Pacific Coast Home Inspections Inc.

**************
Inspector: Todd Graham

Property Inspection Report

Client(s):  Sample
Property address:  1234 Sample
santa rosa ca 95403
Inspection date:  Tuesday, April 6, 2021

This report published on Friday, May 7, 2021 11:19:19 PM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary

General Information
Table of contents
Present during inspection: Realtor
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Inspection fee: 425.00
Payment method: Credit card
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: Built in 1966
Source for main building age: Municipal records or property listing
Occupied: Furniture or stored items were present
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC
2) Some areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
3) The inspector was unable to verify that the glass used in one or more patios was approved safety glass. Glazing located in areas subject to human impact that is not approved safety glass is a safety hazard. Standard building practices require that approved safety glass be used in all railings by a walking surface. Recommend that a qualified contractor evaluate and replace glass if necessary, and per standard building practices.
Photo
Photo 3-1 
4) Flashing appeared to be missing from above one or more deck or porch cover ledger boards, or could not be verified. Missing flashing at this location can cause moisture to accumulate between the ledger boards and the building. Fungal rot may occur in this area and cause the ledger board fasteners to fail. The deck may separate from the building in this event. This is a potential safety hazard. Recommend that a qualified contractor install flashing above ledger boards per standard building practices. For more information, visit:
http://www.reporthost.com/?LB
http://www.reporthost.com/?SD
Photo
Photo 4-1 
5) The risers for stairs at one or more locations varied in height and pose a fall or trip hazard. Risers within the same flight of stairs should vary by no more than 3/8 inch. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 5-1 
Photo
Photo 5-2 
6) One or more sets of stairs were detached. A qualified contractor should repair as necessary.
Photo
Photo 6-1 
Photo
Photo 6-2 
7) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 7-1 
8) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo
Photo 8-1 
Photo
Photo 8-2 
9) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood fiber, Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
10) Soil was in contact with or less than 6 inches from siding or trim. Regardless of what material is used for siding, it should not be in contact with the soil. If made of wood, siding or trim will eventually rot. For other materials, ground or surface water can infiltrate siding or trim and cause damage to the wall structure. Wood-destroying insects are likely to infest and damage the wall structure. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.
Photo
Photo 10-1 
Photo
Photo 10-2 
11) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 11-1 
12) Some nail heads at the composition wood siding were protruding from the wood, or had been nailed in so as to break the surface of the siding, and caulk was missing. Most manufacturers of composition wood siding specify that nail heads should be flush with the surface, and that the surface of the siding should not be broken. If broken, then caulk should be applied to the nail heads to prevent water penetration and subsequent deterioration of the siding. Recommend that a qualified person repair per the siding manufacturer's specifications.
Photo
Photo 12-1 
Photo
Photo 12-2 
13) Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
14) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 14-1 
Photo
Photo 14-2 
Photo
Photo 14-3 
15) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 15-1 
Crawl Space
Table of contents
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Condition of floor substructure above crawl space: Required repairs, replacement and/or evaluation (see comments below)
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Condition of vapor barrier: Not applicable, none installed
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: with vents
16) Evidence of prior water intrusion or accumulation was found in one or more sections of the crawl space. For example, sediment stains on the vapor barrier or foundation, and/or efflorescence on the foundation. Accumulated water is a conducive condition for wood-destroying organisms and should not be present in the crawl space. Recommend that the client review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space. The crawl space should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:
  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, gravity drains and/or sump pump(s) in the crawl space.
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Photo
Photo 16-4 
17) Fungal rot was found at one or more support posts. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 17-1 
Photo
Photo 17-2 
18) One or more support posts were not positively secured to the beam above. While this is common in older homes, current standards require positive connections between support posts and beams above for earthquake reinforcement. Recommend that a qualified contractor repair per standard building practices. For example, by installing metal plates, plywood gussets or dimensional lumber connecting posts and beams.
Photo
Photo 18-1 
Photo
Photo 18-2 
19) No insulation was installed under the floor above the crawl space. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.
Photo
Photo 19-1 
20) No vapor barrier was installed in the crawl space. This is a conducive condition for wood-destroying organisms due to the likelihood of water evaporating from the soil below up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified contractor install a vapor barrier per standard building practices.
21)  One or more indoor crawl space access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency and to prevent dust or odor-laden air from the crawl space entering living spaces.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles, Rolled composition
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Appeared serviceable
22) Flashings at the base of one or more chimneys were substandard. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.

Missing counter flashing
Photo
Photo 22-1 
23) One or more rubber or neoprene pipe flashings were split, cracked and or missing. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor replace flashings where necessary.
Photo
Photo 23-1 
24)  
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Condition of roof structure: Appeared serviceable
Ceiling structure: Ceiling beams
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Condition of roof ventilation: Required repair, replacement and/or evaluation (see comments below)
Roof ventilation type: Open soffit vents
25) One or more sections of roof sheathing in the roof structure were damaged or split. This may significantly weaken the roof structure. Recommend that a qualified contractor repair as necessary.
Photo
Photo 25-1 
Photo
Photo 25-2 
26) One or more attic access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC
27) One or more soffit vents were blocked by insulation. This can reduce air flow through the roof structure or attic and result in reduced service life for the roof surface materials because of high temperatures. Moisture from condensation is also likely to accumulate in the roof structure and/or attic and can be a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary so air flows freely through all vents. For example, by moving or removing insulation and installing cardboard baffles.
Garage or Carport
Table of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Adequate
28) Garage door malfunctioned under standard operations and needed to be closed manually. Recommend that a qualified contractor evaluate and repair or replace opener(s) as necessary.
29) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 100
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Condition of sub-panel(s): Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A: Building exterior
Location of sub-panel #B: Garage
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
30) Panel(s) #A were manufactured by the Zinsco company. These panels and their circuit breakers have a history of problems including bus bars made from aluminum that oxidize and corrode, breakers that don't trip under normal overload conditions, and breakers that appear to be tripped when they're not. This is a potential safety hazard for shock and/or fire. Recommend that a qualified electrician carefully evaluate all Zinsco brand panels and components and make repairs as necessary. Consider replacing Zinsco panels with modern panels that offer more flexibility for new, safer protective technologies like arc fault circuit interrupters (AFCls). For more information, visit:
http://www.reporthost.com/?ZINSCO1
http://www.reporthost.com/?ZINSCO2
Photo
Photo 30-1 
Photo
Photo 30-2 
31) One or more receptacles (outlets) were scorched. The wiring for these receptacles may be damaged due to overheating. Recommend that a qualified electrician replace such receptacles, evaluate related wiring and repair if necessary.
Photo
Photo 31-1 
32) One or more ground fault circuit interrupter (GFCI) receptacles (outlets) wouldn't reset at the kitchen. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
33) One or more electric receptacles (outlets) at the bathroom(s) had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
34) One or more circuit breakers in panel(s) #B were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
Photo
Photo 34-1 
35) No arc fault circuit interrupter (AFCI) breakers were installed for bedroom circuits. These are relatively new devices, and reduce the risk of fire by protecting against overheated or arcing receptacles (outlets) or light fixtures. Consult with a qualified electrician about upgrading circuits to AFCI protection per standard building practices. For more information, visit:
http://www.reporthost.com/?AFCI
36) Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo
Photo 36-1 
Photo
Photo 36-2 Power wire for the furnace
37) One or more electric receptacles (outlets) and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
38) One or more bushings were missing from where wires enter holes in panel(s) #B. This is a potential safety hazard because the wiring insulation can be cut or abraded on the metal edge of the hole(s). Recommend that a qualified electrician install bushings where missing.
Photo
Photo 38-1 
39) One or more knockouts were missing from panel(s) #B. Holes in panels are a potential fire hazard if a malfunction ever occurs inside the panel. Rodents can also enter panels through holes. Recommend that a qualified person install knockout covers where missing and per standard building practices.
Photo
Photo 39-1 
40) One or more wires inside panel(s) #B were loose, and were not terminated. This poses a safety hazard for shock and/or fire. Recommend that a qualified electrician remove any abandoned wiring or repair as necessary. For example, by trimming wires to length and installing wire nuts.
Photo
Photo 40-1 
41) One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 41-1 
42) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.
43) One or more electrical components including switches and/or receptacles appeared to be older than their intended service life. Such old components may pose a fire or shock hazard. Recommend consulting with a qualified electrician to determine which components should be replaced with newer, modern components.
44) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
45) Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 45-1 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Required repair, replacement and/or evaluation (see comments below)
Water service: Public
Location of main water shut-off: Building exterior
Condition of supply lines: Required repair, replacement and/or evaluation (see comments below)
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Condition of fuel system: Required repair, replacement and/or evaluation (see comments below)
Location of main fuel shut-off valve: At gas meter
46) Based on gas odors and/or gas detector readings, gas appeared to be leaking at one or more local shut-off valves. This is an explosion and fire hazard. A qualified contractor and/or the gas utility company should evaluate and repair immediately.

Water heater
47) One or more flexible gas supply connectors were routed through a metal cabinet. Solid iron pipe should be used where gas supply lines are routed through holes in metal cabinets. Continued vibration from this equipment may cause the edge of the metal cabinet to wear through the flexible connector, resulting in gas leaks. This is an explosion and/or fire hazard. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 47-1 
48) Copper water supply pipes were installed. Copper pipes installed prior to the late 1980s may be joined with solder that contains lead, which is a known health hazard especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained approximately 50% lead. The client should be aware of this, especially if children will be using this water supply system. Note that the inspector does not test for toxic materials such as lead. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions include:
  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than 6 hours
  • Install appropriate filters at points of use
  • Use only cold water for cooking and drinking, as hot water dissolves lead more quickly than cold water
  • Use bottled or distilled water
  • Treat well water to make it less corrosive
  • Have a qualified plumber replace supply pipes and/or plumbing components as necessary
For more information visit:
http://www.reporthost.com/?LEADDW
http://www.reporthost.com/?LEAD
49) One or more leaks were found in water supply pipes or fittings. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 49-1 
50) The main water shut-off valve was leaking. Recommend that a qualified plumber repair or replace the valve as necessary.
Photo
Photo 50-1 
51) One or more leaks were found in the shower supply valves. A qualified plumber should repair as necessary.
Photo
Photo 51-1 
52) No sediment trap was installed in the gas supply line at the Water Heater. Sediment traps prevent damage to gas-fired appliances by trapping oil, scale, water condensation and/or debris. Recommend that a qualified contractor install a sediment trap per standard building practices.
Photo
Photo 52-1 
53)  Main line pressure test.
Photo
Photo 53-1 
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Location of water heater: Garage
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Forced air heating system fuel type: Natural gas
Location of forced air furnace: Garage
Condition of forced air ducts and registers: Required repair, replacement and/or evaluation (see comments below)
Condition of burners: Appeared serviceable
Condition of venting system: Required repair, replacement and/or evaluation (see comments below)
54) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
55) The barometric draft damper for the furnace was . This may result in improper drafting and is a potential safety hazard. Recommend that a qualified heating contractor evaluate and repair as necessary.

Corroded, rusty
Photo
Photo 55-1 
56) One or more heating or cooling ducts in an unconditioned space (e.g. crawl space, attic or basement) were not insulated, or the insulation was damaged or deteriorated. This can result in reduced energy efficiency, moisture inside heating ducts, and/or "sweating" on cooling ducts. Recommend that a qualified person repair per standard building practices. For example, by wrapping ducts in insulation with an R-value of R-8.
Photo
Photo 56-1 
Photo
Photo 56-2 
57) The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of under-sink food disposal: Appeared serviceable
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Master bath, first floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
58) The inspector was unable to verify that the glass used in one or more doors by the shower at location(s) #B was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a potential safety hazard. Standard building practices require that approved safety glass be used in enclosures for bathtubs, showers, spas, saunas and steam rooms, and in windows where the bottom edge of the window is less than 60 inches above the drain inlet or standing surface. Wire-reinforced glass is not acceptable. Recommend that a qualified contractor evaluate further to determine if glazing is approved safety glass, and replace glass if necessary, and per standard building practices.
59) The toilet at location(s) #B didn't flush or had a weak flush. Recommend that a qualified plumber evaluate and repair or replace the toilet as necessary.
60) The toilet at location(s) #A and B was loose where it attached to the floor. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
61) The toilet at location(s) #A ran water continuously or didn't shut off after being flushed, and water leaked from the tank into the bowl. Significant amounts of water can be lost through such leaks. If this system uses a septic system, the septic system can be overloaded and cause significant and potentially expensive damage. A qualified person should repair or replace components as necessary.
62) One or more bathtub faucet handles at location(s) #A were loose. Recommend that a qualified person repair or replace handles as necessary.
63) The shower enclosure at location(s) #B was deteriorated, damaged or substandard. Water can damage the wall structure as a result. Recommend that a qualified contractor repair or replace the surround as necessary.
64) The bathtub at location(s) #A was worn, blemished or deteriorated.
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
65) One or more sliding glass doors were difficult to open or close. Recommend that a qualified person maintain, repair or replace door(s) as necessary. Often, cleaning the track and applying a lubricant will help.
66) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.reporthost.com/?ECC
Photo
Photo 66-1 
Photo
Photo 66-2 
Photo
Photo 66-3 


Photo
Photo X-1 
Photo
Photo X-2 
Photo
Photo X-3 
Photo
Photo X-4 
Photo
Photo X-5 
Photo
Photo X-6 
Photo
Photo X-7 
Photo
Photo X-8 
Photo
Photo X-9 
Photo
Photo X-10 
Photo
Photo X-11 
Photo
Photo X-12 
Photo
Photo X-13 
Photo
Photo X-14 
Photo
Photo X-15 
Photo
Photo X-16 
Photo
Photo X-17 
Photo
Photo X-18 
Photo
Photo X-19 
Photo
Photo X-20 
Photo
Photo X-21 
Photo
Photo X-22 
Photo
Photo X-23 
Photo
Photo X-24 
Photo
Photo X-25 
Photo
Photo X-26 
Photo
Photo X-27 
Photo
Photo X-28 
Photo
Photo X-29 
Photo
Photo X-30 
Photo
Photo X-31 
Photo
Photo X-32 
Photo
Photo X-33 
Photo
Photo X-34 
Photo
Photo X-35 
Photo
Photo X-36 
Photo
Photo X-37 
Photo
Photo X-38 
Photo
Photo X-39 
Photo
Photo X-40 
Photo
Photo X-41 
Photo
Photo X-42 
Photo
Photo X-43 
Photo
Photo X-44 
Photo
Photo X-45 
Photo
Photo X-46 
Photo
Photo X-47 
Photo
Photo X-48 
Photo
Photo X-49 
Photo
Photo X-50 
Photo
Photo X-51 
Photo
Photo X-52 
Photo
Photo X-53 
Photo
Photo X-54 
Photo
Photo X-55 
Photo
Photo X-56 
Photo
Photo X-57 
Photo
Photo X-58 
Photo
Photo X-59 
Photo
Photo X-60 
Photo
Photo X-61 
Photo
Photo X-62 
Photo
Photo X-63 
Photo
Photo X-64 
Photo
Photo X-65 
Photo
Photo X-66 
Photo
Photo X-67 
Photo
Photo X-68 
Photo
Photo X-69 
Photo
Photo X-70 
Photo
Photo X-71 
Photo
Photo X-72 
Photo
Photo X-73 
Photo
Photo X-74 
Photo
Photo X-75 
Photo
Photo X-76 
Photo
Photo X-77 
Photo
Photo X-78 
Photo
Photo X-79 
Photo
Photo X-80 
Photo
Photo X-81 
Photo
Photo X-82 
Photo
Photo X-83 
Photo
Photo X-84 
Photo
Photo X-85 
Photo
Photo X-86 
Photo
Photo X-87 
Photo
Photo X-88 
Photo
Photo X-89 
Photo
Photo X-90 
Photo
Photo X-91 
Photo
Photo X-92 
Photo
Photo X-93 
Photo
Photo X-94 
Photo
Photo X-95 
Photo
Photo X-96 
Photo
Photo X-97 
Photo
Photo X-98 
Photo
Photo X-99 

IMPORTANT AGREEMENTS AND LIMITATIONS
SPECIAL NOTE: THE FOLLOWING IS NOT INCLUDED IN THIS INSPECTION: 1. WATER OR
AIR QUALITY 2. PRESENCE OF TOXIC OR CARCINOGENIC MATTER EMITTED FROM THE
GROUND, BUILDING MATERIALS, IN WATER OR AIR SUPPLY OR FROM THE OPERATION OF
ANY EQUIPMENT 3. ITEMS THAT ARE OBSTRUCTED, INACCESSIBLE OR NOT IN PLAIN VIEW. -
The Client is hereby informed that structural and mechanical insurance is available for a nominal fee
from insurance companies. Your real estate agent may be able to help you with obtaining structural
or mechanical insurance coverage. The client understands that the Comments and Notations made
on this report are subjective opinion of the inspector based on observations at the time of inspection.
Therefore, the INSPECTOR desires it be clearly understood he offers NO WARRANTY concerning
future operation or condition of any item inspected - OR - that all defects of such items were observed
at the time of inspection and noted on the report. THEREFORE, the INSPECTOR does not imply that
he warrants or guarantees any item regardless whether they were inspected or reported.
1. What We Do:
a. All inspections are performed in accordance with Standards of Practice. The inspection is of conditions
which are present and visible at the time of the inspection. All mechanical and electrical equipment, systems,
and appliances are operated in normal modes and operating range at the time of the inspection.
b. We shall observe, render an opinion and report which of the parts, components and systems are
not functioning at the time of the inspection or are in need of repair and report on visible existing or
recognized hazards.
c. If you have questions, we will explain what we saw about the item.
2. What We Do Not Do:
a. We do not make guarantees, warranties, representations, or insure the future performance or condition
of any item. If you want a warranty, guarantee, or insurance policy, you must obtain it from a warranty or
insurance company. Please remember that almost every item in any pre-owned home is in used condition
and has ordinary wear and tear, and all houses will change and deteriorate in the future. WE DISCLAIM
ALL OTHER WARRANTIES.
b. We do not inspect any item which we cannot see in a normal inspection. For example, we do not
move furniture, rugs, carpet, paintings, appliances or other furnishings in performing an inspection. We do
not uncover buried pipes or items. We cannot see items covered by wallpaper, flooring or plants. Repairs
or remodeling may hide evidence of prior damage or defects. We do suggest that you ask the seller about
repairs that are covered up or any previous problems because we DO NOT report on past conditions that
appear corrected. We do not inspect for latent defects, therefore, you should obtain a copy of the sellers
disclosure statement.
c. We do not inspect for building codes, soil analysis, adequacy of design, capacity, efficiency size, value,
floor plain location, pollution, habitability, environmental hazards such as asbestos, UFFI, EMF, lead base
paint, etc. Please remember older homes do not meet the same standards as newer homes, even though items in
both may perform the function for which they are intended.
d. We do not allow the inspector to change or add to these printed provisions in any way.
e. We do not hold ourselves to be specialists for any particular item or engineers. We are a general real
estate improvement inspection company. If we report an item is not performing its intended function, needs
repair, or shows evidence of prior damage, we urge you to have that item examined by a specialist before
purchasing the house. We do not and cannot give cost estimates to repair any item.
3. What You Must Do:
a. If you have any complaints about our inspection, you must notify us in writing within seven days
after you discovered any problem, and allow us to reinspect before changing the condition on the item,
except in an emergency.
b. If we report an item is in need of immediate repair, or is not performing its intended function or shows
past damage and you intend to purchase the property anyway, you should first have the item re-inspected by a
specialist in that field (i.e. foundation - structural engineer//plumbing - plumber).
c. You agree that, to the extent allowed by law, any damages for breach of this contract or report are limited
to the amount of the inspection fee only.
d. If you sue on this inspection, but do not prevail, you agree to pay all our reasonable attorney?s fees.
e. You represent to us that (1) the inspector has not made any oral representations that are different from,
or in addition to, what is written in this report, and (2) you agree to each provision of this report by relying
on it any any way, whether or not you sign it.
f. You shall not allow anyone else to use or rely on this report without prior written consent.
THIS REPORT CANNOT AND DOES NOT REPRESENT THE OPERATION OR CONDITION OF ANY ITEM AFTER THE
DATE AND TIME OF THIS INSPECTION. ALL WARRANTIES, EXPRESSED OR IMPLIED ARE DISCLAIMED.