Property Inspection Report

Client(s):  Tasha Pilgrim
Property address:  648 Helen St
Syracuse NY 13203-1010
Inspection date:  Wednesday, September 28, 2022

This report published on Saturday, October 1, 2022 2:20:49 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary

General Information
Table of contents
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool, 56
Payment method: Cash
Type of building: Single family
Buildings inspected: One house
Source for main building age: Municipal records or property listing
Front of building faces: West
Main entrance faces: West
Occupied: Yes
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Driveway material: Asphalt
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Exterior stair material: Wood, Masonry
1) Home inspector observed a missing support post to the deck, reccomend a qualified contractor repair or replace.
Photo
Photo 1-1 
2) Home inspector observed post for the deck were in contact with concrete this could cause the wood to rot prematurely. Recommend a qualified contractor repair or replace.
Photo
Photo 2-1 
Photo
Photo 2-2 
3) Cracks, holes, settlement, heaving and/or deterioration were found in sidewalks and/or patios. Recommend that qualified contractor repair as necessary.
Photo
Photo 3-1 
4) Soil was in contact with one or more wooden deck, porch or balcony support posts. This is a conducive condition for wood destroying organisms. Even if posts are made of treated wood, the cut ends below soil may not have been field treated. Recommend grading soil or repairing as necessary to prevent wood-soil contact.
Photo
Photo 4-1 
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Apparent wall structure: Wood frame
Wall covering: Vinyl
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Concrete block
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)
5) Soil was in contact with or less than 6 inches from siding or trim. Regardless of what material is used for siding, it should not be in contact with the soil. If made of wood, siding or trim will eventually rot. For other materials, ground or surface water can infiltrate siding or trim and cause damage to the wall structure. Wood-destroying insects are likely to infest and damage the wall structure. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.
Photo
Photo 5-1 
6)  
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Exterior door material: Wood
Pier or support post material: Steel
Beam material: Built-up wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Insulation material underneath floor above: None visible
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Partially traversed
Roof surface material: Asphalt or fiberglass composition shingles, Rolled composition
Apparent number of layers of roof surface material: Multiple
7) The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future. The client may also wish to consider having a qualified contractor attempt to issue a "5 year roof certificate."
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
8) Alligatoring, crazing, fissures and/or cracks were found in one or more areas of the flat or low-slope roof surface. This is often caused by exposure to ultraviolet light (the sun), and eventually results in water penetrating the underlying roof membrane and causing leaks. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 8-1 
9)  
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 
Photo
Photo 9-5 
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Not inspected because no access was found
Condition of roof structure: Not determined (inaccessible or obscured)
Roof structure type: Not determined (inaccessible or obscured)
Ceiling structure: Not determined (inaccessible or obscured)
Condition of insulation in attic (ceiling, skylight chase, etc.): Not determined (inaccessible or obscured)
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Vermiculite insulation present: Not determined
Vapor retarder: Not determined (inaccessible or obscured)
Condition of roof ventilation: Not determined (inaccessible or obscured)
Roof ventilation type: Ridge vent(s), Gable end vents, Enclosed soffit vents
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Overhead
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 100
System ground: Cold water supply pipes
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Branch circuit wiring type: non-metallic sheathed, armor clad (AC), metal clad (MC) or flexible metal conduit (FMC), copper
Solid strand aluminum branch circuit wiring present: Not determined (inaccessible or obscured, or panels not opened)
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
10) One or more electric receptacles at the kitchen and/or bathroom(s) had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 10-1 
Photo
Photo 10-2 
11) One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
Photo
Photo 11-1 
Photo
Photo 11-2 
12) One or more electric receptacles had reverse-polarity wiring, where the hot and neutral wires were reversed. This is a shock hazard. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?RPR
Photo
Photo 12-1 
Photo
Photo 12-2 
13) 2-slot receptacles rather than 3-slot, grounded receptacles were installed in one or more areas. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits.
Photo
Photo 13-1 
14) The service drop wires were in contact with trees or vegetation. This can result in damage to wiring insulation or broken wires during high winds. Recommend pruning trees or vegetation as necessary. The utility company may prune trees at no charge.
Photo
Photo 14-1 
15) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Photo
Photo 15-1 
16)  
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Photo
Photo 16-4 
Photo
Photo 16-5 
Photo
Photo 16-6 
Photo
Photo 16-7 
Photo
Photo 16-8 
Photo
Photo 16-9 
Photo
Photo 16-10 
Photo
Photo 16-11 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service: Public
Location of main water shut-off: Basement
Supply pipe material: Copper
Drain pipe material: Plastic
Waste pipe material: Cast iron
Vent pipe material: Cast iron
Sump pump installed: No
Sewage ejector pump installed: No
Location of main fuel shut-off valve: At gas meter
17)  
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Condition of venting system: Required repair, replacement and/or evaluation (see comments below)
18)  
Photo
Photo 18-1 
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Furnace
General heating distribution type(s): Ducts and registers
Type of combustion air supply: No dedicated source visible, uses room air
Condition of venting system: Required repair, replacement and/or evaluation (see comments below)
19) Home inspector observed the vent pipe to the chimney from the furnace was not sealed off. This could be a safety issue due to carbon minoxcide gases being able to backdraft into the basement. Reccomend a qualifed contractor repair or replace.
Photo
Photo 19-1 
Photo
Photo 19-2 
20) The outdoor air temperature was below 65 degrees Fahrenheit during the inspection. Air conditioning systems can be damaged if operated during such low temperatures. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Gas fireplace or stove type: Insert
Gas-fired flue type: Not determined (obscured or inaccessible)
21) Home inspector observed vegitation growing on the chimney, this could lead to premature deterioration recommend a qualified contractor remove the vegitation.
Photo
Photo 21-1 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Range, cooktop, oven type: Electric
22) The kitchen sink drain pipe used an S-trap rather than a P-trap, or no P-trap was visible. Siphons and sudden flows of water in S-Traps can drain all the water out of the trap, leaving it dry. Sewer gases can then enter living areas. Recommend that a qualified plumber repair per standard building practices.
Photo
Photo 22-1 
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: first floor
Location #B: second floor
Bathroom and laundry ventilation type: Windows, Spot exhaust fans
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door material: Wood
Type(s) of windows: Wood, Metal, Multi-pane, Single-hung, Jalousie
Wall type or covering: Drywall, Wood
Ceiling type or covering: Drywall, Wood
Flooring type or covering: Carpet, Wood or wood products
23) Home inspector observed paint pealing on windows this could lead to premature deterioration of the windows recomend a qualified contractor repair or replace.
Photo
Photo 23-1 
24)  
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
Photo
Photo 24-4 
Photo
Photo 24-5 
Photo
Photo 24-6 
Photo
Photo 24-7 
Photo
Photo 24-8 
25)  
Photo
Photo 25-1 
Photo
Photo 25-2 
Photo
Photo 25-3 
Photo
Photo 25-4 
Photo
Photo 25-5 
Photo
Photo 25-6 
Photo
Photo 25-7 
26)  
Photo
Photo 26-1 
Photo
Photo 26-2 

Your default report footer here...