980 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.epa.gov/
http://www.cpsc.gov/
http://www.cdc.gov/

2)   Some wall and floor surfaces were obscured by furniture, stored items and couldn't be fully evaluated.
 
Grounds Return to table of contents
Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
The following items are excluded from this inspection: Shed
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wood
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete, Gravel
Condition of sidewalks and/or patios: Appeared serviceable
3)   Fences were damaged or deteriorated in some areas. A qualified person should repair or replace sections as necessary.

Photo 9  
 

4) Vegetation such as trees, shrubs and/or vines was in contact with or less than one foot from the building exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the building exterior.

Photo 2  

Photo 3  

5)   Minor cracks, settlement, heaving and/or deterioration were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
 
Exterior / Foundation Return to table of contents
Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood fiber
Condition of foundation and footings: Appeared serviceable
Foundation type: Crawlspace
Foundation material: Poured in place concrete
Footing material: Poured in place concrete
Anchor bolts for seismic reinforcement: Not determined
Shear panels for seismic reinforcement: Not determined
Condition of floor substructure: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: 2x6 tongue and groove
Condition of crawl space: Appeared serviceable
Crawl space inspection method: Partially traversed
Insulation material underneath floor above: Fiberglass roll or batt
Ventilation: Appears serviceable
Vapor barrier present: Yes
6) The exterior finish over the entire structure was failing. A qualified painting contractor should prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain the entire structure as per standard building practices.

Photo 6  
 

7) This property was clad with composition wood fiber siding. Many brands of this type of siding by different manufacturers are known to deteriorate and/or fail prematurely due to moisture penetration. Failure is typically visible in the form of swelling, cracking and delamination, especially at the bottom edges. Class action lawsuits have been filed or are being filed against most manufacturers of this material.

Some areas of siding on this structure showed the symptoms described above and need replacement and/or maintenance. For example on the south side. Some manufacturers (Louisiana Pacific) recommend a repair process for this siding where affected areas are sealed with "Permanizer Plus", a flexible primer made by Pittsburgh Paint, followed by two coats of 100% acrylic latex paint. This sealant must be applied to the bottom edges using a brush. The face of the siding can be sprayed. The "Permanizer Plus" sealer isn't required for edges that aren't swollen, cracked or deteriorated, but the acrylic latex should still be brushed on these edges.

A qualified contractor should evaluate and replace siding as necessary, and/or seal and repaint as necessary and as described above, or by other methods specified by the siding's manufacturer.

For more information, visit:
http://www.ppg.com/ppgaf/pl1198.htm - Pittsburgh Paints, PRIMERS -THE FOUNDATION FOR A TOP QUALITY JOB
http://www.siding4u.com/failing_siding_help.htm - Failing LP Siding Help Page

Photo 7  

Photo 8  

8) Evidence of prior water intrusion was found in one or more sections of the crawl space. For example, sediment stains on the vapor barrier or foundation, and/or efflorescence on the foundation. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the crawl space. The client should review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space. The crawl space should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, gravity drains and/or sump pump(s) in the crawl space.

    Photo 47  
     

    9) One or more unlined wooden planter boxes are attached to the side of the building. Wood soil contact exists in such boxes and is a conducive condition for wood-destroying insects and organisms. Recommend either removing them, or modifying them so that no wood-soil contact exists (install plastic or metal liners), and so that they are well drained.

    Photo 5  
     

    10) Caulk was deteriorated around windows, around doors, at siding-trim junctions. A qualified person should repair or replace as necessary. For more information, visit:
    http://www.reporthost.com/_docs/FPL_Caulking_Ins_Outs.pdf

    Photo 11  
     
     
    Roof / Attic Return to table of contents
    Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
    Condition of roof structure: Appeared serviceable
    Roof type: Gable
    Condition of shingle and/or shake roof surface materials: Appeared serviceable
    Roof surface material: Asphalt or fiberglass composition shingles
    Apparent number of layers of roof surface material: Two
    Condition of gutters, downspouts and extensions: Appeared serviceable
    Gutter and downspout material: Metal
    Gutter and downspout installation: Full
    Condition of attic: Appeared serviceable
    Attic inspection method: Viewed from hatch(es)
    Roof structure type: Trusses
    Ceiling structure: Trusses
    Ceiling insulation material: Mineral wool loose fill
    Ceiling insulation depth: 10 inches
    Ceiling insulation rating: R 28
    Roof ventilation: Appears serviceable
    11) One or more exhaust fan ducts in the attic were missing. This is a conducive condition for wood destroying insects and organisms due to increased moisture levels in the attic from the exhaust air. A qualified person should evaluate and make permanent repairs as necessary and as per standard building practices, so all exhaust air is vented outside.

    Photo 36  
     

    12)   The ceiling insulation in some areas of the attic was uneven. This may result in increased heating or cooling costs due to decreased energy efficiency. A qualified person should repair, replace or install insulation as necessary. For more information, visit:
    http://www.eere.energy.gov/consumer/tips/insulation.html

    Photo 37  
     

    13) Moss was growing on the roof. As a result, shingles may lift or be damaged. Leaks may result and/or the roof surface may fail prematurely. This is a conducive condition for wood destroying insects and organisms. Efforts should be taken to kill the moss during its growing season (wet months). Typically zinc-based chemicals are used for this, and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
    http://bryophytes.science.oregonstate.edu/page24.htm

    Photo 12  
     

    14)   This asphalt or fiberglass composition roof surface had two or more layers of roofing materials. When this roof is replaced, recommend a complete "tear off", where all existing layers of roofing are removed before installing new roofing materials. For 20-year rated composition shingles, additional layers of material reduce the new roof material's lifespan as follows:

  • 16-20 years - First roof
  • 12-16 years - Second layer on existing roof

    Removing existing roofing materials will significantly increase the cost of the next roof.
    15)   All attic and roof structure sections more than 10 feet from the access hatch(es) were inaccessible due to possible damage to insulation, limited height. These areas are excluded from the inspection.
     
    Garage / Carport Return to table of contents
    Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
    Type: Attached, Garage
    Condition of garage: Required repair, replacement and/or evaluation (see comments below)
    Type of garage: Solid core
    Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
    Garage vehicle door type: Sectional
    Number of vehicle doors: 1
    Condition of garage floor: Appeared serviceable
    Condition of garage interior: Required repair or evaluation (see comments below)
    16)   The self-closing device on the garage-dwelling door needs adjustment repair or replacing. This door is intended to prevent vehicle fumes from entering living spaces and to slow the spread of fire from the garage to living spaces. A qualified person should evaluate and make repairs as necessary.

    Photo 14  
     

    17)   The threshold at the base of the garage-dwelling door was missing. This door, and a threshold below, are intended to prevent vehicle fumes from entering living spaces and to slow the spread of fire from the garage to living spaces. A threshold prevents flammable materials such as carpeting from being installed under the door. A qualified contractor should evaluated and repair or replace the threshold as necessary.

    Photo 16  
     

    18)   Safety containment cables were missing for one or more vehicle door springs. This is a safety hazard. Safety containment cables prevent springs from snapping free and causing damage or injury. A qualified contractor should evaluate and make repairs or replace components as necessary. For more information on garage door safety issues, visit:
    http://www.cpsc.gov/cpscpub/pubs/523.html
    http://www.ohdstl.com/safety.html

    Photo 18  
     

    19)   The walls between the attached garage and interior living spaces had holes. These surfaces are intended to prevent vehicle fumes from entering living spaces, and to slow the spread of fire from the garage to living spaces. A qualified contractor should evaluate and make repairs as necessary so the attached garage wall and ceiling surfaces that adjoin living spaces are tightly sealed and fire rated as per standard building practices. Typically these surfaces require a one-hour fire rating.

    Photo 30  
     

    20)   Weatherstrip around or at the base of the garage-dwelling door was missing. A qualified person should repair or replace as necessary to prevent vehicle fumes from entering living spaces.

    Photo 15  
     

    21)   Hardware on the garage vehicle door was loose. A qualified person should evaluate and repair as necessary.

    Photo 19  
     

    22)   Some wall and floor areas were obscured by and couldn't be evaluated. These areas are excluded from the inspection.

    Photo 17  
     

    23)   Modifications were made, such as installing interior walls and/or shelving, and limit or reduce the parking space originally available in the garage.

    Photo 31  
     
     
    Electric Return to table of contents
    Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
    Electric service condition: Required repair, replacement and/or evaluation (see comments below)
    Primary service type: Overhead
    Service voltage (volts): 120
    Service amperage (amps): 200
    Primary service overload protection type: Circuit breakers
    Service entrance conductor material: Aluminum
    Main disconnect rating (amps): Not applicable, no single main disconnect
    System ground: Ground rod(s) in soil
    Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
    Condition of sub: Required repair, replacement and/or evaluation (see comments below)
    Location of main service panel #A: Garage
    Location of sub panel #B: Below main panel in garage
    Location of main disconnect: Top bank of breakers in main service panel (split bus)
    Branch circuit wiring type: Nonmetallic sheathed
    Condition of branch circuit wiring: Serviceable
    Solid strand aluminum branch circuit wiring present: None visible
    Smoke detectors present: Yes
    Carbon monoxide detectors present: No
    24)   This property had one or more Federal Pacific Electric brand main service or sub panels that use "Stab-Lok" circuit breakers (panel #B). Both double and single pole versions of these circuit breakers are known to fail by not tripping when they are supposed to. This is a potential but serious fire hazard. Recommend having a qualified electrician replace any and all Federal Pacific panels. For more information, visit: http://www.inspect-ny.com/fpe/fpepanel.htm

    If the Federal Pacific panel(s) are not replaced, then a qualified electrician should thoroughly evaluate the panel(s) and make repairs as necessary. Recommend installing smoke detectors above Federal Pacific panels.

    Photo 22  
     

    25)   This property had one or more Zinsco brand main service or sub panels (panel #A). These panels and their circuit breakers have a variety of problems including:

  • Bus bars made from aluminum that tend to oxidize and corrode
  • Breakers that don't trip under normal overload conditions
  • Breakers that appear to be tripped when they're not

    These problems are a safety hazard due to the risk of fire. Recommend having a qualified electrician replace any and all Zinsco brand panels.

    If the Zinsco panel(s) are not replaced, then a qualified electrician should thoroughly evaluate the panel(s) and components within and make repairs as necessary. Recommend installing smoke detectors above Zinsco panels.

    For more information, visit:
    http://www.inspect-ny.com/electric/Zinsco.htm

    Photo 21  
     

    26)   Some wiring was loose, unsupported, or inadequately supported (in garage). Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.

    Photo 26  
     

    27)   Wire splices were exposed due to not being contained in a covered junction box. For example, in the garage. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 23  

    Photo 27  

    28)   One or more electric baseboard heaters were installed with an electric receptacle located above. Insulation on appliance cords in contact with the heater(s) may be damaged by the heat. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, converting receptacles to junction boxes, moving receptacles and/or moving baseboard heaters.

    Photo 33  
     

    29)   Some electric receptacles had reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. (one in garage)

    Photo 20  
     

    30)   One or more electric receptacles at the following "wet" locations appeared to have no ground fault circuit interrupter (GFCI) protection: kitchen, bathroom(s). This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
    http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf

    Photo 41  
     

    31)   One or more bushings were missing from where wires enter holes in panel #B. This is a safety hazard since the wiring insulation can be cut or abraded on the metal edge of the hole(s). A qualified electrician should install bushings where missing.

    Photo 25  
     

    32)   Energized equipment was exposed at panel #B due to missing closure covers. This is a safety hazard due to the risk of shock. A qualified person should repair as necessary.

    Photo 24  
     

    33)   Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit this article: NFPA urges replacing home smoke alarms after 10 years.

    Photo 32  
     

    34)   Smoke detectors were missing from bedrooms. Additional smoke detectors should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, in each bedroom, and one each level of the building. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    35)   This property had one or more fuel burning appliances and/or an attached garage, and no carbon monoxide detectors were visible. This is a safety hazard. Recommend installing one or more carbon monoxide detectors as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
     
    Plumbing / Fuel Systems Return to table of contents
    Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
    Condition of service and main line: Appeared serviceable
    Location of main water meter: Hatch in driveway
    Location of main water shut: Not located
    Water service: Public
    Water pressure (psi): 65 psi
    Service pipe material: Not determined
    Condition of supply lines: Appeared serviceable
    Supply pipe material: Copper
    Condition of waste lines: Appeared serviceable
    Waste pipe material: Plastic
    36)   One or more outside faucets were missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the building. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

    Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079

    Photo 4  
     

    37)   Copper water supply pipes in buildings built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

    For more information visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
    http://www.epa.gov/safewater/lead/index.html

    Photo 45  
     

    38)   Most water supply pipes in the crawl space were uninsulated. Recommend insulating pipes as per standard building practices for better energy efficiency and to prevent water pipes from freezing.

    Photo 46  
     

    39)   A drain line at the west side of the crawl space was sagging. It mat not drain properly. A qualified person should repair as necessary. For example, install one or more Straps,

    Photo 44  
     

    40)   The inspector was not able to find the main water shut-off valve. The client should consult with the property owner to determine if a shut-off valve exists, find it themselves, or hire a qualified plumber if necessary to find it. If no shut-off valve is found for the structure, then recommend having a qualified plumber install one to more easily allow the water supply to be turned off in the event of an emergency, such as when a supply pipe bursts.
    41)   One or more outside faucets (one on west side) were not evaluated due to their being winterized with covers, and are excluded from this inspection.
     
    Water Heater Return to table of contents
    Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
    Condition of water heater: Appeared serviceable
    Type: Tank
    Estimated age: 2002
    Energy source: Electricity
    Capacity (in gallons): 50
    Manufacturer: U.S. Craftmaster
    Location of water heater: Garage
    42)   The temperature/pressure relief valve drain line was sloped upwards. This is a potential safety hazard due to the risk of explosion from restricted flow. A qualified plumber should evaluate and repair as necessary so the drain line complies with the temperature-pressure relief valve manufacturer's installation instructions. For more information, visit: http://www.reporthost.com/_docs/TPvalve.pdf

    Photo 28  
     

    43)   The water heater did not have seismic straps or struts installed. This is a potential safety hazard. Leaks may also occur in water supply pipes. A qualified person should install seismic straps or struts as necessary and as per standard building practices.
    44)   The temperature-pressure relief valve was leaking. A qualified plumbing contractor should replace this valve.

    Photo 10  
     

    45)   A permanently installed insulated jacket was installed on the water heater. It obscured the manufacturer's information label and most of the water heater. The inspector was unable to fully evaluate the water heater.

    Photo 29  
     
     
    Heating Return to table of contents
    Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
    Condition of heating system: Required repair, replacement and/or evaluation (see comments below)
    Heating type: Radiant, Baseboard
    Fuel type: Electric
    46)   One or more electric baseboard heaters were inoperable (bathroom and NW bedroom). A qualified person should evaluate and repair or replace as necessary.
     
    Fireplaces / Stoves / Chimneys Return to table of contents
    Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
    Location #A: Wood store in living room
    Stove type: Freestanding
    Fuel type: Wood
    Condition of chimneys: Appeared serviceable
    Chimney type: Metal
    47)   A significant amount of creosote (1/8 inch or more) was visible in flue(s) at location # A. A qualified contractor should inspect, clean, and repair if necessary now and annually in the future.

    Photo 13  
     
     
    Kitchen Return to table of contents
    Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
    Condition of counters: Appeared serviceable
    Condition of cabinets: Appeared serviceable
    Condition of sinks and related plumbing: Appeared serviceable
    Condition of range, cooktop: Appeared serviceable
    Range, cooktop type: Electric
    Condition of refrigerator: Appeared serviceable
     
    Bathrooms / Laundry / Sinks Return to table of contents
    Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
    Location #A: Hallway bath
    Location #B: Laundry area in garage
    Condition of counters: Appeared serviceable
    Condition of cabinets: Appeared serviceable
    Condition of sinks and related plumbing: Appeared serviceable
    Condition of toilets: Appeared serviceable
    Condition of bathtubs and related plumbing: Appeared serviceable
    Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments below)
    Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
    48) The exhaust fan at location #A was noisy or vibrates excessively. Moisture may accumulate as a result. A qualified person should evaluate and repair or replace as necessary.
    49)   The shower diverter valve at location #A was defective. A significant amount of water came out of the bathtub spout when the shower was turned on. Water will be wasted as a result. A qualified plumber should evaluate and replace components or make repairs as necessary.

    Photo 42  
     

    50)   The sink drain at location #A used flexible drain pipe. This type of drain pipe is more likely to clog than smooth wall pipe. Recommend having a qualified plumber replace this pipe with standard plumbing components (smooth wall pipe) to prevent clogged drains.

    Photo 40  
     
     
    Interior Rooms / Areas Return to table of contents
    Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
    Exterior door material: Wood, Sliding glass
    Condition of exterior entry doors: Appeared serviceable
    Condition of interior doors: Appeared serviceable
    Type of windows: Aluminum, Multi, Sliding
    Condition of windows: Required repair, replacement and/or evaluation (see comments below)
    Wall type or covering: Drywall
    Condition of walls: Appeared serviceable
    Ceiling type or covering: Drywall, Acoustic spray
    Condition of ceilings: Appeared serviceable
    Flooring type or covering: Carpet, Vinyl
    Condition of flooring: Appeared serviceable
    51)   Many ceiling areas in this structure had ceiling texture possibly installed prior to 1980. This material may contain asbestos, which is a known carcinogen and poses a health hazard. Laws were passed in the United States in 1978 prohibiting use of asbestos in residential structures, but stocks of existing materials have been known to be used for some time thereafter. The client may wish to have this ceiling material tested by a qualified lab to determine if it does contain asbestos.

    In most cases, when the material is intact and in good condition, keeping it encapsulated with paint and not disturbing it may reduce or effectively eliminate the health hazard. If the client wishes to remove the material, or plans to disturb it through remodeling, they should have it tested by a qualified lab and/or consult with a qualified industrial hygienist or asbestos abatement specialist. For more information, visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/453.html

    Photo 34  
     

    52)   Screens in some windows are deteriorated. A qualified person should evaluate and repair or replace as necessary.

    Photo 35  
     

    53)   Deadbolts on one or more exterior doors were inoperable (handle spun freely at front door). A qualified person should repair as necessary.

    Photo 39  
     

    54)   Lock mechanisms on many windows were damaged. A qualified person should repair as necessary.

    Photo 43  
     

    55)   Vinyl flooring was deteriorated in some (kitchen) areas. A qualified person should repair or replace as necessary.

    Photo 38  
     
     
    Structural Pest Findings Return to table of contents
    Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than five feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood destroying organisms may infest, reinfest or become active at anytime. No warranty is provided as part of this inspection.
    Visible evidence of active wood destroying insects: No
    Visible evidence of active wood decay fungi: No
    Visible evidence of past wood destroying insects: No
    Visible evidence of past wood decay fungi: No
    Visible evidence of damage by wood destroying insects: No
    Visible evidence of damage by wood decay fungi: No
    Visible evidence of conditions conducive to wood destroying organisms: Yes
     
    FOLLOW-UP INSPECTION POLICY
    Generally we discourage follow-up inspections for these reasons

    1. Quality of repairs
    If repairs are made to a property based on the results of an inspection, the work should be performed by qualified contractors, not the seller. By qualified, we mean licensed, bonded, state-certified where applicable and with a reasonable amount of experience. Contractors providing repairs should provide legible documentation in the form of work orders and/or receipts. If repairs are made in this way, then there's generally no need for a follow-up inspection. Additionally, it may be better to negotiate a lower price on your home and have repairs made by contractors you choose rather than the seller making repairs as cheaply as possible.

    2. Pest inspections required for some follow-up inspections
    On occasion, some follow-up inspections may require a complete, new structural pest inspection. Examples include:
  • Evaluating a crawl space after carpenter ant infestation was found
  • Evaluating numerous items throughout a structure after a significant amount of time has passed (original inspection in winter, follow-up in summer)

    Our fees for follow-up inspections are as follows:

  • Follow-up inspection: $150
  • Follow-up inspections with a structural pest (WDO/WDI) inspection: $250

    Additional charges usually apply for travel outside of Kitsap County




    SCOPE AND LIMITATIONS OF THIS INSPECTION
    This inspection is limited to a visual observation of the exposed and readily accessible areas of the home. The concealed and inaccessible areas are not included. The following locations are considered inaccessible due to limited height and excluded from this inspection unless otherwise stated:

  • Crawl space areas less than 18 inches in height
  • Attic spaces less than 5 feet in height
  • Spaces under outdoor decks less than 5 feet high

    Observation includes operation of the systems or components by means of the normal user controls. Dismantling of equipment, and destructive testing is not included. Some specific items are also excluded, and these are listed in the following section. If you feel there is a need for evaluation of any of these items, then you will need to arrange for specific inspections.

    Items not Included

    1. Recreational, leisure, playground or decorative equipment or appliances including but not limited to pools, hot tubs, saunas, steam baths, landscape lighting, fountains, shrubs, trees, and tennis courts;
    2. Cosmetic conditions (wallpapering, painting, carpeting, scratches, scrapes, dents, cracks, stains, soiled or faded surfaces on the structure or equipment, soiled, faded, torn, or dirty floor, wall or window coverings etc.);
    3. Noise pollution or air quality in the area;
    4. Earthquake hazard, liquefaction, flood plain, soil, slide potential or any other geological conditions or evaluations;
    5. Engineering level evaluations on any topic;
    6. Existence or non-existence of solder or lead in water pipes, asbestos, hazardous waste, radon, urea formaldehyde urethane, lead paint or any other environmental, flammable or toxic contaminants or the existence of water or airborne diseases or illnesses and all other similar or potentially harmful substances (although the inspector may note the possible existence of asbestos in ceiling texture and furnace duct tape);
    7. Zoning or municipal code (e.g. building, fire, housing (existing buildings), mechanical, electrical, plumbing, etc. code) restrictions or other legal requirements of any kind;
    8. Any repairs which relate to some standard of interior decorating;
    9. Cracked heat exchangers or similar devices in furnaces;
    10. Any evaluation which requires the calculation of the capacity of any system or item that is expected to be part of the inspection. Examples include but are not limited to the calculation of appropriate wattage or wiring of kitchen appliances, appropriate sizing of flues or chimneys, appropriate ventilation to combustion-based items (e.g. furnaces, water heaters, fireplaces etc.), appropriate sizing, spacing and spanning of joists, beams, columns, girders, trusses, rafters, studs etc., appropriate sizing of plumbing and fuel lines, etc.;
    11. Washers and dryers;
    12. Circuit breaker operation;
    13. Specialty evaluations such as private sewage, wells, solar heating systems, alarms, intercom systems, central vacuum systems, wood and coal stoves, pre-fab and zero clearance fireplaces, space heaters, sprinkler systems, gas logs, gas lights, elevators and common areas unless these have been specifically added to the inspection description above but only to the degree that the inspector is capable of evaluating these items;
    14. Items that are not visible and exposed including but not limited to concealed wiring, plumbing, water leaks, under bathtubs and shower stalls due to faulty pans or otherwise, vent lines, duct work, exterior foundation walls (below grade or covered by shrubs or wall/paneling, stored goods etc.) and footings, underground utilities, and systems and chimney flues;
    15. Evaluations involving destructive testing;
    16. Evaluation which requires moving personal goods, debris, furniture, equipment, floor covering, insulation or like materials;
    17. Design problems and adequacy or operational capacity, quality or suitability;
    18. Fireplace drafting;
    19. To prevent damages to units, air conditioning when outside temperature below 60 degrees F or if the unit has not been warmed up or on for at least 24 hours prior to inspection;
    20. Any evaluation which would involve scraping paint or other wall coverings;
    21. Heating system accessories (e.g. humidifiers, electronic air cleaners etc.);
    22. Legal description of property such as boundaries, egress/ingress, etc.;
    23. Quality of materials;
    24. Conformance with plan specifications or manufacturers specifications;
    25. Flood conditions or plains;
    26. Any other characteristics or items which are generally not included in a building inspection report on a regular basis.

    As a part of our service, we sometimes provide approximate, cost of repair estimates for particular items. These estimates should be considered as background information only. It is beyond the scope of this inspection and report to supply you with accurate repair costs. Such estimates should be supplied by contractors who specialize in this type of work. Our estimates should be used only as guidelines. If you intend to negotiate the price of this property based on defects found during this inspection, we strongly suggest you obtain one or more written bids from a licensed contractor(s). It is a conflict of interest for All Point Home Inspections to recommend any specific contractor.

    Evaluations are made as to the present age, and remaining economic life of an item, i.e. water heaters, roofs, plumbing, furnaces, etc. These evaluations are based on visual observation, industry averages and prior experience. THEY ARE NOT OFFERED AS A WARRANTY OR CERTIFICATION OF REMAINING LIFE.

    Disclaimer
    In some cases we may recommend your consulting a specialist such as a structural engineer or licensed electrician. Hiring a specialist can be a prudent means of providing some protection of your financial investment in this property. WE DO NOT MAKE ANY TYPE OF WARRANTY OR GUARANTEE AS TO THE CONDITION OF THE PROPERTY. SOME THINGS MAY REMAIN HIDDEN OR BECOME DEFECTIVE AFTER THE INSPECTION. IT IS NOT POSSIBLE TO DETECT EVERY DEFECT WITHIN A BUILDING DURING THE COURSE OF A GENERAL INSPECTION. THIS REPORT SHOULD BE USED IN CONJUNCTION WITH, AND NOT A REPLACEMENT FOR , A PRE-CLOSING WALK-THROUGH BY THE CLIENT.
    THIS INSPECTION IS NOT AN INSURANCE POLICY AGAINST HIDDEN DEFECTS, OR CONDITIONS THAT ARE NOT VISIBLE AND READILY APPARENT AT THE TIME OF INSPECTION.

    THE COST OF THIS INSPECTION DOES NOT ENTITLE YOU TO ANY TYPE OF PROTECTION FROM HIDDEN FLAWS AND DEFECTS. THIS INSPECTION DOES NOT TRANSFER YOUR ULTIMATE RESPONSIBILITY TO ALL POINT HOME INSPECTIONS.