View as PDF

View summary

Logo

Oasis Inspections LLC

chris@oasisinspect.com
(970) 946-2877
Inspector: Chris Bolos

Property Inspection Report

Client(s):  Jane and John Doe
Property address:  321 Any Street
Castle Valley, Utah 84532
Inspection date:  Monday, August 16, 2021

This report published on Saturday, October 9, 2021 12:46:00 PM MDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeServiceableItem or component is in serviceable condition
Concern typeCommentFor your information
Concern typeInfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Radon Test
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary

General InformationTable of contents
Time started: 10:00
Time finished: 12:30
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Hot
Inspection fee: $735
Payment method: Invoiced
Type of building: Single family, Shop
Buildings inspected: One house, One detached garage
Number of residential units inspected: 1
Age of main building: 25
Source for main building age: Municipal records or property listing
Front of building faces: North
Main entrance faces: South
Occupied: No
1) Evidence of rodent activity was found in the form of feces in the garage. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.reporthost.com/?SEALUP
http://www.reporthost.com/?TRAPUP
http://www.reporthost.com/?CLEANUP
Photo
Photo 1-1 Rodent feces were found behind stored items in garage.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete, Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
2) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, patios and sidewalks, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 2-1 Concrete was deteriorating at front sidewalk.
Photo
Photo 2-2 Broken concrete at driveway.
Photo
Photo 2-3 Cracking found at patio on side of house.
Photo
Photo 2-4 Cracking at detached patio. At a minimum, recommend sealing cracks to prevent water infiltration and further deterioration. Numerous products exist to seal such cracks including hydraulic cement, resilient caulks and epoxy sealants.
3) A hot tub was found on the property. These are specialty items and are beyond the scope of this inspection. Any comments made are as a courtesy only.
Recommend evaluation by a pool/hot tub/spa professional.
Photo
Photo 3-1 Hot tub appeared to be serviceable.
Photo
Photo 3-2 Breaker panel with GFCI breakers was installed near hot tub. Breakers were tested and functional.
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade, Concrete garage slab
Foundation/stem wall material: Concrete slab on grade
4) Conducive conditionsCracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo
Photo 4-1 Minor damage to stucco found above garage.
Photo
Photo 4-2 Holes in stucco finish should be patched to prevent water infiltration and further damage. Numerous stucco repair products exist.
5) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 5-1 Wall penetration at lineset for HVAC had gaps around it. Recommend sealing to prevent vermin infiltration.
6) Conducive conditionsThe paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 6-1 Peeling paint was found at door jambs and casings at exterior doors.
Photo
Photo 6-2 Door at N side of house.
Photo
Photo 6-3 Detached garage door.
Limitations: Radon Testing does not warrant the accuracy of the effectiveness of the program administered and designed by the IEMA/EPA. Oasis Inspections LLC. will provide the client with results of the analysis, but makes no warranties and assumes no liabilities as to the effectiveness in determining whether the levels of radon in the home have been harmful. Radon test only measures the radon present at the specific location and specific time the detectors are in place. Oasis Inspections LLC cannot be assured that the necessary conditions were maintained through out the test period. There can be uncertainty with any radon measurement due to statistical variations and other factors such as the operation of the building and weather conditions the levels of radon can be higher or lower depending on the weather conditions.

While we make every effort to maintain the highest possible quality control and include checks and verification steps in our procedures, we make NO WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, for the consequences of erroneous test results. Neither Oasis Inspections LLC. or its employees or agents shall be liable under any claim or charge in any form or any loss or cost, fees or damages of any nature of kind arising out of, resulting form or connected with, or sustained as a result of any radon test.

This radon test is a screening that serve to indicate the potential for radon levels in the referenced building. It will provide information needed to determine if an additional action or testing is needed. Test conditions: Per the Division of Nuclear safety and the United States EPA, certain conditions must be met prior to and during the test period.

Limitations of Tests: You understand that our control of these conditions are limited to the actual placement of the testing device. Any tampering or manipulation of the test conditions prior to or during the test period are out of our control. Changes in heating and ventilation may raise or lower radon levels. Inclement weather such as storms or high winds can contribute to unreliable test results. The test results are only an average of radon concentration in the area tested during the period the measurement device was exposed. A low level of radon achieved on a short-term test does not necessarily mean that the levels that are below the 4.0 pCi/L action Level. Radon levels may be significantly higher. There is no safe level of radon.

I.E.M.A. suggest regular follow up measurement be made on a Biannual basis ((every Two years) or sooner if any structural changes or renovations to the house have been made.

For more information on radon gas, please visit: https://www.epa.gov/sites/production/files/2015-05/documents/hmbuygud.pdf
7) A reading of 1.43 pCi/L was found after a 48 hr test. This is under the EPA's recommended action level of 4.0 pCi/L. ***No action recommended***
Photo
Photo 7-1 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Partially traversed, Viewed from eaves on ladder
Condition of roof surface material: Appeared serviceable
Roof surface material: Metal panel
Roof type: Gable
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable, Limited evaluation due to little or no rainfall during and prior to the inspection
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Vapor retarder: Installed
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents, Enclosed soffit vents
Garage or CarportTable of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached, Garage
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
8) Automatic door opener was inoperable. Recommend that a qualified contractor evaluate and repair or replace opener(s) as necessary.
Photo
Photo 8-1 Door opener was not functioning, although it appeared there was power to unit.
Photo
Photo 8-2 Recommend checking wire connections at opener and control button.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main service panel #B: Shop
Location of main disconnect: Breaker at top of main service panel, At main disconnect panel outside
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes
9) One or more ground fault circuit interrupter (GFCI) receptacles (outlets) wouldn't trip at the kitchen. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 9-1 GFCI outlet at kitchen counter would not trip.
10) Some outlets were showing a hot/ground reverse with a test instrument. This may also indicate that there is a disconnected neutral somewhere upstream of receptacles in the wiring. This is potentially a shock hazard. Recommend that a qualified electrician evaluate and repair as necessary
Photo
Photo 10-1 Hot/Ground reverse was found on test instrument at outlets.
Photo
Photo 10-2 Outlets along brick wall in main living area had Hot/Ground reverse.
Photo
Photo 10-3 Outlet on brick wall.
Photo
Photo 10-4 Hot/Ground reverse indicated at exterior GFCI outlet near rear door.
11) Smoke alarms were missing, damaged, or missing components. Smoke alarms should be replaced as necessary. For more information, visit:
http://www.reporthost.com/?SMKALRM
Photo
Photo 11-1 Many smoke alarms in home were removed.
Photo
Photo 11-2 
Photo
Photo 11-3 
12) One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 12-1 Many fixtures in home appeared to have burned out light bulbs.
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Building exterior
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Type of irrigation system supply source: Private well
Condition of fuel system: Required repair, replacement and/or evaluation (see comments below)
Visible fuel storage systems: propane tank, in yard
Location of main fuel shut-off valve: At propane tank
13) One or more flexible gas supply connectors were routed through metal furnace cabinet. Solid iron pipe should be used where gas supply lines are routed through holes in metal cabinets. Continued vibration from this equipment may cause the edge of the metal cabinet to wear through the flexible connector, resulting in gas leaks. This is an explosion and/or fire hazard. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 13-1 Flexible gas line was run through metal cabinet at furnace.
Photo
Photo 13-2 Flexible gas appliance connector was improperly installed at gas furnace. Black iron pipe should be installed inside cabinet and stubbed out, then attached to gas appliance connector.
14) Significant corrosion was found in some water supply pipes or fittings. Leaks can occur as a result. Recommend that a qualified plumber evaluate and replace components as necessary.
Photo
Photo 14-1 Corrosion found at water filter fitting in laundry room mechanical closet.
Photo
Photo 14-2 Corrosion at valves under kitchen sink.
Photo
Photo 14-3 Corrosion at under sink water filter.
15) Based on visible equipment or information provided to the inspector, this property appeared to have a yard irrigation (sprinkler) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. When this system is operated, recommend verifying that water is not directed at building exteriors, or directed so water accumulates around building foundations. Sprinkler heads may need to be adjusted, replaced or disabled. Recommend that a qualified plumber verify that a backflow prevention device is installed per standard building practices to prevent cross-contamination of gray water and potable water, and install an expansion tank at the water heater if missing and necessary. Recommend that a qualified specialist evaluate the irrigation system for other defects (e.g. leaks, damaged or malfunctioning sprinkler heads) and repair if necessary.
Photo
Photo 15-1 
16) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC
Photo
Photo 16-1 
17) This property was unoccupied and the plumbing system has not been in continuous operation recently. It's possible for plumbing leaks to exist but not be apparent. Leaks can be small and take time to become visible. The inspector normally operates all accessible and operable plumbing fixtures, but this limited inspection may not reveal small leaks that only become visible after constant use of the plumbing system. After taking occupancy, monitor the plumbing system for leaks that may become apparent. Areas below the house should be evaluated after plumbing has been operated to check for leaks. Any problems that are found should be repaired by a qualified plumber.
18) Based on visible equipment or information provided to the inspector, the water supply to this property appeared to be from a private well. Private well water supplies are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible and accessible components are evaluated. Recommend the following:
  • That a qualified well contractor fully evaluate the well, including a pump/flow test
  • That the well water be tested per the client's concerns (coliforms, pH, contaminants, etc.)
  • Research the well's history (how/when constructed, how/when maintained or repaired, past performance, past health issues)
  • Document the current well capacity and water quality for future reference
For more information, visit:
http://www.reporthost.com/?WELL
Photo
Photo 18-1 Well head was located at rear of house. Submersible pump had been recently replaced.
Photo
Photo 18-2 Vault was located near well head.
Photo
Photo 18-3 Pressure tank and other equipment in vault appeared serviceable.
Photo
Photo 18-4 Pre-cut foam insulation board should be placed on brackets to prevent well system components from freezing. Insulation board was not installed at the time of inspection, but was found inside storage room at detached shed/garage.
19) A water softener system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Water softeners typically work by removing unwanted minerals (e.g. calcium, magnesium) from the water supply. They prevent build-up of scale inside water supply pipes, improve lathering while washing, and prevent spots on dishes. Recommend consulting with the property owner about this system to determine its condition, required maintenance, age, expected remaining life, etc. For more information, visit:
http://www.reporthost.com/?WTRSFT
http://www.reporthost.com/?HRDWTR
Photo
Photo 19-1 
20) A water filtration system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Filter cartridges typically need replacing periodically. Cleaning and other maintenance may also be needed. Recommend consulting with the property owner about this system to determine its condition, required maintenance, age, expected remaining life, etc. For more information, visit:
http://www.reporthost.com/?WTRFLTR
Photo
Photo 20-1 Water filters were found near water heater and under kitchen sink.
Photo
Photo 20-2 
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 5
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Laundry room
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 103°
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace, Wood-burning fireplace or stove
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Required repair, replacement and/or evaluation (see comments below)
Forced air heating system fuel type: Propane
Estimated age of forced air furnace: 25
Location of forced air furnace: Laundry room
Forced air system capacity in BTUs or kilowatts: 100,000
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): Behind return air grill(s)
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Required repair, replacement and/or evaluation (see comments below)
Type of combustion air supply: Vented door
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Condition of controls: Appeared serviceable
Type of combustion air supply: Vent(s) to exterior, Vented door
21) The furnace did not respond to normal controls (thermostat). It appeared to be inoperable. The inspector was only able to perform a limited evaluation. If possible, consult with the property owner and/or review documentation on this system. Recommend that a qualified HVAC contractor evaluate and repair as necessary.
Photo
Photo 21-1 Furnace burners did not light when thermostat was switched to HEAT and a call for heat was initiated. No trouble codes were observed.
22) Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 22-1 HVAC filter was located behind grill enclosure near front door. -
23) Air conditioning system including coil and condenser appeared to be added to existing furnace and ducting in 2016. A/C was tested and serviceable.
Photo
Photo 23-1 
24) The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be near this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo
Photo 24-1 Furnace age appeared to be 25 years.
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning stove type: Freestanding, Pellet stove
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Metal
25) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 25-1 Pellet stove appeared to be in serviceable condition.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of under-sink food disposal: Required repair, replacement and/or evaluation (see comments below)
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: None visible
Condition of refrigerator: Appeared serviceable
26) Kitchen sink faucet handle was broken. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 26-1 Faucet handle was broken.
27) The under-sink food disposal was noisy or vibrated excessively. Recommend that a qualified contractor repair or replace as necessary.
Photo
Photo 27-1 Disposal appeared to be old and was loud during operation.
28) Substandard repairs were found at the sink drain (e.g. tape, sealant, non-standard components). Recommend that a qualified plumber repair per standard building practices.
Photo
Photo 28-1 Taped outlet and deposits found on drain pipe under sink.
29) Cabinet hardware such as hinges, latches, closers, magnets or pulls were loose, missing or damaged at one or more cabinet drawers, doors or turntables. Recommend that a qualified person repair as necessary.
Photo
Photo 29-1 Some cabinet doors were loose when opened and closed.
Photo
Photo 29-2 
Photo
Photo 29-3 Screws at some door hinges were loose.
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Powder room
Location #B: Master bath
Location #C: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
30) The hot and/or cold water supply flow for the sink at location(s) #B was low or inoperable. Recommend that a qualified plumber evaluate and repair as necessary.
Photo
Photo 30-1 Master bathroom sinks had low flow.
Photo
Photo 30-2 Filter screens may be clogged.
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Metal
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl, Multi-pane
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Tile
31) Glass in one or more windows was cracked, broken and/or missing. Recommend that a qualified contractor replace glass where necessary.
Photo
Photo 31-1 Glass at bedroom window in front was cracked.
Photo
Photo 31-2 
32) Tile, stone and/or grout in the flooring in one or more areas was deteriorated (e.g. loose or cracked tiles, missing grout) or substandard. If in a wet area, water can damage the sub-floor. Recommend that a qualified contractor repair as necessary.
Photo
Photo 32-1 Grout was missing and some cracked tiles were found in hallway near front door.
Photo
Photo 32-2 Deteriorated/missing grout found.
Photo
Photo 32-3 Cracked tile and missing grout found.
Photo
Photo 32-4 
33) One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.
Photo
Photo 33-1 Master bedroom door would not latch.
Photo
Photo 33-2 Door was also binding in jamb. Recommend that a qualified person repair as necessary. For example, by trimming doors.
Photo
Photo 33-3 Closet door in hallway also would not latch.
34) A central vacuum system was installed in home. These are specialty items and are beyond the scope of this inspection. Any comments made are as a courtesy only
Photo
Photo 34-1 Vacuum was tested and appeared to be serviceable.
Photo
Photo 34-2 
Wood Destroying Organism FindingsTable of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: Yes
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: Yes
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: Yes
Evidence of prior treatment of wood-destroying insects: No evidence of prior termite treatment was apparent.
Location #A: Detached garage/shop
35) InfestationEvidence of past infestation of drywood termites was found at location(s) #A in the form of galleries or holes in wood with visible wood damage. Recommend the following:[list]
  • Correct any conducive conditions for wood-destroying organisms mentioned in this report.
  • Consult with the property owner about any history of infestation.
  • Have a state-licensed pest control operator evaluate further and treat as necessary.
Photo
Photo 35-1 Conducive conditions for wood destroying organisms found at wood surrounding base of detached garage/shop.
Photo
Photo 35-2 Wood surrounding base of structure was in contact with surrounding soil.
Photo
Photo 35-3 Wood most found found appeared to be non structural and may have been leftover forms for concrete.
Photo
Photo 35-4 Past termite damage was found at N side of structure.
Photo
Photo 35-5 Structural posts were in contact with soil. This is a conducive condition for wood destroying organisms. Pressure treated wood is typically rated for 25 year contact with soil, but the cut ends hidden below grade may not have been treated and can rot quickly. Support posts should be elevated above grade on concrete piers or footings, and be separated from the concrete by metal brackets or an impermeable membrane such as shingle scraps. For other components, soil should be graded and/or removed to maintain these clearances if possible. Otherwise, replacing non-treated wood with treated wood, or installing borate-based products such as Impel rods may help to prevent infestation and damage. For more information, visit:
https://www.reporthost.com/?IMPEL
Photo
Photo 35-6 Wood to soil contact in detached garage.

Thank you for using Oasis Inspections!