Home Detectives

Website: http://homedetectivesinc.com
Email: thehomedetectives@comcast.net
Phone: (773) 418-4029
3450 W 108th St 
Chicago IL 60655-2635 
Illinois State License 450.010599
Inspector: David Abrham

 

Property Inspection Report

Client(s):  John Smith
Property address:  123 Main St.
Anytown, USA
Inspection date:  Monday, August 18, 2014

This report published on Monday, May 02, 2016 12:18:06 PM CDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings


General Information
Return to table of contents

Report number: 092313
Time started: 9:00
Time finished: 1:15
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Cool
Inspection fee:
Payment method:
Type of building: Single family
Buildings inspected: One house, One detached garage
Number of residential units inspected: 1
Age of main building: 94 years
Source for main building age: Municipal records or property listing
Front of building faces: East
Main entrance faces: South
Occupied: No

1) The water service was not turned on during the inspection. The inspector operates only "normal" controls such as faucets, and does not operate shut-off valves to the water meter or house. As a result, plumbing supply, drain waste and vent lines, traps, pumps, fixtures, and some appliances such as water heaters weren't fully evaluated. The water pressure was not determined. Recommend that a qualified person make a full evaluation of the plumbing system after the water supply is turned back on. Areas below the house should be evaluated after plumbing has been operated to check for leaks. Any problems that are found after this evaluation should be repaired by a qualified plumber.
Photo
Photo 1-1
 

2) Based on construction observed, additions, modifications to this property may have been made without the owner having attained permits or inspections from the municipality. Work may have been performed by someone other than a qualified contractor or person. Consult with the property owner about this, and if necessary research permits.

At worst case, if substantial work was performed without permits, this knowledge must be disclosed when the building is sold in the future. This can adversely affect future sales. Also, the local municipality could require costly alterations to bring the building into legal compliance or even require that the additions or modifications be removed.

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood

3) Guardrails at one or more locations with drop-offs higher than 30 inches had gaps that were too large. This poses a safety hazard for children (e.g. falling, getting stuck in railing). Guardrails should not have gaps or voids that allow passage of a sphere equal to or greater than 4 inches in diameter, or 6 inches in diameter at triangular spaces between stair edges and guardrails. Recommend that a qualified contractor repair or replace guardrails per standard building practices.
Photo
Photo 3-1
Photo
Photo 3-2

4) Decking is weathered. Recommend power washing and replacing as needed.
Photo
Photo 4-1
Photo
Photo 4-2
Photo
Photo 4-3
Photo
Photo 4-4
Photo
Photo 4-5
 

5) Missing risers can be a safety hazard for children. Recommend installing risers.
Photo
Photo 5-1
 

6) Soil was in contact with or too close to wooden deck or porch substructure components. This is a conducive condition for wood-destroying organisms. Clearances to soil should be as follows:
  • 12 inches below beams
  • 18 inches below joists
  • 6 inches below support post bases and other wood components
Pressure treated wood is typically rated for 25 year contact with soil, but the cut ends hidden below grade may not have been treated and can rot quickly. Support posts should be elevated above grade on concrete piers or footings, and be separated from the concrete by metal brackets or an impermeable membrane such as shingle scraps. For other components, soil should be graded and/or removed to maintain these clearances if possible. Otherwise, replacing non-treated wood with treated wood, or installing borate-based products such as Impel rods may help to prevent infestation and damage. For more information, visit:
http://www.reporthost.com/?IMPEL
Photo
Photo 6-1
Photo
Photo 6-2

7) Fasteners for joist hangers at decks or porches were missing. All nail holes for such hardware should be filled with approved fasteners such as "Teco" nails. Recommend that a qualified person install approved fasteners where missing.
Photo
Photo 7-1
 

8) Some nails securing decking boards were loose and were not flush with the surfaces of boards. Boards are more likely to loosen and warp. This may pose a safety hazard to those with bare feet. Recommend that a qualified person repair as necessary. For example, by replacing nails or installing screws. Note that existing nails that are simply pounded back in will be likely to loosen again.
Photo
Photo 8-1
Photo
Photo 8-2
Photo
Photo 8-3
 

9) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 9-1
Photo
Photo 9-2
Photo
Photo 9-3
 

10) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 10-1
Photo
Photo 10-2
Photo
Photo 10-3
Photo
Photo 10-4
Photo
Photo 10-5
 

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Metal
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space, Unfinished basement
Foundation/stem wall material: Concrete block
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)

11) Some sections of siding and/or trim were missing, substandard. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 11-1
Photo
Photo 11-2
Photo
Photo 11-3
Photo
Photo 11-4
Photo
Photo 11-5
Photo
Photo 11-6

12) One or more exhaust duct end caps were damaged. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
Photo
Photo 12-1
 

13) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 13-1
Photo
Photo 13-2
Photo
Photo 13-3
Photo
Photo 13-4
Photo
Photo 13-5
 

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Viewed from hatch(es)
Condition of floor substructure above crawl space: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Condition of vapor barrier: Not applicable, none installed
Ventilation type: Unconditioned space

14) One or more indoor crawl space access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency.

15) No insulation was installed under the floor above the crawl space. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above crawl space: Appeared serviceable
Pier or support post material: Steel
Beam material: Steel
Floor structure: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed

16) Handrails at one or more flights of stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.
Photo
Photo 16-1
 

17) Guardrails at one or more locations with drop-offs higher than 30 inches had gaps that were too large. This poses a safety hazard for children (e.g. falling, getting stuck in railing). Guardrails should not have gaps or voids that allow passage of a sphere equal to or greater than 4 inches in diameter, or 6 inches in diameter at triangular spaces between stair edges and guardrails. Recommend that a qualified contractor repair or replace guardrails per standard building practices.
Photo
Photo 17-1
 

18) Guardrails at one or more locations with drop-offs higher than 30 inches were too low. This poses a fall hazard. Guardrails should be at least 36 inches in height. Recommend that a qualified contractor replace or repair guardrails per standard building practices.

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Appeared serviceable

19) Water damage and/or evidence of past leaks was found at one or more skylights. Consult with the property owner to determine if leaks have occurred, or if repairs have been made. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 19-1
Photo
Photo 19-2

20) Lead flashing at one or more plumbing vent pipes was improperly installed. For example, shorter than the vent pipe or not bent over the edge of the vent pipe. Properly installed, the flashing should extend up and over the top edge of the pipe, and be bent down into the pipe. Otherwise, rain water can flow between the pipe and the flashing, resulting in leaks. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair per standard building practices.
Photo
Photo 20-1
 

21) Substandard installation of shingles near ridge.
Photo
Photo 21-1
 

22) Area of roof near chimney appears to have some rafters crowned/bowed creating a bump in the roof surface.
Photo
Photo 22-1
 

23) Gutter flashing was missing in two areas.
Photo
Photo 23-1
Photo
Photo 23-2

24) One or more roofing nails weren't fully seated and shingles were lifting or nail heads were protruding through shingle surfaces. The nails may have loosened, or were not pounded in fully when installed. Shingles are likely to be wind damaged, and leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 24-1
Photo
Photo 24-2

25) One or more roof flashings were substandard. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 25-1
Photo
Photo 25-2
Photo
Photo 25-3
 

26) Branches are in contact with the roof. This condition can cause premature deterioration of roofing material. Recommend trimming branches as needed.
Photo
Photo 26-1
Photo
Photo 26-2

27) Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 27-1
 

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Box vents (roof jacks)

28) Home has been under renovation of a small addition and creation of a cathedral ceiling but is not completed. Recommend consulting with a qualified contractor to complete renovation to code requirements related to maintaining the structural integrity of the roof structure.
Circle in picture indicates a leak at the skylight.
Photo
Photo 28-1
Photo
Photo 28-2
Photo
Photo 28-3
Photo
Photo 28-4
Photo
Photo 28-5
Photo
Photo 28-6

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Condition of garage vehicle door(s): Not determined (inaccessible or obscured)
Number of vehicle doors: 2
Condition of automatic opener(s): None
Condition of garage floor: Required repair, replacement and/or evaluation (see comments below)

29) Shingles are damaged at the edge of the dormer. Recommend repairs to prevent water intrusion.
Photo
Photo 29-1
 

30) Evtrance door to second floor is missing the lockset and deadbolt.
Photo
Photo 30-1
 

31) Handrails are missing.
Photo
Photo 31-1
 

32) Electrical outlets /boxes are missing cover plates, loose outlets or have light fixtures not attached.
Photo
Photo 32-1
Photo
Photo 32-2
Photo
Photo 32-3
 

33) Exterior finish is deteriorated in a number of areas.
Photo
Photo 33-1
Photo
Photo 33-2
Photo
Photo 33-3
 

34) Cracks in the mortar joint indicate some settlement.
Photo
Photo 34-1
 

35) Three electric heaters were present and serviceable however one is loose from the wall and missing a knob.
Photo
Photo 35-1
Photo
Photo 35-2
Photo
Photo 35-3
Photo
Photo 35-4

36) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Photo
Photo 36-1
 

37) Two car garage with a finished / heated second floor.
Photo
Photo 37-1
 

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Service voltage (volts): 120
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 200
System ground: Cold water supply pipes
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Basement
Location of sub-panel #B: Basement
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Copper
Smoke alarms installed: No, recommend install
Carbon monoxide alarms installed: No, recommend install

38) Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo
Photo 38-1
 

39) One or more electric receptacles (outlets) had reverse-polarity wiring, where the hot and neutral wires were reversed. This is a shock hazard. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?RPR
Photo
Photo 39-1
Photo
Photo 39-2
Photo
Photo 39-3
 

40) Smoke alarms were missing . Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM

41) Flexible conduit (bx or greenfield) was observed in a number of areas exceeding the maximum length of 6 feet. Recommend replacement with rigid conduit. The circles indicate other electrical boxes missing covers.
Photo
Photo 41-1
Photo
Photo 41-2
Photo
Photo 41-3
Photo
Photo 41-4
Photo
Photo 41-5
Photo
Photo 41-6
Photo
Photo 41-7
Photo
Photo 41-8
Photo
Photo 41-9
Photo
Photo 41-10
Photo
Photo 41-11
 

42) One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 42-1
Photo
Photo 42-2
Photo
Photo 42-3
Photo
Photo 42-4
Photo
Photo 42-5
Photo
Photo 42-6
Photo
Photo 42-7
Photo
Photo 42-8
Photo
Photo 42-9
Photo
Photo 42-10
Photo
Photo 42-11
Photo
Photo 42-12
Photo
Photo 42-13
Photo
Photo 42-14

43) Carbon monoxide alarms were missing from one or more sleeping areas. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit:
http://www.reporthost.com/?COALRM

44) Kitchen lights are not operable.
Kitchen under the cabinet lights are not operable.
Bedroom near kitchen has one outlet with no power and the ceiling light is inoperable.
Bathroom near living room has no power.
Wall sconces in living room are damaged.

45) The drywall at two can lights is damaged. Recommend repairs to prevent the risk of electrical shock.
Photo
Photo 45-1
Photo
Photo 45-2

46) Water supply pipe obstructs sub panel access door from opening 90 degrees.
Photo
Photo 46-1
 

47) The legend for circuit breakers or fuses in panel(s) #A, B was missing, incomplete, illegible or confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.

48) The service drop wires were in contact with trees or vegetation. This can result in damage to wiring insulation or broken wires during high winds. Recommend pruning trees or vegetation as necessary. The utility company may prune trees at no charge.

49) One circuit breaker in panel(s) #A were in the tripped position. Consult with the property owner to determine why breakers were tripped or off, and that a qualified electrician evaluate and repair if necessary. Note that the inspector does not operate circuit breakers.

Inspector attached red tape to tripped breaker.
Photo
Photo 49-1
 

50) Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 50-1
Photo
Photo 50-2
Photo
Photo 50-3
Photo
Photo 50-4
Photo
Photo 50-5
Photo
Photo 50-6
Photo
Photo 50-7
Photo
Photo 50-8
Photo
Photo 50-9
 

51) Electrical pull box located at rear crawl space appears to supply electrical power to the garage /pool equipment.
Photo
Photo 51-1
 

52) Ground for electrical service.
Photo
Photo 52-1
 

53) Electrical supply is present for pool filtration system. Client may wish to remove this if there are no future plans for a pool.
Photo
Photo 53-1
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Required repair, replacement and/or evaluation (see comments below)
Water service: Public
Location of main water shut-off: Basement
Condition of supply lines: Required repair, replacement and/or evaluation (see comments below)Recommend evaluation when water service is restored.
Supply pipe material: Copper, Galvanized steel
Condition of drain pipes: Required repair, replacement and/or evaluation (see comments below)Recommend evaluation when water service is restored.
Drain pipe material: Plastic, Galvanized steel
Condition of waste lines: Required repair, replacement and/or evaluation (see comments below)Recommend evaluation when water service is restored.
Waste pipe material: Plastic, Galvanized steel, Cast iron
Vent pipe condition: Required repair, replacement and/or evaluation (see comments below)Recommend evaluation when water service is restored.
Vent pipe material: Cast iron
Sump pump installed: No
Sewage ejector pump installed: Yes
Condition of sewage ejector pump: Required repairs, replacement and/or evaluation (see comments below)Recommend evaluation when water service is restored.
Condition of fuel system: Appeared serviceable

54) Galvanized pipe was used for the gas line near the gas meter. Recommend replacing with the proper (black pipe) material.
Photo
Photo 54-1
 

55) The copper water service pipe was embedded in concrete or masonry where it was routed through the foundation, and no protection from damage due to thermal expansion was visible. Copper pipes embedded in concrete or masonry should be wrapped with an approved tape or installed through a sleeve for abrasion protection. Recommend that a qualified contractor repair per standard building practices.

56) The main water shut-off valve was leaking. Recommend that a qualified plumber repair or replace the valve as necessary. Possible mold growth on wall.
Photo
Photo 56-1
Photo
Photo 56-2
Photo
Photo 56-3
Photo
Photo 56-4

57) An open/ uncapped pipe was located in the basement.
Photo
Photo 57-1
 

58) Some or all of the water supply and drain or vent pipes were made of galvanized steel. Based on the age of this structure and the 40-60 year useful life of this piping, it will likely need replacing in the future. Leaks can develop, flooding and/or water damage may occur, flow can be restricted due to scale accumulating inside the piping, and water may be rusty. Note that it is beyond the scope of this inspection to determine what percentage of the piping is older, galvanized steel, as much of it is concealed in wall, floor and/or ceiling cavities. Recommend the following:
  • That a qualified plumber evaluate to better understand or estimate the remaining life
  • Consulting with a qualified plumber about replacement options and costs
  • Budget for replacement in the future
  • Monitor these pipes for leaks and decreased flow in the future
  • Consider replacing old, galvanized steel piping proactively
For more information, visit:
http://www.reporthost.com/?GALVPIPE

59) Copper water pipe was mounted on the wall in the rear bathroom. Recommend consulting the building department for code compliance.
Photo
Photo 59-1
 

60) A sewage ejector pump was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems are typically sealed and involve moving parts. They are subject to clogging and/or damage from disposal of items such as disposable diapers and sanitary napkins. Recommend that this pump and related equipment (piping, valves, etc.) be evaluated by a qualified plumber and repaired if necessary. This should be done per the manufacturer's recommendations in the future, or annually if unable to verify the manufacturer's recommendations. Typically, these pumps have a lifespan of 7-10 years. For more information, visit:
http://www.reporthost.com/?SEWEJPMP
Photo
Photo 60-1
Photo
Photo 60-2

61) One or more hose bibs (outside faucets) were not evaluated due to their being winterized with covers. They are excluded from this inspection.

62) Location of two sewer clean outs in basement.
Photo
Photo 62-1
Photo
Photo 62-2

63) Location of main water shut off located in basement.
Photo
Photo 63-1
 

64) Two main gas shut offs were located, Building exterior and gas meter located in basement.
Photo
Photo 64-1
Photo
Photo 64-2

65) Drain system is present for a pool. Client may wish to remove this if there are no future plans for a pool.
Photo
Photo 65-1
 

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Near, at or beyond service lifeRecommend evaluation when water service is restored.
Type: Tank
Energy source: Natural gas
Location of water heater: Basement
Condition of burners: Not determined (inaccessible, obscured, or gas service off)
Condition of venting system: Appeared serviceable

66) The drain line is missing for the TPR valve. A drain line should be installed to within 6 inches of the floor to prevent scalding in the event the TPR valves releases pressure.
Photo
Photo 66-1
 

67) Appears to be a water leak at the cold water pipe.
Photo
Photo 67-1
 

68) Corrosion is evident at the base of the water heater.
Photo
Photo 68-1
 

69) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Water heater manufactured in 1996, 17 years old.
Photo
Photo 69-1
 

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Radiant
General heating distribution type(s): Pipes and radiators
Last service date of primary heat source: Unknown
Condition of hydronic or steam heat system: Recommend evaluation when water service is restored.
Type of hydronic or steam heat: Radiators
Hydronic or steam heat fuel type: Natural gas
Condition of burners: Required repair, replacement and/or evaluation (see comments below)Recommend evaluation when water service is restored.
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: None
Condition of controls: Required repair, replacement and/or evaluation (see comments below)

70) The boiler burner flames "rolled out" of the combustion chamber. This is a fire hazard due to the possibility of excessive heat damaging heating components, controls and wiring. Recommend that a qualified heating contractor evaluate and repair as necessary.

Evidence of flame roll out. Inspector was unable to test boiler due to no water service.
Photo
Photo 70-1
 

71) The water pipes for the heating system appear to be wrapped with asbestos. Recommend evaluation by a qualified asbestos removal contractor about determination of material type, condition and environmental safety.
Photo
Photo 71-1
Photo
Photo 71-2
Photo
Photo 71-3
Photo
Photo 71-4
Photo
Photo 71-5
Photo
Photo 71-6
Photo
Photo 71-7
Photo
Photo 71-8
Photo
Photo 71-9
Photo
Photo 71-10
Photo
Photo 71-11
Photo
Photo 71-12
Photo
Photo 71-13
Photo
Photo 71-14
Photo
Photo 71-15
 

72) Corrosion in the burner area. Recommend evaluation by an HVAC contractor or replacement of boiler due to age.
Photo
Photo 72-1
 

73) The estimated useful life for most steel boilers is 20 years. This boiler appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.

Boiler is 31 to 39 years old according to the manufacturer.
Photo
Photo 73-1
 

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning fireplace type: Masonry with metal liner
Condition of chimneys and flues: Required repair, replacement and/or evaluation (see comments below)
Wood-burning chimney type: Masonry, with metal liner

74) No spark screen or rain cap was installed at one or more chimney flue terminations. Spark screens reduce the chance of embers exiting the flue and causing fires. They also prevent wildlife (e.g. birds, rodents, raccoons) from entering flues. Rain caps prevent water from entering flues, mixing with combustion deposits and creating caustic chemicals which can corrode flues. They also prevent damage to masonry from freeze-thaw cycles and prevent metal components (e.g. dampers, metal firebox liners) from rusting. Recommend that a qualified person install rain caps with spark screens per standard building practices where missing. Stone cap is also missing
Photo
Photo 74-1
Photo
Photo 74-2

75) One or more metal flue caps for B-vent or L-vent flues were substandard. Such metal flues should terminate with a bird-proof and weatherproof cap. Recommend that a qualified person repair per standard building practices
Photo
Photo 75-1
Photo
Photo 75-2

76) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA

77) The brick chimney was moderately deteriorated. For example, loose or missing mortar, cracked, broken, loose or spalled bricks. Loose bricks can pose a safety hazard, and deteriorated masonry can allow water to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary.
Photo
Photo 77-1
Photo
Photo 77-2
Photo
Photo 77-3
Photo
Photo 77-4
Photo
Photo 77-5
 

78) A fan was installed in the heat vent for the fireplace. The cover is loose.
Photo
Photo 78-1
 

79) Soot deposits were found above the fireplace. This often indicates an inadequate draw, and can be caused by a variety of problems including an incorrect chimney configuration or a chimney blocked by creosote or debris. Recommend that a qualified chimney service contractor evaluate and repair or perform maintenance as necessary.
Photo
Photo 79-1
Photo
Photo 79-2
Photo
Photo 79-3
Photo
Photo 79-4

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)Recommend evaluation when water service is restored.
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: N/A (none installed)
Condition of range, cooktop or oven: Required repair, replacement and/or evaluation (see comments below)
Range, cooktop or oven type: Natural gas
Condition of refrigerator: N/A (none installed)
Condition of built-in microwave oven: N/A (none installed)

80) The range could tip forward. An anti-tip bracket may not be installed. This is a potential safety hazard since the range can tip forward when weight is applied to the open door, such as when a small child climbs on it or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free-standing ranges since 1985. Recommend installing an anti-tip bracket to eliminate this safety hazard. For more information, visit:
http://www.reporthost.com/?ATB

81) 2 cooktop burner(s) were inoperable. Recommend that a qualified person repair as necessary.
Photo
Photo 81-1
Photo
Photo 81-2

82) The light in the exhaust hood was inoperable. Recommend replacing light bulb(s) or that repairs be made by a qualified person if necessary.

83) A kitchen addition was started but not completed. Addition exterior wall appears to rest on an existing concrete slab. Inspector was unable to determine the presence of a footing. Recommend evaluation by a qualified contractor or the local building department.
Photo
Photo 83-1
Photo
Photo 83-2
Photo
Photo 83-3
 

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Half bath, first floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Recommend evaluation when water service is restored.
Condition of toilets: Recommend evaluation when water service is restored.
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Appeared serviceable
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: No

84) The clothes dryer was equipped with a vinyl or mylar, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. They can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow and cause overheating. Recommend that such ducts be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. For more information, visit:
http://www.reporthost.com/?DRYER
Photo
Photo 84-1
Photo
Photo 84-2

85) The toilet at location(s) #B was loose where it attached to the floor. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 85-1
 

86) Vinyl flooring in bathroom at location(s) #B was deteriorated. Water can damage the the sub-floor as a result. Recommend that a qualified contractor replace or repair flooring as necessary.
Photo
Photo 86-1
 

87) The bathtub drain stopper mechanism at location(s) #A was missing. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 87-1
 

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Metal
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall, Plaster
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
Flooring type or covering: Vinyl, linoleum or marmoleum, Wood or wood products, Tile

88) A door swung outward over one or more sets of stairs, and either no landing was installed, or the landing didn't extend at least 20 inches beyond the outermost swing area of the door. This a safety hazard since someone standing on the stairs can fall or be pushed backwards if the door is opened. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 88-1
Photo
Photo 88-2

89) A closet was constructed near the front entrance. The wall is in contact with the radiator. It is not recommended for a radiator to be in contact with possible flammable materials.
Photo
Photo 89-1
Photo
Photo 89-2

90) Stains were found in one or more ceiling areas. The inspector was unable to determine if an active leak exists (e.g. recent dry weather, inaccessible height). Recommend asking the property owner about this, monitoring the stains in the future, and/or having a qualified contractor evaluate and repair if necessary.
Photo
Photo 90-1
Photo
Photo 90-2

91) One or more skylights appeared to have an active leak. A qualified contractor should evaluate and repair as necessary.
Photo
Photo 91-1
Photo
Photo 91-2
Photo
Photo 91-3
Photo
Photo 91-4
Photo
Photo 91-5
 

92) Rear entrance opens to a washroom. Door does not clear sink. Recommend inquiring with building department for code compliance. Door may have to be removed.
Photo
Photo 92-1
Photo
Photo 92-2
Photo
Photo 92-3
 

93) Some exterior door hardware, including locksets were inoperable. Recommend that a qualified person repair or replace as necessary.

Lockset inoperable at rear door.

94) Handle is missing on one window
Photo
Photo 94-1
 

95) One or more walls were damaged. Recommend that a qualified person repair as necessary.
Photo
Photo 95-1
 

96) Vinyl, linoleum or marmoleum flooring in one or more areas was deteriorated. If in a wet area, water can damage the sub-floor as a result. Recommend that a qualified contractor replace or repair flooring as necessary.
Photo
Photo 96-1
Photo
Photo 96-2
Photo
Photo 96-3
Photo
Photo 96-4

97) The rear and side entrance doors had a step that exceeded 8 inches. This condition can pose a trip hazard.
Photo
Photo 97-1
Photo
Photo 97-2

98) Storm door is missing at side entrance.
Photo
Photo 98-1
 

99) The basement windows are deteriorated. Recommend replacement.
Photo
Photo 99-1
Photo
Photo 99-2
Photo
Photo 99-3
Photo
Photo 99-4
Photo
Photo 99-5
 

100) Baseboard is missing in a number of areas.
Photo
Photo 100-1
Photo
Photo 100-2
Photo
Photo 100-3
 

101) Trim cap for bathtub tile in bathroom A does not match the tile. (short)
Photo
Photo 101-1
Photo
Photo 101-2

102) Lock mechanisms on one or more windows were missing. This can pose a security risk. Recommend that a qualified person repair as necessary.
Photo
Photo 102-1
 

103) Wood flooring in one or more areas was significantly worn, deteriorated or damaged. Recommend that a qualified contractor refinish wood flooring as necessary.
Photo
Photo 103-1
Photo
Photo 103-2
Photo
Photo 103-3
Photo
Photo 103-4
Photo
Photo 103-5
Photo
Photo 103-6
Photo
Photo 103-7
Photo
Photo 103-8

104) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.reporthost.com/?ECC

105) Rear side entrance had a ceiling that was too low. Standards vary for minimum ceiling heights, but generally they should be at least 7 feet high except in areas with sloped ceilings where at least half of the area should have 7 foot or higher ceilings. This may pose a safety hazard to tall people.

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: No

Your default report footer here...