All Secure Home Inspections

403 Cumberland Ct SE 
Smyrna GA 30080-8648
Inspector: Wayne Dowtin

Property Inspection Report Ann Daniels

Client(s):  Ann Daniels
Property address:  372 Bridgebrook Ln SW
Smyrna GA 30082-3646
Inspection date:  Friday, September 4, 2020

This report published on Tuesday, September 8, 2020 3:13:46 AM EDT

This report is the exclusive property of this inspection company All Secure Home Inspections LLC and the client(s)Ann Daniels listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary

General Information
Table of contents
Report number: 090420
Time started: 9 am
Time finished: 1:!5 pm
Present during inspection: Client
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Payment method: Credit card, 409.00
Type of building: Single family
Buildings inspected: One house, 4788 sq ft
Number of residential units inspected: 1
Age of main building: Built 1992
Source for main building age: Municipal records or property listing
Front of building faces: North
Main entrance faces: North
Occupied: Yes
1) Many areas and items at this property were obscured by . This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open, Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood
2) One or more decks or porches were unstable due to missing or substandard bracing, or lack of attachment to main structure. This is a safety hazard since severe movement may cause the decks or porches to collapse. A qualified contractor should repair as necessary.
Photo
Photo 2-1 
Photo
Photo 2-2 
Photo
Photo 2-3 
Photo
Photo 2-4 
Photo
Photo 2-5 
Photo
Photo 2-6 
Photo
Photo 2-7 
Photo
Photo 2-8 
Photo
Photo 2-9 
Photo
Photo 2-10 
Photo
Photo 2-11 
Photo
Photo 2-12 
Photo
Photo 2-13 
Photo
Photo 2-14 
Photo
Photo 2-15 
Photo
Photo 2-16 
Photo
Photo 2-17 
Photo
Photo 2-18 
Photo
Photo 2-19 
Photo
Photo 2-20 
Photo
Photo 2-21 
Photo
Photo 2-22 
Photo
Photo 2-23 
Photo
Photo 2-24 
Photo
Photo 2-25 
Photo
Photo 2-26 
Photo
Photo 2-27 
Photo
Photo 2-28 
Photo
Photo 2-29 
Photo
Photo 2-30 
Photo
Photo 2-31 
Photo
Photo 2-32 
Photo
Photo 2-33 
Photo
Photo 2-34 
Photo
Photo 2-35 
Photo
Photo 2-36 
Photo
Photo 2-37 
Photo
Photo 2-38 
Photo
Photo 2-39 
Photo
Photo 2-40 
Photo
Photo 2-41 
Photo
Photo 2-42 
Photo
Photo 2-43 
Photo
Photo 2-44 
Photo
Photo 2-45 
Photo
Photo 2-46 
Photo
Photo 2-47 
Photo
Photo 2-48 
Photo
Photo 2-49 
Photo
Photo 2-50 
Photo
Photo 2-51 
3) Ledger boards for one or more decks, balconies or porches appeared to be attached with nails only. This method of attachment is substandard and may result in such structures separating from the main building. This is a potential safety hazard. Modern standards call for ledger boards to be installed with 1/2 inch lag screws or bolts into solid backing, and brackets such as Simpson Strong Tie DTT2 brackets and threaded rod, connecting interior and exterior joists. Recommend that a qualified contractor repair per standard building practices. For more information, visit:
https://www.reporthost.com/?LB
https://www.reporthost.com/?SD
4) Flashing appeared to be missing from above one or more deck or porch ledger boards, or could not be verified. Missing flashing at this location can cause moisture to accumulate between the ledger boards and the building. Fungal rot may occur in this area and cause the ledger board fasteners to fail. The deck may separate from the building in this event. This is a potential safety hazard. Recommend that a qualified contractor install flashing above ledger boards per standard building practices. For more information, visit:
https://www.reporthost.com/?LB
https://www.reporthost.com/?SD
Photo
Photo 4-1 
Photo
Photo 4-2 
Photo
Photo 4-3 
Photo
Photo 4-4 
Photo
Photo 4-5 
Photo
Photo 4-6 
Photo
Photo 4-7 
Photo
Photo 4-8 
Photo
Photo 4-9 
Photo
Photo 4-10 
Photo
Photo 4-11 
Photo
Photo 4-12 
Photo
Photo 4-13 
Photo
Photo 4-14 
Photo
Photo 4-15 
Photo
Photo 4-16 
Photo
Photo 4-17 
5) One or more sets of stairs were unstable and/or wobbly. A qualified contractor should repair as necessary. For example, by installing additional bracing or supports.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Photo
Photo 5-5 
Photo
Photo 5-6 
Photo
Photo 5-7 
6) One or more deck, patio and/or porch covers were unstable due to substandard bracing, lack of diagonal bracing, or lack of attachment to the main building. This is a safety hazard since severe movement may cause the cover to collapse. A qualified contractor should repair as necessary.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Photo
Photo 6-6 
Photo
Photo 6-7 
Photo
Photo 6-8 
Photo
Photo 6-9 
Photo
Photo 6-10 
Photo
Photo 6-11 
Photo
Photo 6-12 
Photo
Photo 6-13 
Photo
Photo 6-14 
Photo
Photo 6-15 
Photo
Photo 6-16 
Photo
Photo 6-17 
Photo
Photo 6-18 
Photo
Photo 6-19 
Photo
Photo 6-20 
Photo
Photo 6-21 
Photo
Photo 6-22 
Photo
Photo 6-23 
Photo
Photo 6-24 
Photo
Photo 6-25 
Photo
Photo 6-26 
Photo
Photo 6-27 
Photo
Photo 6-28 
Photo
Photo 6-29 
Photo
Photo 6-30 
Photo
Photo 6-31 
Photo
Photo 6-32 
Photo
Photo 6-33 
Photo
Photo 6-34 
Photo
Photo 6-35 
Photo
Photo 6-36 
Photo
Photo 6-37 
Photo
Photo 6-38 
Photo
Photo 6-39 
Photo
Photo 6-40 
7) Handrails at one or more flights of stairs were wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
Photo
Photo 7-4 
Photo
Photo 7-5 
8) Fasteners for the deck, porch or balcony joist hangers were missing. Approved fasteners such as Teco nails should be installed in every nail hole in such hardware. Recommend that a qualified person install approved fasteners where necessary.
Photo
Photo 8-1 
Photo
Photo 8-2 
Photo
Photo 8-3 
Photo
Photo 8-4 
Photo
Photo 8-5 
Photo
Photo 8-6 
Photo
Photo 8-7 
Photo
Photo 8-8 
Photo
Photo 8-9 
Photo
Photo 8-10 
Photo
Photo 8-11 
Photo
Photo 8-12 
Photo
Photo 8-13 
Photo
Photo 8-14 
Photo
Photo 8-15 
Photo
Photo 8-16 
Photo
Photo 8-17 
Photo
Photo 8-18 
Photo
Photo 8-19 
Photo
Photo 8-20 
Photo
Photo 8-21 
Photo
Photo 8-22 
Photo
Photo 8-23 
Photo
Photo 8-24 
Photo
Photo 8-25 
Photo
Photo 8-26 
Photo
Photo 8-27 
Photo
Photo 8-28 
Photo
Photo 8-29 
Photo
Photo 8-30 
Photo
Photo 8-31 
Photo
Photo 8-32 
Photo
Photo 8-33 
Photo
Photo 8-34 
Photo
Photo 8-35 
Photo
Photo 8-36 
Photo
Photo 8-37 
9) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 
Photo
Photo 9-5 
Photo
Photo 9-6 
Photo
Photo 9-7 
Photo
Photo 9-8 
Photo
Photo 9-9 
Photo
Photo 9-10 
Photo
Photo 9-11 
Photo
Photo 9-12 
Photo
Photo 9-13 
Photo
Photo 9-14 
Photo
Photo 9-15 
Photo
Photo 9-16 
Photo
Photo 9-17 
Photo
Photo 9-18 
Photo
Photo 9-19 
Photo
Photo 9-20 
Photo
Photo 9-21 
Photo
Photo 9-22 
Photo
Photo 9-23 
Photo
Photo 9-24 
Photo
Photo 9-25 
Photo
Photo 9-26 
Photo
Photo 9-27 
10) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
Photo
Photo 10-5 
Photo
Photo 10-6 
Photo
Photo 10-7 
Photo
Photo 10-8 
Photo
Photo 10-9 
Photo
Photo 10-10 
Photo
Photo 10-11 
Photo
Photo 10-12 
Photo
Photo 10-13 
Photo
Photo 10-14 
Photo
Photo 10-15 
Photo
Photo 10-16 
Photo
Photo 10-17 
Photo
Photo 10-18 
Photo
Photo 10-19 
Photo
Photo 10-20 
Photo
Photo 10-21 
Photo
Photo 10-22 
Photo
Photo 10-23 
Photo
Photo 10-24 
Photo
Photo 10-25 
Photo
Photo 10-26 
Photo
Photo 10-27 
Photo
Photo 10-28 
Photo
Photo 10-29 
Photo
Photo 10-30 
11) Pavement sloped down towards building perimeters in one or more areas. This may result in water accumulating around building foundations or underneath buildings. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing old pavement and installing new.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 
Photo
Photo 11-6 
Photo
Photo 11-7 
Photo
Photo 11-8 
Photo
Photo 11-9 
Photo
Photo 11-10 
Photo
Photo 11-11 
Photo
Photo 11-12 
Photo
Photo 11-13 
Photo
Photo 11-14 
Photo
Photo 11-15 
Photo
Photo 11-16 
Photo
Photo 11-17 
Photo
Photo 11-18 
Photo
Photo 11-19 
Photo
Photo 11-20 
Photo
Photo 11-21 
Photo
Photo 11-22 
Photo
Photo 11-23 
Photo
Photo 11-24 
Photo
Photo 11-25 
Photo
Photo 11-26 
Photo
Photo 11-27 
Photo
Photo 11-28 
Photo
Photo 11-29 
Photo
Photo 11-30 
Photo
Photo 11-31 
Photo
Photo 11-32 
12) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood fiber
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement, Finished basement
13) Some sections of siding and/or trim were deteriorated and/or damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
Photo
Photo 13-4 
Photo
Photo 13-5 
Photo
Photo 13-6 
Photo
Photo 13-7 
Photo
Photo 13-8 
Photo
Photo 13-9 
Photo
Photo 13-10 
Photo
Photo 13-11 
Photo
Photo 13-12 
Photo
Photo 13-13 
Photo
Photo 13-14 
Photo
Photo 13-15 
Photo
Photo 13-16 
Photo
Photo 13-17 
14) The masonry (brick or stone) veneer was deteriorated or damaged in some areas. Where cracks or openings are exposed, water can enter the wall structure causing mold, fungal growth and structural damage. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by repointing mortar or replacing broken or missing masonry.
Photo
Photo 14-1 
Photo
Photo 14-2 
Photo
Photo 14-3 
Photo
Photo 14-4 
Photo
Photo 14-5 
Photo
Photo 14-6 
Photo
Photo 14-7 
Photo
Photo 14-8 
Photo
Photo 14-9 
Photo
Photo 14-10 
15) Untreated wood siding and/or trim was in contact with concrete or masonry at the exterior. Moisture collected between the two materials or wicking up into the wood is a conducive condition for wood-destroying organisms. Wood siding or trim should be installed with a minimum clearance of 1-2 inches between it and concrete or masonry below it at building exteriors. Monitor these areas for rot or infestation in the future and repair if needed. Recommend that a qualified person repair per standard building practices. For example, by trimming siding or trim as needed.
Photo
Photo 15-1 
Photo
Photo 15-2 
Photo
Photo 15-3 
Photo
Photo 15-4 
Photo
Photo 15-5 
Photo
Photo 15-6 
Photo
Photo 15-7 
Photo
Photo 15-8 
Photo
Photo 15-9 
Photo
Photo 15-10 
Photo
Photo 15-11 
Photo
Photo 15-12 
Photo
Photo 15-13 
Photo
Photo 15-14 
Photo
Photo 15-15 
Photo
Photo 15-16 
Photo
Photo 15-17 
Photo
Photo 15-18 
Photo
Photo 15-19 
Photo
Photo 15-20 
16) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Photo
Photo 16-4 
Photo
Photo 16-5 
Photo
Photo 16-6 
Photo
Photo 16-7 
Photo
Photo 16-8 
Photo
Photo 16-9 
Photo
Photo 16-10 
Photo
Photo 16-11 
Photo
Photo 16-12 
Photo
Photo 16-13 
Photo
Photo 16-14 
Photo
Photo 16-15 
Photo
Photo 16-16 
Photo
Photo 16-17 
Photo
Photo 16-18 
17) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
Photo
Photo 17-5 
Photo
Photo 17-6 
Photo
Photo 17-7 
18) Caulk was in some areas. For example, around windows and/or around doors. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
https://www.reporthost.com/?CAULK
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
Photo
Photo 18-4 
Photo
Photo 18-5 
Photo
Photo 18-6 
Photo
Photo 18-7 
Photo
Photo 18-8 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Appeared serviceable
Insulation material underneath floor above: Fiberglass roll or batt
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground, Viewed from ground with binoculars
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
19) Stains were found on one or more gutters that indicate past leaks have occurred. However, the inspector was unable to verify that the gutters do or don't leak because of lack of recent rainfall. Monitor the gutters in the future while it's raining to determine if gutters leak. If they do, then recommend that a qualified person repair as necessary to prevent water from coming in contact with the building or accumulating around the building foundation.
20) Stains were found at the front of one or more gutters and indicate that the gutters have overflowed. If they have overflowed, it's usually due to debris clogging gutters or downspouts. The inspector was unable to verify that the gutters and downspouts drained adequately due to lack of recent, significant rainfall. Monitor the roof drainage system in the future while it's raining to determine if problems exist. Then if necessary, recommend that a qualified person clean, repair or replace gutters, downspouts and/or extensions.
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
Photo
Photo 20-4 
Photo
Photo 20-5 
Photo
Photo 20-6 
Photo
Photo 20-7 
Photo
Photo 20-8 
Photo
Photo 20-9 
Photo
Photo 20-10 
Photo
Photo 20-11 
Photo
Photo 20-12 
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Mineral wool roll or batt
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Vapor retarder: None
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents, Enclosed soffit vents
Garage or Carport
Table of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
21) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Photo
Photo 21-1 
Photo
Photo 21-2 
Photo
Photo 21-3 
Photo
Photo 21-4 
Photo
Photo 21-5 
Photo
Photo 21-6 
Photo
Photo 21-7 
Photo
Photo 21-8 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 150
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Not determined (components inaccessible or obscured)
Main disconnect rating (amps): 150
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Basement
Location of main disconnect: No single main disconnect, use all breakers in main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: non-metallic sheathed
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: Yes
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
22) One or more standard exterior electric receptacles were being used for appliances or systems that were constantly in use. This is a safety hazard for shock since water can reach receptacle slots. Recommend that a qualified person install "while in use" receptacle covers as necessary. For more information, visit:
https://www.reporthost.com/?INUSECVR
23)  Several lights not working ( Client stated many bulbs recently blown)
Photo
Photo 23-1 
Photo
Photo 23-2 
Photo
Photo 23-3 
Photo
Photo 23-4 
Photo
Photo 23-5 
Photo
Photo 23-6 
Photo
Photo 23-7 
Photo
Photo 23-8 
Photo
Photo 23-9 
Photo
Photo 23-10 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 45
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Location of main fuel shut-off valve: At gas meter
24) A fire suppression system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems normally require periodic inspection by a specialist to ensure correct operation. For example, checking for possible backflow contamination of the potable water system, or correct operation of valves and gauges. Recommend that a qualified specialist inspect this system in accordance with National Fire Prevention Association (NFPA) 25 standards.
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
25) One or more water shut-off valves were not labeled, and their function is unknown. Recommend consulting with the property owner to determine valves' functions, that you verify this yourself, or if necessary that a qualified plumber evaluate. Recommend labeling valves as necessary.
Photo
Photo 25-1 
Photo
Photo 25-2 
Photo
Photo 25-3 
Photo
Photo 25-4 
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2017
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 120
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Source for last service date of primary heat source: Client
Condition of forced air heating/(cooling) system: Appeared serviceable
Estimated age of forced air furnace: 2007 Basement/ attic 1992
Location of forced air furnace: Basement, Attic
Condition of furnace filters: Required replacement
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior, east
Type: Split system
Condition of controls: Appeared serviceable
26) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
https://www.reporthost.com/?ANFURINSP
Photo
Photo 26-1 
Photo
Photo 26-2 
Photo
Photo 26-3 
Photo
Photo 26-4 
Photo
Photo 26-5 
Photo
Photo 26-6 
Photo
Photo 26-7 
27) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. The inspector was unable to determine the age of this unit. Be aware that it may be near, at, or beyond its useful life and may need replacing or significant repairs at any time. Recommend attempting to determine the age (ask property owner or service technician), and budgeting for a replacement if necessary.
Photo
Photo 27-1 
Photo
Photo 27-2 
Photo
Photo 27-3 
Photo
Photo 27-4 
Photo
Photo 27-5 
28) The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be near and/or beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.

Basement 2007 (13)/ Attic 1992 (28)
Photo
Photo 28-1 
Photo
Photo 28-2 
Photo
Photo 28-3 
Photo
Photo 28-4 
Photo
Photo 28-5 
Photo
Photo 28-6 
29) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
30)  1.Forced Air Heating system was leaking in basement ( No catch Pan)
2. Pump had a cut/slice in electrical cord
Photo
Photo 30-1 
Photo
Photo 30-2 
Photo
Photo 30-3 
Photo
Photo 30-4 
Photo
Photo 30-5 
Photo
Photo 30-6 
Photo
Photo 30-7 
Photo
Photo 30-8 
Photo
Photo 30-9 
Photo
Photo 30-10 
Photo
Photo 30-11 
Photo
Photo 30-12 
Photo
Photo 30-13 
Photo
Photo 30-14 
Photo
Photo 30-15 
Photo
Photo 30-16 
Photo
Photo 30-17 
Photo
Photo 30-18 
Photo
Photo 30-19 
Photo
Photo 30-20 
Photo
Photo 30-21 
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Condition of gas-fired fireplaces or stoves: Required repair, replacement and/or evaluation (see comments below)
Gas fireplace or stove type: Converted wood-burning fireplace
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: B-vent
31) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
https://www.reporthost.com/?CSIA
32) Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit:
https://www.reporthost.com/?ANGFINSP
33) The gas fireplace or stove was not fully evaluated because the pilot light was off or a lighting procedure was required. The inspector only operates normal controls (e.g. on/off switch or thermostat) and does not light pilot lights or operate gas shut-off valves. Recommend that the client review all documentation for such gas appliances and familiarize themselves with the lighting procedure. If necessary, a qualified specialist should assist in lighting such appliances, and make any needed repairs.
Photo
Photo 33-1 
Photo
Photo 33-2 
Photo
Photo 33-3 
Photo
Photo 33-4 
Photo
Photo 33-5 
Photo
Photo 33-6 
Photo
Photo 33-7 
Photo
Photo 33-8 
Photo
Photo 33-9 
Photo
Photo 33-10 
Photo
Photo 33-11 
34) One or more gas fireplaces or stoves did not respond to normal controls (e.g. on/off switch, thermostat, remote control) and were not fully evaluated as a result. The pilot light or gas supply may have been turned off, or some other condition may have prevented operation. The inspector only operates normal controls and does not light pilot lights or operate gas shut-off valves. Consult with the property owner, review all documentation for such gas appliances, and become familiar with the lighting procedure. If necessary, a qualified specialist should assist in lighting such appliances, and make any needed repairs.
Photo
Photo 34-1 
Photo
Photo 34-2 
Photo
Photo 34-3 
Photo
Photo 34-4 
Photo
Photo 34-5 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, Master bath
Location #B: Full bath, second floor
Location #C: Full bath, first floor
Location #D: Half bath, first floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes
35) The bathroom with a shower or bathtub at location(s) # didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified contractor install exhaust fans per standard building practices where missing in bathrooms with showers or bathtubs.
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Wood
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products
Condition of stairs, handrails and guardrails: Appeared serviceable
36) One or more bedrooms had windows that wouldn't open or were stuck shut. Unless a bedroom has an exterior entry door, at least one window requires adequate egress in the event of a fire or emergency to allow escape or to allow access by emergency personnel. Recommend that a qualified contractor repair or make modifications per standard building practices. For more information, visit:
https://www.reporthost.com/?EGRESS
Photo
Photo 36-1 
Photo
Photo 36-2 
37) One or more windows that were designed to open and close were stuck shut. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo
Photo 37-1 
Photo
Photo 37-2 
Photo
Photo 37-3 
Photo
Photo 37-4 
Photo
Photo 37-5 
Photo
Photo 37-6 
Photo
Photo 37-7 
Photo
Photo 37-8 
Photo
Photo 37-9 
Photo
Photo 37-10 
Photo
Photo 37-11 
Photo
Photo 37-12 
Photo
Photo 37-13 
Photo
Photo 37-14 
Photo
Photo 37-15 
Photo
Photo 37-16 
Photo
Photo 37-17 
Photo
Photo 37-18 
Photo
Photo 37-19 
Photo
Photo 37-20 
38) One or more window screens were damaged or deteriorated. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.
Photo
Photo 38-1 
Photo
Photo 38-2 
Photo
Photo 38-3 
Photo
Photo 38-4 
Photo
Photo 38-5 
39) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
Photo
Photo 39-1 
Photo
Photo 39-2 
Photo
Photo 39-3 
Photo
Photo 39-4 
Photo
Photo 39-5 
Photo
Photo 39-6 
Photo
Photo 39-7 
Photo
Photo 39-8 
Photo
Photo 39-9 
Photo
Photo 39-10 
Photo
Photo 39-11 
Photo
Photo 39-12 
Photo
Photo 39-13 
Photo
Photo 39-14 
Photo
Photo 39-15 
Photo
Photo 39-16 
Photo
Photo 39-17 
Photo
Photo 39-18 
Photo
Photo 39-19 
Photo
Photo 39-20 
40) Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.
Photo
Photo 40-1 
Photo
Photo 40-2 
Photo
Photo 40-3 
Photo
Photo 40-4 
Photo
Photo 40-5 
Photo
Photo 40-6 
Photo
Photo 40-7 
Photo
Photo 40-8 
Photo
Photo 40-9 
Photo
Photo 40-10 
Photo
Photo 40-11 
Photo
Photo 40-12 
Photo
Photo 40-13 
Photo
Photo 40-14 
Photo
Photo 40-15 
Photo
Photo 40-16 
Photo
Photo 40-17 
Wood Destroying Organism Findings
Table of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: No


Photo
Photo X-1 
Photo
Photo X-2 
Photo
Photo X-3 
Photo
Photo X-4 
Photo
Photo X-5 
Photo
Photo X-6 
Photo
Photo X-7 
Photo
Photo X-8 
Photo
Photo X-9 
Photo
Photo X-10 
Photo
Photo X-11 
Photo
Photo X-12 
Photo
Photo X-13 
Photo
Photo X-14 
Photo
Photo X-15 
Photo
Photo X-16 
Photo
Photo X-17 
Photo
Photo X-18 
Photo
Photo X-19 
Photo
Photo X-20 
Photo
Photo X-21 
Photo
Photo X-22 
Photo
Photo X-23 
Photo
Photo X-24 
Photo
Photo X-25 
Photo
Photo X-26 
Photo
Photo X-27 
Photo
Photo X-28 
Photo
Photo X-29 
Photo
Photo X-30 
Photo
Photo X-31 
Photo
Photo X-32 
Photo
Photo X-33 
Photo
Photo X-34 
Photo
Photo X-35 
Photo
Photo X-36 
Photo
Photo X-37 
Photo
Photo X-38 
Photo
Photo X-39 
Photo
Photo X-40 
Photo
Photo X-41 
Photo
Photo X-42 
Photo
Photo X-43 
Photo
Photo X-44 
Photo
Photo X-45 
Photo
Photo X-46 
Photo
Photo X-47 
Photo
Photo X-48 
Photo
Photo X-49 
Photo
Photo X-50 
Photo
Photo X-51 
Photo
Photo X-52 
Photo
Photo X-53 
Photo
Photo X-54 
Photo
Photo X-55 
Photo
Photo X-56 
Photo
Photo X-57 
Photo
Photo X-58 
Photo
Photo X-59 
Photo
Photo X-60 
Photo
Photo X-61 
Photo
Photo X-62 
Photo
Photo X-63 
Photo
Photo X-64 
Photo
Photo X-65 
Photo
Photo X-66 
Photo
Photo X-67 
Photo
Photo X-68 
Photo
Photo X-69 
Photo
Photo X-70 
Photo
Photo X-71 
Photo
Photo X-72 
Photo
Photo X-73 
Photo
Photo X-74 
Photo
Photo X-75 
Photo
Photo X-76 
Photo
Photo X-77 
Photo
Photo X-78 
Photo
Photo X-79 
Photo
Photo X-80 
Photo
Photo X-81 
Photo
Photo X-82 
Photo
Photo X-83 
Photo
Photo X-84 
Photo
Photo X-85 
Photo
Photo X-86 
Photo
Photo X-87 
Photo
Photo X-88 
Photo
Photo X-89 
Photo
Photo X-90 
Photo
Photo X-91 
Photo
Photo X-92 
Photo
Photo X-93 
Photo
Photo X-94 
Photo
Photo X-95 
Photo
Photo X-96 
Photo
Photo X-97 
Photo
Photo X-98 
Photo
Photo X-99 
Photo
Photo X-100 
Photo
Photo X-101 
Photo
Photo X-102 
Photo
Photo X-103 
Photo
Photo X-104 
Photo
Photo X-105 
Photo
Photo X-106 
Photo
Photo X-107 
Photo
Photo X-108 
Photo
Photo X-109 
Photo
Photo X-110 
Photo
Photo X-111 
Photo
Photo X-112 
Photo
Photo X-113 
Photo
Photo X-114 
Photo
Photo X-115 
Photo
Photo X-116 
Photo
Photo X-117 
Photo
Photo X-118 
Photo
Photo X-119 
Photo
Photo X-120 
Photo
Photo X-121 
Photo
Photo X-122 
Photo
Photo X-123 
Photo
Photo X-124 
Photo
Photo X-125 
Photo
Photo X-126 
Photo
Photo X-127 
Photo
Photo X-128 
Photo
Photo X-129 
Photo
Photo X-130 
Photo
Photo X-131 
Photo
Photo X-132 
Photo
Photo X-133 
Photo
Photo X-134 
Photo
Photo X-135 
Photo
Photo X-136 
Photo
Photo X-137 
Photo
Photo X-138 
Photo
Photo X-139 
Photo
Photo X-140 
Photo
Photo X-141 
Photo
Photo X-142 
Photo
Photo X-143 
Photo
Photo X-144 
Photo
Photo X-145 
Photo
Photo X-146 
Photo
Photo X-147 
Photo
Photo X-148 
Photo
Photo X-149 
Photo
Photo X-150 
Photo
Photo X-151 
Photo
Photo X-152 
Photo
Photo X-153 
Photo
Photo X-154 
Photo
Photo X-155 
Photo
Photo X-156 
Photo
Photo X-157 
Photo
Photo X-158 
Photo
Photo X-159 
Photo
Photo X-160 
Photo
Photo X-161 
Photo
Photo X-162 
Photo
Photo X-163 
Photo
Photo X-164 
Photo
Photo X-165 
Photo
Photo X-166 
Photo
Photo X-167 
Photo
Photo X-168 
Photo
Photo X-169 
Photo
Photo X-170 
Photo
Photo X-171 
Photo
Photo X-172 
Photo
Photo X-173 
Photo
Photo X-174 
Photo
Photo X-175 
Photo
Photo X-176 
Photo
Photo X-177 
Photo
Photo X-178 
Photo
Photo X-179 
Photo
Photo X-180 
Photo
Photo X-181 
Photo
Photo X-182 
Photo
Photo X-183 
Photo
Photo X-184 
Photo
Photo X-185 
Photo
Photo X-186 
Photo
Photo X-187 
Photo
Photo X-188 
Photo
Photo X-189 
Photo
Photo X-190 
Photo
Photo X-191 
Photo
Photo X-192 
Photo
Photo X-193 
Photo
Photo X-194 
Photo
Photo X-195 
Photo
Photo X-196 
Photo
Photo X-197 
Photo
Photo X-198 
Photo
Photo X-199 
Photo
Photo X-200 
Photo
Photo X-201 
Photo
Photo X-202 
Photo
Photo X-203 
Photo
Photo X-204 
Photo
Photo X-205 
Photo
Photo X-206 
Photo
Photo X-207 
Photo
Photo X-208 
Photo
Photo X-209 
Photo
Photo X-210 
Photo
Photo X-211 
Photo
Photo X-212 
Photo
Photo X-213 
Photo
Photo X-214 
Photo
Photo X-215 
Photo
Photo X-216 
Photo
Photo X-217 
Photo
Photo X-218 
Photo
Photo X-219 
Photo
Photo X-220 
Photo
Photo X-221 
Photo
Photo X-222 
Photo
Photo X-223 
Photo
Photo X-224 
Photo
Photo X-225 
Photo
Photo X-226 
Photo
Photo X-227 
Photo
Photo X-228 
Photo
Photo X-229 
Photo
Photo X-230 
Photo
Photo X-231 
Photo
Photo X-232 
Photo
Photo X-233 
Photo
Photo X-234 
Photo
Photo X-235 
Photo
Photo X-236 
Photo
Photo X-237 
Photo
Photo X-238 
Photo
Photo X-239 
Photo
Photo X-240 
Photo
Photo X-241 
Photo
Photo X-242 
Photo
Photo X-243 
Photo
Photo X-244 
Photo
Photo X-245 
Photo
Photo X-246 
Photo
Photo X-247 
Photo
Photo X-248 
Photo
Photo X-249 
Photo
Photo X-250 
Photo
Photo X-251 
Photo
Photo X-252 
Photo
Photo X-253 
Photo
Photo X-254 
Photo
Photo X-255 
Photo
Photo X-256 
Photo
Photo X-257 
Photo
Photo X-258 
Photo
Photo X-259 
Photo
Photo X-260 
Photo
Photo X-261 
Photo
Photo X-262 
Photo
Photo X-263 
Photo
Photo X-264 
Photo
Photo X-265 
Photo
Photo X-266 
Photo
Photo X-267 
Photo
Photo X-268 A/C unit off balance by 1 inch
Photo
Photo X-269 imbalanced A/C unit not level
Photo
Photo X-270 
Photo
Photo X-271 
Photo
Photo X-272 
Photo
Photo X-273 
Photo
Photo X-274 
Photo
Photo X-275 
Photo
Photo X-276 
Photo
Photo X-277 
Photo
Photo X-278 
Photo
Photo X-279 
Photo
Photo X-280 
Photo
Photo X-281 
Photo
Photo X-282 
Photo
Photo X-283 
Photo
Photo X-284 
Photo
Photo X-285 
Photo
Photo X-286 
Photo
Photo X-287 
Photo
Photo X-288 
Photo
Photo X-289 
Photo
Photo X-290 
Photo
Photo X-291 
Photo
Photo X-292 
Photo
Photo X-293 
Photo
Photo X-294 
Photo
Photo X-295 
Photo
Photo X-296 
Photo
Photo X-297 
Photo
Photo X-298 
Photo
Photo X-299 
Photo
Photo X-300 
Photo
Photo X-301 
Photo
Photo X-302 failing gutter seams
Photo
Photo X-303 
Photo
Photo X-304 
Photo
Photo X-305 
Photo
Photo X-306 
Photo
Photo X-307 over saturation external moisture in wood trim and soffit
Photo
Photo X-308 
Photo
Photo X-309 
Photo
Photo X-310 
Photo
Photo X-311 
Photo
Photo X-312 
Photo
Photo X-313 
Photo
Photo X-314 
Photo
Photo X-315 
Photo
Photo X-316 
Photo
Photo X-317 
Photo
Photo X-318 
Photo
Photo X-319 
Photo
Photo X-320 
Photo
Photo X-321 
Photo
Photo X-322 
Photo
Photo X-323 
Photo
Photo X-324 
Photo
Photo X-325 
Photo
Photo X-326 
Photo
Photo X-327 
Photo
Photo X-328 
Photo
Photo X-329 
Photo
Photo X-330 
Photo
Photo X-331 
Photo
Photo X-332 
Photo
Photo X-333 
Photo
Photo X-334 
Photo
Photo X-335 
Photo
Photo X-336 
Photo
Photo X-337 
Photo
Photo X-338 
Photo
Photo X-339 
Photo
Photo X-340 
Photo
Photo X-341 
Photo
Photo X-342 
Photo
Photo X-343 
Photo
Photo X-344 
Photo
Photo X-345 
Photo
Photo X-346 
Photo
Photo X-347 
Photo
Photo X-348 
Photo
Photo X-349 
Photo
Photo X-350 
Photo
Photo X-351 
Photo
Photo X-352 
Photo
Photo X-353 
Photo
Photo X-354 
Photo
Photo X-355 
Photo
Photo X-356 
Photo
Photo X-357 
Photo
Photo X-358 
Photo
Photo X-359 
Photo
Photo X-360 
Photo
Photo X-361 
Photo
Photo X-362 
Photo
Photo X-363 
Photo
Photo X-364 
Photo
Photo X-365 
Photo
Photo X-366 
Photo
Photo X-367 
Photo
Photo X-368 
Photo
Photo X-369 
Photo
Photo X-370 
Photo
Photo X-371 
Photo
Photo X-372 
Photo
Photo X-373 
Photo
Photo X-374 
Photo
Photo X-375 
Photo
Photo X-376 loose floor vent near kitchen entrance
Photo
Photo X-377 
Photo
Photo X-378 
Photo
Photo X-379 
Photo
Photo X-380 
Photo
Photo X-381 
Photo
Photo X-382 Gas valve under deck to fireplace
Photo
Photo X-383 
Photo
Photo X-384 
Photo
Photo X-385 
Photo
Photo X-386 
Photo
Photo X-387 
Photo
Photo X-388 
Photo
Photo X-389 
Photo
Photo X-390 
Photo
Photo X-391 
Photo
Photo X-392 
Photo
Photo X-393 
Photo
Photo X-394 
Photo
Photo X-395 
Photo
Photo X-396 
Photo
Photo X-397 
Photo
Photo X-398 
Photo
Photo X-399 
Photo
Photo X-400 
Photo
Photo X-401 
Photo
Photo X-402 
Photo
Photo X-403 
Photo
Photo X-404 
Photo
Photo X-405 
Photo
Photo X-406 
Photo
Photo X-407 
Photo
Photo X-408 
Photo
Photo X-409 
Photo
Photo X-410 
Photo
Photo X-411 
Photo
Photo X-412 
Photo
Photo X-413 
Photo
Photo X-414 
Photo
Photo X-415 
Photo
Photo X-416 
Photo
Photo X-417 
Photo
Photo X-418 
Photo
Photo X-419 
Photo
Photo X-420 
Photo
Photo X-421 
Photo
Photo X-422 
Photo
Photo X-423 
Photo
Photo X-424 
Photo
Photo X-425 
Photo
Photo X-426 
Photo
Photo X-427 
Photo
Photo X-428 
Photo
Photo X-429 
Photo
Photo X-430 
Photo
Photo X-431 
Photo
Photo X-432 
Photo
Photo X-433 
Photo
Photo X-434 
Photo
Photo X-435 
Photo
Photo X-436 
Photo
Photo X-437 
Photo
Photo X-438 
Photo
Photo X-439 
Photo
Photo X-440 
Photo
Photo X-441 
Photo
Photo X-442 
Photo
Photo X-443 
Photo
Photo X-444 
Photo
Photo X-445 
Photo
Photo X-446 
Photo
Photo X-447 
Photo
Photo X-448 
Photo
Photo X-449 
Photo
Photo X-450 
Photo
Photo X-451 
Photo
Photo X-452 
Photo
Photo X-453 
Photo
Photo X-454 
Photo
Photo X-455 
Photo
Photo X-456 
Photo
Photo X-457 
Photo
Photo X-458 
Photo
Photo X-459 
Photo
Photo X-460 
Photo
Photo X-461 
Photo
Photo X-462 
Photo
Photo X-463 
Photo
Photo X-464 
Photo
Photo X-465 
Photo
Photo X-466 
Photo
Photo X-467 
Photo
Photo X-468 
Photo
Photo X-469 
Photo
Photo X-470 
Photo
Photo X-471 
Photo
Photo X-472 
Photo
Photo X-473 
Photo
Photo X-474 
Photo
Photo X-475 
Photo
Photo X-476 
Photo
Photo X-477 
Photo
Photo X-478 
Photo
Photo X-479 
Photo
Photo X-480 
Photo
Photo X-481 
Photo
Photo X-482 
Photo
Photo X-483 
Photo
Photo X-484 
Photo
Photo X-485 
Photo
Photo X-486 
Photo
Photo X-487 
Photo
Photo X-488 
Photo
Photo X-489 
Photo
Photo X-490 
Photo
Photo X-491 
Photo
Photo X-492 
Photo
Photo X-493 
Photo
Photo X-494 
Photo
Photo X-495 
Photo
Photo X-496 
Photo
Photo X-497 
Photo
Photo X-498 
Photo
Photo X-499 
Photo
Photo X-500 
Photo
Photo X-501 
Photo
Photo X-502 
Photo
Photo X-503 
Photo
Photo X-504 
Photo
Photo X-505 
Photo
Photo X-506 
Photo
Photo X-507 
Photo
Photo X-508 
Photo
Photo X-509 
Photo
Photo X-510 
Photo
Photo X-511 
Photo
Photo X-512 
Photo
Photo X-513 
Photo
Photo X-514 
Photo
Photo X-515 
Photo
Photo X-516 
Photo
Photo X-517 
Photo
Photo X-518 
Photo
Photo X-519 
Photo
Photo X-520 
Photo
Photo X-521 
Photo
Photo X-522 
Photo
Photo X-523 
Photo
Photo X-524 
Photo
Photo X-525 
Photo
Photo X-526 
Photo
Photo X-527 
Photo
Photo X-528 
Photo
Photo X-529 
Photo
Photo X-530 
Photo
Photo X-531 
Photo
Photo X-532 
Photo
Photo X-533 
Photo
Photo X-534 
Photo
Photo X-535 
Photo
Photo X-536 
Photo
Photo X-537 
Photo
Photo X-538 
Photo
Photo X-539 
Photo
Photo X-540 
Photo
Photo X-541 
Photo
Photo X-542 
Photo
Photo X-543 
Photo
Photo X-544 
Photo
Photo X-545 
Photo
Photo X-546 
Photo
Photo X-547 
Photo
Photo X-548 
Photo
Photo X-549 
Photo
Photo X-550 
Photo
Photo X-551 
Photo
Photo X-552 
Photo
Photo X-553 
Photo
Photo X-554 
Photo
Photo X-555 
Photo
Photo X-556 
Photo
Photo X-557 
Photo
Photo X-558 
Photo
Photo X-559 
Photo
Photo X-560 
Photo
Photo X-561 
Photo
Photo X-562 
Photo
Photo X-563 
Photo
Photo X-564 
Photo
Photo X-565 
Photo
Photo X-566 
Photo
Photo X-567 
Photo
Photo X-568 
Photo
Photo X-569 
Photo
Photo X-570 
Photo
Photo X-571 
Photo
Photo X-572 
Photo
Photo X-573 
Photo
Photo X-574 
Photo
Photo X-575 
Photo
Photo X-576 
Photo
Photo X-577 
Photo
Photo X-578 
Photo
Photo X-579 
Photo
Photo X-580 
Photo
Photo X-581 
Photo
Photo X-582 
Photo
Photo X-583 
Photo
Photo X-584 
Photo
Photo X-585 
Photo
Photo X-586 
Photo
Photo X-587 
Photo
Photo X-588 
Photo
Photo X-589 
Photo
Photo X-590 
Photo
Photo X-591 
Photo
Photo X-592 
Photo
Photo X-593 
Photo
Photo X-594 
Photo
Photo X-595 
Photo
Photo X-596 
Photo
Photo X-597 
Photo
Photo X-598 
Photo
Photo X-599 
Photo
Photo X-600 
Photo
Photo X-601 
Photo
Photo X-602 
Photo
Photo X-603 
Photo
Photo X-604 
Photo
Photo X-605 
Photo
Photo X-606 
Photo
Photo X-607 
Photo
Photo X-608 
Photo
Photo X-609 
Photo
Photo X-610 
Photo
Photo X-611 
Photo
Photo X-612 
Photo
Photo X-613 
Photo
Photo X-614 
Photo
Photo X-615 
Photo
Photo X-616 
Photo
Photo X-617 
Photo
Photo X-618 
Photo
Photo X-619 
Photo
Photo X-620 
Photo
Photo X-621 
Photo
Photo X-622 
Photo
Photo X-623 
Photo
Photo X-624 
Photo
Photo X-625 
Photo
Photo X-626 
Photo
Photo X-627 
Photo
Photo X-628 
Photo
Photo X-629 
Photo
Photo X-630 
Photo
Photo X-631 
Photo
Photo X-632 
Photo
Photo X-633 
Photo
Photo X-634 
Photo
Photo X-635 
Photo
Photo X-636 
Photo
Photo X-637 
Photo
Photo X-638 
Photo
Photo X-639 
Photo
Photo X-640 
Photo
Photo X-641 
Photo
Photo X-642 
Photo
Photo X-643 
Photo
Photo X-644 
Photo
Photo X-645 
Photo
Photo X-646 
Photo
Photo X-647 insulation fallen down or over stored in attic
Photo
Photo X-648 
Photo
Photo X-649 
Photo
Photo X-650 
Photo
Photo X-651 
Photo
Photo X-652 
Photo
Photo X-653 
Photo
Photo X-654 previous water damages from previously leaking roof
Photo
Photo X-655 
Photo
Photo X-656 
Photo
Photo X-657 
Photo
Photo X-658 
Photo
Photo X-659 
Photo
Photo X-660 
Photo
Photo X-661 
Photo
Photo X-662 
Photo
Photo X-663 
Photo
Photo X-664 
Photo
Photo X-665 
Photo
Photo X-666 
Photo
Photo X-667 
Photo
Photo X-668 
Photo
Photo X-669 
Photo
Photo X-670 
Photo
Photo X-671 
Photo
Photo X-672 
Photo
Photo X-673 
Photo
Photo X-674 
Photo
Photo X-675 
Photo
Photo X-676 
Photo
Photo X-677 
Photo
Photo X-678 
Photo
Photo X-679 
Photo
Photo X-680 
Photo
Photo X-681 
Photo
Photo X-682 
Photo
Photo X-683 
Photo
Photo X-684 
Photo
Photo X-685 
Photo
Photo X-686 
Photo
Photo X-687 
Photo
Photo X-688 
Photo
Photo X-689 
Photo
Photo X-690 
Photo
Photo X-691 
Photo
Photo X-692 
Photo
Photo X-693 
Photo
Photo X-694 
Photo
Photo X-695 
Photo
Photo X-696 
Photo
Photo X-697 
Photo
Photo X-698 
Photo
Photo X-699 
Photo
Photo X-700 
Photo
Photo X-701 
Photo
Photo X-702 
Photo
Photo X-703 
Photo
Photo X-704 
Photo
Photo X-705 
Photo
Photo X-706 
Photo
Photo X-707 
Photo
Photo X-708 
Photo
Photo X-709 
Photo
Photo X-710 

This Inspection was visual only and was performed at the request of the client listed this inspection and report is considered comprehensive not exhaustive there are discoveries all along the process and other discoveries may be found completely through to the final inspection by the client any further discoveries found by the client may be included in this report up until the final inspection only if the discoveries are brought to the attention of the inspector 3 days before closing. The inspector and inspection company listed are not held liable to any repairs or discoveries from any repairs made after this inspection date.