This is an actual home inspection report published in 10 minutes, starting from the time the report was uploaded from the ReportHost Pro software to the ReportHost website.  The 10 minute time included resizing and uploading digital pictures, spell checking and publishing.

An example of a report that took 20 minutes can be found here.


Website: http://www.allpointinspections.com/
Phone: (XXX) XXX-XXXX
XXXXX XXXXXXXX XX 
Poulsbo, WA 98370
Inspector: Jim Gallant

 

Full General Home Inspection and Structural Pest Inspection
WA State Dept. Agriculture ICN# XXXXXXXXXXX
Client(s): XXXXXX XXXXXXX
Property address: XXXX XXXXXXXX XX
XXXXXXX XX
Inspection date: XX/XX/XXXX
This report published on XX/XX/XXXX XX:XX:XX PM PDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

WAC 16-228-2045 requires that a diagram be prepared for WDO (Wood Destroying Organism) inspection reports. A copy is available upon request.

For information on follow-up inspections, please see the bottom section of this report.


Thank you for choosing All Point Home Inspections. We've made every effort to provide you with a thorough, high quality inspection, and hope that the information in this report proves to be valuable in your consideration of this property. If for any reason you are unsatisfied with this report, or have questions after reviewing it, please don't hesitate to call us. If you are satisfied, please tell your friends about us.

This inspection complies with the American Society of Home Inspectors' (ASHI) Standards of Practice and the National Association of Home Inspectors' (NAHI) Standards of Practice. This report is intended to identify major defects within a structure that significantly affect its habitability or that cost in excess of $500 to repair, although minor defects may be noted in the report. Cosmetic items such as damaged molding, trim, doors, cabinets, interior paint or carpet are generally excluded from this report.

Home inspection reports by nature focus on defects and may seem negative in tone. Some features of this property may be in excellent condition and of high quality but have not been mentioned, or been deemed adequate in the report. This is not meant to downplay this property's assets, but to focus on alerting you to potentially expensive problems. Bear in mind that all homes, regardless of their age, have some number of defects.

Areas of the property that are excluded due to lack of access are vulnerable to infestation and damage from wood destroying insects and organisms.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection only involves a minor expense 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.

  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating
Fireplaces / Stoves / Chimneys
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas
Structural Pest Findings
 

General Information 
Return to table of contents

Report number: XXXXXXXXXX
Time started: 1:00 PM
Time finished: 3:10PM
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions: Partly cloudy
Temperature: Cool
Ground condition: Damp
Inspection fee: $XXX
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Age of building(s): XXXX
Source for building age: Realtor
Front of building faces: West
Main entrance faces: West
Occupied: Yes
Property owner's name: XXXXX
1)   Some wall and floor surfaces were obscured by furniture, stored items and couldn't be fully evaluated.
 
Grounds 
Return to table of contents

Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
The following items are excluded from this inspection: Shed
Condition of fences and gates: Appeared serviceable
Fence and gate material: Wood
Site profile: Minor slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete, Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of decks, porches and/or balconies: Appeared serviceable
Condition of guardrails: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of exterior stairs: Appeared serviceable
Condition of handrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood
2)   Guardrails in some areas with drop-offs higher than 30 inches were missing. This is a safety hazard. Standard building practices require that they:

  • Be installed at drop-offs higher than 30 inches
  • Be securely and permanently attached
  • Be at least 36 inches in height
  • Not be climbable by children
  • Not have gaps or voids that allow passage of a sphere equal to or greater than four inches in diameter

    A qualified contractor should evaluate and repair, replace or install guardrails as necessary, and as per standard building practices.

  • Photo 4  
     

    3)   Handrails at one or more flights of stairs were missing. This is a safety hazard. Standard building practices require that handrails be:

  • Installed at stairs with three or more risers
  • Sized and shaped so your hand can encircle them
  • Permanently and securely attached, and able to withstand a 200 pound force in any direction at any point
  • Continuous and extend for the entire flight of the stairs
  • Located between 30 and 38 inches above the leading edge of the stair treads

    A qualified person should repair, replace or install as necessary and as per standard building practices.

  • Photo 5  
     

    4) Vegetation such as trees, shrubs and/or vines was in contact with or less than one foot from the building exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the building exterior.

    Photo 2  
     
     
    Exterior / Foundation 
    Return to table of contents

    Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
    Condition of wall covering: Appeared serviceable
    Apparent wall structure: Wood frame
    Wall covering: Wood, Wood fiber, Brick veneer
    Condition of foundation and footings: Appeared serviceable
    Foundation type: Crawlspace
    Foundation material: Poured in place concrete
    Anchor bolts for seismic reinforcement: Installed
    Anchor bolts for seismic reinforcement were observed at: Crawl space
    Shear panels for seismic reinforcement: Not determined
    Condition of floor substructure: Appeared serviceable
    Pier or support post material: Wood
    Beam material: Solid wood
    Floor structure: Solid wood joists
    Condition of crawl space: Appeared serviceable
    Crawl space inspection method: Traversed
    Insulation material underneath floor above: Fiberglass roll or batt
    Ventilation: Appears serviceable
    Vapor barrier present: Yes
    5) One or more minor cracks (1/8 inch or less) were found in the foundation.

    Photo 22  
     

    6) Cardboard was found in the crawl space. All cellulose-based debris or stored items should be removed to avoid attracting wood destroying insects.

    Photo 21  
     
     
    Roof / Attic 
    Return to table of contents

    Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
    Condition of roof structure: Appeared serviceable
    Roof type: Gable, Hipped
    Condition of shingle and/or shake roof surface materials: Appeared serviceable
    Roof surface material: Asphalt or fiberglass composition shingles
    Apparent number of layers of roof surface material: One
    Condition of exposed flashings: Appeared serviceable
    Condition of gutters, downspouts and extensions: Appeared serviceable
    Gutter and downspout material: Metal
    Gutter and downspout installation: Full
    Condition of attic: Appeared serviceable
    Attic inspection method: Traversed
    Roof structure type: Rafters
    Ceiling structure: Ceiling beams
    Ceiling insulation material: Mineral wool loose fill
    Ceiling insulation depth: 8 inches
    Ceiling insulation rating: R 30
    7)   The pull-down attic stairs in the attached garage ceiling were not fire-rated. This ceiling should have a one-hour fire rating to slow or prevent the spread of fire from the attached garage to attic spaces above the living areas. A qualified contractor should evaluate and make modifications to these stairs as necessary so they have a one hour fire rating. Other options include removing them or replacing them with commercially made, fire-rated stairs. Examples of possible solutions include:

  • Installing 5/8 inch Type X sheetrock on the lower surface of the stair door and eliminating gaps around the edges of the door.
  • Removing the stairs and installing a traditional hatch made with 5/8 inch Type X sheetrock.
  • Installing a Battic Door and installing sheetrock over it as described at their website, http://www.batticdoor.com
  • Replacing these stairs with fire-rated stairs such as Calvert USA Fire resistant commercial aluminum folding attic stairs, http://www.calvertusa.com

  • Photo 7  
     
     
    Garage / Carport 
    Return to table of contents

    Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
    Type: Attached, Garage
    Condition of garage: Appeared serviceable
    Type of garage: Solid core
    Condition of garage vehicle door(s): Appeared serviceable
    Garage vehicle door type: Sectional
    Number of vehicle doors: 2
    Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
    Condition of garage interior: Required repair or evaluation (see comments below)
    8)   No "photo eye" sensors were installed for one or more vehicle door's electric door opener. They've been required on all automatic door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit:
    http://www.cpsc.gov/cpscpub/pubs/523.html
    http://www.ohdstl.com/safety.html

    Photo 10  
     

    9)   The door stop on the garages-house door should be removed. This door is intended to be a fire-safe door and should self-close at all times.

    Photo 12  
     

    10)   When the inspector tested the south vehicle door's auto-reverse mechanism, the door bracket popped off the chain. This happened twice. A qualified contractor should evaluate both doors and repair as necessary.

    Photo 9  
     
     
    Electric 
    Return to table of contents

    Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
    Electric service condition: Appeared serviceable
    Primary service type: Underground
    Service voltage (volts): 120
    Service amperage (amps): 200
    Primary service overload protection type: Circuit breakers
    Service entrance conductor material: Aluminum
    Main disconnect rating (amps): 200
    System ground: Unable to determine
    Condition of main service panel: Appeared serviceable
    Location of main service panel #A: Garage
    Location of sub panel #B: In back yard (for RV?)
    Location of main disconnect: Breaker at top of main service panel
    Branch circuit wiring type: Nonmetallic sheathed
    Condition of branch circuit wiring: Serviceable
    Solid strand aluminum branch circuit wiring present: None visible
    Smoke detectors present: Yes
    Carbon monoxide detectors present: Yes
    11)   Some (one on east wall of garage) electric receptacles had reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    Photo 8  
     

    12)   One or more ground fault circuit interrupter (GFCI) type receptacles were found to have an open ground (one at south building exterior and one in kitchen). GFCI protection will still work with an open ground, but ideally repairs should be made as necessary so grounding is correct with these receptacles. A qualified electrician should evaluate and make repairs as necessary.

    Photo 6  

    Photo 15  

    13)   Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit this article: NFPA urges replacing home smoke alarms after 10 years.
    14)   Smoke detectors were missing from bedrooms. Additional smoke detectors should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, in each bedroom, and one each level of the building. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html

    Photo 13  
     

    15)   Some cover plates on receptacle boxes were missing (garage ceiling). They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. A qualified person should repair as necessary.

    Photo 11  
     

    16)   Some (one in kitchen) light fixtures were inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner. Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.

    Photo 16  
     

    17)   Some electric receptacles were not evaluated because of furniture, stored items, childproof covers.

    Photo 18  
     
     
    Plumbing / Fuel Systems 
    Return to table of contents

    Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
    Location of main water meter: Southwest corner of front yard
    Location of main water shut: Blue handled valve in garage
    Water service: Public
    Water pressure (psi): 44 psi
    Condition of supply lines: Appeared serviceable
    Supply pipe material: Copper
    Condition of waste lines: Appeared serviceable
    Location of main fuel shut: Valve by gas meter on south side
    Visible fuel storage systems: None
    18)   One or more outside faucets were missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the building. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

    Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079

    19)   Some water supply pipes in the crawl space were uninsulated. Recommend insulating pipes as per standard building practices for better energy efficiency and to prevent water pipes from freezing.

    Photo 20  
     
     
    Water Heater 
    Return to table of contents

    Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
    Condition of water heater: Appeared serviceable
    Type: Instantaneous
    Energy source: Natural gas
    Capacity (in gallons): N/A
    Manufacturer: Rinnai
     
    Heating 
    Return to table of contents

    Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
    Location of heating system: Garage
    Heating type: Forced air
    Fuel type: Natural gas
    Manufacturer: Carrier
    Last service date: 4/17/07
    Source for last service date: Realtor
    Condition of burners: Appeared serviceable
    Condition of venting system: Appeared serviceable
    Condition of combustion air supply: Appeared serviceable
    Condition of distribution system: Appeared serviceable
    Distribution system: Ducts and registers
    Condition of controls: Appeared serviceable
    Condition of air filters: Appeared serviceable
    Location of air filters: Behind return air grill
    20)   The estimated useful life for most forced air furnaces is 15 to 20 years. The inspector was unable to determine the age of the furnace. The client should be aware that this furnace may be near, at, or beyond its useful life and may need replacing or significant repairs at any time. Recommend attempting to determine the furnace's age (ask property owner or service technician), and budgeting for a replacement if necessary.
     
    Fireplaces / Stoves / Chimneys 
    Return to table of contents

    Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
    Condition of fireplaces, stoves: Appeared serviceable
    Location #A: Family room
     
    Kitchen 
    Return to table of contents

    Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
    Condition of counters: Appeared serviceable
    Condition of cabinets: Appeared serviceable
    Condition of sinks and related plumbing: Appeared serviceable
    Condition of garbage disposal: Appeared serviceable
    Condition of dishwasher: Appeared serviceable
    Condition of range, cooktop: Appeared serviceable
    Range, cooktop type: Electric
    21)   The dishwasher wasn't securely attached to the counter above. Fasteners were missing. A qualified person should repair as necessary.

    Photo 14  
     

    22)   The estimated useful life for most kitchen appliances is 10 to 15 years. The following appliances appeared to be beyond this age and/or their useful lifespan and may need replacing at any time: dishwasher, refrigerator. Recommend budgeting for replacements in the near future.
     
    Bathrooms / Laundry / Sinks 
    Return to table of contents

    Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
    Location #A: Main hall bath
    Location #B: Master bath
    Location #C: Laundry room
    Condition of counters: Appeared serviceable
    Condition of cabinets: Appeared serviceable
    Condition of sinks and related plumbing: Appeared serviceable
    Condition of toilets: Appeared serviceable
    Condition of bathtubs and related plumbing: Appeared serviceable
    Condition of ventilation systems: Appeared serviceable
    23)   The clothes dryer was equipped with a foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

    Photo 17  
     
     
    Interior Rooms / Areas 
    Return to table of contents

    Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
    Exterior door material: Wood, Metal, Sliding glass
    Condition of exterior entry doors: Appeared serviceable
    Condition of interior doors: Appeared serviceable
    Type of windows: Wood, Multi, Sliding, Casement, Single hung
    Condition of windows: Required repair, replacement and/or evaluation (see comments below)
    Wall type or covering: Drywall
    Condition of walls: Appeared serviceable
    Ceiling type or covering: Drywall
    Condition of ceilings: Appeared serviceable
    Flooring type or covering: Carpet, Vinyl, Wood
    24)   Seals between multi-pane glass in some (one by front door, one in living room) windows appear to have failed based on condensation or stains between the panes of glass. A qualified contractor should evaluate and replace glass where necessary.

    The client should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Windows or glass doors other than those that the inspector identified may also have failed seals and need glass replaced too.

    Photo 3  

    Photo 19  

    25)   Screens in some windows were (at casement windows).
     
    Structural Pest Findings 
    Return to table of contents

    Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than five feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood destroying organisms may infest, reinfest or become active at anytime. No warranty is provided as part of this inspection.
    Visible evidence of active wood destroying insects: No
    Visible evidence of active wood decay fungi: No
    Visible evidence of past wood destroying insects: No
    Visible evidence of past wood decay fungi: No
    Visible evidence of damage by wood destroying insects: No
    Visible evidence of damage by wood decay fungi: No
    Visible evidence of conditions conducive to wood destroying organisms: Yes
     
    FOLLOW-UP INSPECTION POLICY
    Generally we discourage follow-up inspections for these reasons

    1. Quality of repairs
    If repairs are made to a property based on the results of an inspection, the work should be performed by qualified contractors, not the seller. By qualified, we mean licensed, bonded, state-certified where applicable and with a reasonable amount of experience. Contractors providing repairs should provide legible documentation in the form of work orders and/or receipts. If repairs are made in this way, then there's generally no need for a follow-up inspection. Additionally, it may be better to negotiate a lower price on your home and have repairs made by contractors you choose rather than the seller making repairs as cheaply as possible.

    2. Pest inspections required for some follow-up inspections
    On occasion, some follow-up inspections may require a complete, new structural pest inspection. Examples include:
  • Evaluating a crawl space after carpenter ant infestation was found
  • Evaluating numerous items throughout a structure after a significant amount of time has passed (original inspection in winter, follow-up in summer)

    Our fees for follow-up inspections are as follows:

  • Follow-up inspection: $150
  • Follow-up inspections with a structural pest (WDO/WDI) inspection: $250

    Additional charges usually apply for travel outside of Kitsap County




    SCOPE AND LIMITATIONS OF THIS INSPECTION
    This inspection is limited to a visual observation of the exposed and readily accessible areas of the home. The concealed and inaccessible areas are not included. The following locations are considered inaccessible due to limited height and excluded from this inspection unless otherwise stated:

  • Crawl space areas less than 18 inches in height
  • Attic spaces less than 5 feet in height
  • Spaces under outdoor decks less than 5 feet high

    Observation includes operation of the systems or components by means of the normal user controls. Dismantling of equipment, and destructive testing is not included. Some specific items are also excluded, and these are listed in the following section. If you feel there is a need for evaluation of any of these items, then you will need to arrange for specific inspections.

    Items not Included

    1. Recreational, leisure, playground or decorative equipment or appliances including but not limited to pools, hot tubs, saunas, steam baths, landscape lighting, fountains, shrubs, trees, and tennis courts;
    2. Cosmetic conditions (wallpapering, painting, carpeting, scratches, scrapes, dents, cracks, stains, soiled or faded surfaces on the structure or equipment, soiled, faded, torn, or dirty floor, wall or window coverings etc.);
    3. Noise pollution or air quality in the area;
    4. Earthquake hazard, liquefaction, flood plain, soil, slide potential or any other geological conditions or evaluations;
    5. Engineering level evaluations on any topic;
    6. Existence or non-existence of solder or lead in water pipes, asbestos, hazardous waste, radon, urea formaldehyde urethane, lead paint or any other environmental, flammable or toxic contaminants or the existence of water or airborne diseases or illnesses and all other similar or potentially harmful substances (although the inspector may note the possible existence of asbestos in ceiling texture and furnace duct tape);
    7. Zoning or municipal code (e.g. building, fire, housing (existing buildings), mechanical, electrical, plumbing, etc. code) restrictions or other legal requirements of any kind;
    8. Any repairs which relate to some standard of interior decorating;
    9. Cracked heat exchangers or similar devices in furnaces;
    10. Any evaluation which requires the calculation of the capacity of any system or item that is expected to be part of the inspection. Examples include but are not limited to the calculation of appropriate wattage or wiring of kitchen appliances, appropriate sizing of flues or chimneys, appropriate ventilation to combustion-based items (e.g. furnaces, water heaters, fireplaces etc.), appropriate sizing, spacing and spanning of joists, beams, columns, girders, trusses, rafters, studs etc., appropriate sizing of plumbing and fuel lines, etc.;
    11. Washers and dryers;
    12. Circuit breaker operation;
    13. Specialty evaluations such as private sewage, wells, solar heating systems, alarms, intercom systems, central vacuum systems, wood and coal stoves, pre-fab and zero clearance fireplaces, space heaters, sprinkler systems, gas logs, gas lights, elevators and common areas unless these have been specifically added to the inspection description above but only to the degree that the inspector is capable of evaluating these items;
    14. Items that are not visible and exposed including but not limited to concealed wiring, plumbing, water leaks, under bathtubs and shower stalls due to faulty pans or otherwise, vent lines, duct work, exterior foundation walls (below grade or covered by shrubs or wall/paneling, stored goods etc.) and footings, underground utilities, and systems and chimney flues;
    15. Evaluations involving destructive testing;
    16. Evaluation which requires moving personal goods, debris, furniture, equipment, floor covering, insulation or like materials;
    17. Design problems and adequacy or operational capacity, quality or suitability;
    18. Fireplace drafting;
    19. To prevent damages to units, air conditioning when outside temperature below 60 degrees F or if the unit has not been warmed up or on for at least 24 hours prior to inspection;
    20. Any evaluation which would involve scraping paint or other wall coverings;
    21. Heating system accessories (e.g. humidifiers, electronic air cleaners etc.);
    22. Legal description of property such as boundaries, egress/ingress, etc.;
    23. Quality of materials;
    24. Conformance with plan specifications or manufacturers specifications;
    25. Flood conditions or plains;
    26. Any other characteristics or items which are generally not included in a building inspection report on a regular basis.

    As a part of our service, we sometimes provide approximate, cost of repair estimates for particular items. These estimates should be considered as background information only. It is beyond the scope of this inspection and report to supply you with accurate repair costs. Such estimates should be supplied by contractors who specialize in this type of work. Our estimates should be used only as guidelines. If you intend to negotiate the price of this property based on defects found during this inspection, we strongly suggest you obtain one or more written bids from a licensed contractor(s). It is a conflict of interest for All Point Home Inspections to recommend any specific contractor.

    Evaluations are made as to the present age, and remaining economic life of an item, i.e. water heaters, roofs, plumbing, furnaces, etc. These evaluations are based on visual observation, industry averages and prior experience. THEY ARE NOT OFFERED AS A WARRANTY OR CERTIFICATION OF REMAINING LIFE.

    Disclaimer
    In some cases we may recommend your consulting a specialist such as a structural engineer or licensed electrician. Hiring a specialist can be a prudent means of providing some protection of your financial investment in this property. WE DO NOT MAKE ANY TYPE OF WARRANTY OR GUARANTEE AS TO THE CONDITION OF THE PROPERTY. SOME THINGS MAY REMAIN HIDDEN OR BECOME DEFECTIVE AFTER THE INSPECTION. IT IS NOT POSSIBLE TO DETECT EVERY DEFECT WITHIN A BUILDING DURING THE COURSE OF A GENERAL INSPECTION. THIS REPORT SHOULD BE USED IN CONJUNCTION WITH, AND NOT A REPLACEMENT FOR , A PRE-CLOSING WALK-THROUGH BY THE CLIENT.
    THIS INSPECTION IS NOT AN INSURANCE POLICY AGAINST HIDDEN DEFECTS, OR CONDITIONS THAT ARE NOT VISIBLE AND READILY APPARENT AT THE TIME OF INSPECTION.

    THE COST OF THIS INSPECTION DOES NOT ENTITLE YOU TO ANY TYPE OF PROTECTION FROM HIDDEN FLAWS AND DEFECTS. THIS INSPECTION DOES NOT TRANSFER YOUR ULTIMATE RESPONSIBILITY TO ALL POINT HOME INSPECTIONS.