Cascade Sierra Home Inspections


4500 Truxel Rd Apt 1133 
Sacramento CA 95834-3743
Inspector: James Mecorney

  

Property Inspection Report

Client(s):  John and Jane Doe
Property address:  123 Main Street
Sacramento CA 95834
Inspection date:  Sunday, December 11, 2016

This report published on Thursday, April 13, 2017 8:06:07 AM PDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary


General Information
Return to table of contents

Inspection #: YOL-0103
Time started: 1230
Time finished: 330
Present during inspection: Client
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1925
Source for main building age: Client
Front of building faces: North
Main entrance faces: North
Occupied: Yes, Furniture or stored items were present

1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC

2) The water service was turned on during the inspection. The inspector operates only "normal" controls such as faucets, and does not operate shut-off valves to the water meter or house. As a result, plumbing supply, drain waste and vent lines, traps, pumps, fixtures, and some appliances such as water heaters may not have been fully evaluated. The water pressure was not determined, unless specifically noted. Recommend that a qualified person make a full evaluation of the plumbing system. Areas below the house should be evaluated after plumbing has been operated to check for leaks. Any problems that are found after this evaluation should be repaired by a qualified plumber.

3) The propane service was turned on during the inspection. The inspector operates only "normal" controls such as thermostats, and does not operate shut-off valves to the gas meter or house. As a result, supply lines, service connections, shut-off valves, and some appliances such as water heaters may not have been fully evaluated. Recommend that a qualified person make a full evaluation of the gas plumbing system. Any problems that are found after this evaluation should be repaired by a qualified plumber.

4) Electricity was available during the inspection. The inspector operates only "normal controls" such as switches or knobs, and does not reset or turn on circuit breakers or remove or install fuses, except where appropriate and noted. As a result, branch circuit wiring, receptacles, fixtures such as lights and fans, switches, ground fault circuit interrupter (GFCI) devices, arc fault circuit interrupter (AFCI) devices, and some appliances such as electrically powered water heaters, forced air furnaces, heat pumps, air conditioning units, and kitchen appliances may not have been fully evaluated.

5) Some areas and items at this property were obscured by furniture and stored items. This includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Brick
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Wood, Brick

6) This property was accessed by a driveway or private road shared with nearby properties. Shared driveways or private roads are excluded from this inspection. Comments in this report related to them are made as a courtesy only and are not meant to be a substitute for a evaluation by a specialist if repairs are needed. Recommend that the client review the recorded agreements regarding the driveway, the deeds of the property owners involved, and easements permitting access to, use of, and maintenance of the driveway.
Photo
Photo 6-1
 

7)  
Photo
Photo 7-1
Photo
Photo 7-2
Photo
Photo 7-3
 

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space, Post and pier
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall):

8) One or more large trees were very close to the foundation. Tree roots can cause significant structural damage to foundations, or may have already caused damage (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to foundations.
Photo
Photo 8-1
 

9) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 9-1
Photo
Photo 9-2

10) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 10-1
 

11)  
Photo
Photo 11-1
Photo
Photo 11-2
Photo
Photo 11-3
Photo
Photo 11-4
Photo
Photo 11-5
Photo
Photo 11-6

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Viewed from hatch(es)
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Engineered wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Condition of vapor barrier: Not applicable, none installed
Vapor barrier present: None visible
Condition of crawl space ventilation: Required repairs, replacement and/or evaluation (see comments below)
Ventilation type: Unconditioned space, with vents

12) Evidence of prior water intrusion or accumulation was found in one or more sections of the crawl space. For example, sediment stains on the vapor barrier or foundation, and/or efflorescence on the foundation. Accumulated water is a conducive condition for wood-destroying organisms and should not be present in the crawl space. Recommend that the client review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space. The crawl space should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:
  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, gravity drains and/or sump pump(s) in the crawl space.
Photo
Photo 12-1
Photo
Photo 12-2

13) No under-floor insulation was installed in the crawl space. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.
Photo
Photo 13-1
Photo
Photo 13-2

14) No vapor barrier was installed in the crawl space. This is a conducive condition for wood-destroying organisms due to the likelihood of water evaporating from the soil below up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified contractor install a vapor barrier per standard building practices.
Photo
Photo 14-1
Photo
Photo 14-2

15) One or more outdoor crawl space access hatches or doors were missing, damaged, deteriorated or substandard. Water and/or vermin can enter the crawl space. Recommend that a qualified person replace, install or repair hatches or doors where necessary.

Crawlspace vent screen on west side of house was not attached to the foundation. Recommend permanent attachment of vent screen using masonry screws.

16)  
Photo
Photo 16-1
Photo
Photo 16-2
Photo
Photo 16-3
 

17)  
Photo
Photo 17-1
Photo
Photo 17-2
Photo
Photo 17-3
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from eaves on ladder
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: Multiple
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)

18) Flashings at the base of one or more chimneys were missing. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.

There was no metal flashing at the chimney. In addition, there was visible water staining visible in the attic at the chimney penetration. Recommend evaluation and installation of metal flashing by a qualified roofer. See also note in attic section.
Photo
Photo 18-1
Photo
Photo 18-2

19) Nail heads were exposed at one or more shingles. More than just a few exposed nail heads may indicate a substandard roof installation. Recommend applying an approved sealant over exposed nail heads now and as necessary in the future to prevent leaks.
Photo
Photo 19-1
Photo
Photo 19-2

20) One or more gutters and/or downspouts were leaking, corroded and/or damaged. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 20-1
Photo
Photo 20-2
Photo
Photo 20-3
 

21) Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 21-1
 

22) Moss was growing on the roof. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate-based chemicals are used for this and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
http://www.reporthost.com/?MOSS
Photo
Photo 22-1
Photo
Photo 22-2
Photo
Photo 22-3
 

23)   The service for the satellite dish, including the co-axial feed and the tripod for the dish, appeared to be secured with fasteners driven through the shingles. This compromises the integrity of the roof covering, and could lead to water damage. recommend evaluation and repair by a qualified roofer.
Photo
Photo 23-1
Photo
Photo 23-2
Photo
Photo 23-3
 

24)  
Photo
Photo 24-1
Photo
Photo 24-2
Photo
Photo 24-3
Photo
Photo 24-4
Photo
Photo 24-5
 

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-38
Vermiculite insulation present:
Vapor retarder: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents, Open soffit vents

25) One or more attic access hatches or doors were too small to allow easy access. Such hatches should be at least 22 x 30 inches in size, and in safely accessed areas. Recommend that a qualified person modify attic access points per standard building practices.
Photo
Photo 25-1
 

26)  
Photo
Photo 26-1
Photo
Photo 26-2
Photo
Photo 26-3
Photo
Photo 26-4
Photo
Photo 26-5
Photo
Photo 26-6

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 2
Service voltage (volts): 120-240
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 125
System ground: Not determined, not readily apparent
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Laundry room
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: non-metallic sheathed, copper
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: No, recommend install
Carbon monoxide alarms installed: Yes, but not tested

27) One or more electric receptacles at the kitchen, bathroom(s), laundry area and/or exterior had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI

28) One or more electric receptacles at the bedroom(s), dining room, living room, parlor and/or closet(s) had no visible arc fault circuit interrupter (AFCI) protection, or the inspector was unable to determine if AFCI protection was present. This is a potential safety hazard. Recommend that a qualified electrician evaluate and install AFCI protection if necessary and per standard building practices. General guidelines for AFCI-protected receptacles include the following locations:
  • Bedrooms (since 1999)
  • Kitchens, laundry areas, family rooms, dining rooms, living rooms, parlors, libraries, dens and recreation rooms, sunrooms, closets and hallways (since 2014)
For more information, visit:
http://www.reporthost.com/?AFCI

29) One or more modern, 3-slot electric receptacles were found with an open ground. Three-slot receptacles should have a hot, a neutral and a ground wire connected. Homeowners often install new 3-slot receptacles on older, 2-wire circuits that only have hot and neutral wires. This is a shock hazard when appliances that require a ground are used with these receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. Where the electric system was installed prior to when grounded circuits were required (1960s), it is permissible to replace 3-slot receptacles with 2-slot receptacles to prevent appliances that require a ground from being plugged in to an ungrounded circuit. However, the client should be aware of this limitation when planning use for various rooms, such as an office. For newer electric systems, circuits should be repaired so grounded, 3-wire cables provide power to 3-slot receptacles. Recommend that a qualified electrician repair per standard building practices.

Bedroom receptacles were changed to 3 slot, with the original 2 rubber-insulated conductors. Recommend replacement with 2 slot outlets, or rewire bedroom circuit with modern 3 wire conductors.
Photo
Photo 29-1
Photo
Photo 29-2
Photo
Photo 29-3
 

30) Smoke alarms were missing from one or more bedrooms. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
Photo
Photo 30-1
Photo
Photo 30-2
Photo
Photo 30-3
 

31) Carbon monoxide alarms were missing from one or more sleeping areas. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit:
http://www.reporthost.com/?COALRM

32) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.

33) 2-slot receptacles rather than 3-slot, grounded receptacles were installed in one or more areas. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits.
Photo
Photo 33-1
Photo
Photo 33-2

34) One or more "plug-in" type carbon monoxide alarms were found. Because such CO alarms can be easily removed, recommend that home buyers verify that CO alarms haven't been removed upon taking occupancy. If removed, then recommend installing new CO alarms in the vicinity of sleeping areas and on each level. Note that some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. For more information, visit:
http://www.reporthost.com/?COALRM
Photo
Photo 34-1
 

35) One or more light fixtures were loose. Recommend that a qualified electrician repair or replace light fixtures as necessary.

Light fixture in closet was loose. This is a safety hazard. Recommend repair by a qualified person. Also recommend replacement of incandescent light bulbs in closet with Compact Fluorescent Lights (CFL's), as traditional incandescent bulbs produce a substantial amount of heat and can also be a fire hazard.
Photo
Photo 35-1
Photo
Photo 35-2

36) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Photo
Photo 36-1
 

37)  
Photo
Photo 37-1
Photo
Photo 37-2
Photo
Photo 37-3
Photo
Photo 37-4
Photo
Photo 37-5
Photo
Photo 37-6
Photo
Photo 37-7
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Shared well
Location of main water shut-off: Building exterior
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Required repair, replacement and/or evaluation (see comments below)
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Sewage ejector pump installed: No
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: propane tank
Location of main fuel shut-off valve: At propane tank, At building exterior

38) One or more drain line traps were substandard (e.g. "S", "U" or drum traps). Traps can siphon or run dry and cause sewer gases to enter living spaces. Recommend that a qualified plumber repair per standard building practices. For example, by replacing with modern "P" traps. For more information, visit:
http://www.reporthost.com/?TRAP

Lavatory drain (bathroom) Had S-trap. recommend evaluation by a qualified plumber.
Photo
Photo 38-1
Photo
Photo 38-2
Photo
Photo 38-3
 

39) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC

40) Based on information provided to the inspector, the water supply to this property is from a shared or community well. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Recommend that the client review the recorded agreements regarding the well, the deeds of the property owners involved, and easements permitting access to, use of, and maintenance of the water system. If no shared well agreement exists, access to the well water supply will be uncertain. Also recommend the following:
  • That a qualified well contractor fully evaluate the well, including a conducting a pump/flow test
  • That the well water be tested per the client's concerns (e.g. coliforms, pH, contaminants)
  • Research the well's history (e.g. how/when constructed, how/when maintained or repaired)
  • If the well is not on the client's property, verify that the well's property owner does not harm the well water's quality through land use practices
  • Document the current well capacity and water quality for future reference

41)  
Photo
Photo 41-1
Photo
Photo 41-2
Photo
Photo 41-3
Photo
Photo 41-4
Photo
Photo 41-5
Photo
Photo 41-6
Photo
Photo 41-7
 

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Propane
Estimated age: 1998
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Laundry room
Hot water temperature tested: No
Condition of burners: Not determined (inaccessible, obscured, or gas service off)
Condition of venting system: Appeared serviceable

42) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be at this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 42-1
Photo
Photo 42-2

43)  
Photo
Photo 43-1
Photo
Photo 43-2
Photo
Photo 43-3
Photo
Photo 43-4

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Electric heaters
General heating distribution type(s): Ducts and registers
Condition of electric heaters (not forced air): Required repair, replacement and/or evaluation (see comments below)
Electric heater type (not forced air): Wall mounted
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Propane
Location of forced air furnace: Attic
Condition of furnace filters: Required replacement
Location for forced air filter(s): Behind return air grill(s)
Condition of forced air ducts and registers: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: south
Type: Split system
Condition of controls: Appeared serviceable

44) One or more fan-assisted electric heaters were inoperable. Recommend that a qualified electrician repair or replace heaters as necessary.

Wall mounted electric heater in kitchen was not producing hot air. Recommend evaluation by a qualified technician.
Photo
Photo 44-1
Photo
Photo 44-2
Photo
Photo 44-3
 

45) Recommend that home buyers replace or clean HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or cleaning them as necessary. How frequently they need replacing or cleaning depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 45-1
 

46)  
Photo
Photo 46-1
Photo
Photo 46-2
Photo
Photo 46-3
Photo
Photo 46-4
Photo
Photo 46-5
Photo
Photo 46-6
Photo
Photo 46-7
Photo
Photo 46-8

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning stove type: Freestanding
Condition of chimneys and flues: Required repair, replacement and/or evaluation (see comments below)
Wood-burning chimney type: Masonry

47) There was a masonry chimney present, but appeared to have been abandoned. The chimney cap appeared to be decorative and made of wood, and appeared to have protruding nails, as seen from the ground with binoculars. If this chimney is put into use in the future as a wood burning chimney, recommend evaluation by a qualified technician to determine the condition of the flue and chimney cap.
Photo
Photo 47-1
Photo
Photo 47-2

48)  
Photo
Photo 48-1
Photo
Photo 48-2
Photo
Photo 48-3
 

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: N/A (none installed)
Condition of range, cooktop or oven: N/A (none installed)
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: N/A (none installed)

49)  
Photo
Photo 49-1
Photo
Photo 49-2
Photo
Photo 49-3
Photo
Photo 49-4
Photo
Photo 49-5
 

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing:
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Central exhaust fan
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

50) The inspector was unable to verify that the glass used in one or more windows at location(s) #A was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a potential safety hazard. Standard building practices require that approved safety glass be used in enclosures for bathtubs, showers, spas, saunas and steam rooms, and in windows where the bottom edge of the window is less than 60 inches above the drain inlet or standing surface. Wire-reinforced glass is not acceptable. Recommend that a qualified contractor evaluate further to determine if glazing is approved safety glass, and replace glass if necessary, and per standard building practices.
Photo
Photo 50-1
 

51) The sink drain pipe at location(s) #A used an S-trap rather than a P-trap, or no P-trap was visible. Siphons and sudden flows of water in S-Traps can drain all the water out of the trap, leaving it dry. Sewer gases can then enter living areas. Recommend that a qualified plumber repair per standard building practices.

See note in Plumbing section.

52)  
Photo
Photo 52-1
Photo
Photo 52-2
Photo
Photo 52-3
Photo
Photo 52-4
Photo
Photo 52-5
 

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Glass panel, French doors
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Wood, Multi-pane, Single-pane
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall or plaster
Ceiling type or covering: Drywall or plaster
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products, Tile

53) The inspector was unable to verify that the glass used in one or more exterior doors was approved safety glass. Glazing that is not approved safety glass, located in areas subject to human impact, is a safety hazard. Standard building practices generally require that approved safety glass be used in swinging and sliding doors except where "art glass," jalousie windows or glazing smaller than a 3-inch opening is used. Recommend that a qualified contractor evaluate further to determine if glazing is approved safety glass, and replace glass if necessary, and per standard building practices.
Photo
Photo 53-1
Photo
Photo 53-2
Photo
Photo 53-3
 

54) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.reporthost.com/?ECC
Photo
Photo 54-1
Photo
Photo 54-2

55)  
Photo
Photo 55-1
Photo
Photo 55-2
Photo
Photo 55-3
Photo
Photo 55-4
Photo
Photo 55-5
Photo
Photo 55-6

The Parties Understood and Agreed as follows:

1. INSPECTOR GUARANTEES to perform a visual inspection of the home and to provide CLIENT with a written inspection report identifying the defects that INSPECTOR both observed and deemed material. INSPECTOR may offer comments as a courtesy, but these comments will not comprise the bargained-for report. The report is only supplementary to the sellers disclosure.

2. INSPECTOR agrees to perform the inspection in accordance to the current Standards of Practice of the National Association of Certified Home Inspectors posted at http://www.nachi.org/sop.htm.

3. CLIENT understands that the inspection will be performed in accordance to the aforementioned Standards, which contain certain limitations, exceptions, and exclusions.

4. The inspection and report are performed and prepared for the use of CLIENT, who gives INSPECTOR permission to discuss observations with real estate agents, owners, repair persons and other interested parties. INSPECTOR accepts no responsibility for use or misinterpretation by third parties.

5. INSPECTOR does not perform engineering, architectural, plumbing, or any other job function requiring an occupational license in the jurisdiction where the inspection is taking place, unless the inspector holds a valid occupational license, in which case he/she may inform the CLIENT that he/she is so licensed, and is therefore qualified to go beyond this basic home inspection, and for additional fee, perform additional inspections beyond those within the scope of the basic home inspection.

6. In the event of a claim against INSPECTOR, CLIENT agrees to supply INSPECTOR with the following: (1) Written notification of adverse conditions within 14 days of discovery, and (2) Access to the premises. Failure to comply with the above conditions will release INSPECTOR and its agents from any and all obligations.

7. HOLD HARMLESS AGREEMENT: CLIENT agrees to hold any and all real estate agents involved in the purchase of the property to be inspected harmless and keep them exonerated from all loss, damage, liability or expense occasioned or claimed by reasons of acts or neglects of the INSPECTOR or his employees or visitors or of independent contractors engaged or paid by INSPECTOR for the purpose of inspecting the subject home.

8. In the event that CLIENT fails to prove any adverse claims against INSPECTOR in a court of law, then the CLIENT will pay all legal costs, expenses and fees of INSPECTOR in defending said claims.

9. If any provision of this Agreement is declared invalid or unenforceable by any court, the remaining provisions will remain in effect. This agreement represents the entire agreement between the parties. No change or modification shall be enforceable against any party unless such change or modification is in writing and signed by the parties. This Agreement shall be binding upon and enforceable by the parties and their heirs, executors, administrators, successors and assigns. CLIENT shall have no cause of action against INSPECTOR after one year after from the date of the inspection.

10. Payment, by CLIENT or CLIENTs representative, is due in full at the inspection site, upon completion of the on-site inspection. The CLIENT will pay all legal and time expenses incurred in collecting due payments.




"A Home Inspection is a Non-Invasive Visual Examination of a Residential Dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or other essential systems or portions of the home, as identified and agreed to by the Client and Inspector, such as: Roof ~ Exterior ~ Basement / Foundation ~ Heating Cooling ~ Plumbing ~ Electrical ~ Fireplace ~ Attic & Insulation ~ Doors, Windows & Interior."
From NACHI Standards of Practice


"There are conditions that require the removal of some part of the building to observe, measure, or test otherwise concealed construction. Such intrusive inspections require some demolition and should be performed only with the permission of the owner and by experienced, qualified mechanics."
-From the U.S. Department of Housing and Urban Development's
Residential Rehabilitation Inspection Guide, 2000


- HOMES BEING INSPECTED DO NOT "PASS" OR "FAIL" -
A home inspector merely discloses his or her findings and reports those findings to the client. Everyone involved graduates to a state of higher learning, and the client can now make better informed decisions about the purchase of a home and its future needs of upkeep and repair.

Four key areas of most home/building inspections cover the exterior, the basement or crawlspace areas, the attic or crawlspace areas and the living areas. Inspectors typically will spend sufficient time in all of these areas to visually look for a host of red flags, tell-tale clues and signs or defects and deficiencies.

The inspected areas of a home/building will consist of all of the major visible and accessible electro-mechanical systems as well as the major visible and accessible structural systems and components of a building as they appeared and functioned at the time and date of the inspection.

Inspectors typically do not provide warranties or guaranties with their inspections and reports. Buyers should therefore not rely on the inspection as any form of insurance policy against any latent, hidden, concealed or future defects and deficiencies.

The following are also some key items that buyers should remember and consider when reviewing their inspection reports:
* Inspections are not code compliance evaluations.
* Inspection reports are not structural engineering reports.
* Systems and components that are off during the inspection are not tested or reactivated.
* Buyers should consult with and ask questions of owners and their representatives.
* Roof inspections and their components are typically done from eaves or street level with binoculars.
* Reports are confidential and are meant exclusively for buyers, and not brokers or owners.
* Inspectors typically will not find each and every defect in a building, hence buyers should anticipate future typical defects and deficiencies.
* Further evaluation by specialists is recommended for any areas showing defects/deficiencies.
* A final walk-through inspection should be carried out the day before closing by the new owners to double check the condition of the building.



Limitations:
I. An inspection is not technically exhaustive.
II. An inspection will not identify concealed or latent defects.
III. An inspection will not deal with aesthetic concerns or what could be deemed matters of taste, cosmetic, etc.
IV. An inspection will not determine the suitability of the property for any use.
V. An inspection does not determine the market value of the property or its marketability.
VI. An inspection does not determine the advisability or inadvisability of the purchase of the inspected property.
VII. An inspection does not determine the life expectancy of the property or any components or systems therein.
VIII. An inspection does not include items not permanently installed.
IX. These Standards of Practice apply only to homes with four or fewer dwelling units.

Exclusions:
I. The inspectors are not required to determine:
A. Property boundary lines or encroachments.
B. The condition of any component or system that is not readily accessible.
C. The service life expectancy of any component or system.
D. The size, capacity, BTU, performance, or efficiency of any component or system.
E. The cause or reason of any condition.
F. The cause for the need of repair or replacement of any system or component.
G. Future conditions.
H. The compliance with codes or regulations.
I. The presence of evidence of rodents, animals or insects.
J. The presence of mold, mildew or fungus.
K. The presence of air-borne hazards.
L. The presence of birds.
M. The presence of other flora or fauna.
N. The air quality.
O. The existence of asbestos.
P. The existence of environmental hazards.
Q. The existence of electro-magnetic fields.
R. The presence of hazardous materials including, but not limited to, the presence of lead in paint.
S. Any hazardous waste conditions.
T. Any manufacturer recalls or conformance with manufacturer installation or any information included in the consumer protection bulletin.
U. Operating costs of systems.
V. Replacement or repair cost estimates.
W. The acoustical properties of any systems.
X. Estimates of how much it will cost to run any given system.

II. The inspectors are not required to operate:
A. Any system that is shut down.
B. Any system that does not function properly.
C. Or evaluate low voltage electrical systems such as, but not limited to:
1. Phone lines.
2. Cable lines.
3. Antennae.
4. Lights.
5. Remote controls.
D. Any system that does not turn on with the use of normal operating controls.
E. Any shut off valve.
F. Any electrical disconnect or over current protection devices.
G. Any alarm systems.
H. Moisture meters, gas detectors or similar equipment.



III. The inspectors are not required to:

A. Move any personal items or other obstructions,
such as, but not limited to:

1. Throw rugs.
2. Furniture.
3. Floor or wall coverings.
4. Ceiling tiles
5. Window coverings.
6. Equipment.
7. Plants.
8. Ice.
9. Debris.
10. Snow.
11. Water.
12. Dirt.
13. Foliage.
14. Pets

B. Dismantle, open, or uncover any system or component.
C. Enter or access any area which may, in the opinion of the inspector, to be unsafe or risk personal safety.
D. Enter crawlspaces or other areas that are unsafe or not readily accessible.
E. Inspect underground items such as, but not limited to, underground storage tanks or other indications of their presence, whether abandoned or actively used.
F. Do anything which, in the inspector's opinion, is likely to be unsafe or dangerous to the inspector or others or damage property, such as, but not limited to, walking on roof surfaces, climbing ladders, entering attic spaces or negotiating with dogs.
G. Inspect decorative items.
H. Inspect common elements or areas in multi-unit housing.
I. Inspect intercoms, speaker systems, radio-controlled, security devices or lawn irrigation systems.
J. Offer guarantees or warranties.
K. Offer or perform any engineering services.
L. Offer or perform any trade or professional service other than home inspection.
M. Research the history of the property, report on its potential for alteration, modification, extendibility, or its suitability for a specific or proposed use for occupancy.
N. Determine the age of construction or installation of any system structure, or component of a building, or differentiate between original construction or subsequent additions, improvements, renovations or replacements thereto.
O. Determine the insurability of a property.