High Desert Inspections

http://HighDesertInspections.com
5645 E Hidden Valley Dr 
Reno NV 89502-9637
Inspector: Matthew Pillsbury
Inspector's email: HighDesertInspections@gmail.com
Inspector's phone: (775) 360-6105
Title picture

Property Inspection Report
Unofficial version!

Client(s): Nancy Cowie and Janet Brooks
Property address: 10510 Whiskey Jack Ct
Truckee CA 96161-2765
Inspection date: Monday, May 5, 2025

This report published on Monday, May 5, 2025 11:22:36 PM PDT

Appears Serviceable is defined as: fulfilling its function adequately; usable; in working order.

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings
View summary

General InformationTable of contents
Report number: 050525-01
Time started: 10:00
Time finished: 7:00
Present during inspection: Client, Property owner
Client present for discussion at end of inspection: No
Inspector: Matt Pillsbury
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Ground condition: Damp
Recent weather: Dry (no rain)
Overnight temperature: Cold
Inspection fee: 450.00
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1997
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: Furniture or stored items were present
1)  Evidence of rodent infestation was found in the form of feces, urine stains and/or damaged insulation in the attic and/or crawl space. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
https://www.reporthost.com/?SEALUP
https://www.reporthost.com/?TRAPUP
https://www.reporthost.com/?CLEANUP
Photo
Photo 1-1 
Photo
Photo 1-2 
Photo
Photo 1-3 
Photo
Photo 1-4 
Photo
Photo 1-5 
Photo
Photo 1-6 
Photo
Photo 1-7 
Photo
Photo 1-8 
Photo
Photo 1-9 
Photo
Photo 1-10 
Photo
Photo 1-11 
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of retaining walls: Appeared serviceable
Retaining wall material: Concrete
Site profile: Steep slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Asphalt, Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
2)  Hardware for one or more decks, balconies or porches such as joist hangers were significantly corroded. Corroded hardware is more likely to fail prematurely, and is a potential safety hazard. Recommend that a qualified contractor replace significantly corroded hardware as necessary.
Photo
Photo 2-1 
Photo
Photo 2-2 
Photo
Photo 2-3 
Photo
Photo 2-4 
3)  Guardrails at one or more locations with drop-offs higher than 30 inches were damaged and/or missing components, and pose a fall hazard. Recommend that a qualified person repair guardrails as necessary.
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
Photo
Photo 3-4 
Photo
Photo 3-5 
4)  Fungal rot was found in support posts at one or more decks or porches. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 4-1 
Photo
Photo 4-2 
Photo
Photo 4-3 
Photo
Photo 4-4 
Photo
Photo 4-5 
Photo
Photo 4-6 
Photo
Photo 4-7 
Photo
Photo 4-8 
Photo
Photo 4-9 
5)  Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Photo
Photo 5-5 
Photo
Photo 5-6 
6)  The driveway sloped down towards the garage or house. Based on observations made during the inspection, significant amounts of water appear to have accumulated around building foundations in buildings as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing and installing new pavement.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Photo
Photo 6-6 
Photo
Photo 6-7 
Photo
Photo 6-8 
Photo
Photo 6-9 
Photo
Photo 6-10 
Photo
Photo 6-11 
7)  The driveway was undermined in one or more areas, where soil has eroded out from beneath. Recommend that a qualified person repair as necessary to prevent further erosion and undermining.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
8)  The asphalt driveway surface was worn and is prone to developing cracks from water penetration. Recommend that a qualified person reseal the driveway. For more information, visit:
https://www.reporthost.com/?RAD
Photo
Photo 8-1 
Photo
Photo 8-2 
9)  Wooden deck or porch surfaces and/or railings were overdue for normal maintenance. Recommend that a qualified person clean and preserve as necessary. Where decks have been coated with a finish such as opaque stains or paint, it may be too difficult to strip the finish and apply anything but paint or opaque stain. Where transparent stain or penetrating oil has been applied in the past, recommend that a penetrating oil be used. For more information, visit:
https://www.reporthost.com/?PENOIL
https://www.reporthost.com/?DKMAIN
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 
Photo
Photo 9-5 
Photo
Photo 9-6 
Photo
Photo 9-7 
Photo
Photo 9-8 
Photo
Photo 9-9 
Photo
Photo 9-10 
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame, Log
Wall covering: Wood, Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
Anchor bolts or hold downs for seismic reinforcement: Installed
Shear panels for seismic reinforcement: Installed
10)  Fungal rot was found in one or more logs. For example, at butt ends of logs and/or on up-facing log surfaces. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be removed or replaced.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
Photo
Photo 10-5 
Photo
Photo 10-6 
Photo
Photo 10-7 
11)  Some sections of siding and/or trim were deteriorated and/or loose. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 
Photo
Photo 11-6 
Photo
Photo 11-7 
Photo
Photo 11-8 
12)  Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture may enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco may become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
Photo
Photo 12-5 
Photo
Photo 12-6 
Photo
Photo 12-7 
Photo
Photo 12-8 
Photo
Photo 12-9 
13)  Gaps between logs or between logs and chinking were found, or deteriorated chinking was found in one or more areas. Some log homes use milled logs that fit tightly together and are designed so as to not require chinking ("chinkless"). Others do require chinking and possibly "backer rods" between logs for a tight seal. Regardless of the type, when gaps are present repairs should be made to prevent air, moisture and insect infiltration from outside. Typically this is done by applying chinking, which can be synthetic or mortar-based. Recommend that a qualified person apply chinking where necessary. For more information, visit:
https://www.reporthost.com/?LOGCHNK
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
Photo
Photo 13-4 
Photo
Photo 13-5 
Photo
Photo 13-6 
Photo
Photo 13-7 
Photo
Photo 13-8 
Photo
Photo 13-9 
Photo
Photo 13-10 
Photo
Photo 13-11 
Photo
Photo 13-12 
Photo
Photo 13-13 
Photo
Photo 13-14 
Photo
Photo 13-15 
Photo
Photo 13-16 
Photo
Photo 13-17 
Photo
Photo 13-18 
Photo
Photo 13-19 
Photo
Photo 13-20 
14)  One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 14-1 
Photo
Photo 14-2 
Photo
Photo 14-3 
Photo
Photo 14-4 
Photo
Photo 14-5 
Photo
Photo 14-6 
Photo
Photo 14-7 
Photo
Photo 14-8 
Photo
Photo 14-9 
15)  One or more holes or gaps were found in or below the foundation. Vermin may enter the building substructure as a result. Recommend that a qualified person repair as necessary.
Photo
Photo 15-1 
Photo
Photo 15-2 
16)  The transition between one or more decks and the log exterior was substandard. Various techniques are normally used to prevent water intrusion and retention at such locations, including the use of flashing or brackets to separate the deck from the exterior. Without such measures, water can be retained between the deck and logs resulting in high moisture levels. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor knowledgeable in log home construction repair per standard building practices. For more information, visit:
https://www.reporthost.com/?LOGDECK
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Photo
Photo 16-4 
Photo
Photo 16-5 
Photo
Photo 16-6 
Photo
Photo 16-7 
Photo
Photo 16-8 
Photo
Photo 16-9 
17)  The finish on the log exterior was worn, faded or thinning, or mold/mildew was present on logs. The logs can be damaged by moisture. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person prep and refinish the log exterior. Logs should first be cleaned of dirt, grease, mold and mildew with an appropriate cleaner and pressure washer. It is good practice to then apply a preservative (typically borate-based) to prevent rot and insect infestation, before applying the final finish. Ideally the same brand of finish should be applied to minimize problems from incompatible finish products. For more information, visit:
https://www.reporthost.com/?LOGFNSH
https://www.reporthost.com/?LOGMT
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
Photo
Photo 17-5 
Photo
Photo 17-6 
18)  Trees were in contact with or were close to the building at one or more locations. Damage to the building may occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
Photo
Photo 18-4 
Photo
Photo 18-5 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Building exterior
Location of crawl space access point #B: Hall closet
Crawl space access points that were opened and viewed, traversed or partially traversed: A, B
Condition of floor substructure above: Required repairs, replacement and/or evaluation (see comments below)
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Required repairs, replacement and/or evaluation (see comments below)
Insulation material underneath floor above: Fiberglass roll or batt
Condition of vapor barrier: Not applicable, none installed
Vapor barrier present: None visible
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: with vents
19)  Fungal rot was found at one or more sill plates and/or wall sheeting. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 19-1 
Photo
Photo 19-2 
Photo
Photo 19-3 
Photo
Photo 19-4 
Photo
Photo 19-5 
Photo
Photo 19-6 
Photo
Photo 19-7 
Photo
Photo 19-8 
20)  No vapor barrier was installed in the crawl space. This is a conducive condition for wood-destroying organisms due to the likelihood of water evaporating from the soil below up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified contractor install a vapor barrier per standard building practices.
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
21)  Under-floor insulation was missing in many areas. This may result in reduced energy efficiency. Recommend that a qualified contractor repair or replace insulation as necessary. Consider having all insulation replaced.
Photo
Photo 21-1 
Photo
Photo 21-2 
Photo
Photo 21-3 
Photo
Photo 21-4 
Photo
Photo 21-5 
Photo
Photo 21-6 
Photo
Photo 21-7 
Photo
Photo 21-8 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Age of roof surface(s): 1997
Roof inspection method: Traversed
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Gutter and downspout material: Not applicable, none installed
Gutter and downspout installation: None
22)  The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future.
Photo
Photo 22-1 
Photo
Photo 22-2 
Photo
Photo 22-3 
Photo
Photo 22-4 
Photo
Photo 22-5 
Photo
Photo 22-6 
Photo
Photo 22-7 
Photo
Photo 22-8 
Photo
Photo 22-9 
23)  Some composition shingles were cracked. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.

Ridge cap
Photo
Photo 23-1 
Photo
Photo 23-2 
Photo
Photo 23-3 
Photo
Photo 23-4 
Photo
Photo 23-5 
24)  Significant amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
Photo
Photo 24-4 
Photo
Photo 24-5 
25)  Moss was growing on the roof. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate-based chemicals are used for this and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
https://www.reporthost.com/?MOSS
Photo
Photo 25-1 
Photo
Photo 25-2 
Photo
Photo 25-3 
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Location of attic access point #A: first floor, Bathroom
Attic access points that were opened and viewed, traversed or partially traversed: A
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists, Ceiling beams
Condition of insulation in attic (ceiling, skylight chase, etc.): Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Vapor retarder: Installed
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s), Enclosed soffit vents
26)  Ceiling insulation was significantly damaged or deteriorated, apparently by rodents. This may result in reduced energy efficiency and may produce unpleasant odors. For energy efficiency and sanitary reasons, recommend that a qualified contractor replace all ceiling insulation.
Photo
Photo 26-1 
Photo
Photo 26-2 
Photo
Photo 26-3 
Photo
Photo 26-4 
Photo
Photo 26-5 
Photo
Photo 26-6 
Photo
Photo 26-7 
Garage or CarportTable of contents
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Detached, Garage
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 2
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage interior: Required repair or evaluation (see comments below)
Condition of detached garage or carport structure: Required repair, replacement and/or evaluation (see comments below)
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame, Log
Condition of roof structure: Appeared serviceable
Age of roof surface(s): 1997
Roof inspection method: Traversed
Roof type: Gable
Roof surface material: Asphalt or fiberglass composition shingles
27)  The garage floor and driveway are leaking and causing water damage and wood rot. Recommend that a qualified contractor repair as necessary. All rotten wood should be replaced. Note that this may require significant repairs.
Photo
Photo 27-1 
Photo
Photo 27-2 
Photo
Photo 27-3 
Photo
Photo 27-4 
Photo
Photo 27-5 
Photo
Photo 27-6 
Photo
Photo 27-7 
Photo
Photo 27-8 
Photo
Photo 27-9 
Photo
Photo 27-10 
Photo
Photo 27-11 
Photo
Photo 27-12 
Photo
Photo 27-13 
Photo
Photo 27-14 
Photo
Photo 27-15 
28)  Some sections of siding and/or trim were deteriorated, damaged and/or rotten. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 28-1 
Photo
Photo 28-2 
Photo
Photo 28-3 
Photo
Photo 28-4 
Photo
Photo 28-5 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 125
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 125
System ground: Concrete encased electrode
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Building exterior
Location of main service panel #B: Garage
Location of sub-panel #C: Under stair closet
Location of main disconnect: At main disconnect panel outside
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Branch circuit wiring type: non-metallic sheathed, copper
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Installed and appear to be functioning properly at this time
Carbon monoxide alarms installed: Yes and appeared to be working property at this time
Smoke alarm power source(s): Battery
29)  One or more cover plates for switches, receptacles or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 29-1 
Photo
Photo 29-2 
30)  The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Photo
Photo 30-1 
Photo
Photo 30-2 
31)  One or more light fixtures/ceiling fans were inoperable (didn't turn on when nearby switches were operated). Recommend that a qualified electrician evaluate and repair or replace fixtures as necessary.
Photo
Photo 31-1 
32)  Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 32-1 
Photo
Photo 32-2 
Photo
Photo 32-3 
Photo
Photo 32-4 
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water meter: By street
Location of main water shut-off: Crawl space, Building exterior
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Required repair, replacement and/or evaluation (see comments below)
Drain pipe material: Plastic
Condition of waste lines: Required repair, replacement and/or evaluation (see comments below)
Waste pipe material: Plastic
Location(s) of plumbing clean-outs: Crawl space, Building exterior
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Sewage ejector pump installed: No
Type of irrigation system supply source: Public
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: None visible
Location of main fuel shut-off valve: At gas meter
33)  One or more leaks were found in drain and/or waste pipes or fittings. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 33-1 
Photo
Photo 33-2 
Photo
Photo 33-3 
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Near, at or beyond service life
Type: Tank
Energy source: Natural gas
Estimated age: 1997
Capacity (in gallons): Not determined (label obscure or inaccessible)
Temperature-pressure relief valve installed: Yes
Manufacturer: Not determined (label obscure or inaccessible)
Location of water heater: Crawl space
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
34)  A permanently installed insulated jacket was installed on the water heater. It obscured the manufacturer's information label and/or most of the water heater. The inspector was unable to fully evaluate the water heater.
Photo
Photo 34-1 
35)  The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 35-1 
Photo
Photo 35-2 
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of electric heaters (not forced air): Appeared serviceable
Electric heater type (not forced air): Wall mounted
Condition of forced air heating/(cooling) system: Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 1997
Forced air heating system manufacturer: Goodman
Forced air furnace model #: GMPN100-4 REV A
Forced air furnace serial number: 9711832653
Location of forced air furnace: Crawl space
Forced air system capacity in BTUs or kilowatts: 90,500
Condition of furnace filters: Required replacement
Location for forced air filter(s): Behind return air grill(s)
Condition of forced air ducts and registers: Required repair, replacement and/or evaluation (see comments below)
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
Condition of controls: Appeared serviceable
36)  The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
https://www.reporthost.com/?ANFURINSP
Photo
Photo 36-1 
Photo
Photo 36-2 
Photo
Photo 36-3 
Photo
Photo 36-4 
37)  The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo
Photo 37-1 
Photo
Photo 37-2 
Photo
Photo 37-3 
38)  The air handler's primary condensate drain line was missing. Significant amounts of water can be produced by this system. Recommend repairing as necessary so condensate water drains well away from the foundation. For example, by installing a line outside.
Photo
Photo 38-1 
Photo
Photo 38-2 
Photo
Photo 38-3 
39)  One or more heating or cooling air supply registers were missing. The air flow cannot be controlled as a result. Recommend installing registers where missing.

1st floor bathroom,
Photo
Photo 39-1 
40)  Recommend that home buyers replace or clean HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or cleaning them as necessary. How frequently they need replacing or cleaning depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Required repair, replacement and/or evaluation (see comments below)
Gas fireplace or stove type: Metal pre-fab fireplace
Fan or blower installed in gas-fired fireplace or stove: Yes
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: Direct vent
41)  Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit:
https://www.reporthost.com/?ANGFINSP
Photo
Photo 41-1 
Photo
Photo 41-2 
Photo
Photo 41-3 
42)  The glass front on the gas fireplace had a hazy film. This is typically a mineral residue left from water vapor as the gas burns. It may be possible to clean this fogging by removing the glass from the fireplace and using a gas appliance ceramic glass cleaner, available through gas fireplace and stove distributors and installers. Ammonia-based products, such as common glass cleaners, should not be used since they can cause damage or etching to the glass, or make the haze permanent. It may be possible for a homeowner to remove the glass for cleaning, if the instructions for the fireplace are available and if the homeowner is experienced in such repairs. Consult with a qualified specialist for more information, or to have them do the cleaning.
Photo
Photo 42-1 
Photo
Photo 42-2 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Oven, Cooktop, Dishwasher, Refrigerator, Under-sink food disposal
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Required repair, replacement and/or evaluation (see comments below)
Condition of ranges, cooktops and/or ovens: Required repair, replacement and/or evaluation (see comments below)
Range, cooktop, oven type: Natural gas
Type of ventilation: Down draft exhaust
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Condition of hot water dispenser: N/A (none installed)
Condition of trash compactor: N/A (none installed)
43)  The cooktop downdraft exhaust fan was damaged, fan would not retract. Recommend that a qualified person repair as necessary.
Photo
Photo 43-1 
44)  Gaps, no caulk, or substandard caulking were found between countertops and backsplashes and/or around the sink. Water may penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing caulk.
Photo
Photo 44-1 
Photo
Photo 44-2 
Photo
Photo 44-3 
Photo
Photo 44-4 
Photo
Photo 44-5 
Photo
Photo 44-6 
Photo
Photo 44-7 
Photo
Photo 44-8 
Photo
Photo 44-9 
45)  Many cabinet door handles or drawer pulls were missing. Where operation is difficult, recommend installing handles and/or pulls.
Photo
Photo 45-1 
Photo
Photo 45-2 
Photo
Photo 45-3 
Photo
Photo 45-4 
46)  Water was leaking at the sink faucet base or handles. Recommend that a qualified plumber repair as necessary.

Downstairs sink,
Photo
Photo 46-1 
Photo
Photo 46-2 
Photo
Photo 46-3 
Photo
Photo 46-4 
47)  The dishwasher wasn't securely attached to the counter or cabinets. Fasteners were missing and/or substandard. Recommend that a qualified person install fasteners per standard building practices.
Photo
Photo 47-1 
Photo
Photo 47-2 
Photo
Photo 47-3 
48)  The sink had minor wear, blemishes or deterioration.
Photo
Photo 48-1 
Photo
Photo 48-2 
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: 3/4 bath, first floor
Location #B: 3/4 bath, second floor
Location #C: Laundry room/area, second floor
Location #D: Half bath, Garage
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
Bathroom and laundry ventilation type: Windows
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: No
49)  The toilet at location(s) #B was loose where it attached to the floor. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 49-1 
50)  Pedestal sink, at location(s) #A was loose. Recommend repairing or replacing as necessary.
Photo
Photo 50-1 
51)  The bathroom with a shower or bathtub at location(s) #A and B didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified contractor install exhaust fans per standard building practices where missing in bathrooms with showers or bathtubs.
Photo
Photo 51-1 
Photo
Photo 51-2 
52)  Water damage was found in shelving or cabinet components below one or more sinks at location(s) #B. Recommend that a qualified contractor repair as necessary after any plumbing leaks have been repaired. If moisture is present then concealed areas should be dried thoroughly.
Photo
Photo 52-1 
Photo
Photo 52-2 
53)  The toilet tank was cracked or broken at location(s) #A. Recommend that a qualified plumber replace toilet(s) or components as necessary. Where cracks have resulted in leaks, additional repairs due to water damage may be needed.

was loose
Photo
Photo 53-1 
Photo
Photo 53-2 
54)  One or more leaks were found at the toilet at location(s) #D. A qualified plumber should repair as necessary.
Photo
Photo 54-1 
55)  The shower head at location(s) #B was leaking. Recommend that a qualified person repair as necessary.
Photo
Photo 55-1 
Photo
Photo 55-2 
56)  The laundry room didn't have an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified contractor install an exhaust fan per standard building practices.
Photo
Photo 56-1 
57)  Tile, stone and/or grout in the flooring at location(s) #B was deteriorated (e.g. loose or cracked tiles, missing grout) or substandard. Water can damage the sub-floor as a result. Recommend that a qualified contractor repair as necessary.
Photo
Photo 57-1 
Photo
Photo 57-2 
Photo
Photo 57-3 
Photo
Photo 57-4 
58)  Tile, caulk and/or grout in the shower enclosure at location(s) #A and B were deteriorated (e.g. loose or cracked tiles, missing grout) or substandard. Water may leak through gaps and damage the wall or floor structure as a result. Recommend that a qualified contractor repair as necessary. Note that the condition of the structure behind and below the shower enclosure is unknown due to it being concealed.
Photo
Photo 58-1 
Photo
Photo 58-2 
Photo
Photo 58-3 
Photo
Photo 58-4 
Photo
Photo 58-5 
Photo
Photo 58-6 
Photo
Photo 58-7 
Photo
Photo 58-8 
Photo
Photo 58-9 
Photo
Photo 58-10 
59)  The sink drain stopper mechanism at location(s) #B was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 59-1 
60)  Caulk around the base of the toilet at location(s) #B was missing, substandard and/or deteriorated. Modern standards require caulk to be installed around the entire toilet base where it meets the floor for sanitary reasons. Without it, soiled water can soak into flooring and sub-floor materials if the toilet overflows. Condensation from the toilet can also soak into the flooring. Recommend that a qualified person caulk around toilet bases per standard building practices.
Photo
Photo 60-1 
Photo
Photo 60-2 
61)  Rubber water supply hoses were installed at the clothes washer. These hoses are prone to bursting when deteriorated, which can result in flooding and significant water damage. Recommend upgrading to braided, stainless steel hoses.
Photo
Photo 61-1 
Photo
Photo 61-2 
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood, Metal, Glass panel, Sliding glass
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Wood, Metal, Casement
Condition of walls and ceilings: Required repairs, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall
Ceiling type or covering: Drywall, Wood & beam
Condition of flooring: Appeared serviceable
Flooring type or covering: Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
62)  The seal between multi-pane glass in one or more sliding glass doors appeared to have failed based on condensation or stains between the panes of glass. Recommend that a qualified contractor evaluate and replace glass where necessary.

Be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Glass doors or windows other than those that the inspector identified may also have failed seals and need glass replaced too.
Photo
Photo 62-1 
Photo
Photo 62-2 
Photo
Photo 62-3 
63)  Fungal rot was found at one or more exterior door jambs. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo
Photo 63-1 
Photo
Photo 63-2 
Photo
Photo 63-3 
64)  One or more exterior doors were sticking. Recommend that a qualified person repair as necessary.
Photo
Photo 64-1 
Photo
Photo 64-2 
65)  One or more sliding glass doors were difficult to open or close. Recommend that a qualified person maintain, repair or replace door(s) as necessary. Often, cleaning the track and applying a lubricant will help.
Photo
Photo 65-1 
Photo
Photo 65-2 
Photo
Photo 65-3 
66)  Crank handles at some windows were missing and/or loose. Recommend that a qualified person replace handles or make repairs as necessary.
Photo
Photo 66-1 
Photo
Photo 66-2 
Photo
Photo 66-3 
Photo
Photo 66-4 
Photo
Photo 66-5 
Photo
Photo 66-6 
67)  One or more walls were cracked and/or had substandard repairs. Recommend that a qualified person repair as necessary.

Master bedroom, downstairs bathroom
Photo
Photo 67-1 
Photo
Photo 67-2 
Photo
Photo 67-3 
Photo
Photo 67-4 
68)  The lock mechanisms on one or more sliding glass doors were inoperable. Recommend that a qualified person repair as necessary.
Photo
Photo 68-1 
Photo
Photo 68-2 
Wood Destroying Organism FindingsTable of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: Yes
Visible evidence of active wood decay fungi: Yes
Visible evidence of past wood-destroying insects: Yes
Visible evidence of past wood decay fungi: Yes
Visible evidence of damage by wood-destroying insects: Yes
Visible evidence of damage by wood decay fungi: Yes
Visible evidence of conditions conducive to wood-destroying organisms: Yes
Location #A: Front of garage
Location #B: Garage floor
69)  Evidence of active infestation of carpenter ants was found at location(s) #A and B in the form of live insects with visible wood damage. Recommend the following:
  • Correct any conducive conditions for wood-destroying organisms mentioned in this report.
  • Consult with the property owner about any history of infestation.
  • Have a state-licensed pest control operator evaluate further and treat as necessary.
Photo
Photo 69-1 
Photo
Photo 69-2 
Photo
Photo 69-3 
Photo
Photo 69-4 
Photo
Photo 69-5 
Photo
Photo 69-6