View as PDF

View summary

Logo

Key Point Home Inspector LLC

519 127th St 
College Point NY 11356-1239
Inspector: TIANSHU ZHAO

Home Inspection Sample

Client(s):  *****
Property address:  *****
Inspection date:  Wednesday, March 22, 2023

This report published on Wednesday, March 22, 2023 3:31:36 AM EDT

This report is the exclusive property of Key Point Home Inspection LLC. and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Thank you for choosing Key Point Home Inspection LLC. We've made every effort to provide you with a thorough, high quality inspection, and hope that the information in this report proves to be valuable in your consideration of this property. If for any reason you are unsatisfied with this report, or have questions after reviewing it, please don't hesitate to call us 347-935-5669. If you are satisfied, please tell your friends and colleagues about us. A letter or testimonial, which you can email is a wonderful complement.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary

General Information
Table of contents
Report number: sample
Time started: 10AM
Time finished: 1PM
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cold
Type of building: Single family
Buildings inspected: One house, One detached garage
Number of residential units inspected: 1
Age of main building: 73
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: No
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
https://www.reporthost.com/?EPA
https://www.reporthost.com/?CPSC
https://www.reporthost.com/?CDC
2) The natural gas service was not turned on during the inspection. The inspector operates only "normal" controls such as thermostats, stove burner knobs, and on/off switches, and does not operate gas shut-off valves or activate pilot lights. As a result, items such as but not limited to the gas supply system, gas-fired water heater(s), gas-fired forced air furnace(s), gas fireplace(s), stove(s), and range(s) weren't fully evaluated. The inspector was unable to test for gas leaks. Recommend that a qualified person make a full evaluation of the gas supply system and gas-fired appliances after the gas supply is turned back on. Any problems that are found after this evaluation should be repaired by a qualified contractor.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Metal
3) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
Photo
Photo 3-4 
Photo
Photo 3-5 
Photo
Photo 3-6 
4) Cracks, holes, settlement, heaving and/or deterioration were found in sidewalks and/or patios. Recommend that qualified contractor repair as necessary.
Photo
Photo 4-1 
Photo
Photo 4-2 
Photo
Photo 4-3 
5) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
6) Pavement sloped down towards building perimeters in one or more areas. This may result in water accumulating around building foundations or underneath buildings. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing old pavement and installing new.
Photo
Photo 6-1 
7) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Metal
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Poured in place concrete, Concrete block
Footing material (under foundation stem wall): Poured in place concrete
8) Flashing at one or more locations was damaged. Leaks can occur as a result. Recommend that a qualified person repair, replace or install flashing as necessary, and per standard building practices.
Photo
Photo 8-1 
9) One or more planters were attached to the building exterior. This can result in high levels of moisture at the building exterior near planters. It is a conducive condition for wood-destroying organisms. Recommend removing planters, or repairing so there is a gap of at least 2 inches between planters and the building exterior for better airflow and to allow building exteriors to dry quickly.
Photo
Photo 9-1 
10) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
11) Caulk was deteriorated in some areas. For example, around windows. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
https://www.reporthost.com/?CAULK
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
12)  
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
13)  Fence near the garage in the backyard is loose, recommend a licensed professional to repair.
Photo
Photo 13-1 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood, Metal
14) The risers for stairs at one or more locations varied in height and pose a fall or trip hazard. Risers within the same flight of stairs should vary by no more than 3/8 inch. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 14-1 
Photo
Photo 14-2 
Photo
Photo 14-3 
15) Fungal rot was found at one or more exterior door jambs. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo
Photo 15-1 
Photo
Photo 15-2 
16) One or more exterior doors were difficult to latch. Recommend that a qualified person repair as necessary.

The red entrance door were difficult to latch and the storm door shows a gap at top when closed.
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: Multiple
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below), Limited evaluation due to little or no rainfall during and prior to the inspection
17) One or more roof flashings were lifting. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 17-1 
18) One or more downspouts were loose and/or damaged. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
Photo
Photo 18-4 
Photo
Photo 18-5 
Photo
Photo 18-6 
Photo
Photo 18-7 
19) Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 19-1 
20) This asphalt or fiberglass composition roof surface appeared to have two or more layers of shingles. Additional layers of composition shingles typically last only 80% of their rated life, and the shingle manufacturer's warranty may be voided. The client should be aware that all layers of roofing will need to be removed when this roof surface needs replacing.
Photo
Photo 20-1 
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Condition of insulation in attic (ceiling, skylight chase, etc.): Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Vermiculite insulation present: None visible
Condition of roof ventilation: Not determined (inaccessible or obscured)
Roof ventilation type: Gable end vents
21) Attic insulation at one or more attic walls was falling down and/or damaged. Heating and cooling costs will likely be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices.

The moisture barrier on the insulation are damaged, recommend replacing it by licensed contractor.
Photo
Photo 21-1 
Photo
Photo 21-2 
Photo
Photo 21-3 
Photo
Photo 21-4 
22) One or more attic or roof vent screens were missing, deteriorated or substandard. Recommend that a qualified person replace or repair screens as necessary to prevent birds or vermin from entering the attic.
Photo
Photo 22-1 
Garage or Carport
Table of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Detached, Garage
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: None visible
23) Entrance door on the side of the garage do not have a lock set, recommend installing lock set.
Photo
Photo 23-1 
24) Too much vegetation growing on the side of the garage exterior, damaging the wall, window sill, and gutter. recommend evaluate by an insured landscaper and repair by licensed contractor.
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
25) One or more garage vehicle doors were damaged or deteriorated. Recommend that a qualified contractor repair or replace door(s) as necessary. Back side is insulated but not covered with cover.
Photo
Photo 25-1 
26)  
Photo
Photo 26-1 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 100
System ground: Cold water supply pipes
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: copper
Solid strand aluminum branch circuit wiring present: Yes
Ground fault circuit interrupter (GFCI) protection present: Yes
Smoke alarms installed: Installed and appear to be functioning properly at this time
Carbon monoxide alarms installed: Yes and appeared to be working property at this time
27) One or more branch circuits with solid-strand aluminum wires were found. Problems due to expansion and contraction with this type of wiring can cause overheating at connections between the wire and devices such as switches and receptacles, or at splices. This is a potential fire hazard. The Consumer Products Safety Commission recommends either discontinuing use of circuits with aluminum wiring, removing the wiring, or that an electrician determine if copper wire can be pig-tailed onto the ends of the aluminum wire. A qualified electrician should evaluate the full electrical system and repair as necessary. For more information, visit:
https://www.reporthost.com/?ALWIRE1
https://www.reporthost.com/?ALWIRE2
Photo
Photo 27-1 
28) One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the kitchen wouldn't reset when tripped. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 28-1 
29) One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
https://www.reporthost.com/?DBLTAP
Photo
Photo 29-1 
30) Smoke alarms were missing from one or more bedrooms. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom and on each level. For more information, visit:
https://www.reporthost.com/?SMKALRM
31) 2-slot receptacles rather than 3-slot, grounded receptacles were installed in one or more areas. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits.
Photo
Photo 31-1 
32) one of the breaker is missing the neutral line. recommend licensed electrician to evaluate and repair.
Photo
Photo 32-1 
Photo
Photo 32-2 
33) One or more wall switches were broken or damaged. Recommend that a qualified electrician replace wall switches as necessary.
Photo
Photo 33-1 
Photo
Photo 33-2 
34) The legend for circuit breakers or fuses in panel(s) #A was missing, incomplete, illegible or confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.
Photo
Photo 34-1 
Photo
Photo 34-2 
35) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Photo
Photo 35-1 
36) One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 36-1 
37)  Lack of lighting above stairs going to the second floor, recommend licensed electrician to evaluate and install.
Photo
Photo 37-1 
Photo
Photo 37-2 
38)  Lamp light switch controls the outlet on the same wall in the living room
Photo
Photo 38-1 
Photo
Photo 38-2 
Photo
Photo 38-3 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Water service: Public
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic, Galvanized steel, Brass
Condition of waste lines: Required repair, replacement and/or evaluation (see comments below)
Waste pipe material: Plastic, Galvanized steel, Cast iron
Vent pipe condition: Not determined (inaccessible, obscured, or water service off)
Vent pipe material: Not determined (inaccessible or obscured)
Sump pump installed: No
Sewage ejector pump installed: No
Type of irrigation system supply source: Public
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground, in basement
Location of main fuel shut-off valve: At gas meter, At oil tank
39) The house trap was unable to inspect because the pit was filled with dirt.
Photo
Photo 39-1 
40) One or more drain pipes or fittings were substandard. Recommend that a qualified plumber evaluate and repair as necessary and per standard building practices.

Flexible drain pipe tent to catch more sediments in the ridges than brass or pvc pipes, recommend licensed plumber to evaluate and repair.
Photo
Photo 40-1 
41)  
Photo
Photo 41-1 
42)  
Photo
Photo 42-1 
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Not determined (inaccessible, obscured, or water, power or gas service off)
Type: Tank
Energy source: Natural gas
Estimated age: 7 years old
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Condition of burners: Not determined (inaccessible, obscured, or gas service off)
Condition of venting system: Appeared serviceable
43) The temperature-pressure relief valve drain line was too short. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. Recommend that a qualified plumber repair per standard building practices. For example, by extending the drain line to within 6 inches of the floor, or routing it to drain outside. For more information, visit:
https://www.reporthost.com/?TPRVALVE

Photo
Photo 43-1 
44) The water heater's gas supply was off, local gas shut-off was off and/or pilot light was off. The water heater and hot water supply system (e.g. faucets, controls) were not fully evaluated because of this. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the water heater is operable. Note that per the standards of practice for various professional home inspection organizations, the inspector does not operate shut-off valves, pilot lights or over-current protection devices, or any controls other than "normal controls."
Photo
Photo 44-1 
Photo
Photo 44-2 
Photo
Photo 44-3 
45)  
Photo
Photo 45-1 
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Oil
Estimated age of forced air furnace: 3 years old
Location of forced air furnace: Basement
Forced air system capacity in BTUs or kilowatts: 72000 btu/h
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): Inside air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Not determined (inaccessible, obscured, or gas or oil service off)
Type of combustion air supply: Intake duct
Condition of venting system: Appeared serviceable
46) The gas or oil-fired forced air furnace appeared to have been serviced within the last year based on information provided to the inspector or labeling on the equipment. If this is true, then routine servicing is not needed at this point. However a qualified HVAC contractor should inspect, clean, and service this system, and make repairs if necessary annually in the future. For more information visit:
https://www.reporthost.com/?ANFURINSP
47) The last service date of the forced air heating/cooling system appeared to be within the last year based on information provided to the inspector or labeling on the equipment. If this is true, then routine servicing is not needed at this point. However a qualified HVAC contractor should inspect, clean, and service this system, and make repairs if necessary annually in the future.
48)  
Photo
Photo 48-1 
Photo
Photo 48-2 
Photo
Photo 48-3 
49)  The forced air heating duct registers seems to be dirty, recommend to evaluate further and clean.
Photo
Photo 49-1 
Photo
Photo 49-2 
Photo
Photo 49-3 
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: Direct vent
50) The brick chimney was moderately deteriorated. For example, loose or missing mortar, cracked, broken, loose or spalled bricks. Loose bricks can pose a safety hazard, and deteriorated masonry can allow water to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary.
Photo
Photo 50-1 
51) Mortar at the brick chimney was deteriorated (e.g. loose, missing, cracked). As a result, water is likely to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary. For example, by repointing the mortar.
Photo
Photo 51-1 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of dishwasher: Near, at or beyond service life
Condition of ranges, cooktops and/or ovens: Appeared serviceable, Not determined, Range was not turned on because gas was off.
Range, cooktop, oven type: Natural gas
Type of ventilation: Wall or ceiling mounted fan, Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
52) The dishwasher was inoperable. Recommend that a qualified specialist evaluate and repair or replace as necessary.
Photo
Photo 52-1 
53) The exhaust fan over the range recirculated the exhaust air back into the kitchen. This may be due to no duct being installed, baffles not being installed, or problems with duct work. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. Recommend that a qualified contractor evaluate and repair as necessary so exhaust air is ducted outdoors.
Photo
Photo 53-1 
54) The kitchen sink drain pipe used an S-trap rather than a P-trap, or no P-trap was visible. Siphons and sudden flows of water in S-Traps can drain all the water out of the trap, leaving it dry. Sewer gases can then enter living areas. Recommend that a qualified plumber repair per standard building practices.
Photo
Photo 54-1 
55) Water was leaking at the sink faucet base or handles. Recommend that a qualified plumber repair as necessary.
Photo
Photo 55-1 
56) It is believe that the gas was off during inspection, therefore the gas fire range was not fully inspected.
Photo
Photo 56-1 
Photo
Photo 56-2 
57)  The original wall vent above the window cannot be operable during the inspection, recommend a licensed professional to repair or remove.
Photo
Photo 57-1 
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Half bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Not determined
58) The toilet at location(s) #B didn't flush or had a weak flush. Recommend that a qualified plumber evaluate and repair or replace the toilet as necessary.
Photo
Photo 58-1 
Photo
Photo 58-2 
59) One or more bathtub faucet handles at location(s) #A were loose. Recommend that a qualified person repair or replace handles as necessary.
Photo
Photo 59-1 
Photo
Photo 59-2 
60) The clothes dryer exhaust duct was disconnected in one or more places. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Moisture can accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person make permanent repairs as necessary. For more information, visit:
https://www.reporthost.com/?DRYER
Photo
Photo 60-1 
Photo
Photo 60-2 
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of windows and skylights: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl, Multi-pane, Double-hung
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Wood or wood products, Laminate
Condition of stairs, handrails and guardrails: Appeared serviceable
61) One or more doors on the second floor are hard to latch or lock, recommend licensed professional to repair.
Photo
Photo 61-1 
Photo
Photo 61-2 
Photo
Photo 61-3 
Photo
Photo 61-4 
Photo
Photo 61-5 
62) One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo
Photo 62-1 
Photo
Photo 62-2 
Photo
Photo 62-3 
63) Lock mechanisms on one or more windows were damaged and/or inoperable. This can pose a security risk. Recommend that a qualified person repair as necessary.
Photo
Photo 63-1 
Photo
Photo 63-2 
Photo
Photo 63-3 
Photo
Photo 63-4 
Photo
Photo 63-5 
Photo
Photo 63-6 
64) Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.

Certified Master Inspector- Safe at Home Book
Fogarty Inspection Services Group is providing you with a 226 page Safe at Home Book as part of your inspection report. This book is full of helpful
safety information for items and issues around the home. You may save the link for future viewing anytime you wish. Click the link below and enjoy,
as a gift from us.
Safe Home Book
The Safe Home Book contains chapters on the following:
CHILD SAFETY 12 safety devices to protect your children, crib safety, furniture and TV tip-over hazards, anti-tip brackets, window falls, safety glass,
child-proofing windows and stairs, garage doors and openers, trampoline safety, tree swings, tree houses.
LADDERS AND STAIRWAYS Ladder safety, attic pull-down ladders, stairways, deck safety.
SWIMMING POOL SAFETY Home pools, swimming pool barriers, pool alarms, pool drain hazards, pool water pathogens, saunas.
HOME SECURITY Burglar-resistant homes, bump keys, the 10 best places to hide valuables in your home, window bars, safe rooms (panic rooms).
FIRE SAFETY Dryer vent safety, pilot lights, hearths and hearth extensions, holiday safety, fire stops, clothes closet lighting, barbecue safety,
kerosene heaters, attached garage fire containment, non-conforming bedrooms, window wells, fire extinguishers, smoke alarms, fire sprinklers,
house numbers.
ELECTRICAL SAFETY Aluminum wiring, knob-and-tube wiring, ungrounded electrical receptacles, ground-fault circuit interrupters (GFCI), arc-fault
circuit interrupters (AFCI), electric fences, generators.
ENVIRONMENTAL CONCERNS Asbestos, asbestos cement siding, lead facts, formaldehyde, carbon monoxide, back drafting, fireplace fuel,
ventless fireplaces, mold, central humidifers, bathroom ventilation, sewer gases, pesticides, pet allergens, grey water, backflow prevention, carpeted
bathrooms, chinese drywall, home heating oil tanks, underground fuel storage tanks, compost pile hazards, Hantavirus, plants and indoor air quality.
MOTHER NATURE Earthquake preparedness, tornado inspections, wind mitigation, windbreaks, tree dangers, lightning, poison ivy, oak and sumac,
rodents, bed bugs, venomous pests, snow guards, defensible space, emergency preparedness.
ELDERLY SAFETY Aging in place, aging in place checklist, anti-scald valves.