Summary

Client(s):  Joe and Mary Smith
Property address:  123Tree Lane
TreeTown, NY 11111
Inspection date:  Wednesday, May 9, 2012

This report published on Sunday, March 31, 2024 2:27:26 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information


Interior rooms first floor
2) An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html

Interior rooms upstairs
4) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes.(SW room) They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

Exterior
7) One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.

Garage
19) The pull-down attic stairs in the attached garage ceiling aren't fire-rated. This ceiling should have a one-hour fire rating to slow or prevent the spread of fire from the attached garage to attic spaces above the living areas. A qualified contractor should evaluate and make modifications to these stairs as necessary so they have a one hour fire rating. Other options include removing them or replacing them with commercially made, fire-rated stairs. Examples of possible solutions include:
  • Installing 5/8 inch Type X sheetrock on the lower surface of the stair door and eliminating gaps around the edges of the door.
  • Removing the stairs and installing a traditional hatch made with 5/8 inch Type X sheetrock.
  • Installing a Battic Door and installing sheetrock over it as described at their website.
  • Replacing these stairs with fire-rated stairs such as those from:

http://www.calvertusa.com/

Attic
22) Evidence of "light to moderate" rodent infestation was found in one or more areas. The Center for Disease Control (CDC) defines this as less than 20 feces per square foot. Rodent infestation may be a safety hazard due to the risk of contracting Hantavirus Pulmonary Syndrome (HPS). HPS is a rare (only 20-50 cases per year in the United states) but deadly (40% mortality rate) disease transmitted by infected rodents through urine, droppings, or saliva. Humans can contract the disease when they breathe in aerosolized virus. For example, from sweeping up rodent droppings.

Recommend following guidelines in the CDC's Clean Up, Trap Up, Seal Up article for eradicating rodents, cleaning up their waste and nesting materials, and preventing future infestations. While Hantavirus is believed to survive less than one week in droppings and urine, specific precautions should be taken during clean up. The client(s) may wish to consult with a qualified, licensed pest control operator for eliminating the infestation. A qualified licensed abatement contractor or industrial hygienist could be contacted for clean up. If the infestation was minimal, clean up of rodent waste and nesting materials in non-living spaces (crawl spaces and attics) may not be necessary, or may be performed for aesthetic reasons only (odor and appearance).

Heating and cooling
26) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.
27) The estimated useful life for air conditioning compressors is 8 to 15 years. This unit appears to have exceeded this age and may need replacing at any time. Recommend budgeting for a replacement in the near future. Fins are damaged on exterior unit and insulation is missing from pipe. These will reduce the efficiency of the unit.
Photo
Photo 27-1 
Photo
Photo 27-2 

Fireplaces, woodstoves and chimneys
33) The masonry chimney is significantly deteriorated and requires major repairs, such as rebuilding, replacing bricks, and/or replacing the crown or concrete caps at the top 14 courses. Recommend having a qualified chimney service contractor or mason evaluate chimney and repair as necessary.
Cost estimate: $3,500 or more
Photo
Photo 33-1 

Kitchen
38) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
39) Sink light should be flourescent or at a minimum enclosed, fire hazard with curtain.
Photo
Photo 39-1