Property Inspection Report

Client(s):  Paul Radar
Property address:  33150 Shorebird Ave
Anchor Point AK 99556
Inspection date:  Monday, May 14, 2018

This report published on Monday, May 14, 2018 10:20:17 PM AKDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Primary Shutoffs

View summary


General Information
Return to table of contents

Report number: 18-0512B
Time started: 4:30
Time finished: 7:30
Present during inspection: Client
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Payment method: Cash
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Front of building faces: East
Main entrance faces: Northwest
Occupied: No

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Gravel
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood

1) Ledger boards for one or more decks, balconies or porches appeared to be attached with nails only. This method of attachment is substandard and may result in such structures separating from the main building. This is a potential safety hazard. Modern standards call for ledger boards to be installed with 1/2 inch lag screws or bolts into solid backing. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 1-1
Photo
Photo 1-2
Photo
Photo 1-3
Photo
Photo 1-4

2) The corner post on the entry porch is too high, creating an uneven deck surface. This may be a result of the post not being installed to a depth that prevents the effect of frost heaving. I recommend modifying the post with an adjustable post bracket to allow adjustment now and when necessary in the future.
Photo
Photo 2-1
 

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground, from a ladder
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space, Concrete pilings

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Solid wood joists, Engineered wood joists
Condition of vapor barrier: Appeared serviceable
Vapor barrier present: Yes, Full
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: Unconditioned space

3) One or more support posts were not positively secured to the beam above. While this is common in older homes, current standards require positive connections between support posts and beams above for earthquake reinforcement. Recommend that a qualified contractor repair per standard building practices. For example, by using the appropriate fasteners in the brackets that have been installed at each post.
Photo
Photo 3-1
Photo
Photo 3-2
Photo
Photo 3-3
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Metal panel
Roof type: Shed

4) A roof flashing was lapped incorrectly. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary. For example, by re-installing the lower piece of trim under the upper piece of trim so that water will go over it, instead of under.
Photo
Photo 4-1
 

5) All three rubber or neoprene pipe flashings were loose or lifting. Leaks can result from windblown rain or snow accumulation. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary to prevent leaks. For example, by replacing or securing flashings as necessary and sealing per vent boot manufactures recommendations.

Devices known as crickets should be installed up-slope of all roof penetrations on a metal roof to divert snow and ice around the vent stacks in the future. See figure 5-4 for an example.

Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
Photo
Photo 5-4

6) Gutters and downspouts were missing throughout. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Consider adding rain water escapement systems in the future to minimize the effects of water damage to the structure.

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Spray polyurethane foam
Approximate attic insulation R value (may vary in areas): R-38

7) No accessible attic spaces were found or inspected at this property. The inspector attempts to locate attic access points and evaluate attic spaces where possible. When a home is occupied, such access points may be obscured by stored items or furnishings. Home inspection standards of practice do not require inspectors to move stored items, furnishings or personal belongings. If such access points are found in the future and/or made accessible, a qualified person should fully evaluate those attic spaces and roof structures.

8) From over-spray at the eaves, along the gable, and at the ridge, it appears that a closed cell insulation system has been used in the roof, and if the rafter bays are filled, a R value of greater than 38 would be present. See diagram 8-1 of an example of a closed cell roof system.
Photo
Photo 8-1
 

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod in soil
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Entry
Location of main disconnect: At main disconnect panel outside
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested

9) One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the kitchen and full bath wouldn't trip when tested and/or wouldn't trip with a test instrument. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 9-1
Photo
Photo 9-2

10) One or more electric receptacles at the exterior and/or crawl space had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
Photo
Photo 10-1
Photo
Photo 10-2
Photo
Photo 10-3
Photo
Photo 10-4

11) Wire splices were exposed and were not contained in a covered junction box. This is a potential shock or fire hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing permanently mounted junction boxes with cover plates where needed to contain wiring splices.
Photo
Photo 11-1
Photo
Photo 11-2

12) One or more cover plates for switches, receptacles, light fixtures or junction boxes were missing. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 12-1
Photo
Photo 12-2
Photo
Photo 12-3
Photo
Photo 12-4
Photo
Photo 12-5
 

13) One or more electric receptacles appeared to have no power. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician evaluate and repair.
Photo
Photo 13-1
 

14) Extension cords were being used as permanent wiring in the master bedroom. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate or needs updating. Extension cords may also be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend discussing the purpose with the homeowner, and if it is not essential, to disconnect. If it is essential, I recommend a qualified electrician add an appropriate power source/connection.

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Crawl space
Condition of supply lines: Appeared serviceable
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Required repair, replacement and/or evaluation (see comments below)
Vent pipe material: Plastic
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter

15) One vent stack has been broken by snow load at the roof line. I recommend that a qualified individual repairs the break, for example, with a coupling.
Photo
Photo 15-1
Photo
Photo 15-2

16) See roof section for comment on pipe vents boots.

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Closet

17) The water heater did not have earthquake straps or struts installed. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person install earthquake straps or struts as necessary and per standard building practices.
Photo
Photo 17-1
 

18) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be near this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Gas stoves
General heating distribution type(s): None, individual heaters
Condition of controls: Appeared serviceable

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range: Required repair, replacement and/or evaluation (see comments below)
Range type: Natural gas
Type of ventilation: Built into microwave over range but recirulating.
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Required repair, replacement and/or evaluation (see comments below)

19) The range could tip forward. An anti-tip bracket may not be installed. This is a potential safety hazard since the range can tip forward when weight is applied to the open door, such as when a small child climbs on it or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free-standing ranges since 1985. Recommend installing an anti-tip bracket to eliminate this safety hazard.

20) The exhaust fan over the range recirculated the exhaust air back into the kitchen. This may be due to no duct being installed, baffles not being installed, or problems with duct work. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. Recommend that a qualified contractor evaluate and repair as necessary so exhaust air is ducted outdoors.
Photo
Photo 20-1
 

21) The microwave oven was inoperable. Recommend that a qualified person evaluate and repair or replace as necessary.
Photo
Photo 21-1
 

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: 3/4 bath, Master bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Fiberglass or vinyl
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl, Multi-pane, Sliding, Single-hung, Fixed
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall, Wood
Ceiling type or covering: Drywall
Condition of flooring: Appeared servicable
Flooring type or covering: Wood or wood products
Condition of stairs, handrails and guardrails: Appeared serviceable

22) Condensation or staining was visible between multi-pane glass in one or more windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo
Photo 22-1
 

Primary Shutoffs
Return to table of contents


23) Electrical Service Main
Photo
Photo 23-1
 

24) Water Main
Photo
Photo 24-1
Photo
Photo 24-2
Photo
Photo 24-3
Photo
Photo 24-4

25) Natural Gas Main Shutoff
Photo
Photo 25-1
 

26) Primary Septic/Sewer Cleanout
Photo
Photo 26-1
Photo
Photo 26-2


Photo
Photo X-1
Photo
Photo X-2
Photo
Photo X-3
Photo
Photo X-4
Photo
Photo X-5
Photo
Photo X-6
Photo
Photo X-7
Photo
Photo X-8
Photo
Photo X-9
Photo
Photo X-10
Photo
Photo X-11
Photo
Photo X-12
Photo
Photo X-13
Photo
Photo X-14
Photo
Photo X-15
Photo
Photo X-16
Photo
Photo X-17
Photo
Photo X-18
Photo
Photo X-19
Photo
Photo X-20
Photo
Photo X-21
Photo
Photo X-22
Photo
Photo X-23
Photo
Photo X-24
Photo
Photo X-25
Photo
Photo X-26
Photo
Photo X-27
Photo
Photo X-28
Photo
Photo X-29
Photo
Photo X-30
Photo
Photo X-31
Photo
Photo X-32
Photo
Photo X-33
Photo
Photo X-34
Photo
Photo X-35
Photo
Photo X-36
Photo
Photo X-37
Photo
Photo X-38
Photo
Photo X-39
Photo
Photo X-40
Photo
Photo X-41
Photo
Photo X-42
Photo
Photo X-43
Photo
Photo X-44
Photo
Photo X-45
Photo
Photo X-46
Photo
Photo X-47
Photo
Photo X-48
Photo
Photo X-49
Photo
Photo X-50
Photo
Photo X-51
Photo
Photo X-52
Photo
Photo X-53
Photo
Photo X-54
Photo
Photo X-55
Photo
Photo X-56
Photo
Photo X-57
Photo
Photo X-58
Photo
Photo X-59
Photo
Photo X-60
Photo
Photo X-61
Photo
Photo X-62
Photo
Photo X-63
Photo
Photo X-64