Inspector: Timber Turner
[ashigold]

Gem State Home Inspections

Client(s):  Pebbles & Bam Bam Flintstones
Property address:  8762 Bedrock lane
Hayden ID 83835-4504
Inspection date:  Wednesday, May 16, 2018

This report published on Thursday, October 11, 2018 9:37:51 PM PDT

Please understand that there are limitations to this inspection. Many components of the home are not visible during the inspection and very little historical information is provided in advance of the inspection. While we can reduce your risk of purchasing a home, we cannot eliminate it, nor can we assume it. Even the most comprehensive inspection cannot be expected to reveal every condition you may consider significant to ownership. In addition to those improvements recommended in our report, we recommend that you budget for unexpected repairs. On average, we have found that setting aside roughly one percent of the value of the home on an annual basis is sufficient to cover unexpected repairs.

ASHI Certified Inspector

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeServiceableItem or component is in satifactory condition
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation & A/C If Applicable (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary

General Information
Table of contents
Report number: 5776848
Time started: 3:00
Present during inspection: Realtor
Client present for discussion at end of inspection: No
Weather conditions during inspection: Cloudy
Temperature during inspection: Warm, 71° degrees
Sq. footage.: 2072
Payment method: Credit card
Age of main building: 2018
Source for main building age: Municipal records or property listing
Front of building faces: Northeast
Main entrance faces: Northwest
Occupied: No
1) The client should be aware that a break-in period occurs during the first year or two after a building is constructed. Some amount of settlement and shrinkage is inevitable as temperature and humidity varies during the seasons. Systems may need adjustment or repair after experiencing constant, prolonged and/or heavy usage. Overall performance of the building exterior has not yet been tested by a wide variety of weather conditions.

Also, it is beyond the scope of this inspection to determine if all permits have been approved or signed off. Consult with the builder and/or municipality to determine if all necessary permits have been approved.
Photo
Photo 1-1 
Photo
Photo 1-2 
Photo
Photo 1-3 
Photo
Photo 1-4 
Site profile: Minor slope
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Deck, porch and/or balcony material: Concrete
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Apparent wall structure: Wood frame
Wall covering: Cement fiber, Stone or faux stone veneer
Apparent foundation type: Crawl space
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
Crawl Space
Table of contents
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Hall closet
Sub-floor material: Oriented strand board
Pier or support post material: Bearing wall
Beam material: Built-up wood
Floor structure above: Engineered wood joists
Insulation material underneath floor above: Fiberglass roll or batt
Vapor barrier present: Yes, Full
Ventilation type: with vents
2) The crawl space was dry at time of inspection. Crawl space insulation and duct work satisfactory. Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Photo
Photo 2-1 
Photo
Photo 2-2 
Photo
Photo 2-3 
Photo
Photo 2-4 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future.
Age of roof surface(s): 2018
Roof inspection method: Traversed
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Architectural shingles
Roof type: Gable
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Gutter and downspout material: Metal
Gutter and downspout installation: Full
3) The rain cap for the heating b-vent needs to be sealed. Leaks can occur. Recommend that a qualified person repair as needed.
Photo
Photo 3-1 
Photo
Photo 3-2 
4) Nail heads were exposed at several shingles. Recommend applying an approved sealant over exposed nail heads now and as necessary in the future to prevent leaks.
Photo
Photo 4-1 
Photo
Photo 4-2 
Photo
Photo 4-3 
Photo
Photo 4-4 
Photo
Photo 4-5 
Photo
Photo 4-6 
Photo
Photo 4-7 
Photo
Photo 4-8 
5) Architectural roofing has a average life expectancy between 20 to 35 years depending on the weather conditions and attic ventilation.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
Photo
Photo 5-5 
Photo
Photo 5-6 
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so.
Attic inspection method: Traversed
Condition of roof structure: Serviceable
Roof structure type: Trusses
roof material: Oriented strand board
Ceiling structure: Trusses
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): R-38
Roof ventilation type: Ridge vent(s), Enclosed soffit vents
6) Attic Insulation and venting.
Photo
Photo 6-1 
Photo
Photo 6-2 
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 
Photo
Photo 6-6 
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type of door between garage and house: Metal, With visible fire-resistance rating
Condition of garage vehicle door(s): Appears serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Satisfactory
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Limitations: The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Copper, Not determined, not readily apparent
Location of main service panel #A: Garage
Location of main disconnect: Breaker at bottom of main service panel
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Branch circuit wiring type: Non-metallic sheathed
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: Yes
Smoke alarms installed: Yes
Carbon monoxide alarms installed: Yes
Smoke alarm power source(s): Hard wired
7) Wire splices were exposed and were not contained in a covered junction box in the crawl space. This is a potential shock or fire hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing permanently mounted junction boxes with cover plates where needed to contain wiring splices.

This could be for future light in the crawl pace.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
8) Electrical panel is well marked.
Photo
Photo 8-1 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Serviceable
Water service: Public
Location of main water meter: End of driveway
Location of main water shut-off: In hall closet
Service pipe material: Plastic
Supply pipe material: PEX plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
Location(s) of plumbing clean-outs: Building exterior
Vent pipe material: Plastic
Condition of fuel system: Serviceable
Location of main fuel shut-off valve: At gas meter
Location of main fuel shut-off valve: By furnace
9) One flexible gas supply connector was routed through a metal cabinet for the gas fireplace. Solid iron pipe or grommets should be used where gas supply lines are routed through holes in metal cabinets. Continued vibration from this equipment may cause the edge of the metal cabinet to wear through the flexible connector, resulting in gas leaks. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 9-1 
Photo
Photo 9-2 
10) Based on visible equipment or information provided to the inspector, this property appeared to have a yard irrigation (sprinkler) system. These are specialty systems and are excluded from this inspection. A recent backflow tag was found in 2018
Photo
Photo 10-1 
Photo
Photo 10-2 
11) Main water shutoff valve is located under the stairs.
Photo
Photo 11-1 
Water Heater
Table of contents
Type: Tank
Energy source: Natural gas
Estimated age: 2018
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Manufacturer: Ruud
Location of water heater: Garage
Hot water temperature tested: Yes
Condition of burners: Satisfactory
Condition of combustion air supply: Satisfactory
Heating, Ventilation & A/C If Applicable (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace, Gas fireplace or stove
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: New construction
Source for last service date of primary heat source: Label
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2018
Forced air heating system manufacturer: Ruud
Location of forced air furnace: Garage
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At top of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of venting system: Appeared serviceable
Type of combustion air supply: Vent(s) to exterior
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Estimated age of heat pump or air conditioning unit: 2018
Manufacturer of cooling system and/or heat pump: Ruud
Condition of controls: Appeared serviceable
12) Drywall dust, and construction debris such as drywall dust and/or sawdust was found behind or below heating or cooling air supply registers. Drywall dust in particular can reduce the life of heating and cooling equipment if left to circulate. At a minimum, recommend vacuuming ducts at each register. Consider having a qualified contractor clean the ducts.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
Photo
Photo 12-4 
13) The clip for the furnace filter needs to be reattached.
Photo
Photo 13-1 
Photo
Photo 13-2 
14) Recommend that home buyers replace or clean HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or cleaning them as necessary. How frequently they need replacing or cleaning depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 14-1 
15) The last service date of the forced air heating/cooling system appeared to be within the last year based on information provided to the inspector or labeling on the equipment. If this is true, then routine servicing is not needed at this point. However a qualified HVAC contractor should inspect, clean, and service this system, and make repairs if necessary annually in the future.
Photo
Photo 15-1 
Photo
Photo 15-2 
Photo
Photo 15-3 
Photo
Photo 15-4 
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Condition of gas-fired fireplaces or stoves: Required repair, replacement and/or evaluation (see comments below)
Gas fireplace or stove type: Metal pre-fab fireplace
Fan or blower installed in gas-fired fireplace or stove: Yes
Gas-fired flue type: Direct vent
16) Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit:
http://www.reporthost.com/?ANGFINSP
Photo
Photo 16-1 
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, dishwashers, refrigerators, freezers, ice makers, hot water dispensers and water filters; Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Under-sink food disposal, Microwave oven
Condition of counters: Serviceable.
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Serviceable.
Condition of under-sink food disposal: Required repair, replacement and/or evaluation (see comments below)
Condition of dishwasher: Appears serviceable.
Range, cooktop or oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop, ducted to exterior
Condition of refrigerator: N/A (none installed)
Condition of built-in microwave oven: Serviceable.
17) The on and off switch is inoperable for the garbage disposal.
Photo
Photo 17-1 
Photo
Photo 17-2 
18) Inspector removed toe kick from the dishwasher. No leaks were noted at time of inspection.
Photo
Photo 18-1 
19) The kitchen was in working order at time of inspection.
Photo
Photo 19-1 
Photo
Photo 19-2 
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, first floor
Location #B: Laundry room/area, first floor
Location #C: Full bath, Master bath, second floor
Location #D: Full bath, second floor
Condition of counters: Serviceable.
Condition of cabinets: Appeared serviceable
Condition of flooring: Satisfactory
Condition of sinks and related plumbing: Serviceable.
Condition of toilets: Serviceable.
Condition of bathtubs and related plumbing: Serviceable.
Condition of shower(s) and related plumbing: Serviceable.
Bathroom and laundry ventilation type: Windows, with individual ducts
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes
20) Inspector filled the sink(s) and bathtub(s). Ran shower water and flushed toilet(s). No leaks were noted at time of inspection.
Photo
Photo 20-1 
Photo
Photo 20-2 
Photo
Photo 20-3 
Photo
Photo 20-4 
Photo
Photo 20-5 
Photo
Photo 20-6 
Photo
Photo 20-7 
Photo
Photo 20-8 
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Exterior door material: Fiberglass or vinyl, Glass panel
Type(s) of windows: Vinyl, Multi-pane, Sliding, Single-hung, Fixed
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum
Condition of stairs, handrails and guardrails: Satisfactory


This report is not a guaranty or warranty. Anything can fail at any time. This inspection report is only
reporting on the conditions as observed at the time of the inspection, and is not intended to be considered as a
guaranty or warranty, expressed or implied, of the adequacy of, or performance of, systems or structures, or
their component parts, or of their remaining life expectancy or usefulness. Systems, equipment and
components can, and do, fail—randomly and without prior warning.

Please review your pre-inspection agreement
We appreciate the opportunity to be of service. Should you have any questions about the general condition of the house in the future, we would be happy to answer these. There is no fee for this telephone consulting. Our fees are based
on a single visit to the property. If additional visits are required for any reason, additional fees may be assessed.

Thank You,
Timber Turner

Gem State Home Inspections
208-640-1673