View summary

Habitation Investigation

https://www.homeinspectionsinohio.com
(614) 413-0075 · (937) 205-4758
Inspector: Laura Troth
Title picture

Inspection Report
Unofficial version!

Client(s): New Build Client
Property address: Pre-Drywall Inspection
Commercial Point OH 43116
Inspection date: Friday, August 15, 2025

This report published on Thursday, October 16, 2025 12:33:59 PM EDT

"No home is perfect. Keep things in perspective. Do not kill your deal over things that do not matter. It is inappropriate to demand that a seller address deferred maintenance, conditions already listed on the seller's disclosure or nit-picky items."

The above is an excerpt from Sell Your Home For More by Nick Gromicko.

Acceptance of this report and/or relying on the information within constitutes acceptance of the real estate inspection agreement limits for the client listed above even if the agreement is not signed. Reliance on a home inspection report that was originally performed for a different home buyer removes warranties. Home Inspections are not a pass/fail. The purpose is to identify the condition of the home as much as can be done at the time of the inspection. It is out of the scope of the home inspection to give estimates for repairs. We recommend that contractors be utilized prior to closing to provide repair estimates.

If you are not the person identified as the client above then you need to attain permission from the client above and you need to have your own home inspection completed.

It is not typical to request to remedy those items which are small maintenance items. Your real estate agent will be your best source to help determine which items (if any) are appropriate to request for correction or improvement

Table of Contents

General Information
Foundation, Basement and Grounds
Exterior Wall Coverings
Electric System
HVAC System and Mechanical
Plumbing
Floor System
Wall System
Interiors, Windows and Doors
Roof System
Roof Covering
Fireplaces, Decorative Gas Appliances and Chimneys
View summary

General InformationTable of contents
Present during inspection: Client
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Hot
Ground condition: Dry
Recent weather: Dry (no rain)
Overnight temperature: Warm
Type of building: Single family residence
IMPORTANT NOTE: If repairs are recommended in this report, they should be performed by a qualified, licensed contractor. Repairs should be made in accordance with national and local building codes, the designer's specifications, and per the installation instructions of the manufacturer of the building materials or components. Some municipalities have requirements that exceed national requirements, such as those in areas prone to high winds, floods, snow or earthquakes. This is not a code inspection. It is not the inspector's responsibility to understand these requirements and recommend (or not recommend) specific repairs based on the property's location. Blueprint reading and verification of is outside the scope of the pre drywall inspection.
Foundation, Basement and GroundsTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the foundation and crawl space. Below-grade foundation walls and footings are excluded from this inspection. Some amount of cracking is normal in foundation walls and concrete slabs due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. Crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.

For more information, visit: http://www.reporthost.com/?FOUNDATION
Rough grade: Not completed
Footing material (under foundation stem wall): Not visible
Foundation type: Concrete slab on grade
Foundation/stem wall material: Poured in place concrete
Perimeter drain present: No
Anchor bolts or hold downs for seismic reinforcement: Installed
1) Repair/Replace -  Grading is sloped to direct water towards the foundation. Exterior grading should be completed to help ensure proper drainage. Consider additional soil to account for the normal settling that will occur.
Photo
Photo 1-1 
Photo
Photo 1-2 
Photo
Photo 1-3 
2) Repair/Maintain -  Wooden form used to frame in the pouring of concrete was not yet removed. Recommend removal to reduce conducive condition for wood destroying insects.
Photo
Photo 2-1 
3) Repair/Maintain -  Based on the observed slope, standing water or evidence of past standing water (e.g. sediment, mud) one or more drains should be installed in . Consult with the builder about this.
4) Comment -  One or more hairline cracks were found in the concrete slab floor(s). These are common in large, poured concrete slabs, especially when control joints are not installed to control cracking. They may not be a structural concern. Regardless, consult with the builder about them.
Photo
Photo 4-1 
Photo
Photo 4-2 
5) Comment -  Anchor bolts or tie downs were observed. They were in good condition and positioning.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Exterior Wall CoveringsTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall covering: Wood
Type of underlayment: House wrap
6) Repair/Maintain -  One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 6-1 
Photo
Photo 6-2 
7) Repair/Maintain -  House wrap was missing/incomplete in areas. Recommend repairing/improving.
Photo
Photo 7-1 
8) Repair/Maintain -  Gaps exist at openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and conditioned air loss. Inspector is unable to determine condition of underlying material.
Photo
Photo 8-1 
9) Comment -  Tyvek wrap was installed and was taped appropriately so as to help prevent moisture intrusion.
Photo
Photo 9-1 
Photo
Photo 9-2 
10)   -  Exterior siding was not yet installed.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Electric SystemTable of contents
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 200
Service entrance conductor material: Stranded aluminum
System ground: Ground rod(s) in soil
Location of main service panels: Building exterior
Location of sub-panels: Garage
Branch circuit wiring type: Non-metallic sheathed
11) Safety, Repair/Replace, Serviceable -  Loose bracing for at least two electrical boxes.

Recommend repairs.
Photo
Photo 11-1 
Photo
Photo 11-2 
12) Comment -  Wiring was roughed in for various locations such as outlets and lights however outlets and fixtures not yet installed.

Recommend having all outlets tested prior to close
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
13) Comment -  Electric panel and meter not fully installed yet.
Photo
Photo 13-1 
Photo
Photo 13-2 
HVAC System and MechanicalTable of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
Heating system #1 type: Forced air
Heating system #1 energy source: Natural gas
Heating system #1 distribution type: Ducts and registers
General cooling system type: Split system
Cooling system and/or heat pump energy source: Electric
Gas service type: Natural gas
Gas piping material: Steel pipe, Corrugated stainless steel (CSST)
14) Comment -  Not fully installed yet. Not tested.
Photo
Photo 14-1 
Photo
Photo 14-2 
15) Comment -  Underground gas pipe and/or meter not yet installed.
Photo
Photo 15-1 
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Service pipe material: Plastic
Interior supply pipe material: PEX plastic
Interior drain, waste and vent pipe material: Plastic
Water heater #1 type: Tank
Water heater #1 energy source: Electric
16) Comment -  Your water meter and shut off location.

Water meter not yet installed.
Photo
Photo 16-1 
17) Comment -  Water heater was not installed/fully installed. Not able to test
Photo
Photo 17-1 
Floor SystemTable of contents
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by insulation or lack of access are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

For information on floor construction, visit: http://www.reporthost.com/?FRMFLOOR
For information on under-floor insulation, visit: http://www.reporthost.com/?INSFLOOR
Pier or support post material: Engineered
Beam material: Engineered
Floor structure above: Engineered, Concrete slab
Sub-floor sheathing: Oriented strand board (OSB), Concrete slab
18) Comment -  Generally the flooring system (engineered joists) was in good condition.
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
Limitations: Structural components such as studs and support posts, and other components such as piping, wiring and/or ducting that are obscured by wall insulation are excluded from this inspection. The inspector does not determine if studs, support posts, sill plates, bottom plates, top, connectors etc. are of adequate size, spanning or spacing. For information on wall construction, visit: http://www.reporthost.com/?FRMWALLFor information on wall insulation, visit: http://www.reporthost.com/?INSWALL
Vertical wall structure: Wood
Wall bracing type: Gypsum board
19) Comment -  Generally the wall system was in good condition.
Photo
Photo 19-1 
Photo
Photo 19-2 
Photo
Photo 19-3 
Photo
Photo 19-4 
Interiors, Windows and DoorsTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Exterior door material: Metal
Type(s) of windows: Vinyl
20) Comment -  Windows were tested and all operated.
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
Photo
Photo 20-4 
21) Comment -  Interior doors not installed yet
Photo
Photo 21-1 
Photo
Photo 21-2 
Limitations: Structural components such as rafters, joists and trusses, and other components such as piping, wiring and/or ducting that are obscured by insulation or lack of access are excluded from this inspection. The inspector does not determine if rafters, joists, purlins, collar ties, rafter ties, trusses, etc. are of adequate size, spanning or spacing. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so.

For more information, visit: http://www.reporthost.com/?FRMROOF
Roof structure type: Trusses
Ceiling structure: Trusses
Roof sheathing material: Oriented strand board (OSB)
Roof ventilation type: Ridge vent(s) Soffit(s) comb0
22) Repair/Replace -  Gutters were not installed / missing. Recommend installing to help control water and to direct it away from the foundation.
Photo
Photo 22-1 
Photo
Photo 22-2 
23)   -  No roof structure concerns were observed.
Photo
Photo 23-1 
Photo
Photo 23-2 
Photo
Photo 23-3 
Photo
Photo 23-4 
Roof CoveringTable of contents
Limitations: Some items were not visible or readily accessible such waterproof or ice dam membranes and are excluded from this inspection. Solar heating/roofing components are also excluded. Any comments made regarding these items are made as a courtesy only. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.

For more information, visit: http://www.reporthost.com/?ROOF
Roof inspection method: Pole camera
Roof surface material: Asphalt or fiberglass composition shingles
24) Comment -  The roof covering was generally in good condition and roof penetrations were installed properly.
If small concerns were also identified, be certain to have those addressed.
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
Photo
Photo 24-4 
Photo
Photo 24-5 
Photo
Photo 24-6 
Photo
Photo 24-7 
Photo
Photo 24-8 
Photo
Photo 24-9 
Photo
Photo 24-10 
Photo
Photo 24-11 
Photo
Photo 24-12 
25) Comment -  The plumbing vent type rubber boot(s) were in good condition.
Photo
Photo 25-1 
Photo
Photo 25-2 
Fireplaces, Decorative Gas Appliances and ChimneysTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Wood-burning type: Metal pre-fab fireplace
26) Comment -  Gas fireplace insert not fully installed. Not tested.
Photo
Photo 26-1