Inspector: Timber Turner
ASHI Lic #262353
Title picture Title picture

Gem State Home Inspections
Unofficial version!

Client(s): Commercial Building
Property address: 7777 Commerce Dr.
Coeur D Alene ID 83815-8780
Inspection date: Saturday, October 22, 2022

This report published on Tuesday, October 3, 2023 5:59:29 AM PDT

Please understand that there are limitations to this inspection. Many components of the home are not visible during the inspection and very little historical information is provided in advance of the inspection. While we can reduce your risk of purchasing a home, we cannot eliminate it, nor can we assume it. Even the most comprehensive inspection cannot be expected to reveal every condition you may consider significant to ownership.

ASHI Certified Inspector
Click to verify
Click to verify
Monroe Certified Infrared Thermographer Passed the National Home Inspector ExaminationState of Idaho MFD Home Certifications

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeRepair RecommendedItem was not functioning as designed or intended. Correction should be performed, and may require a professional, specialist, or other knowledgeable person.
Concern typeMaintenance ReminderRecommend routine attention and maintenance to keep item in proper working condition.
Concern typeInvestigate FurtherRecommend additional investigation, research, or review by a specialist and/or client
Concern typeInformational CommentReport comment included for your information and consideration.

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation & A/C (HVAC) 6 units
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Offices, Interior, Doors and Windows
Detached Office
View summary

General InformationTable of contents
Time started: 8:00
Client present for discussion at end of inspection: No
Inspector: Timber and Patrick
Weather conditions during inspection: Cloudy
Temperature during inspection: Cold
Type of building: Commercial
Age of main building: 2008
Source for main building age: Municipal records or property listing
Occupied: Yes, Furniture or stored items were present
1)  To view the summary. Click on the link in the upper left hand corner or under table contents.
2)  Evidence of pest activity was found in the form of dead bird and nesting material (both north and south side) in the attic and dead rodent in the crawlspace. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.reporthost.com/?SEALUP
http://www.reporthost.com/?TRAPUP
http://www.reporthost.com/?CLEANUP
Photo
Photo 2-1 
Photo
Photo 2-2 
Photo
Photo 2-3 
Photo
Photo 2-4 
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Fence and gate material: Chain link
Site profile: Level
Driveway material: Asphalt
Sidewalk material: Poured in place concrete
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Deck, porch and/or balcony material: Concrete
Exterior stair material: Concrete
3)  Minor cracks and spalling was found in the driveway and front sidewalk. Spalling is common in our area due to deicers. Client should monitor and consider sealing cracks. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo
Photo 3-1 
Photo
Photo 3-2 
Photo
Photo 3-3 
Photo
Photo 3-4 
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Apparent wall structure: Wood frame
Wall covering: Cement fiber, Stone or faux stone veneer
Apparent foundation type: Crawl space, Finished basement
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
4)  Untreated wood was in contact with concrete or masonry at the exterior. Moisture can collect between the two materials and wick up into the wood. Wood should be installed with a minimum clearance of 1-2 inches between it and concrete or masonry below it at building exteriors. Monitor these areas for rot or infestation in the future and repair if needed.
Photo
Photo 4-1 
Photo
Photo 4-2 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Closet
Location of crawl space access point #B: Office
Crawl space access points that were opened and viewed, traversed or partially traversed: A, B
Sub-floor material: Oriented strand board
Pier or support post material: Bearing wall
Floor structure above: Engineered wood joists
Insulation material underneath floor above: Fiberglass roll or batt
Vapor barrier present: Yes
Ventilation type: with vents
5)  Under-floor insulation and insulation around heating ducts was falling down and missing in some areas. This may result in reduced energy efficiency and leave pipes susceptible to freezing. Recommend that a qualified person repair or replace insulation as necessary.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Photo
Photo 5-5 
Photo
Photo 5-6 
Photo
Photo 5-7 
Photo
Photo 5-8 
Photo
Photo 5-9 
Photo
Photo 5-10 
6)  The vapor barrier in some areas of the crawl space was loose or askew. Soil was exposed as a result and will allow water from the soil to evaporate up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified person replace or repair the vapor barrier where necessary and per standard building practices.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
7)  Minor microbial staining was visible on floor sheathing in the crawlspace. Such staining usually occurs due to elevated humidity in the crawlspace, and subsequent elevated moisture levels in the sheathing. When humid crawlspace conditions have been corrected, it's likely that such staining will stop growing. Mold abatement specialists can remediate current microbial staining which typically involves the following:
  • Clean microbial staining from wood surfaces
  • Treat wood surfaces with mildewcides
  • Prime wood with special primers
Note that the inspector is not a mold specialist or industrial hygienist and provides no professional opinion on health issues related to microbial growth.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
Photo
Photo 7-4 
8)  A crawlspace exhaust fan was installed. However the inspector was unable to operate the fan or fully evaluate it because inspector could not find a switch and/or thermostat. Recommend asking current owner's regarding operation. Exhaust fans help reduce humid conditions in crawlspace and reduce the chance of microbial staining. See above for further discussion.
Photo
Photo 8-1 
Photo
Photo 8-2 
Photo
Photo 8-3 
Photo
Photo 8-4 
9)  The crawl space was dry at time of inspection. Note that all crawlspace areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
Photo
Photo 9-4 
Photo
Photo 9-5 
Photo
Photo 9-6 
Photo
Photo 9-7 
Photo
Photo 9-8 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future.
Roof inspection method: Traversed
Roof surface material: Architectural shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Gutter and downspout material: Metal
Gutter and downspout installation: Partial
10)  Roofing nails weren't fully seated and shingles were lifting and nail heads were protruding through shingle surfaces. The nails may have loosened, or were not pounded in fully when installed. Shingles are likely to be wind damaged, and leaks can occur as a result. Recommend that a qualified contractor repair as necessary.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
Photo
Photo 10-5 
Photo
Photo 10-6 
Photo
Photo 10-7 
Photo
Photo 10-8 
Photo
Photo 10-9 
Photo
Photo 10-10 
Photo
Photo 10-11 
Photo
Photo 10-12 
11)  Moss was growing on the roof. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate-based chemicals are used for this and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
http://www.reporthost.com/?MOSS
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
12)  Kick-out flashing was missing at roof locations. Such flashing should be located at the bottom of slopes where roof surfaces intersect with exterior walls above. It directs rainwater away from exterior walls and into gutters so that rainwater is less likely to run down the front surfaces of siding or flow behind siding. Depending on the exposure (e.g. roof overhang, height of exterior wall, direction of prevailing rain) this may or may not be an issue. Recommend that a qualified contractor install kickout flashings where missing and per standard building practices.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
13)  Architectural roofing has an average life expectancy between 25 to 35 years depending on the weather conditions and attic ventilation.

http://www.improvementcenter.com/roofing/new-roofing-years-it-can-last.html

Only a partial gutter system was installed. Standard building practices call for gutters, downspouts and extensions to be installed at all lower roof edges to convey water well away from the building foundation. Without a drainage system, the crawlspace or basement below the house, may accumulate water. Foundation footings are also more likely to settle or become undermined. Recommend consulting with a qualified contractor about installing a roof drainage system per standard building practices.

Roof surface sections were designed so as to be prone to accumulating debris and/or snow. For example, where two slopes converge. Accumulated debris in these areas can result in leaks. At a minimum, monitor such areas for accumulated debris in the future and clean as necessary.
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
Photo
Photo 13-4 
Photo
Photo 13-5 
Photo
Photo 13-6 
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so.
Attic inspection method: Traversed
Location of attic access point #A: Hall closet
Location of attic access point #B: Hall closet
Attic access points that were opened and viewed, traversed or partially traversed: A, B
Roof structure type: Trusses
roof material: Plywood
Ceiling structure: Trusses
Ceiling insulation material: Fiberglass roll or batt, Cellulose loose fill
Roof ventilation type: Ridge vent(s), Enclosed soffit vents
14)  Heating or cooling ducts in an unconditioned space (e.g. attic) were not insulated, or the insulation was damaged or deteriorated. This can result in reduced energy efficiency, moisture inside heating ducts, and/or "sweating" on cooling ducts. Recommend that a qualified person repair per standard building practices. For example, by wrapping ducts in insulation with an R-value of R-8.
Photo
Photo 14-1 BLUE arrow pointing to insulated duct
YELLOW arrow pointing to exposed duct
Photo
Photo 14-2 
15)  Attic insulation and venting.
Photo
Photo 15-1 
Photo
Photo 15-2 
Photo
Photo 15-3 
Photo
Photo 15-4 
Photo
Photo 15-5 
Photo
Photo 15-6 
Photo
Photo 15-7 
Photo
Photo 15-8 
16)  Exhaust fan duct for range at the microwave in the attic was not attached to an exterior vent hood or cap. As a result, conditioned air will enter the attic when the fan is operated. This can result in excessive moisture in the attic. No adverse conditions were observed at time of inspection.
Photo
Photo 16-1 
Photo
Photo 16-2 
Limitations: The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 600
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Location of main service panel #A: Building exterior
Location of main service panel #B: Building exterior
Location of sub-panel #C: Building exterior
Location of sub-panel #D: Hall Closet
Branch circuit wiring type: Non-metallic sheathed (AC) Armor clad flexible
Ground fault circuit interrupter (GFCI) protection present: Yes
Smoke alarms installed: Yes
Carbon monoxide alarms installed: Yes
17)  The building meets current standards.

Current safety standards recommend smoke alarms should be installed in each bedroom, in hallways leading to bedrooms, and on each level. They have a limited lifespan and should be replaced every 10 years. Batteries in smoke alarms should be changed when taking occupancy and annually in the future. Carbon monoxide alarms should be installed near sleeping areas and on each level in homes with a fuel-burning appliance or attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
http://www.reporthost.com/?COALRM
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
18)  Equipment for a generator system was found. Generators, transfer switches and any associated wiring are excluded from this inspection. Recommend that the client consult with the property owner or review documentation to familiarize themselves with the operation of this system.
Photo
Photo 18-1 
Photo
Photo 18-2 
19)  Electrical panels were labeled. A recent electrical tag was noted.

Only a cursory evaluation of some panels was performed during the inspection due to the vulnerability of medical equipment. For a full evaluation, the client should hire a qualified electrician.
Photo
Photo 19-1 
Photo
Photo 19-2 
Photo
Photo 19-3 
Photo
Photo 19-4 
Photo
Photo 19-5 
Photo
Photo 19-6 
Photo
Photo 19-7 
Photo
Photo 19-8 
Photo
Photo 19-9 
Photo
Photo 19-10 
Photo
Photo 19-11 
Photo
Photo 19-12 
Photo
Photo 19-13 
Photo
Photo 19-14 
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service: Private well
Location of main water meter: N/A
Location of main water shut-off: Basement, In mechanical room
Service pipe material: Plastic
Supply pipe material: PEX plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
Location(s) of plumbing clean-outs: Building exterior
Vent pipe material: Plastic
Location of main fuel shut-off valve: At gas meter
Location of main fuel shut-off valve: By furnace
20)  A fire suppression system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems normally require periodic inspection by a specialist to ensure correct operation. For example, checking for possible backflow contamination of the potable water system, or correct operation of valves and gauges. Recommend that a qualified specialist inspect this system in accordance with National Fire Prevention Association (NFPA) 25 standards.

Sprinkler pipes were run in unconditioned spaces and were not insulated. When system is serviced, recommend asking specialist about this. Freezing pipes can cause damage.
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
Photo
Photo 20-4 
Photo
Photo 20-5 
Photo
Photo 20-6 
Photo
Photo 20-7 
Photo
Photo 20-8 
Photo
Photo 20-9 
Photo
Photo 20-10 
21)  One sewer clean out was noted at the east side of the building.

Based on the age of this structure, recommend that a qualified plumber inspect the waste lines using a video scope device to determine if they need repair or replacement. Property owners are usually responsible for repairs to the side sewer and publicly owned lateral lines. Such repairs can be expensive.

Photo
Photo 21-1 
22)  Main water shutoff valve is located in basement mechanical room.
Photo
Photo 22-1 
23)  A sewage ejector pump was installed on the premises. Pump cycled at time of inspection. These are specialty systems and not a part of a typical home inspection. These systems are typically sealed and involve moving parts. They are subject to clogging and/or damage from disposal of items such as disposable diapers and sanitary napkins. Recommend that this pump and related equipment (piping, valves, etc.) be evaluated by a qualified plumber and repaired if necessary. This should be done per the manufacturer's recommendations in the future, or annually if unable to verify the manufacturer's recommendations. Typically, these pumps have a lifespan of 7-10 years. For more information, visit:
http://www.reporthost.com/?SEWEJPMP
Photo
Photo 23-1 
24)  Sprinkler systems should be winterized this time of year.

Based on visible equipment, this property appeared to have a yard irrigation (sprinkler) system. These are specialty systems and are not a part of a typical home inspection. A recent backflow test tag was visible dated 2022. Backflow tests are required annually in many municipalities in our area to prevent cross-contamination of potable water.
Photo
Photo 24-1 
25)  Based on visible equipment or information provided to the inspector, the water supply to this property appeared to be from a private well. Private well water supplies are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible and accessible components are evaluated. Recommend the following:
  • That a qualified well contractor fully evaluate the well, including a pump/flow test
  • That the well water be tested per the client's concerns (coliforms, pH, contaminants, etc.)
  • Research the well's history (how/when constructed, how/when maintained or repaired, past performance, past health issues)
  • Document the current well capacity and water quality for future reference
For more information, visit:
http://www.reporthost.com/?WELL
Photo
Photo 25-1 
Photo
Photo 25-2 
Water HeaterTable of contents
Type: Tank
Energy source: Natural gas
Estimated age: 2006
Capacity (in gallons): 75
Temperature-pressure relief valve installed: Yes
Manufacturer: Rheem
Location of water heater: Mechanical room, Basement
Hot water temperature tested: Yes
26)  The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be at this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future.

Maintaining your water heater for maximum life. See link for more information.

https://www.thisoldhouse.com/how-to/how-to-maintain-water-heater
Photo
Photo 26-1 
Photo
Photo 26-2 
Photo
Photo 26-3 
Photo
Photo 26-4 
Photo
Photo 26-5 
Photo
Photo 26-6 
Heating, Ventilation & A/C (HVAC) 6 unitsTable of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace, Heat pump, Electric heaters, Gas fireplace or stove
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: 10/21/21
Source for last service date of primary heat source: Label
Electric heater type (not forced air): Wall mounted, fan-assisted
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2006, Attic unit was 2018
Forced air heating system manufacturer: Carrier
Location of forced air furnace: Mechanical room, Closet, First floor
Location for forced air filter(s): At top of air handler
Type of combustion air supply: Vent(s) to exterior
Cooling system and/or heat pump fuel type: Electric
Type: Split system, Ductless heat pump
Estimated age of heat pump or air conditioning unit: Five units were 2007, 1 unit was 2018
Manufacturer of cooling system and/or heat pump: Carrier
27)  The gas and electric forced air furnaces and A/C's appeared to have been serviced within the last year based on information provided to the inspector or labeling on the equipment. If this is true, then routine servicing is not needed at this point. However, a qualified HVAC contractor should inspect, clean, and service this system, and make repairs if necessary annually in the future.

The filters should be changed upon move in. How often a filter should be changed depends on environmental factors (ie pets, smoking, dust, etc) but a general rule of thumb is every 3 months. Adjust time according to observation.

The estimated useful life for most forced air furnaces is 15-20 years, A/C condensing units is 10-15 years. Some furnaces and A/C condensing units appeared to be near this age and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the future.

For more information visit:
http://www.reporthost.com/?ANFURINSP
Photo
Photo 27-1 
Photo
Photo 27-2 
Photo
Photo 27-3 
Photo
Photo 27-4 
Photo
Photo 27-5 
Photo
Photo 27-6 
Photo
Photo 27-7 
Photo
Photo 27-8 
Photo
Photo 27-9 
Photo
Photo 27-10 
Photo
Photo 27-11 
Photo
Photo 27-12 
Photo
Photo 27-13 
Photo
Photo 27-14 
Photo
Photo 27-15 
Photo
Photo 27-16 
28)  Mini ductless split systems work most efficiently when cleaned and serviced regularly. Filters are typically present that need periodic cleaning. Recommend asking owner's if units have been serviced lately and have a qualified HVAC specialist service unit if they haven't.

See links for manufacturers recommendations.

http://mitsubishi-electric.com.au/how-to-clean-air-conditioner-filter.html

https://na.panasonic.com/us/home-and-building-solutions/heating-air-conditioning/mini-split/discontinued-e12nkua-single-split
Photo
Photo 28-1 
Photo
Photo 28-2 
Photo
Photo 28-3 
Photo
Photo 28-4 
Photo
Photo 28-5 
Photo
Photo 28-6 
29)  The outdoor air temperature was below 65 degrees Fahrenheit during the inspection. Air conditioning systems can be damaged if operated during such low temperatures. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
Photo
Photo 29-1 
Photo
Photo 29-2 
Photo
Photo 29-3 
Photo
Photo 29-4 
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Gas fireplace or stove type: Converted wood-burning fireplace
Fan or blower installed in gas-fired fireplace or stove: No
Gas-fired flue type: B-vent, Wood surround
30)  Gas fireplace was functional at time of inspection.

Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit:
http://www.reporthost.com/?ANGFINSP
Photo
Photo 30-1 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, dishwashers, refrigerators, freezers, ice makers, hot water dispensers and water filters; Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Refrigerator, Under-sink food disposal, Microwave oven
Condition of counters: Serviceable.
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Serviceable.
Condition of under-sink food disposal: Appears serviceable
Condition of dishwasher: Appears serviceable.
Range, cooktop or oven type: Electric
Type of ventilation: Hood over range or cooktop, ducted to exterior
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Serviceable.
31)  Inspector performs a limited function test of appliances and runs dishwasher for short cycle. Deficiencies at time of inspection are noted above if present.

Inspector removed dishwasher toe kick and no leaks were observed at time of inspection.
Photo
Photo 31-1 
Photo
Photo 31-2 
Photo
Photo 31-3 
Photo
Photo 31-4 
Photo
Photo 31-5 
Photo
Photo 31-6 
Photo
Photo 31-7 
Photo
Photo 31-8 
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Laundry room/area, basement
Location #B: Half bath, first floor
Location #C: Half bath, first floor
Location #D: Half bath, first floor
Location #E: Half bath, first floor, north
Condition of counters: Serviceable.
Condition of cabinets: Appeared serviceable
Condition of flooring: Satisfactory
Condition of sinks and related plumbing: Serviceable.
Condition of toilets: Serviceable.
Condition of bathtubs and related plumbing: Serviceable.
Condition of shower(s) and related plumbing: Serviceable.
Bathroom and laundry ventilation type: Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: No
32)  No access or only limited access was available to the back of the clothes washer and dryer, and to utility hook-ups located behind the appliances. The inspector normally attempts to determine the presence of a gas vs. electric power supply, the configuration of the stand pipe, whether the dryer exhaust duct is serviceable, etc. Because of the lack of access, the inspector was unable to fully evaluate and/or describe the hook-ups and appliances.

Recommend clearing dryer duct of lint upon move in and periodically in the future to reduce fire hazard. Dryer vent should be as straight and short as possible to minimize lint collection.
Photo
Photo 32-1 
Photo
Photo 32-2 
33)  Inspector ran water in the sink(s) flushed toilets. No leaks were noted at time of inspection.

Fill valve/ball cock was leaking at toilet at location(s) #E. As leak is within tank, no adverse conditions were observed. This does indicate fill valve will need replacing in the future. These can be obtained at most home improvement stores.
Photo
Photo 33-1 
Photo
Photo 33-2 
Photo
Photo 33-3 
Photo
Photo 33-4 
Photo
Photo 33-5 
Photo
Photo 33-6 
Photo
Photo 33-7 
Photo
Photo 33-8 
Photo
Photo 33-9 
Photo
Photo 33-10 
Photo
Photo 33-11 
Photo
Photo 33-12 
Offices, Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door material: Metal, Glass panel
Type(s) of windows: Vinyl, Multi-pane, Fixed
Wall type or covering: Drywall
Ceiling type or covering: Drywall, Wood & beam
Condition of flooring: Satisfactory
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Tile
34)  Condensation or staining was visible between multi-pane glass in many windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo
Photo 34-1 
Photo
Photo 34-2 
Photo
Photo 34-3 
Photo
Photo 34-4 
35)  A central vacuum system was found. Typically, central vacuum system's exhaust is vented to exterior. This vacuum system was vented to crawlspace. Conditioned air and dust can enter crawlspace.

The central vacuum exhaust duct terminated in the crawl space. Recommend that a qualified person install, repair or replace the duct as necessary so it terminates outdoors, and per standard building practices. For more information, visit:
https://www.reporthost.com/?DRYER
Photo
Photo 35-1 
Photo
Photo 35-2 
Photo
Photo 35-3 
Photo
Photo 35-4 
36)  A security system was found. Transfer switches and any associated electrical are a specialty system. Recommend that the client consult with the property owner or review documentation to familiarize themselves with the operation of this system
37)  The property was equipped with fire extinguishers. Those designed for commercial use can be refilled and resealed by companies who specialize in this service. Inexpensive models are disposable. Unfortunately, an expiration date cannot be fully trusted and there is no foolproof way to know if an extinguisher is no longer functional. Due to the extremely destructive potential of fires and the relatively low cost of extinguishers, it is advisable to replace or recharge questionable extinguishers.

Extinguishers are classified based on their chemical ingredients, all of which have their own strengths and limitations. It is important to know what type of extinguisher combats what type of fire. Fire extinguishers are critical indoor/outdoor components that must be maintained and inspected regularly.

Recommend hiring a qualified service contractor to evaluate, maintain and/or replace fire extinguishers as needed now and in the future annually. Property owners and managers should be be familiar with current and local laws and per standard fire code jurisdiction. It is beyond the scope of this inspection to determine the adequate number of fire extinguishers needed on the premise, to test their ratings, or to test fire them. As such, they are excluded from this report.

Any mention of these materials in this report is made as a courtesy only, Consult with specialists as necessary for this type of evaluation

From Fire Extinguisher Maintenance and Inspection - InterNACHI http://www.nachi.org/fire-extinguisher-maintenance-inspection.htm#ixzz2ugHYhqYf
Photo
Photo 37-1 
Photo
Photo 37-2 
Photo
Photo 37-3 
Detached OfficeTable of contents
Type: Detached
Exterior door material: Metal, Glass panel
Apparent wall structure: Wood frame
Roof inspection method: Traversed
Roof type: Gable
Roof surface material: Architectural shingles
38)  Architectural roofing has an average life expectancy between 25 to 35 years depending on the weather conditions and attic ventilation.

http://www.improvementcenter.com/roofing/new-roofing-years-it-can-last.html
Photo
Photo 38-1 
Photo
Photo 38-2 
Photo
Photo 38-3 
Photo
Photo 38-4 
Photo
Photo 38-5 
Photo
Photo 38-6 
Photo
Photo 38-7 
Photo
Photo 38-8 
39)  Attic insulation and venting.

What appeared to be past water stains were visible on the roof structure at locations in the attic. However, no elevated levels of moisture were found at these stains during the inspection. The stains may have been caused by a past leak. Recommend asking the property owner about past leaks. Monitor these areas in the future, especially after heavy rains to determine if active leaks exist. If leaks are found, recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 39-1 
Photo
Photo 39-2 
Photo
Photo 39-3 
Photo
Photo 39-4 
Photo
Photo 39-5 
Photo
Photo 39-6 
Photo
Photo 39-7 
Photo
Photo 39-8 
40)  Windows or doors were installed with no "drip cap" or "Z" flashings installed above them. Better building practices call for such flashings, which greatly reduce the chance of leaks above windows and doors. Without this flashing, caulk and paint must be maintained or water can enter the wall structure and cause rot and possible structural damage. Depending on the exposure (e.g. roof overhang, height of exterior wall, direction of prevailing rain) this may or may not be an issue. The client should monitor these areas in the future and maintain caulk and paint as necessary.
Photo
Photo 40-1 
41)  Non-metallic sheathed wiring in the attic was routed on surfaces within 6 feet of access hatches or doors, and was subject to damage. Wiring can be damaged when hatches are lifted and set aside, when stored items are moved into or out of the attic, etc. This is a potential hazard. Care should be taken when entering and exiting attic.
Photo
Photo 41-1