Home Inspection Report

Client(s):  Your name
Property address:  1234 your street
your state
Inspection date:  Thursday, April 23, 2020

This report published on Thursday, April 23, 2020 2:56:57 PM EDT

This report is the exclusive property of SK2 Home Inspections and the client(s) listed in this report title. Use of this report by any unauthorized persons is prohibited

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
Minor DefectCorrection likely involves only a minor expense
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information
DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Conducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary

General InformationTable of contents
Time started: 2 pm
Time finished: 5:30 pm
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Hot
Ground condition: Dry
Recent weather: Dry (no rain)
Overnight temperature: Cool
Buildings inspected: One house
Age of main building: 42 yrs
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: No, Furniture or stored items were present
1) Safety, Comment - Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
https://www.reporthost.com/?EPA
https://www.reporthost.com/?CPSC
https://www.reporthost.com/?CDC
2) Repair/Replace - Evidence of rodent infestation was found in the form of feces and/or traps in the attic and/or interior rooms. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
https://www.reporthost.com/?SEALUP
https://www.reporthost.com/?TRAPUP
https://www.reporthost.com/?CLEANUP
Photo
Photo 2-1 Under the kitchen sink.
Photo
Photo 2-2 The main attic.
3) Evaluate - Comment
Photo
Photo 3-1 There are termite bait stations located around the exterior of the dwelling. Recommend buyer ask seller about this.
Photo
Photo 3-2 
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wood
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
4) Repair/Replace, Damage - One or more landscaping timbers were rotten or damaged by wood-destroying insects. Recommend that a qualified person replace as necessary or removed them if not needed.
Photo
Photo 4-1 
Photo
Photo 4-2 
5) Repair/Maintain - One or more fences were damaged or deteriorated and need repair.
Photo
Photo 5-1 
Photo
Photo 5-2 The fence post is rotted, the fence can fall and damage the house. Recommend a qualified contractor remove, replace.
6) Maintain - Vegetation was overgrown around equipment for one or more utilities such as gas or electric meters. Vegetation should be pruned or removed as necessary to allow unobstructed access.
Photo
Photo 6-1 
7) Monitor - The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo
Photo 7-1 
Photo
Photo 7-2 
8) Monitor - Pavement sloped down towards building perimeters in one or more areas. This may result in water accumulating around building foundations or underneath buildings. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing old pavement and installing new.
Photo
Photo 8-1 
Exterior and FoundationTable of contents
Wall inspection method: Viewed from ground, from a ladder
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Vinyl
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade
Foundation/stem wall material: Concrete block
9) Repair/Replace, Conducive conditions - Flashing at one or more locations was damaged, substandard and/or loose. Leaks can occur as a result. Recommend that a qualified person repair, replace or install flashing as necessary, and per standard building practices.
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 The garage roof.
10) Repair/Replace, Conducive conditions - One or more sections of horizontal trim boards had no "Z" flashing installed above them where they met siding. "Z" flashing should be installed above these boards to reduce the chance of leaks and/or water entrapment between the trim and siding. Without this flashing, caulk and paint must be diligently maintained, or water can cause rot and possible structural damage. Recommend that a qualified contractor install flashing above horizontal trim boards where missing and per standard building practices. Note that when trim or siding is removed to install flashing, damaged wood may be found and additional repairs may be needed.
Photo
Photo 10-1 
11) Repair/Replace - Many sections of siding and/or trim were loose, damaged, substandard and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 11-1 The siding is loose.
Photo
Photo 11-2 The decorative corner trims are deteriorated, rotted. Recommend a qualified contractor remove all rotted wood and replace.
Photo
Photo 11-3 The garage.
Photo
Photo 11-4 The garage.
Photo
Photo 11-5 The garage.
Photo
Photo 11-6 The siding is loose.
Photo
Photo 11-7 The garage.
Photo
Photo 11-8 
Photo
Photo 11-9 
Photo
Photo 11-10 
Photo
Photo 11-11 The siding is loose.
Photo
Photo 11-12 The garage.
Photo
Photo 11-13 The siding is loose.
Photo
Photo 11-14 The siding is loose in many areas around the bottom of the wall.
Photo
Photo 11-15 
Photo
Photo 11-16 
Photo
Photo 11-17 
Photo
Photo 11-18 
Photo
Photo 11-19 
Photo
Photo 11-20 The garage roof.
Photo
Photo 11-21 There is a gap between the sections of siding.
12) Repair/Maintain, Monitor, Conducive conditions - One or more windows or doors were installed with no "drip cap" or "Z" flashings installed above them. Better building practices call for such flashings, which greatly reduce the chance of leaks above windows and doors. Without this flashing, caulk and paint must be maintained or water can enter the wall structure and cause rot and possible structural damage. Depending on the exposure (e.g. roof overhang, height of exterior wall, direction of prevailing rain) this may or may not be an issue. The client should monitor these areas in the future and maintain caulk and paint as necessary. Consult with a qualified contractor about installing flashings where needed, and per standard building practices. Note that when trim or siding is removed to install flashing, damaged wood may be found and additional repairs may be needed.
Photo
Photo 12-1 
13) Repair/Maintain, Conducive conditions -
Photo
Photo 13-1 There is exposed wood framing at the left of the garage door. Recommend a qualified contractor repair to prevent water contact.
14) Repair/Maintain, Conducive conditions - Fence(s) were attached to or in contact with the building exterior. Such attachments can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary so there is at least a 2-inch gap between fences and building exteriors.
Photo
Photo 14-1 
15) Repair/Maintain - One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo
Photo 15-1 
16) Maintain, Conducive conditions - Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Photo
Photo 16-4 
Photo
Photo 16-5 
17) Maintain, Conducive conditions - Trees were in contact with or were close to the building at one or more locations. Damage to the building may occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 17-1 
18) Maintain, Conducive conditions - Caulk was missing and/or substandard in some areas. For example, around windows, around doors, at siding butt joints, at siding-trim junctions and/or at wall penetrations. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
https://www.reporthost.com/?CAULK
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
19) Comment, Conducive conditions - Firewood was stored so that it was in contact with or close to the building exterior. This is a conducive condition for wood-destroying organisms. Recommend storing firewood outdoors in an open area, and as far away from buildings as practical to keep insects away from buildings. For more information visit:
https://www.reporthost.com/?FWWDI
Photo
Photo 19-1 
20) Comment - One or more shutters were deteriorated.
Photo
Photo 20-1 The wood spacer behind the shutter is rotted. Recommend a qualified contractor remove all rotted wood and replace.
21) Comment - The parging (decorative coating) on one or more foundation walls was damaged or deteriorated. This is not a structural concern, but the client may want this repaired for appearance's sake.
Photo
Photo 21-1 
Age of roof surface(s): 2 yrs
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full
22) Repair/Replace, Maintain -
Photo
Photo 22-1 There are gaps in the leaf guards. Recommend a qualified contractor repair.
Photo
Photo 22-2 The leaf guard is damaged.
Photo
Photo 22-3 
Photo
Photo 22-4 The leaf guards are missing.
23) Repair/Replace, Conducive conditions - Some composition shingles were damaged. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 23-1 There is shingle damage at the front entry where the large tree over hangs.
24) Repair/Replace - One or more downspouts or downspout extensions drained onto driveways/ walkways. This can result in ice or moss forming on driveways/ walkways, and can pose a fall hazard. Recommend that a qualified person install or modify extensions as necessary so rainwater isn't directed onto driveways/ walkways.
Photo
Photo 24-1 
25) Repair/Replace - Extensions such as splash blocks or drain pipes for one or more downspouts were missing, poorly sloped and/or substandard. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 25-1 
Photo
Photo 25-2 
Photo
Photo 25-3 
Photo
Photo 25-4 
26) Maintain, Monitor -
Photo
Photo 26-1 There are removable leaf guards installed on the gutters, leafs and debris can still enter the gutters. Recommend monitoring these areas.
Photo
Photo 26-2 
27) Maintain, Conducive conditions - Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 27-1 
Photo
Photo 27-2 
Photo
Photo 27-3 
28) Maintain, Conducive conditions - Significant amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Photo
Photo 28-1 
29) Maintain, Conducive conditions - Vegetation such as trees, shrubs, and/or vines overhung the roof surface or were in contact with the roof edge. Organic debris such as leaves or needles are likely to accumulate in gutters and on the roof surface. Gutters can overflow and cause water to come in contact with the building exterior or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Vegetation in contact with the roof can damage the roof surface and/or the roof drainage system. Recommend pruning vegetation so as to not be in contact with the roof and to not overhang the roof surface. If vegetation is too tall then it should be pruned at least 10 feet above the roof surface.
Photo
Photo 29-1 
Photo
Photo 29-2 
Photo
Photo 29-3 
Attic and Roof StructureTable of contents
Attic inspection method: Traversed
Location of attic access point #A: Garage
Location of attic access point #B: Hallway
Attic access points that were opened and viewed, traversed or partially traversed: A, B
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-15
Roof ventilation type: Box vents (roof jacks), Enclosed soffit vents
30) Safety, Repair/Maintain - The ladder was damaged at the pull-down attic stairs. This is a fall hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 30-1 
31) Repair/Replace - The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
32) Repair/Replace - The soffit vents were clogged with paint. This can reduce air flow through the roof structure or attic and result in reduced service life for the roof surface materials because of high temperatures. Moisture from condensation is also likely to accumulate in the roof structure and/or attic. Recommend that a qualified person repair as necessary so air flows freely through all vents. For example, by cleaning screens or replacing screens with 1/8-inch to 1/4-inch wire mesh.
Photo
Photo 32-1 
33) Repair/Replace - One or more exhaust fan ducts in the attic were not attached to a vent hood or cap. As a result, conditioned air will enter the attic when the fan is operated. Ducts terminating near an attic vent but without a dedicated vent hood or cap will likely blow conditioned air back into the attic. This can result in excessive moisture in the attic. Recommend that a qualified contractor repair per standard building practices, so exhaust fan ducts are permanently fastened to vent hoods or caps.
Photo
Photo 33-1 The dryer vent appears to be loose at the roof connection.
34) Repair/Maintain - The attic access hatch was not insulated. Weatherstripping was also missing. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency. For more information, visit:
https://www.reporthost.com/?ATTACC
35) Repair/Maintain - Cardboard baffles that are intended to keep insulation from blocking soffit vents in the attic were loose and had fallen down. Attic and/or roof structure ventilation can be reduced as a result. The service life for the roof surface materials can also be reduced because of high temperatures. Moisture from condensation is also likely to accumulate in the roof structure and/or attic and can be a conducive condition for wood-destroying organisms. Recommend that a qualified person repair or reattach baffles as necessary.
Photo
Photo 35-1 
36) Repair/Maintain - One or more animal (e.g. bird, squirrel) nests were found in the attic. Nesting materials should be removed. Surrounding insulation should be repaired or replaced if necessary. Holes or openings into the attic (e.g. screens, gaps) should be repaired as necessary by a qualified person to prevent future nesting or vermin intrusion.
Photo
Photo 36-1 The main attic.
37) Maintain, Conducive conditions - One or more soffit vents were blocked by insulation. This can reduce air flow through the roof structure or attic and result in reduced service life for the roof surface materials because of high temperatures. Moisture from condensation is also likely to accumulate in the roof structure and/or attic and can be a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary so air flows freely through all vents. For example, by moving or removing insulation and installing cardboard baffles.
Photo
Photo 37-1 
38) Evaluate, Monitor - What appeared to be past water stains were visible on the roof structure at one or more locations in the attic. However, no elevated levels of moisture were found at these stains during the inspection. The stains may have been caused by a past leak. Recommend asking the property owner about past leaks. Monitor these areas in the future, especially after heavy rains to determine if active leaks exist. If leaks are found, recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 38-1 The garage attic.
Photo
Photo 38-2 The garage attic.
Photo
Photo 38-3 The main attic.
Garage or CarportTable of contents
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Condition of garage floor: Appeared serviceable
Condition of garage interior: Required repair or evaluation (see comments below)
39) Safety, Repair/Replace - The threshold installed at the base of the door between the garage and the house was damaged. House to garage doors prevent fire and fumes from spreading from the garage to the house. Thresholds prevent fire and fumes from spreading underneath the door. This is a potential safety hazard. Recommend that a qualified person repair/replace the threshold per standard building practices.
Photo
Photo 39-1 The house/ garage threshold is damaged. recommend a qualified contractor replace.
40) Safety, Repair/Replace - The pull-down attic stairs installed in the attached garage ceiling had no visible fire-resistance rating. Current standard building practices call for wooden-framed ceilings that divide the house and garage to have a fire-resistance rating. Installing pull-down attic stairs intended for interior spaces compromises the ceiling's fire resistance. Recommend that a qualified person repair as necessary to restore the ceiling's fire resistance. For example, by modifying, replacing or removing the stairs. Note that commercially made, fire resistance-rated stairs are available. For more information, visit:
https://www.reporthost.com/?FIREATTSTR
41) Safety, Repair/Maintain, Evaluate - The auto-reverse mechanism on one or more automatic openers for garage vehicle doors was inoperable. This is a potential safety hazard. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
https://www.reporthost.com/?NRGD
42) Repair/Replace, Evaluate - One or more automatic vehicle door openers were inoperable. Recommend that a qualified contractor evaluate and repair or replace opener(s) as necessary.
Photo
Photo 42-1 The garage door opener made a popping sound and smoke came from the unit when the inspector was evaluating the operation. Recommend a qualified contractor evaluate, repair/ replace.
43) Repair/Replace, Evaluate - One or more garage vehicle doors wouldn't close with the automatic opener because the opener auto-reversed while the door was closing. This can be caused by photoelectric sensors being out of adjustment, the door binding, the mechanical auto-reverse sensor having problems, etc. Note that because of this, the inspector was unable to verify that the auto-reverse functions for the automatic opener were operable. A qualified person should evaluate, repair as necessary and verify that auto-reverse functions are working.
44) Repair/Replace, Evaluate - When ever water intrusion/ damaged is present the possibility of structure damage is possible.
Photo
Photo 44-1 The garage.
Photo
Photo 44-2 There is water damage to the wall above the garage door. Recommend a qualified contractor evaluate, repair. All deteriorated, rotted wood should be removed.
45) Repair/Maintain - Weatherstripping sealing one or more garage vehicle doors was deteriorated. Recommend replacing or installing weatherstripping where necessary to prevent water and/or vermin intrusion.
Photo
Photo 45-1 The bottom of the garage door.
46) Comment - Many floor areas were obscured by stored items and couldn't be fully evaluated.
Photo
Photo 46-1 
Photo
Photo 46-2 
Photo
Photo 46-3 
47) Comment - One or more garage vehicle doors had minor damage or deterioration.
Photo
Photo 47-1 The garage door.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil, Cold water supply pipes
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: non-metallic sheathed, armor clad (AC), metal clad (MC) or flexible metal conduit (FMC)
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
48) Safety, Repair/Replace, Evaluate - Components for the bonding system were missing and/or substandard. This is a potential safety hazard due to the risk of shock. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 48-1 There is no bond jumper across the water meter.
49) Safety, Repair/Replace, Evaluate - One or more electric receptacles at the laundry area and/or garage had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
https://www.reporthost.com/?GFCI
Photo
Photo 49-1 The laundry room.
50) Safety, Repair/Replace - The electric meter box was loose or not securely attached to the structure. This is a potential safety hazard. A qualified electrician should repair as necessary.
Photo
Photo 50-1 
51) Safety, Repair/Replace - Panel(s) #A had inadequate working space. This is a safety hazard when opening or working in panels. Electric panels should have the following clearances:
  • An open area 30 inches wide by 3 feet deep in front of the panel
  • 6 feet 6 inches of headroom in front of the panel
  • The wall below the panel is clear to the floor
  • The center of the grip of the operating handle of the switch or circuit breaker not more than 6 feet 7 inches above the floor or working platform
Recommend that a qualified contractor repair or make modifications per standard building practices. If panels must be opened for repairs, then a qualified electrician should perform repairs.
Photo
Photo 51-1 
52) Safety, Repair/Replace - Neutral wires were doubled or bundled together under the same lug on the neutral bus bar in panel(s) #A. This is a potential safety hazard in the event that one of the circuits needs to be isolated during servicing. For one neutral to be disconnected, other neutrals from energized circuits sharing the same lug will be loosened. Power surges may result on the energized circuits and result in damage or fire. Also, multiple wires under the same lug may not be secure, resulting in loose wires, arcing, sparks and fire. Recommend that a qualified electrician repair per standard building practices. For more information, visit:
https://www.reporthost.com/?DTNB
Photo
Photo 52-1 
53) Safety, Repair/Replace - Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo
Photo 53-1 The garage.
Photo
Photo 53-2 The garage.
54) Safety, Repair/Replace - One or more light boxes were damaged. This is a potential safety hazard for shock or fire. Recommend that a qualified electrician repair as necessary.
Photo
Photo 54-1 The light box in the garage attic is broke.
55) Safety, Repair/Replace - Conduit and/or fittings at one or more locations were Rusted. This is a potential safety hazard for shock or fire. Recommend that a qualified electrician repair as necessary.
Photo
Photo 55-1 The garage.
56) Safety, Repair/Replace - One or more electric receptacles and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
Photo
Photo 56-1 The box is loose in the wall.
Photo
Photo 56-2 The sitting room.
Photo
Photo 56-3 The kitchen.
Photo
Photo 56-4 The kitchen.
Photo
Photo 56-5 The kitchen.
Photo
Photo 56-6 The box is loose inside the wall.
57) Safety, Repair/Replace - A 3-slot receptacle was installed for the clothes dryer. Most modern clothes dryers use both 120 and 240 volts (120 for timers and motors, and 240 for heating elements) and either require or are more safely installed with a 4-slot receptacle. With 3-conductor wiring, the ground wire rather than a neutral wire is used to carry the return current back for the 120 volt leg. The clothes dryer's metal frame can become energized if the neutral wire becomes loose at the receptacle or panel. While 3-wire clothes dryer circuits were allowed prior to 1996 and are commonly found, they are considered unsafe due to the risk of shock. Recommend that a qualified electrician convert this to a 4-wire circuit. Note that this may require installing a new circuit wire from the panel to the clothes dryer location.
Photo
Photo 57-1 The laundry room.
58) Safety, Repair/Replace - One or more light fixtures installed outside were loose and/or damaged. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair as necessary.
Photo
Photo 58-1 
Photo
Photo 58-2 The front entry.
Photo
Photo 58-3 The rear entry light box is loose in the wall.
59) Safety, Repair/Replace - Smoke alarms were missing from one or more bedrooms, from one or more hallways leading to bedrooms and/or in the attached garage. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
https://www.reporthost.com/?SMKALRM
60) Safety, Repair/Replace -
Photo
Photo 60-1 The door bell transformer installed in the laundry closet needs to be replaced.
61) Safety, Repair/Maintain - Wires protruded from the front surface of panel(s) #A when the cover was removed. This is a potential safety hazard for shock when the panel cover is removed or installed because the wires will move and be in contact with the cover when doing so. Recommend that a qualified electrician repair as necessary so wires are contained inside the panel(s) and are not in contact with the cover.
Photo
Photo 61-1 
62) Safety, Repair/Maintain - Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
https://www.reporthost.com/?SMKALRMLS
Photo
Photo 62-1 
63) Safety, Repair/Maintain -
Photo
Photo 63-1 The neutral wire for the main service wire is not twisted tightly, this can cause overheating of the wire. Recommend a licensed electrical contractor repair.
64) Safety, Minor Defect - One or more exterior receptacle covers were broken. This is a potential shock hazard. Recommend that a qualified person replace covers where necessary.
Photo
Photo 64-1 
65) Safety, Evaluate - Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.
66) Repair/Replace, Evaluate - One or more electric receptacles appeared to have no power. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician evaluate and repair.
Photo
Photo 66-1 
Photo
Photo 66-2 
Photo
Photo 66-3 The master bathroom.
Photo
Photo 66-4 The hall bathroom.
Photo
Photo 66-5 The kitchen.
67) Repair/Replace - One or more light fixtures were loose. Recommend that a qualified electrician repair or replace light fixtures as necessary.
Photo
Photo 67-1 The master bathroom.
Photo
Photo 67-2 
68) Repair/Maintain, Evaluate - The legend for circuit breakers or fuses in panel(s) #A was missing, incomplete, illegible or confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.
Photo
Photo 68-1 
69) Repair/Maintain - The meter box is significantly rusted. recommend cleaning and painting.
Photo
Photo 69-1 
70) Evaluate - One or more circuit breakers in panel(s) #A were in the off position. Consult with the property owner to determine why breakers were tripped or off, and that a qualified electrician evaluate and repair if necessary. Note that the inspector does not operate circuit breakers.
Photo
Photo 70-1 
71) Evaluate - One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 71-1 The garage.
72) Comment -
Photo
Photo 72-1 The inspector was unable to determine to function of the switch in the kitchen. Recommend buyer ask seller about this.
Photo
Photo 72-2 The inspector was unable to determine to function of the switch in the garage. Recommend buyer ask seller about this.
73) Comment -
Photo
Photo 73-1 The door bell cover is missing.
74) Comment -
Photo
Photo 74-1 The main disconnect is located in the garage.
75) - Comment
Photo
Photo 75-1 The corner bedroom light switch is upside down.
76) - Comment
Photo
Photo 76-1 There appears to be an electrical switch removed in the hall bathroom. Recommend buyer ask seller about this.
Plumbing / Fuel SystemsTable of contents
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water meter: Mechanical closet.
Location of main water shut-off: In mechanical room, In utility room, closet
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Condition of waste lines: Appeared serviceable
Location(s) of plumbing clean-outs: Building exterior
Vent pipe condition: Appeared serviceable
Sump pump installed: No
77) Safety, Comment - Copper water supply pipes were installed. Copper pipes installed prior to the late 1980s may be joined with solder that contains lead, which is a known health hazard especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained approximately 50% lead. The client should be aware of this, especially if children will be using this water supply system. Note that the inspector does not test for toxic materials such as lead. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions include:
  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than 6 hours
  • Install appropriate filters at points of use
  • Use only cold water for cooking and drinking, as hot water dissolves lead more quickly than cold water
  • Use bottled or distilled water
  • Treat well water to make it less corrosive
  • Have a qualified plumber replace supply pipes and/or plumbing components as necessary
For more information visit:
https://www.reporthost.com/?LEADDW
https://www.reporthost.com/?LEAD
78) Repair/Replace, Evaluate - Significant corrosion was found in some water supply pipes or fittings. Leaks can occur as a result. Recommend that a qualified plumber evaluate and replace components as necessary.
Photo
Photo 78-1 
79) Repair/Replace - One or more hose bibs were not the "frost-free" design, and are more likely to freeze during cold weather than frost-free hose bibs. Recommend that a qualified plumber upgrade these with frost-free hose bibs to prevent freezing, pipes bursting, flooding and possible water damage.
Photo
Photo 79-1 
80) Minor Defect - One or more hose bibs weren't anchored securely to the structure's exterior. Water supply pipes can be stressed when hose bibs are turned on and off and when hoses are pulled. Leaks may occur as a result. Recommend that a qualified person install fasteners per standard building practices.
Photo
Photo 80-1 
81) Comment -
Photo
Photo 81-1 The sitting room.
Photo
Photo 81-2 There is no shutoff valve installed for the rear water spigot.
82) Comment -
Photo
Photo 82-1 The main water shutoff is located in the mechanical closet.
Water HeaterTable of contents
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: 5 yrs
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Manufacturer: Rheem
Model number: PROE50 2 RH91
Location of water heater: Mechanical room, Closet
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 114
83) Safety, Repair/Replace, Evaluate - The bonding wire was missing at the water piping for the water heater. This is a potential safety hazard for shock. Normally, metallic non-current carrying systems such as water and gas piping are connected electrically (bonded) to reduce potential energy differences between such systems, and the risk of shock. Recommend that a qualified electrician or contractor evaluate and repair per standard building practices.
Photo
Photo 83-1 The mechanical closet.
84) Comment - The estimated useful life for most water heaters is 8-12 years.
Photo
Photo 84-1 The water heater was manufactured in 2014.
85) Comment - A water heater was installed in or over a finished living space or in an area where leaking can cause damage, and no catch pan or drain was installed. Catch pans and drains prevent water damage to finished interior spaces below if or when the water heater leaks or is drained. If concerned, consult with a qualified contractor about installing these. Note that drain lines for catch pans are usually installed below the floor level and are difficult at best to install in an existing home.
Photo
Photo 85-1 The mechanical closet.
Heating, Ventilation and Air Condition (HVAC)Table of contents
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: 10/2/2018
Source for last service date of primary heat source: Label
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Electric
Forced air heating system manufacturer: Bryant
Forced air furnace model #: FE4ANF002
Forced air furnace serial number: 3214A83314
Location of forced air furnace: Mechanical room, Closet
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At top of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior
Estimated age of heat pump or air conditioning unit: 5 yrs
Manufacturer of cooling system and/or heat pump: Bryant
Heat pump or air conditioner model number: 280ANV02400EAAA
Heat pump or air conditioner serial number: 280ANV024-A
86) Safety, Repair/Replace - Debris, dirt and/or dust were visible in one or more sections of supply and/or return air ducts for the heating or cooling system. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Agency (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers." At a minimum, the visible debris should be thoroughly cleaned. Recommend that a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit:
https://www.reporthost.com/?DUCTCLEAN
Photo
Photo 86-1 
Photo
Photo 86-2 The return air register in the hall ceiling.
87) Repair/Replace - This home had a forced air heating or cooling system with a centrally located return-air source. A gap of a (< 1/2 inch) between the door and the floor below are required. Gaps below doors provide a path for air in rooms to the centrally located return-air duct.
Photo
Photo 87-1 There is a central return air.
88) Repair/Maintain - The covers for one or more heating and/or cooling system air filters were loose. Unfiltered air can enter the return air supply and reduce indoor air quality. Recommend that a qualified person repair as necessary.
Photo
Photo 88-1 
89) Maintain - The gas or oil-fired forced air furnace appeared to have been serviced within the last year based on information provided to the inspector or labeling on the equipment. If this is true, then routine servicing is not needed at this point. However a qualified HVAC contractor should inspect, clean, and service this system, and make repairs if necessary annually in the future. For more information visit:
https://www.reporthost.com/?ANFURINSP
Photo
Photo 89-1 
90) Maintain - Recommend that home buyers replace or clean HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or cleaning them as necessary. How frequently they need replacing or cleaning depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
91) Maintain - The cooling fins at the heat pump or air conditioning condensing unit were dirty. Energy efficiency can be reduced as a result. Recommend that a qualified person clean fins as necessary.
Photo
Photo 91-1 
Photo
Photo 91-2 
92) Comment - The Wall blocked access to the furnace. The inspector was unable to fully evaluate this system.
Photo
Photo 92-1 The furnace is blocked by the wall structure, there are screws in the cover between the wall and the furnace. The inspector was unable to remove the screws to remove the covers. The interior of the furnace was not evaluated.
Photo
Photo 92-2 
93) Comment - The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be this age and/or its useful lifespan a
Photo
Photo 93-1 The furnace was manufactured in 2014.
94) Comment - The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years.
Photo
Photo 94-1 The A/C units manufacture date is 2014.
Fireplaces, Stoves, Chimneys and FluesTable of contents
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning fireplace type: Metal pre-fab
Fan or blower installed in wood-burning fireplace or stove: No
Condition of chimneys and flues: Near, at or beyond service life
Wood-burning chimney type: Metal, with wood enclosure
95) Safety, Repair/Replace -
Photo
Photo 95-1 The structure was wobbly from the roof line to the top, it appears there is structure damage. Recommend a qualified contractor evaluate, repair.
96) Safety, Repair/Replace -
Photo
Photo 96-1 The siding is melted at the top of the chimney structure, it appears the flue piping is disconnected inside the wood structure. Recommend a qualified contractor evaluate, repair. Separation of the wood burning fireplace flue is a fire hazard.
Photo
Photo 96-2 
97) Safety, Repair/Maintain, Evaluate - One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
https://www.reporthost.com/?CSIA
98) Safety, Repair/Maintain - The fireplace's firebox was significantly deteriorated. For example, loose, cracked, pitted or broken firebricks, gaps between bricks and/or missing mortar. Heat from the fireplace may penetrate the firebox. This is a potential fire hazard. Recommend that a qualified contractor repair as necessary.
Photo
Photo 98-1 
99) Repair/Replace - The glass doors for the fireplace were difficult to operate and/or deteriorated. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 99-1 The glass doors are hard to open and close and the glass is scorched.
100) Repair/Replace -
Photo
Photo 100-1 The slab has settled causing a separation of the hearth. Recommend a qualified contractor repair.
101) Comment - Significant amounts of ash or fire materials were present in one or more fireplace or wood stove fireboxes. As a result, the inspector was unable to fully view or evaluate the firebox(es) and/or components inside (e.g. firebrick, metal liner, log lighter). These components are excluded from this inspection.
Photo
Photo 101-1 
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Refrigerator
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
102) Repair/Replace - The sink sprayer was inoperable and/or leaking. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 102-1 
103) Repair/Replace - The under-sink food disposal was noisy. Recommend that a qualified contractor repair or replace as necessary.
Photo
Photo 103-1 
104) Repair/Replace - The cooktop exhaust fan was noisy or vibrated excessively. Recommend that a qualified person repair or replace as necessary.
105) Repair/Maintain - One or more cabinet drawers were difficult to open or close. Recommend that a qualified person repair as necessary.
Photo
Photo 105-1 
106) Minor Defect - The light in the exhaust hood was inoperable. Recommend replacing light bulb(s) or that repairs be made by a qualified person if necessary.
Bathrooms, Laundry and SinksTable of contents
Location #A: Master bath
Location #B: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans
107) Safety, Maintain - The clothes dryer exhaust duct appeared to need cleaning. Significant amounts of lint build-up were visible and may reduce air flow. This is a fire hazard. Recommend that a qualified person clean this duct now and as necessary in the future. Some chimney sweeps or heating/cooling duct cleaners perform this service. For more information, visit:
https://www.reporthost.com/?DRYER
108) Repair/Replace, Maintain -
Photo
Photo 108-1 The dryer is vented through the roof, this makes it difficult to clean the dryer vent. recommend a qualified contractor reroute the vent to the gable end of the dwelling.
109) Repair/Replace, Evaluate, Conducive conditions - The toilet at location(s) #A and B was loose where it attached to the floor. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 109-1 The master bathroom.
Photo
Photo 109-2 The hall bathroom.
110) Repair/Replace - The exhaust fan at location(s) #A was noisy. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.
Photo
Photo 110-1 The master bathroom.
111) Repair/Replace - No catch pan or drain was installed at the clothes washing machine location in a finished space. Catch pans and drains prevent water damage to finished interior spaces if or when the washing machine leaks, overflows or is drained. If concerned, consult with a qualified contractor about installing a catch pan. Note that installing a drain line for a catch pan routed to the outdoors may not be feasible. As an alternative, a water alarm can be installed in the catch pan. For more information visit:
https://www.reporthost.com/?WTRALRM
Photo
Photo 111-1 
112) Repair/Replace - The bathroom diverter valve leak while in use. Recommend a licensed plumbing contractor repair/replace.
Photo
Photo 112-1 The master bathroom.
113) Repair/Maintain, Conducive conditions - Caulk was missing around the base of the bathtub spout, or there was a gap behind it, at location(s) #A. Water may enter the wall structure behind the bathtub. Recommend that a qualified person repair as necessary to eliminate the gap. For example, by installing or replacing caulk if the gap is small enough. For larger gaps, a shorter spout nipple or an escutcheon plate can be installed.
Photo
Photo 113-1 The master bathroom.
114) Repair/Maintain, Conducive conditions - Gaps, no caulk, or substandard caulking were found between the bathtub and the at location(s) #A and B. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 114-1 The master bathroom.
Photo
Photo 114-2 The master bathroom.
Photo
Photo 114-3 The hall bathroom.
Photo
Photo 114-4 The hall bathroom.
115) Repair/Maintain - Gaps, no caulk, or substandard caulking were found at location(s) #A. Water can penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing or replacing caulk.
Photo
Photo 115-1 The master bathroom.
Photo
Photo 115-2 The master bathroom.
116) Repair/Maintain - The bathtub drain stopper mechanism at location(s) #A was missing. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 116-1 The master bathroom.
117) Repair/Maintain - The clothes dryer exhaust duct was routed through an unheated space (e.g. crawl space, basement, attic) and was not insulated. Condensation can accumulate inside the duct. In extreme cases ducts can be blocked by pooled water. Recommend that a qualified person permanently install R-4 insulation around the duct per standard building practices.
118) Maintain -
Photo
Photo 118-1 Recommend cleaning and maintaining the washer service box.
119) Maintain -
Photo
Photo 119-1 Recommend cleaning the hall bathroom toilet tank.
120) Comment - No access or only limited access was available to the back of the clothes washer and dryer, and to utility hook-ups located behind the appliances. The inspector normally attempts to determine the presence of a gas vs. electric power supply, the configuration of the stand pipe, whether the dryer exhaust duct is serviceable, etc. Because of the lack of access, the inspector was unable to fully evaluate and/or describe the hook-ups and appliances.
121) Comment -
Photo
Photo 121-1 There appears to be an epoxy coating on the bathroom sinks. Recommend buyer asking seller about this and all warranties.
122) Comment -
Photo
Photo 122-1 The master bathroom has been refinished. Recommend buyer ask seller about this and all warranties.
123) Comment -
Photo
Photo 123-1 The bifold doors block ease of access to the dryer.
124) Comment -
Photo
Photo 124-1 Recommend buyer ask seller for installation requirements for the wall covering in the master bathroom.
Interior, Doors and WindowsTable of contents
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Metal, Sliding glass
Condition of interior doors: Required repair, replacement and/or evaluation (see comments below)
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Double-hung
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall or plaster
Ceiling type or covering: Drywall or plaster
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
125) Repair/Replace, Evaluate - Floors in one or more areas were not level. This can be caused by foundation settlement or movement of the foundation, posts and/or beams. Significant repairs may be needed to make floors level. Recommend that a qualified contractor and/or engineer evaluate further. Repairs should be performed by a qualified contractor.
Photo
Photo 125-1 There are humps in many areas of the dwelling at the exterior walls, this is from the slab settling below the foundation.
Photo
Photo 125-2 The master bathroom floor slopes towards the interior wall.
126) Repair/Replace - One or more exterior doors were difficult to open or close and/or were sticking. Recommend that a qualified person repair as necessary.
Photo
Photo 126-1 The front entry door hits the frame.
127) Repair/Replace - Trim or jambs around one or more exterior doors was damaged. Recommend that a qualified person repair, replace or install as necessary.
Photo
Photo 127-1 The front entry.
128) Repair/Replace - Some exterior door hardware, including hinges were missing screws. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 128-1 There are screws missing from the front entry door hinge. Recommend a qualified contractor repair.
129) Repair/Replace - Some interior door hardware (hinges) were loose. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 129-1 The middle bedroom.
Photo
Photo 129-2 The corner bedroom.
130) Repair/Replace - Carpeting in one or more areas was loose. Recommend that a qualified contractor repair as necessary. For example, by stretching or replacing carpeting.
Photo
Photo 130-1 The master bedroom closet.
Photo
Photo 130-2 The master bathroom.
Photo
Photo 130-3 The carpet seams were not glued at the dining room post.
131) Repair/Maintain - Weatherstripping around one or more exterior doors was damaged. Water may enter the building, or energy efficiency may be reduced. Recommend that a qualified person repair or replace weatherstripping as necessary.
Photo
Photo 131-1 The rear entry door.
132) Repair/Maintain - Metal thresholds at one or more exterior doors sagged or flexed when stepped on. Recommend that a qualified person repair as necessary to minimize sagging or movement, to ensure that the threshold is securely attached, and apply caulk or weather stripping materials to make a weatherproof seal.
Photo
Photo 132-1 The front entry.
133) Repair/Maintain - One or more interior doors were sticking in the door jamb and were difficult to operate. Recommend that a qualified person repair as necessary. For example, by trimming doors.
Photo
Photo 133-1 The middle bedroom.
Photo
Photo 133-2 The corner bedroom.
Photo
Photo 133-3 The corner bedroom.
Photo
Photo 133-4 The master bathroom.
134) Repair/Maintain - Tile, stone and/or grout in the flooring in one or more areas was deteriorated (e.g. loose or cracked tiles, missing grout) or substandard. If in a wet area, water can damage the sub-floor. Recommend that a qualified contractor repair as necessary.
Photo
Photo 134-1 The front entry closet.
135) Evaluate, Comment -
Photo
Photo 135-1 There is a wire hanging from the ceiling in the mechanical closet. Recommend buyer ask seller about this.
136) Evaluate - Patches or evidence of prior repairs were found in one or more walls or ceilings. Recommend asking the property owner about the repairs (e.g. why necessary, whether prior leaks have occurred).
Photo
Photo 136-1 The master bathroom.
137) Comment - One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
Photo
Photo 137-1 The front entry door has holes in it.
138) Comment -
Photo
Photo 138-1 There is an open access to the bathtub drains in the sitting room. Recommend buyer ask seller about this.
Wood Destroying Organism FindingsTable of contents
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: Yes
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: Yes
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: Yes
Visible evidence of conditions conducive to wood-destroying organisms: Yes

The main purpose of a home inspection is to give you the information needed to make an informed decision on the purchase. Some of the content are items that need to be maintained by the buyer.