This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a risk of injury or death
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Minor Defect
Correction likely involves only a minor expense
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Roof covering: Asphalt/Fiberglass composition 30 year architectural shingles
Estimated age of roof: 1995 See Sellers Disclosure
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
4) The roof shingles are a 30 year architectural composition shingle. Evidence of hail and high wind damage such as, significant pock marks and granular loss was found on the shingles throughout the roof. A licensed roofing contractor further evaluate the roof shingles for the cost of repairs and/or replacement cost options. SPECIAL NOTE: There was a huge hail, rain and wind storm in the Alamogordo area in 2017 or 2018 that caused significant damage and roofs had to be replaced. Recommend consulting with the property owner about this roof condition. Property owner should consider contacting their Homeowners Insurance Company for further evaluation of hail and wind damage for a possible insurance claim..
Photo 4-1 Photo 4-2
Photo 4-3 Photo 4-4
Photo 4-5 Photo 4-6
Photo 4-7 Photo 4-8
Photo 4-9 Photo 4-10
Photo 4-11 Photo 4-12
Photo 4-13 Photo 4-14
Photo 4-15 Photo 4-16
5) Vegetation such as shrubs and/or vines are in contact with the metal roof for covered deck. The vegetation may prevent rain from flowing off the roof easily and cause damage to the roof. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
Photo 5-1 Photo 5-2
6) The solar panels prevent a full inspection of the roof shingles. As a result this area is excluded from the inspection.
Photo 6-1 Photo 6-2
7) We have included the following pictures to show the metal roofs appear to be in good condition.
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200
Service voltage (volts): 120/240
Location of main breaker panel: Laundry Room
Location of main disconnect: Breaker at bottom of main service panel
Service entrance conductor material: Copper
System ground: Ground rod in soil
Main disconnect rating (amps): 200
Branch circuit wiring type: Copper
8) Solar panels, transfer switches and any associated wiring are excluded from this inspection. Recommend that the client consult with the property owner or review documentation to familiarize themselves with the operation of this system.
Photo 8-1 Photo 8-2
9) Inspector removed breaker panel cover, no problems were noted today.
Primary A/C energy source: Electric, RUUD Mfg date 2021
Primary Air conditioning type: Split system
Distribution system: Sheet metal ducts
Manufacturer: Intertherm
Model: FEBB-020HA
Filter location: In return air duct in furnace
11) The air filter is missing for the heating and air conditioning system. As a result, unfiltered air will flow through the system, and the heating equipment life and the indoor air quality may be reduced. Correctly sized filter(s) should be installed on the furnace as necessary
Photo 11-1 Photo 11-2
12) The retainer clips are broken and/or missing the secures the bottom panel door of the furnace in place. The furnace panel is being held on by a wedge.
Photo 12-1 Wedge being used to keep furnace panel on. Photo 12-2
13) Heating and Air Conditioning system was tested and appears to be in working condition. Heat temperature, A/C temperature and air flow was verified to each room register. NOTE: We verified temperature and air flow at each register but do not include every picture of each register, only a few sample pictures to show system is in working condition.
Location of main water shut-off valve: At meter and in crawlspace
Location of main water meter: At street
Water service: Public
Service pipe material: What’s visible is PEX
Supply pipe material: Polybutylene with PEX repairs
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
14) Dryer exhaust vents should be checked and cleaned, if necessary, prior to using dryer or installing a different dryer. For safety reason this cleaning should be performed twice a year.
15) Testing the water softener filter system is not part of this inspection. However, we do check for leaks on connections and no issues were noted today.
Photo 15-1 Photo 15-2
16) Sprinkler system is not part of this inspection. Recommend consulting with the property owner to verify sprinkler system is in working condition and if possible familiarize client with systems operation.
Photo 16-1
17) Washer and Dryer are not part of the inspection. Recommend consulting with the property owner to verify they are in working condition, if they stay with the sale of the house.
Photo 17-1 Photo 17-2 Washer box and hose bibs appear to be in good condition.
Inspection method: Viewed from removing skirting panels in multiple areas.
Insulation material underneath floor above: Fiberglass roll or batt
Pier or support post material: Concrete Blocks
Beam material: Steel
Floor structure above: Solid wood joists
Vapor barrier present: Yes
18) The particle board subflooring in the crawlspace in the area under the washer and water heater closet has water damage, deterioration and is cracked. SPECIAL NOTE: See Interior Page for additional information and Sellers Disclosure about previous water leak. Also, the electrical receptacle in this area is loose and not securely attached risk. Recommend having a qualified contractor further evaluate the floor in this area for cost of repairs and make repairs where necessary.
Photo 18-1 Photo 18-2
19) We have included the following pictures to show the type of foundation construction blocking pier supports, floor insulation and underbelly barrier liner. Everything that was viewed appears to be in good condition, except for the defects as previously mentioned.
20) The dishwasher is excessively noisy. A qualified appliance technician should evaluate the dishwasher and repair as necessary, or replace the dishwasher if necessary.
Photo 20-1
21) Right rear stove top burner is inoperable. A qualified appliance technician should evaluate and repair as necessary.
Photo 21-1
22) All appliances were tested and appear to be in working condition, except for the defects as previously mentioned.
Photo 22-1 Photo 22-2
Photo 22-3 Photo 22-4
Photo 22-5 Refrigerator temperature Photo 22-6 Freezer temperature
Photo 22-7 Photo 22-8 Sample of dishwasher drying temperature
23) Water supply shut off valves below both bathroom sinks and the shut off valve for the main bathroom toilet are corroded and/or seized up (can't turn handles). Standard plumbing practices require all plumbing fixtures to have individual water shut off valves that are functional. For example, if any plumbing fixture should leak, water can be turned off at fixture without turning whole house off until repairs are made. A licensed plumber should make repairs as necessary so the shut off valves are operational or replace the shut off valves if necessary.
Photo 23-1 Photo 23-2
Photo 23-3 Photo 23-4
Photo 23-5 Photo 23-6
24) The main bathroom sink drain leaks. The sink stoppers are seized and inoperable on both bathroom sinks. Repairs should be made by a licensed plumber as necessary.
Photo 24-1 Photo 24-2 Moisture meter reading 59% to show leak.
Photo 24-3 Photo 24-4
Photo 24-5 Photo 24-6
25) The master bathroom sink drains slowly. Drain should be cleared as necessary, and by a licensed plumber if necessary.
Photo 25-1 Photo 25-2
26) Caulking is missing and/or showing signs of deterioration where the bathtub meets the surround enclosure. Caulking should be reapplied where necessary to prevent water intrusion and damage to the wall structure.
Photo 26-1 Photo 26-2
Photo 26-3
27) Water stains and/or minor water damage was found in the shelving or cabinet components below the master bathroom sink. The client(s) should evaluate and consider having repairs made.
28) The living room floor electric receptacle and/or the box it is installed in is loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety concern due to the risk of shock and fire. A licensed electrician should make repairs as necessary.
Photo 28-1
29) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future.
Photo 29-1
30) The flooring in the laundry room area in front of the washer and furnace closet is soft and weak when walked on. SPECIAL NOTE: See Crawlspace Page for additional information.
Photo 30-1 Photo 30-2
Photo 30-3 Photo 30-4
Photo 30-5 Photo 30-6
31) Minor cracks were found in ceilings and walls in one or more areas. They are not a structural concern, but the client(s) may want to repair these for aesthetic reasons.
Photo 31-1 Photo 31-2
Photo 31-3 Photo 31-4
Photo 31-5 Photo 31-6
Photo 31-7 Photo 31-8
Photo 31-9 Photo 31-10
32) The living room ceiling fan wobbles during operation. A licensed electrician should make repairs as necessary.
Photo 32-1
33) The southwest bedroom closet and the master bedroom doors will not latch when closed. Repairs should be made as necessary. For example, aligning latch plates with door handle latch bolts.
Photo 33-1 Photo 33-2
Photo 33-3 Photo 33-4
Photo 33-5 Photo 33-6
34) Minor stains were found in the southwest bedroom closet, the southeast bedroom closet, and laundry room ceiling areas. However, no elevated levels of moisture were found. The stains may be due to past roof leaks. Recommend asking the property owner about this, and monitoring the stained areas in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, a qualified contractor should evaluate and repair as necessary.
Photo 34-1 Photo 34-2
Photo 34-3 Photo 34-4
35) Vinyl flooring is damaged and/or showing signs of deterioration in the laundry room, dining room, and kitchen areas.
Photo 35-1 Photo 35-2
Photo 35-3 Photo 35-4
36) Carpeting in one or more rooms is damaged, deteriorated, loose, and/or stained
Photo 36-1 Photo 36-2
Photo 36-3 Photo 36-4
Photo 36-5 Photo 36-6
37) All accessible electrical receptacles, switches, and light fixtures were tested.
38) Phone jacks and TV hook-ups and cables are not part of this inspection.
39) Mold observation and testing is not part of this inspection.
In summary we consider this house to be in good condition. Thank you for selecting our firm for your inspection needs. If you have any questions, comments or concerns regarding the inspection report or the property, please feel free to call us.