View as PDF

View summary

Real Time Home Inspections

3150 Ezie Ave 
Clovis CA 93611-5164
Inspector: Greg Marty

Property Inspection Report

Client(s):  Sample Report Only
Property address:  13457 Fourth St. Yucaipa Ca
Inspection date:  Sunday, August 19, 2018

This report published on Wednesday, August 29, 2018 10:33:30 AM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Exterior and Foundation

View summary

General Information
Table of contents
Time finished: 10:30
Present during inspection: Client
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Hot
Type of building: Condo
Buildings inspected: One condominium unit
Number of residential units inspected: 1
Age of main building: Built in 1990, 28 yrs old
Front of building faces: South
Main entrance faces: West
Occupied: No
1) The residential dwelling unit appeared to be part of a complex that is managed and maintained by a "Home Owners" or "Condo" association. This inspection is limited to a visual evaluation of the systems and components that are located within the dwelling unit inspected. The current condition of "Common Elements" are excluded from this inspection. Such elements include, but are not limited to:
  • The building site condition, structural stability, drainage systems and insulation
  • All exterior surfaces, materials and structure
  • All roof surfaces, materials and structure
  • All attic spaces
  • The building foundation, floor substructure and all spaces below, such as basements and/or crawl spaces
  • All stairs, landings, porches, hallways, walks and balconies, elevators, utility metering, parking stalls/ports
  • All decks, patios, pools, spas, recreational areas/equipment
  • All common areas on the property
Any comments regarding these items in this report have been made as a courtesy only. Consult with the Home Owner's or Condo Association regarding these items.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Exterior stair material: Concrete, Metal
2) One or more treads at exterior stairs were loose. This is a potential fall hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 2-1 
3) This property was accessed by a driveway or private road shared with nearby properties. Shared driveways or private roads are excluded from this inspection. Comments in this report related to them are made as a courtesy only and are not meant to be a substitute for a evaluation by a specialist if repairs are needed. Recommend that the client review the recorded agreements regarding the driveway, the deeds of the property owners involved, and easements permitting access to, use of, and maintenance of the driveway.
Photo
Photo 3-1 
4) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 4-1 Cracks in driveway
5) Shared property landscaping is lacking general maintenance and upkeep.
Photo
Photo 5-1 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Not inspected because i wasnt granted access
Garage or Carport
Table of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Detached
Condition of garage vehicle door(s): Appeared serviceable
6) Garage was not inspected due to being blocked by car.
Photo
Photo 6-1 Garage was found to be inaccessible due to parked car
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: Not determined (components inaccessible or obscured)
Estimated service amperage: Not determined (components inaccessible or obscured)
Service entrance conductor material: Not determined (components inaccessible or obscured)
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Building exterior
Location of main service panel #B: Hallway
Location of main disconnect: Not determined (inaccessible or obscured, or not readily apparent)
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
7) One or more receptacles were broken or damaged. This is a potential shock or fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.
Photo
Photo 7-1 Broken receptacle
8) One or more electric receptacles had reverse-polarity wiring, where the hot and neutral wires were reversed. This is a shock hazard. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?RPR
Photo
Photo 8-1 Hot and Neutral reversed in kitchen next to sink
9) One or more electrical components including switches and/or receptacles appeared to be older than their intended service life. Such old components may pose a fire or shock hazard. Recommend consulting with a qualified electrician to determine which components should be replaced with newer, modern components.
Photo
Photo 9-1 
Photo
Photo 9-2 Broken light switch
Photo
Photo 9-3 Broken bathroom light switch
10) One or more electric receptacles and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
Photo
Photo 10-1 
11) One or more light fixtures installed outside were loose. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair as necessary.
Photo
Photo 11-1 Loose Light fixture
Photo
Photo 11-2 
12) The inspector was unable to open and evaluate panel(s) #A because panel(s) were locked. The condition of these panel(s) is unknown and they are excluded from this inspection. Repairs may be needed. Recommend that a qualified person correct conditions, or that a qualified contractor make repairs if necessary so panels can be opened, and that a qualified person fully evaluate panel(s).
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
13) One or more hose bibs leaked while off. When hose bibs leak while turned off, it's often caused by a worn valve seat or a loose bonnet. When hose bibs leak while turned on, it may be due to worn "packing" around the stem or a defective backflow prevention device. Recommend that a qualified plumber repair as necessary.
Photo
Photo 13-1 Leaking Hose Bib
Photo
Photo 13-2 
14) The inspector did not determine the location of the main water shut-off valve, or verify that a readily accessible shut-off valve in the building exists. Recommend consulting with the property owner to determine if a main shut-off valve exists, locating it yourself, or that a qualified plumber find it if necessary. If no readily accessible main shut-off valve is found in the building, then recommend that a qualified plumber install one so the water supply can be quickly turned off in the event of an emergency, such as when a supply pipe bursts.
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Not determined (inaccessible, obscured, or water, power or gas service off)
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Required repair, replacement and/or evaluation (see comments below), Plenum below filters needs servicing
Forced air heating system fuel type: Natural gas
Location of forced air furnace: Closet
Condition of furnace filters: Appeared serviceable
15) Plenum duct needs cleaning and sanitation due to a large amount of dust and debris
Photo
Photo 15-1 New Filter, but dirty plenum.
Photo
Photo 15-2 HVAC filter plenum is in need of cleaning and sanitation
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Required repair, replacement and/or evaluation (see comments below), Loose next to stove
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Not determined
Condition of ranges, cooktops and/or ovens: Near, at or beyond service life
Range, cooktop, oven type: Natural gas
Type of ventilation: ducted to exterior
Condition of refrigerator: N/A (none installed)
16) The dishwasher was inoperable. Recommend that a qualified specialist evaluate and repair or replace as necessary.
17) Water damage was found in shelving or cabinets below the sink. Recommend that a qualified contractor repair as necessary after any plumbing leaks have been repaired. If moisture is present then concealed areas should be dried thoroughly.
Photo
Photo 17-1 Signs of past moisture and swelling to kitchen sink shelf
18) One or more filters for the cooktop exhaust fan were damaged. Recommend replacing filters as necessary.
19) Water supply shut off valve for refrigerator leaks
Photo
Photo 19-1 Kitchen refrigerator water shut off valve slight leak
20) One or more cabinet drawers were difficult to open or close. Recommend that a qualified person repair as necessary.
Photo
Photo 20-1 Hard to function drawers in kitchen
21) The cooktop exhaust fan was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 21-1 Vent hood was inoperable at time of inspection
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Location #B: Master bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
22) The floor by the shower at location(s) #A was water-damaged. Recommend that a qualified person repair as necessary.
Photo
Photo 22-1 Soft flooring next to tub, possibly due to tub spillage
23) Hall bath shower head and beauty ring are loose. Recommend having a licensed plumber evaluate and repair as needed.
Photo
Photo 23-1 Shower head loose
24) Hall Bath Vanity sink stopper was found to be disconnected. Recommend that a qualified person repair as needed.
Photo
Photo 24-1 Hall Bath faucet stopper is not connected
Photo
Photo 24-2 
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of interior doors: Required repair, replacement and/or evaluation (see comments below)
Condition of windows and skylights: Appeared serviceable
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
25) Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary. For more information, visit:
http://www.reporthost.com/?SQUEAK
Photo
Photo 25-1 Squeaks in flooring at hallway, bathroom and bedrooms
26) The lock mechanisms on one or more sliding glass doors were inoperable. Recommend that a qualified person repair as necessary.

Slider screen lock bent
Photo
Photo 26-1 Lock at screen door is bent and not functioning
27) One or more interior doors were damaged. Recommend that a qualified person replace or repair doors as necessary.

Hall bath door delaminated
Photo
Photo 27-1 Delaminated hall bath door
28) Bedroom(s) closet doors were missing door guides at floor. This can pose a safety hazard when moving doors in there normal function. Doors can fall of track easily. Recommend having a qualified person repair as needed.
Photo
Photo 28-1 Missing closet door guides in bedrooms
29) Damaged base molding living room. Recommend that a qualified person repair as needed.
Photo
Photo 29-1 Damaged base molding in liv rm
30) Surface scratches and chipping noticed at flooring in living room and hallway.
Photo
Photo 30-1 Scratches in laminate flooring
Photo
Photo 30-2 
Photo
Photo 30-3 chipping in floor covering
31) Missing vertical blind louver.
Photo
Photo 31-1 
32) Front door threshold was found to be loose and gave under foot pressure. Appears to be missing adequate support. Recommend having a qualified person evaluate as needed.
Photo
Photo 32-1 Loose threshold at front entry. Gives under foot
33) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
Photo
Photo 33-1 dents and dings in front door
Photo
Photo 33-2 weather strip at front door is torn or has cuts
34)  
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of foundation and footings: Not determined
35) Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo
Photo 35-1 Stucco cracking
36) Broken and inoperable Doorbell button at front door. Recommend having a qualified person repair as needed.
Photo
Photo 36-1 broken and non functional door bell
37) Caulk was deteriorated in some areas. For example, at siding-trim junctions and/or at wall penetrations. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK
Photo
Photo 37-1 Missing and worn caulking at exterior wood trim

Your default report footer here...