Property Inspection Report

Client(s):  Ty Carter
Property address:  4161 Marlton Avenue
Los Angeles Ca 90008
Inspection date:  Friday, November 9, 2018

This report published on Saturday, November 10, 2018 9:34:19 AM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Dear customer:

Thank you for choosing KS Home Inspections to perform the following inspection on the property you wish to purchase.
This report is the exclusive property of KS Home Inspections and the individual/s paying for the inspection fee and report. Use of this report by any unauthorized persons is prohibited.

All findings should be made to KS Home Inspections.

This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.

We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, see paint peeling off Walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.

While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.

This inspection report was prepared in a format specifically for the individual/s paying for the inspections fee and report and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the individual/s paying for inspections fee and report and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.

If you have any questions regarding this report, please feel free to call us.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundations
Crawl Spaces
Roofs
Attics and Roof Structures
Garages and Carports
Electric
Plumbing / Fuel Systems
Water Heaters
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interiors, Doors and Windows

View summary

General Information
Table of contents
Time started: 12:00 PM
Time finished: 3:45 PM
Present during inspection: Client, Tenant, Realtor
Client present for discussion at end of inspection: No
Inspector: Ken Steverson
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Ground condition: Dry
Recent weather: Dry (no rain)
Overnight temperature: Cool
Inspection fee: 800.00
Payment method: Check
Number of residential units inspected: 6
Age of main building: 1950
Source for main building age: Municipal records or property listing
Front of building faces: East
Location or alternate name for unit 1: A
Location or alternate name for unit 2: B
Location or alternate name for unit 3: C
Location or alternate name for unit 4: D
Location or alternate name for unit 5: E
Location or alternate name for unit 6: F
1) Units 1, 2, 3, 4, 5 and/or 6 were occupied and/or contained furniture, stored items and/or debris. As a result, some areas were obscured, hidden or inaccessible. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.

See Interior Photos
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveways and parking areas: Appeared serviceable
Driveways and parking areas material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior and Foundations
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Stucco
Condition of foundations and footings: Appeared serviceable
Apparent foundation types: Crawl space
Foundation/stem wall material: Concrete block, Post and pier construction, no stem wall
Footing material (under foundation stem walls): Poured in place concrete
2) Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo
Photo 2-1 
Photo
Photo 2-2 
Photo
Photo 2-3 
Photo
Photo 2-4 
Photo
Photo 2-5 
Photo
Photo 2-6 
Photo
Photo 2-7 
Photo
Photo 2-8 
Photo
Photo 2-9 
Photo
Photo 2-10 
3) Chipping paint was noted on the structures trim and window muntins. Recommend repainting trim and resealing and painting window muntins as necessary.
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
Photo
Photo 3-4 
Photo
Photo 3-5 
Photo
Photo 3-6 
Photo
Photo 3-7 
Photo
Photo 3-8 
4) Exterior Photos
Photo
Photo 4-1 
Photo
Photo 4-2 
Photo
Photo 4-3 
5)  Recommend replacing bath tub repair access ad the exterior of Unit D.
Photo
Photo 5-1 
Crawl Spaces
Table of contents
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Pier or support post material: Concrete, Concrete block
Beam material: Built-up wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Insulation material underneath floor above: None visible
Condition of vapor barrier: Not applicable, none installed
Vapor barrier present: None visible
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: Unconditioned space
6) No under-floor insulation was installed in the crawl space. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.
Photo
Photo 6-1 
7) No vapor barrier was installed in the crawl space. This is a conducive condition for wood-destroying organisms due to the likelihood of water evaporating from the soil below up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified contractor install a vapor barrier per standard building practices.
8) Crawlspace Photos
Photo
Photo 8-1 
Photo
Photo 8-2 
Photo
Photo 8-3 
Photo
Photo 8-4 
Photo
Photo 8-5 
Photo
Photo 8-6 
Photo
Photo 8-7 
Photo
Photo 8-8 
Photo
Photo 8-9 
Photo
Photo 8-10 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof type: Hipped
Apparent number of layers of roof surface material: Multiple
Condition of exposed flashings: Appeared serviceable
9) All Vents over 3 inches in diameter should have a rain cap. Recommend installation.
Photo
Photo 9-1 
10) Nail heads were exposed at one or more shingles. More than just a few exposed nail heads may indicate a substandard roof installation. Recommend applying an approved sealant over exposed nail heads now and as necessary in the future to prevent leaks.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
11) This asphalt or fiberglass composition roof surface appeared to have two or more layers of shingles. Additional layers of composition shingles typically last only 80% of their rated life, and the shingle manufacturer's warranty may be voided. The client should be aware that all layers of roofing will need to be removed when this roof surface needs replacing.
Photo
Photo 11-1 
Photo
Photo 11-2 
12) Roof Photos
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
Photo
Photo 12-5 
Photo
Photo 12-6 
Photo
Photo 12-7 
Photo
Photo 12-8 
Photo
Photo 12-9 
Photo
Photo 12-10 
Attics and Roof Structures
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Mineral wool loose fill
Vapor retarder: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Enclosed soffit vents
13) The roof decking is composed of shingles which was common place at the time of construction. The shingle decking is known to leak over time. Dark spots in the roofs decking are evidence of past water intrusion. Recommend changing the roof decking next time the roof is reshingled.
Photo
Photo 13-1 
14) Attic Photos
Photo
Photo 14-1 
Photo
Photo 14-2 
Photo
Photo 14-3 
Photo
Photo 14-4 
Photo
Photo 14-5 
Garages and Carports
Table of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Condition of garage vehicle doors: Appeared serviceable
Types of garage vehicle doors: Tilt
Condition of garage interiors: Appeared serviceable
Ventilation in garages: Exists
15) The garage has 6 parking spots with 3 garage doors. Not all tenants have cars and use the garage area. Some garage door remotes were unavailable. The garage doors were manually checked for functionality.
Photo
Photo 15-1 
Photo
Photo 15-2 
Photo
Photo 15-3 
Photo
Photo 15-4 
Photo
Photo 15-5 
Photo
Photo 15-6 
Photo
Photo 15-7 
Photo
Photo 15-8 
Photo
Photo 15-9 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Typical service voltage (volts): 120
Typical estimated service amperage: 75
Typical primary service overload protection type: Circuit breakers
Typical service entrance conductor material: Stranded copper
Typical main disconnect rating (amps): Not applicable, no single main disconnect
Typical system ground: Not determined, not readily apparent
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: copper
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
16) Electric panel(s) at unit(s) 1, 2, 3, 4, 5 and/or 6 had circuit breakers manufactured by the Zinsco company. These circuit breakers have a history of problems including not tripping under normal overload conditions and appearing to be tripped when they're not. This is a potential safety hazard for shock and/or fire. Recommend that a qualified electrician carefully evaluate all panels with Zinsco brand circuit breakers and make repairs as necessary. Consider replacing panels with Zinso brand circuit breakers with modern panels that offer more flexibility for new, safer protective technologies like arc fault circuit interrupters (AFCls). For more information, visit:
http://www.reporthost.com/?ZINSCO1
http://www.reporthost.com/?ZINSCO2
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
17) Federal Pacific Electric company electrical panels were noted in the structures main electrical panel. There is significant evidence that both double and single pole versions of these circuit breakers fail by not tripping when they are supposed to. However, in 2011 the Consumer Products Safety Commission (CPSC) closed an investigation into this product because they did not have enough data to establish that the circuit breakers pose a serious risk of injury to consumers. Regardless, and due to other evidence of safety issues, recommend that a qualified electrician carefully evaluate all Federal Pacific panels and make repairs as necessary. Consider replacing Federal Pacific panels with modern panels that offer more flexibility for new, safer protective technologies like ground fault circuit interrupters (GFCls) and arc fault circuit interrupters (AFCls). For more information, visit:
http://www.reporthost.com/?FP1
http://www.reporthost.com/?FP2
http://www.reporthost.com/?FP3
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
18) 2-slot receptacles rather than 3-slot, grounded receptacles were installed in one or more areas at unit(s) 1, 2, 3, 4, 5 and/or 6. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits.
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
Photo
Photo 18-4 
Photo
Photo 18-5 
Photo
Photo 18-6 
Photo
Photo 18-7 
19) Electrical Panel Photos
Photo
Photo 19-1 
Photo
Photo 19-2 
Photo
Photo 19-3 
Photo
Photo 19-4 
Photo
Photo 19-5 
Photo
Photo 19-6 
Photo
Photo 19-7 
Photo
Photo 19-8 
Photo
Photo 19-9 
Photo
Photo 19-10 
Photo
Photo 19-11 
Photo
Photo 19-12 
Photo
Photo 19-13 
Photo
Photo 19-14 
Photo
Photo 19-15 
Photo
Photo 19-16 
Photo
Photo 19-17 
Photo
Photo 19-18 
Photo
Photo 19-19 
Photo
Photo 19-20 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service: Public
Typical water pressure (psi): 95 PSI
Condition of supply lines: Appeared serviceable
Typical supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Galvanized steel
Condition of waste lines: Not determined (inaccessible, obscured, or water service off)
Waste pipe material: Cast iron
Location of main fuel shut-off valve(s): At gas meter(s)
20) The water supply pressure was greater than 80 pounds per square inch (PSI). Pressures above 80 PSI may void warranties for some appliances such as water heaters or washing machines. Flexible supply lines to washing machines are likely to burst with higher pressures. 40-80 PSI is considered the normal range for water pressure in a home, and most plumbers recommend 50-60 PSI . Typically, the pressure cannot be regulated at the water meter. Recommend that a qualified plumber evaluate and make modifications to reduce the pressure to below 80 PSI . Installing a pressure reducing valve on the main service pipe is a common solution to this problem. If one exists, then it should be adjusted, repaired or replaced as necessary to maintain lower pressures. Note that installing a pressure reducing valve creates a "closed system," which may require installing an expansion tank at the water heater if one is not already installed.
Photo
Photo 20-1 
21) Pin holes and/or corrosion were visible on one or more copper water supply pipes at unit(s) 3. This can occur with acidic water, and from flux applied at fittings for soldering when the pipes were installed or repaired. Leaks can occur from pinholes and corrosion usually indicates past leaks. Recommend consulting with the local municipality and/or a qualified plumber about the local water supply's pH level, and researching solutions for this if necessary. Also recommend that a qualified plumber evaluate and replace water supply components if necessary.
Photo
Photo 21-1 
Photo
Photo 21-2 
22) Steel piping for the gas service located outside was significantly corroded. Gas leaks can result. Recommend evaluation by a qualified contractor to determine if piping needs replacing. If not, then a qualified person should prep and paint lines as necessary with a rust-preventative paint. Very corroded pipes should be replaced by a qualified contractor.
Photo
Photo 22-1 
Photo
Photo 22-2 
23) The inspector performed a "functional flow test" during the inspection, where multiple fixtures were run simultaneously and checked for significantly decreased flow. For example, the shower flow did not decrease significantly when the toilet was flushed.
24) Water Meter
Photo
Photo 24-1 
25) Gas Meters
Photo
Photo 25-1 
26) Plumbing Photos
Photo
Photo 26-1 
Photo
Photo 26-2 
Photo
Photo 26-3 
Photo
Photo 26-4 
Photo
Photo 26-5 
Photo
Photo 26-6 
Photo
Photo 26-7 
Water Heaters
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heaters: Appeared serviceable
Types: Tank
Energy sources: Natural gas
27) The outer flame shield for the water heater combustion chamber at unit(s) 3 was missing. This is a potential fire hazard. Recommend that a qualified person replace any missing flame shields.
Photo
Photo 27-1 
28) The hot water temperature at unit(s) 2, 3, 5 and/or 6 was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD
Photo
Photo 28-1 Unit B
Photo
Photo 28-2 Unit C
Photo
Photo 28-3 Unit E
Photo
Photo 28-4 Unit F
29) The estimated useful life for most water heaters is 8-12 years. The water heater at unit(s) 1 appeared to be at this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 29-1 
Photo
Photo 29-2 
Photo
Photo 29-3 
30) The water heater at unit(s) 1, 2, 3, 4 and/or 5 was installed in or over a finished living space or in an area where leaking can cause damage, and no catch pan or drain was installed. Catch pans and drains prevent water damage to finished interior spaces below if or when the water heater leaks or is drained. If concerned, consult with a qualified contractor about installing these. Note that drain lines for catch pans are usually installed below the floor level and are difficult at best to install in an existing home.
Photo
Photo 30-1 
Photo
Photo 30-2 
Photo
Photo 30-3 
Photo
Photo 30-4 
31) Water Heater Photos
Photo
Photo 31-1 
Photo
Photo 31-2 
Photo
Photo 31-3 
Photo
Photo 31-4 
32)  Water Heater Photos B
Photo
Photo 32-1 
Photo
Photo 32-2 
Photo
Photo 32-3 
Photo
Photo 32-4 
33)  Water Heater Photos C
Photo
Photo 33-1 
Photo
Photo 33-2 
Photo
Photo 33-3 
34)  Water Heater Photos D
Photo
Photo 34-1 
Photo
Photo 34-2 
Photo
Photo 34-3 
Photo
Photo 34-4 
35)  Water Heater Photos E
Photo
Photo 35-1 
Photo
Photo 35-2 
Photo
Photo 35-3 
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
Heating system type(s): Wall Heaters
Heating distribution type(s): None, individual heaters
Electric heater type (not forced air): Wall mounted
Condition of controls: Appeared serviceable
36) Heaters in units A,C and D were not operable at the time of inspection. Pilot lights were not lit. Recommend the local gas company light pilot lights and evaluate heaters.
Photo
Photo 36-1 Unit A
Photo
Photo 36-2 Unit A
Photo
Photo 36-3 Unit C
Photo
Photo 36-4 Unit C
Photo
Photo 36-5 Unit C
37) No permanent air conditioning units were installed at the time of inspection.
38) Wall heaters in units B, E and F were operational using normal operating controls.
Photo
Photo 38-1 Unit B
Photo
Photo 38-2 Unit B
Photo
Photo 38-3 Unit E
Photo
Photo 38-4 Unit E
Photo
Photo 38-5 Unit F
Photo
Photo 38-6 Unit F
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposals: Required repair, replacement and/or evaluation (see comments below)
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Natural gas
39) The range could tip forward at unit(s) 1, 2, 3, 4, 5 and/or 6. An anti-tip bracket may not be installed. This is a potential safety hazard since the range can tip forward when weight is applied to the open door, such as when a small child climbs on it or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free-standing ranges since 1985. Recommend installing an anti-tip bracket to eliminate this safety hazard. For more information, visit:
http://www.reporthost.com/?ATB
40) The under-sink food disposal was inoperable at unit(s) 4. Recommend that a qualified contractor repair or replace as necessary.
Photo
Photo 40-1 
41) Kitchen Photos A
Photo
Photo 41-1 
Photo
Photo 41-2 
Photo
Photo 41-3 
Photo
Photo 41-4 Unit A
Photo
Photo 41-5 
42) Kitchen Photos B
Photo
Photo 42-1 
Photo
Photo 42-2 
Photo
Photo 42-3 
43) Kitchen Photos C
Photo
Photo 43-1 
Photo
Photo 43-2 
Photo
Photo 43-3 
Photo
Photo 43-4 
44) Kitchen Photos D
Photo
Photo 44-1 
Photo
Photo 44-2 
Photo
Photo 44-3 
45) Kitchen Photos E
Photo
Photo 45-1 
Photo
Photo 45-2 
Photo
Photo 45-3 
Photo
Photo 45-4 
46) Kitchen Photos F
Photo
Photo 46-1 
Photo
Photo 46-2 
Photo
Photo 46-3 
Photo
Photo 46-4 
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
47) The toilet was loose where it attached to the floor at unit(s) 6. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 47-1 
Photo
Photo 47-2 
48) Leak from the hot water line was noted in the bathroom of unit(s) 3. A qualified person should repair as necessary.
Photo
Photo 48-1 
49) Bathroom Photos A
Photo
Photo 49-1 
Photo
Photo 49-2 
Photo
Photo 49-3 
Photo
Photo 49-4 
Photo
Photo 49-5 
Photo
Photo 49-6 
Photo
Photo 49-7 
Photo
Photo 49-8 
Photo
Photo 49-9 
Photo
Photo 49-10 
50) Bathroom Photos B
Photo
Photo 50-1 
Photo
Photo 50-2 
Photo
Photo 50-3 
Photo
Photo 50-4 
Photo
Photo 50-5 
Photo
Photo 50-6 
Photo
Photo 50-7 
Photo
Photo 50-8 
Photo
Photo 50-9 
Photo
Photo 50-10 
51) Bathroom Photos C
Photo
Photo 51-1 
Photo
Photo 51-2 
Photo
Photo 51-3 
Photo
Photo 51-4 
Photo
Photo 51-5 
Photo
Photo 51-6 
Photo
Photo 51-7 
Photo
Photo 51-8 
Photo
Photo 51-9 
Photo
Photo 51-10 
52) Bathroom Photos D
Photo
Photo 52-1 
Photo
Photo 52-2 
Photo
Photo 52-3 
Photo
Photo 52-4 
Photo
Photo 52-5 
Photo
Photo 52-6 
Photo
Photo 52-7 
53) Bathroom Photos E
Photo
Photo 53-1 
Photo
Photo 53-2 
Photo
Photo 53-3 
Photo
Photo 53-4 
Photo
Photo 53-5 
Photo
Photo 53-6 
Photo
Photo 53-7 
Photo
Photo 53-8 Low flow was noted at the shower head. Recommend a licensed plumber evaluate and repair.
Photo
Photo 53-9 
Photo
Photo 53-10 
54) Bathroom Photos F
Photo
Photo 54-1 
Photo
Photo 54-2 
Photo
Photo 54-3 
Photo
Photo 54-4 
Photo
Photo 54-5 
Photo
Photo 54-6 
Photo
Photo 54-7 
Photo
Photo 54-8 
Photo
Photo 54-9 
Photo
Photo 54-10 
Interiors, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Metal, Single-pane
Condition of flooring: Appeared serviceable
Flooring type or covering: Hardwood
55) Crank handles at some windows were stripped at unit(s) 3 and 4. Recommend that a qualified person replace handles or make repairs as necessary.
Photo
Photo 55-1 Unit C
Photo
Photo 55-2 Unit D
56) Interior Photos A
Photo
Photo 56-1 
Photo
Photo 56-2 
Photo
Photo 56-3 
Photo
Photo 56-4 
Photo
Photo 56-5 
Photo
Photo 56-6 
Photo
Photo 56-7 
57) Interior Photos B
Photo
Photo 57-1 
Photo
Photo 57-2 
Photo
Photo 57-3 
Photo
Photo 57-4 
Photo
Photo 57-5 
Photo
Photo 57-6 
58) Interior Photos C
Photo
Photo 58-1 
Photo
Photo 58-2 
Photo
Photo 58-3 
Photo
Photo 58-4 
Photo
Photo 58-5 
Photo
Photo 58-6 
Photo
Photo 58-7 
Photo
Photo 58-8 
59) Interior Photos D
Photo
Photo 59-1 
Photo
Photo 59-2 
Photo
Photo 59-3 
Photo
Photo 59-4 
Photo
Photo 59-5 
60) Interior Photos F
Photo
Photo 60-1 
Photo
Photo 60-2 
Photo
Photo 60-3 
Photo
Photo 60-4 
Photo
Photo 60-5 
Photo
Photo 60-6 
Photo
Photo 60-7 
Photo
Photo 60-8 
61) Smoke detectors ans carbon monoxide alarms have been installed in most units in needed areas.

Unit A and E have no Carbon Monoxide alarm. Recommend installation.
Photo
Photo 61-1 
Photo
Photo 61-2 
Photo
Photo 61-3 
Photo
Photo 61-4 
Photo
Photo 61-5 
Photo
Photo 61-6 
Photo
Photo 61-7 
Photo
Photo 61-8 
Photo
Photo 61-9 
Photo
Photo 61-10 
Photo
Photo 61-11 
Photo
Photo 61-12 
62)  Interior Photos E
Photo
Photo 62-1 
Photo
Photo 62-2 
Photo
Photo 62-3 
Photo
Photo 62-4 
Photo
Photo 62-5 


Photo
Photo X-1 
Photo
Photo X-2 

1.1. A Home Inspection is a non-invasive, visual examination of a residential dwelling, performed for a fee, which is designed to identify observed material defects within specific components of said dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or other essential systems or portions of the home, as identified and agreed to by the Client and Inspector, prior to the inspection process.

I. A home inspection is intended to assist in evaluation of the overall condition of the dwelling. The inspection is based on observation of the visible and apparent condition of the structure and its components on the date of the inspection, and not the prediction of future conditions.

II. A home inspection will not reveal every concern that exists or ever could exist, but only those material defects observed on the day of the inspection.

III. A home inspection can include a survey and/or analysis of energy flows and usage in a residential property if the client requests it.

1.2. A Material Defect is a condition of a residential real property, or any portion of it, that would have a significant, adverse impact on the value of the real property, or that involves an unreasonable risk to people on the property. The fact that a structural element, system or subsystem is near, at or beyond the end of the normal useful life of such a structural element, system or subsystem is not by itself a material defect.

1.3. An Inspection Report shall describe and identify, in written format, the inspected systems, structures, and components of the dwelling, and shall identify material defects observed. Inspection reports may contain recommendations regarding conditions reported or recommendations for correction, monitoring or further evaluation by professionals, but this is not required.
A complete copy of the STANDARDS OF PRACTICE we adhere to can be found at the following link: http://www.nachi.org/sop.htm