Property Inspection Report
Unofficial version!

Client(s): Prasanna Thawale
Property address: 30943 Savannah Ct
Novi MI 48377-1565
Inspection date: Thursday, June 20, 2024

This report published on Sunday, June 23, 2024 3:09:07 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

This report is a "snapshot" of the property on the date of the inspection. The structure and all related components may continue to deteriorate/wear out with time and may not be in the same condition on the day of closing.
Components found to be operating properly and in good condition on the date of inspection may be damaged/inoperable, especially if the home was occupied on the date of the inspection. Homeowners may continue to live in the home for several weeks or months after the inspection and damage may be caused during that time or while moving out.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Basement
Kitchen
Bathrooms
Interior rooms
View summary

General informationTable of contents
Type of building: Condo
Time started: 4:30pm
Time finished: 6:30pm
Client email: Prasanna.thawale08@gmail.com
Client phone number: 818-748-5560
Inspection Fee: $450
Payment method: Zelle
Present during inspection: Client(s), Realtor(s)
Occupied: No, but furnishings and stored items are present
Weather conditions: Partly cloudy
Temperature: Hot, 85⁰
Ground condition: Damp, Recent rain
Foundation type: Finished basement
The following items are excluded from this inspection: Security system
1)  Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.
Photo
Photo 1-1 
Photo
Photo 1-2 
Photo
Photo 1-3 
Photo
Photo 1-4 
Foundation material: Poured in place concrete
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
2)  Waterproof cover(s) over one or more electric receptacles are damaged or broken. This is a safety hazard due to the risk of shock and fire. Damaged covers should be replaced where necessary.
Photo
Photo 2-1 
Photo
Photo 2-2 
3)  The roof appeared to be a single layer and was in good condition.
4)  The overhead garage door was operable and the safety reverse sensors were working.
Photo
Photo 4-1 
Inspection method: Partially traversed
Roof structure type: Trusses
Insulation material: Fiberglass loose fill
5)  The attic is dry, well insulated and well ventilated.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Photo
Photo 5-5 
Photo
Photo 5-6 
Photo
Photo 5-7 Roof decking is dry.
Photo
Photo 5-8 Roof decking is dry.
Electric serviceTable of contents
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 100
Service voltage (volts): 120/240
System ground: Ground rod(s) in soil, Cold water supply pipes
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: No
6)  The main electrical service panel and sub panel are in good condition.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Water heaterTable of contents
Estimated age: Installed in 2015
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Manufacturer: American
7)   The water heater is operating properly and safely.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
Photo
Photo 7-4 Carbon monoxide test.
Photo
Photo 7-5 View of burners ignited.
Photo
Photo 7-6 
Heating and coolingTable of contents
Estimated age: A/C and furnace manufactured in 2008
Primary heating system energy source: Natural gas
Primary heat system type: Forced air
Primary A/C energy source: Electric
Primary Air conditioning type: Split system
Distribution system: Sheet metal ducts
Manufacturer: Lennox
8)  The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit:
http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
9)  Battery needs replacing on thermostat.
Photo
Photo 9-1 
10)  Air handler filter(s) should be checked monthly in the future and replaced or washed as necessary.
Photo
Photo 10-1 
Photo
Photo 10-2 
11)  The air conditioning was operating properly
Photo
Photo 11-1 
Photo
Photo 11-2 Serial number indicates year of manufacture.
12)   The furnace is operating properly and safely.
Photo
Photo 12-1 Serial number indicates year of manufacture
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
Photo
Photo 12-5 View of burners ignited.
Photo
Photo 12-6 
Photo
Photo 12-7 Humidifier valve was found in the off position. It was turned on for testing the humidifier and then was returned to the off position.
Plumbing and laundryTable of contents
Water service: Public
Service pipe material: Copper
Supply pipe material: Copper
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
13)  The main electric pump and battery backup pumps are operating properly.
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
Photo
Photo 13-4 Recommend installing cap on the pipe that is no longer being used. Sometimes condensation can form in the pipe and may drip onto the floor.
14)  Water meter
Photo
Photo 14-1 
15)  Both laundry appliances are operating properly. The dryer has a gas hook up.
Photo
Photo 15-1 
Photo
Photo 15-2 Gas hookup.
Fireplaces, woodstoves and chimneysTable of contents
Fireplace type: Metal prefabricated
16)  Unable to get pilot light to stay lit. Recommend further evaluation by a qualified contractor.
Photo
Photo 16-1 
Insulation material underneath floor above: Fiberglass roll or batt
Beam material: Steel
Floor structure above: Solid wood joists
17)  One or more ground fault circuit interrupter (GFCI) electric receptacles are tripped and will not reset. This is a safety hazard due to the risk of fire and/or shock. A qualified electrician should evaluate and make repairs as necessary.
Photo
Photo 17-1 
18)  Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.
Photo
Photo 18-1 Basement closet
19)  Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

Behind water heater
Photo
Photo 19-1 
Photo
Photo 19-2 Closet
20)  Radon mitigation system installed. Looks to have been recently serviced.
Photo
Photo 20-1 
Photo
Photo 20-2 Last service date
Photo
Photo 20-3 
Photo
Photo 20-4 
21)  Radon test started at 5:30 pm on 6-20. Monitor was picked up at 10 am on 6-23. Radon levels are in acceptable range.

For more information on radon visit www.epa.gov/radon
Photo
Photo 21-1 
Photo
Photo 21-2 Radon monitor serial number.
Photo
Photo 21-3 
Photo
Photo 21-4 
22)   Some or all foundation walls were not visible for inspection due to stored items or the walls being finished.
Photo
Photo 22-1 
Photo
Photo 22-2 
Photo
Photo 22-3 
Photo
Photo 22-4 
23)  All kitchen appliances are operating properly.
24)  The "flapper valve" in one or more toilets did not reseat after flushing. Significant amounts of water can be lost through such leaks. A qualified plumber should evaluate and repair or replace components as necessary.

Basement bathroom
Photo
Photo 24-1 
25)  Shower head arm loose in basement bathroom. Repeated movement can cause damage to plumbing fittings and leaks may develop.
Recommend that the pipe be secured.
Photo
Photo 25-1 
Photo
Photo 25-2 Backside of shower head.
26)  Jacuzzi tub functioning properly.
Photo
Photo 26-1 
Interior roomsTable of contents
27)  Tile, stone and/or grout flooring is damaged and/or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary. For example, replacing broken tiles and deteriorated grout, and resealing grout.
Photo
Photo 27-1 
Photo
Photo 27-2 Grout deteriorated
Photo
Photo 27-3 
28)  One or more light fixtures are damaged and/or deteriorated. A qualified electrician should evaluate and repair or replace light fixtures where necessary.

Shades missing.
Photo
Photo 28-1