125 Superior St Port Jefferson Station NY 11776-3340
Inspection date:
Sunday, February 11, 2024
This report published on Saturday, February 17, 2024 10:45:29 AM EST
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Major Defect
Correction likely involves a significant expense
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Minor Defect
Correction likely involves only a minor expense
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Serviceable
Item or component is in serviceable condition
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Present during inspection: Client, Property owner, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), overcast 45 degrees
Temperature during inspection: Cool
Inspection fee: $350
Payment method: Cash
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 50 years
Source for main building age: Realtor
Front of building faces: South
Main entrance faces: South
Occupied: Yes
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit: https://www.reporthost.com/?EPA https://www.reporthost.com/?CPSC https://www.reporthost.com/?CDC
2) Evidence of rodent infestation was found in the form of feces in the basement. Under electrical panel. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles: https://www.reporthost.com/?SEALUP https://www.reporthost.com/?TRAPUP https://www.reporthost.com/?CLEANUP
Under the Electrical Panel
Photo 2-1 Photo 2-2
3) Many areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of patio: Near, at or beyond service life, Backyard Patio
Driveway material: Asphalt
Condition of driveway: Near, at or beyond service life
Condition of porch covers: Appeared serviceable, Front porch cover
Condition of porch: Appeared serviceable, Front porch
Porch material: Concrete
Site profile: Level, Minor slope
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Condition of front porch cover: Appeared serviceable
Patio, porch cover material and type: Covered (Refer to Roof section)
4) Driveway is near its expected life time. Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the driveway, For safety reasons, recommend that a qualified contractor evaluate and replace.
5) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the backyard patio. For safety reasons, recommend that a qualified contractor repair or replace as necessary to eliminate trip hazards.
Photo 5-1 Back patio slabs shifted. Photo 5-2
6) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. It can be a conducive condition for wood-destroying organisms. Recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo 6-1 Back patio. Pitched toward house. Photo 6-2 Right side. Bay window
Photo 6-3 Right side of house. Fireplace chimney area. Photo 6-4
Photo 6-5 Front right of house Photo 6-6 Front Dining room window
Photo 6-7 Front, right of front entrance. Photo 6-8
Photo 6-9 Photo 6-10
7) Cracks, holes, settlement, heaving and/or deterioration were found in sidewalks and/or patios. Recommend that qualified contractor repair as necessary.
8) One or more large tree stumps were close to the building exterior. Wood-destroying insects such as carpenter ants nest in such stumps and are more likely to infest the building as a result. Recommend that large tree stumps within a few feet of the building be removed by a qualified tree service contractor.
Photo 8-1
9) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
10) Pavement sloped down towards building perimeters in one or more areas. This may result in water accumulating around building foundations or underneath buildings. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing old pavement and installing new.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground, from a ladder
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Vinyl, Brick veneer
Condition of foundation and footings: Not determined, Soil grade was less than 1 inch to view foundation.
Foundation/stem wall material: Poured in place concrete, Not determined (inaccessible or obscured), Half basement boiler area revealed a section of the foundation which appears to be a poured concrete foundation.
Wall covering: Wood, Vinyl, Brick veneer
Apparent foundation type: Finished basement
Foundation/stem wall material: Poured in place concrete, Concrete slab on grade
11) Some sections of siding and/or trim were split. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo 11-1 Photo 11-2
Photo 11-3 Photo 11-4 Appears to be original shingles underneath siding.
12) Flashing at one or more locations was missing. Leaks can occur as a result. Recommend that a qualified person repair, replace or install flashing as necessary, and per standard building practices.
Roof left of the house and above the left garage.
Photo 12-1 Right side lower roof area. Near fireplace chimney. Photo 12-2 Left garage, lower roof peak.
13) One or more exhaust duct end caps were . Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
Photo 13-1
14) Soil was in contact with or less than 6 inches from siding or trim. Regardless of what material is used for siding, it should not be in contact with the soil. If made of wood, siding or trim will eventually rot. For other materials, ground or surface water can infiltrate siding or trim and cause damage to the wall structure. Wood-destroying insects are likely to infest and damage the wall structure. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.
Photo 14-1
15) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo 15-1 Caulk trim of front door and the Cornice above door as well. Photo 15-2 Replace garage door trim
Photo 15-3 Photo 15-4
Photo 15-5 Front left door entrance. Photo 15-6 Left rear of house. Caulk holes located by gas meter.
Photo 15-7 Right rear roof area by fireplace chimney.
16) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo 16-1 Right rear of house. Photo 16-2 Front, right of house
Photo 16-3 Front right of house.
17) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo 17-1 Photo 17-2
18) Caulk was deteriorated and/or substandard in some areas. For example, . Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit: https://www.reporthost.com/?CAULK
Photo 18-1 Rear roof meets Rear upper roof. Under the gutter area Needs Caulk. Photo 18-2 Right side house. Bay window.
Photo 18-3 Right side of house. Bay window. Photo 18-4 Multiple exterior light fixtures in need of caulk or replace caulk.
Photo 18-5 Multiple exterior light fixtures in need of caulk or replace caulk. Photo 18-6 Left front door area.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Not determined (inaccessible or obscured), Basement was finished with a drop ceiling
Floor structure above: Solid wood joists, view from boiler room revealed solid wood 2 x 6 joists
Condition of insulation underneath floor above: Not determined (inaccessible or obscured), basement was finished with drop ceiling
19) Finished basement with drop ceilng, stored items and furniture. Limited access.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed, Viewed from eaves on ladder, Viewed from ground
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: Single
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below), Some areas of the gutters appeared to be pulling a way from the facia. Recommend a qualified contractor to evaluate and repair.
20) Flashings at the base of one or more chimneys were loose and/or missing counter flashing. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo 20-1 Photo 20-2
Photo 20-3 Photo 20-4
Photo 20-5
21) Extensions such as splash blocks or drain pipes for one or more downspouts were clogged and/or substandard. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo 21-1 Photo 21-2 Clogged downspout
Photo 21-3 Photo 21-4
Photo 21-5 Downspouts from higher roof need to be extended to the lower gutter. Draining water will erode the shingles prematurely in that area. Recommend a qualified contractor to repair.
22) One or more were loose. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Some areas of the gutters appeared to be pulling a way from the facia. Recommend a qualified contractor to evaluate and repair.
Photo 22-1 Photo 22-2
23) Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo 23-1 Photo 23-2
24) Significant amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Required repair, replacement and/or evaluation (see comments below), Some insulation in lower attic had fallen and not properly installed. Recommend a qualified contractor to repair.
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-15, R-19
Condition of roof ventilation: Poor/ Fair. Soffits were not visible in attic.
Roof ventilation type: Ridge vent(s), Gable end vents, Mechanical vents with powered fan
25) The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
Photo 25-1 Photo 25-2
Photo 25-3 Photo 25-4
Photo 25-5
26) One or more attic access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency. For more information, visit: https://www.reporthost.com/?ATTACC
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Required repair, replacement and/or evaluation (see comments below), Garage doors were inoperable and rope was tied to the door and its tracks. Garage door was blocked by stored items.
Type of door between garage and house: Metal
Condition of garage vehicle door(s): Not determined (inaccessible or obscured)
Type of garage vehicle door: Roll
Condition of door between garage and house: Required repair, replacement and/or evaluation (see comments below)
Type of door between garage and house: Hollow core
Condition of garage vehicle door(s): Not determined (inaccessible or obscured), Garage doors were inoperable and rope was tied to the door and its tracks. Garage door was blocked by stored items.
Number of vehicle doors: 2
Condition of garage floor: Required repair, replacement and/or evaluation (see comments below), Further evaluation recommended. Majority of the flooring was obstructed with stored items.
Condition of garage interior: Further evaluation recommended. Majority of the walls were obstructed with stored items.
Garage ventilation: None visible
27) The door between the garage and the house did not appear to be fire resistant, or the inspector was unable to verify that it was via a label. This is a potential safety hazard. House to garage doors, to prevent fire and fumes from spreading from the garage into interior living space, should be constructed of fire-resistant materials. Doors, generally considered to be suitable for the purpose, are solid core wood, steel, honeycomb steel or a door that has been factory labeled as fire rated. Recommend that a qualified contractor replace or repair the door and, at that time, make any other corrections that might be required to provide suitable fire resistance between the garage and the dwelling per standard building practices. For more information, visit: https://www.reporthost.com/?AGFR
Photo 27-1
28) The door between the garage and the house has been modified with a pet door, and is no longer fire-resistant. This is a potential safety hazard. House to garage doors, to prevent fire and fumes from spreading from the garage into interior living space, should be constructed of fire-resistant materials. Doors, generally considered to be suitable for the purpose, are solid core wood, steel, honeycomb steel or a door that has been factory labeled as fire rated. Recommend that a qualified contractor replace or repair the door and, at that time, make any other corrections that might be required to provide suitable fire resistance between the garage and the dwelling per standard building practices. For more information, visit: https://www.reporthost.com/?AGFR
Photo 28-1
29) One or more gaps and/or pet doors were found in the attached garage walls or ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit: https://www.reporthost.com/?AGFR
Photo 29-1 Photo 29-2
30) The attic access hatch in the garage was blocked by a vehicle or stored items. The inspector was unable to enter, view or traverse the attic space over the garage. This area is excluded from this inspection.
Photo 30-1 Rope preventing door to be tested. Photo 30-2 Rope preventing door to be tested.
Photo 30-3 Right front garage Photo 30-4 Left front garage.
Photo 30-5 Left side of garage. Photo 30-6 Floor covered with carpet.
Photo 30-7 Majority of garage inaccessible to inspect. Photo 30-8 Majority of garage inaccessible to inspect.
Photo 30-9 Photo 30-10
Photo 30-11 Rear of garage, Right side. Photo 30-12 Right rear of garage.Majority of garage inaccessible to inspect.
Photo 30-13 Photo 30-14
Photo 30-15 Right side of garage. Majority of garage inaccessible to inspect. Photo 30-16 Right rear of garage. Majority of garage inaccessible to inspect.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Overhead
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 100
System ground: Not determined, not readily apparent
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Ground fault circuit interrupter (GFCI) protection present: Not determined
Smoke alarms installed: No, or fewer than recommended are installed
Carbon monoxide alarms installed: Not installed or fewer installed than recommended
31) Electrical drop down conduit is not sealed and can cause moisture into the electrical panel. Improper siding install around electric meter. Recommend a qualified contractor to evaluate and repair.
Photo 31-1 Photo 31-2
Photo 31-3 Water can make it's way into the electrical panel.Recommend a qualified contractor to seal any gaps along the conduit. Photo 31-4 Water can make it's way into the electrical panel.Recommend a qualified contractor to seal any gaps along the conduit.
32) Substandard wiring was found at the building exterior and/or attic. For example, exposed wiring, unterminated wires, missing or broken cover plates, loose or substandard conduit and/or extension or lamp cord used as permanent wiring. This is a safety hazard. Recommend that a qualified electrician evaluate and repair as necessary and per standard building practices.
Photo 32-1 Main attic. Photo 32-2 Garage ceiling. No cover plate for junction box.
Photo 32-3 Loose wiring along floor in laundry room. Photo 32-4 Rear Main attic. Wire possibly capped and laying on fiberglass.
33) One or more electric receptacles at the kitchen, bathroom(s), full bath and/or garage had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
Outdoors (since 1973)
Bathrooms (since 1975)
Garages (since 1978)
Kitchens (since 1987)
Crawl spaces and unfinished basements (since 1990)
Photo 33-1 No GFCI on kitchen splash back wall. Photo 33-2 Kitchen GFCI test.
Photo 33-3 No GFCI in Master bathroom.
34) Panel(s) #A had inadequate working space. This is a safety hazard when opening or working in panels. Electric panels should have the following clearances:
An open area 30 inches wide by 3 feet deep in front of the panel
6 feet 6 inches of headroom in front of the panel
The wall below the panel is clear to the floor
The center of the grip of the operating handle of the switch or circuit breaker not more than 6 feet 7 inches above the floor or working platform
Recommend that a qualified contractor repair or make modifications per standard building practices. If panels must be opened for repairs, then a qualified electrician should perform repairs.
Photo 34-1 Photo 34-2
35) Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo 35-1 Master bedroom door.
36) One or more electric receptacles and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
Photo 36-1 Left Rear bedroom. Right entrance receptacle loose. Photo 36-2 Basement receptacle loose.
Photo 36-3
37) One or more modern, 3-slot electric receptacles were found with an open ground. This is a shock hazard when appliances that require a ground are used with these receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. Recommend that a qualified electrician repair as necessary so all receptacles are grounded per standard building practices.
Photo 37-1 Front. Right of garage. No GFCI also. Photo 37-2
38) One or more sections of outdoor wiring were exposed and . This is a potential shock hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing conduit, re-routing wires or replacing wiring.
Photo 38-1 Backyard. Right of rear sliding doors.
39) Smoke alarms were missing from one or more bedrooms, from one or more hallways leading to bedrooms and/or on one or more levels. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom and on each level. For more information, visit: https://www.reporthost.com/?SMKALRM
40) Aluminum wiring found. Suggest that a license electrician evaluate and replace. Amateur repair with electric tape is also a safety issue.
Photo 40-1 Electrical tape repair most lily done by a non licensed electrician. Photo 40-2
Photo 40-3 Photo 40-4
41) One or more slots where circuit breakers are normally installed were open in panel(s) #A. Energized equipment was exposed and is a shock hazard. Recommend that a qualified person install closure covers where missing.
Photo 41-1 Covered with duct tape.
42) One or more knockouts were missing from panel(s) #A. Holes in panels are a potential fire hazard if a malfunction ever occurs inside the panel. Rodents can also enter panels through holes. Recommend that a qualified person install knockout covers where missing and per standard building practices.
43) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit: https://www.reporthost.com/?SMKALRMLS
Photo 43-1
44) Carbon monoxide alarms were missing from one or more sleeping areas and/or on one or more levels. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit: https://www.reporthost.com/?COALRM
45) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.
It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.
46) One or more globes or covers for light fixtures were missing or damaged. Recommend replacing as necessary to avoid exposed bulbs. With closet lighting or where flammable stored objects are near light fixtures, missing or broken covers can be a fire hazard.
Photo 46-1 Kitchen Photo 46-2 Hallway bathroom.
47) The service drop wires were in contact with trees or vegetation. This can result in damage to wiring insulation or broken wires during high winds. Recommend pruning trees or vegetation as necessary. The utility company may prune trees at no charge.
48) Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
49) GFCI at pool area tested and failed. Recommend a licensed electrician to evaluate and repair if needed.
Photo 49-1
50) No GFCI in Laundry room for washing machine. Recommend a licensed electrician replace with GFCI outlet.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Inaccessible in basement behind enclosed wall.
Water service: Public
Location of main water shut-off: Basement, Not determined (obscured, inaccessible or none found)
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable, Not determined (inaccessible, obscured, or water service off), Basement was finished with drop down ceiling. Plumbing for kitchen are inaccessible. Plumbing in lower attic appeared serviceable.
Drain pipe material: Not determined (inaccessible or obscured)
Condition of waste lines: Appeared serviceable
Waste pipe material: Not determined (inaccessible or obscured)
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: None visible
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter
51) Water was discolored when bathtubs or sinks were filled, or when showers were operated. This can be caused by water stagnating in water supply pipes, rust accumulating in pipes or in the water heater, or sediment being present in the water supply. Recommend flushing the water supply piping and the water heater. If that fails to resolve the issue, then have a qualified plumber evaluate and repair as necessary.
52) One or more valve leaks were found in boiler room by irrigation back flow valve. A qualified plumber should repair as necessary.
Photo 52-1 Photo 52-2
53) The inspector did not determine the location of the main water shut-off valve, or verify that a readily accessible shut-off valve in the building exists. Recommend consulting with the property owner to determine if a main shut-off valve exists, locating it yourself, or that a qualified plumber find it if necessary. If no readily accessible main shut-off valve is found in the building, then recommend that a qualified plumber install one so the water supply can be quickly turned off in the event of an emergency, such as when a supply pipe bursts.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: No
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
55) Rust was found at the supply pipes or fittings. This can indicate past leaks, or that leaks are likely to occur in the future. Recommend that a qualified plumber evaluate and replace components or make repairs as necessary.
Photo 55-1
56) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be near this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Furnace
General heating distribution type(s): Pipes and radiators
Last service date of primary heat source: Unknown
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Hydronic (hot water)
Hydronic or steam heat fuel type: Natural gas
Condition of burners: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
Condition of venting system: Appeared serviceable
Peerles Boiler 115,000 BTU:
57) Based on the location and the visible venting, the boiler had a substandard source of combustion and/or dilution air. All gas and oil-fired appliances require adequate air for combustion, dilution and ventilation. This is a potential safety hazard and may result in combustion fumes entering living spaces. Recommend that a qualified HVAC contractor evaluate and repair per standard building practices
Photo 57-1 Photo 57-2 Hot water heater and furnace located behind closet doors.
58) No service switch. A service switch is a safety issue to assure that a technician would not be injured if the system would turn on from another location. Recommend a qualified contractor to evaluate and repair.
59) Exhaust ventilation may be compromised. A licensed technician should service the system and evaluate and repair if needed.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry
60) No spark screen or rain cap was installed at one or more chimney flue terminations. Spark screens reduce the chance of embers exiting the flue and causing fires. They also prevent wildlife (e.g. birds, rodents, raccoons) from entering flues. Rain caps prevent water from entering flues, mixing with combustion deposits and creating caustic chemicals which can corrode flues. They also prevent damage to masonry from freeze-thaw cycles and prevent metal components (e.g. dampers, metal firebox liners) from rusting. Recommend that a qualified person install rain caps with spark screens per standard building practices where missing.
Photo 60-1
61) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at: https://www.reporthost.com/?CSIA
Photo 61-1 Photo 61-2
Photo 61-3 Damper switch is operable.
62) The brick chimney was moderately deteriorated. For example, loose or missing mortar, cracked, broken, loose or spalled bricks. Loose bricks can pose a safety hazard, and deteriorated masonry can allow water to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary.
Photo 62-1 Photo 62-2
Photo 62-3 Photo 62-4
Photo 62-5 Photo 62-6
Photo 62-7
63) One or more masonry chimney crowns were worn and/or cracked. Crowns are meant to keep water off of the chimney structure and prevent damage from freeze-thaw cycles. Chimney crowns are commonly constructed by mounding concrete or mortar on the top chimney surface, however this is substandard. A properly constructed chimney crown should:
Be constructed using either precast concrete slabs, cast-in-place steel reinforced concrete, solid stone, or metal
Be sloped down from the flue a minimum of 3 inches of fall per foot of run
Extend a minimum of 2 1/2 inches beyond the face of the chimney on all sides
Not directly contact the flue liner (if installed), with the gap filled with flexible caulk
Have flashing installed between the bottom of the crown and the top of the brick chimney
Recommend that a qualified contractor repair or replace crowns as necessary, and per standard building practices.
Photo 63-1 Photo 63-2
Photo 63-3 Photo 63-4
64) Mortar at the brick chimney was deteriorated (e.g. loose, missing, cracked). As a result, water is likely to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary. For example, by repointing the mortar.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of cooktops.: Required repair, replacement and/or evaluation (see comments below), Left front burner was not at operable temperature.
Range, cooktop, oven type: Electric
Type of ventilation: Wall or ceiling mounted fan
65) One or more cabinets, drawers and/or cabinet doors were loose. Recommend that a qualified person repair or replace as necessary.
Photo 65-1 Photo 65-2
66) 1 cooktop burner(s) were inoperable. Recommend that a qualified person repair as necessary.
Photo 66-1 Photo 66-2
Photo 66-3 Photo 66-4
67) One or more cabinet drawers were loose. Recommend that a qualified person repair as necessary.
68) Oven was not tested at the time of the inspection because of stored items obstructed the appliance.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, second floor, Master Bathroom
Location #B: Full bath, second floor, 2nd Floor Hall Bathroom
Location #C: Half bath, first floor, 1st Floor Bathroom
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Location #A: Full bath, Half bath, first floor, 1st Floor Bathroom
Location #B: Full bath, second floor, Hallway Bathroom
Location #C: Full bath, Master bath, second floor
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of flooring: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
69) Water damage was found in shelving or cabinet components below one or more sinks at location(s) #C. Recommend that a qualified contractor repair as necessary after any plumbing leaks have been repaired. If moisture is present then concealed areas should be dried thoroughly.
Photo 69-1
70) One or more handles controlling water flow to the shower at location(s) #B and C were inoperable. Recommend that a qualified person repair or replace handles as necessary.
Recommend a licensed plumber to evaluate and repair.
Photo 70-1 Photo 70-2
71) Gaps, no caulk, or substandard caulking were found between countertops and backsplashes at location(s) #A, B and C. Water can penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing or replacing caulk.
Photo 71-1 Photo 71-2
Photo 71-3 Photo 71-4
Photo 71-5 Photo 71-6
Photo 71-7 Photo 71-8
Photo 71-9
72) Tile, stone and/or grout in the flooring at location(s) #B was deteriorated (e.g. loose or cracked tiles, missing grout) or substandard. Water can damage the sub-floor as a result. Recommend that a qualified contractor repair as necessary.
Photo 72-1 Master bathroom Photo 72-2
Photo 72-3
73) One or more sink drains were leaking at location(s) #B. A qualified person should repair as necessary.
Photo 73-1 Photo 73-2
Photo 73-3
74) Caulk around the base of the toilet at location(s) # was missing, substandard and/or deteriorated. Modern standards require caulk to be installed around the entire toilet base where it meets the floor for sanitary reasons. Without it, soiled water can soak into flooring and sub-floor materials if the toilet overflows. Condensation from the toilet can also soak into the flooring. Recommend that a qualified person caulk around toilet bases per standard building practices.
75) Caulk was missing around the base of the bathtub spout, or there was a gap behind it, at location(s) #. Water may enter the wall structure behind the bathtub. Recommend that a qualified person repair as necessary to eliminate the gap. For example, by installing or replacing caulk if the gap is small enough. For larger gaps, a shorter spout nipple or an escutcheon plate can be installed.
Photo 75-1
76) Gaps, no caulk, or substandard caulking were found between the bathtub and the floor and/or walls at location(s) #B. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo 76-1 Photo 76-2
Photo 76-3
77) The shower head at location(s) #C was dripping when the shower was turned off. Recommend that a qualified person repair as necessary.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Storm door handle inoperable. Recommend replacing.
Exterior door material: Fiberglass or vinyl, Glass panel
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Metal, Single-pane, Sliding
Wall type or covering: Drywall, Paneling
Ceiling type or covering: Drywall
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below), Wood flooring of the second level living near stairs appear loose. Recommend a qualified contractor to evaluate and repair.
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
78) Handrails at one or more flights of stairs were wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo 78-1 Handrail to Upper level bedrooms.
79) Condensation or staining was visible between multi-pane glass in many windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's U-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.
Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo 79-1 Photo 79-2
Photo 79-3 Photo 79-4
Photo 79-5 Photo 79-6
Photo 79-7 Photo 79-8
Photo 79-9
80) Wood flooring in one or more areas was buckling. This may indicate that the floor has been exposed to water or that the flooring was not allowed to equalize in moisture content before being installed. Consult with the property owner and/or have a qualified specialist evaluate. It's likely that affected areas of the wood flooring will need to be refinished to obtain a flat surface. For more information, visit: https://www.reporthost.com/?WDFLRPRB
Photo 80-1 2nd level of split. Photo 80-2
Photo 80-3 Photo 80-4
81) Crank handles at windows were loose and/or broken. Recommend that a qualified person replace handles or make repairs as necessary.
Dining room window difficult to close. Handle appears to be stripped. Recommend replacement by a qualified contractor.
Photo 81-1
82) One or more window screens were damaged or deteriorated. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.
Photo 82-1 Rear top window Photo 82-2 Rear top window
83) One or more walls . Recommend that a qualified person repair as necessary.
Photo 83-1 Photo 83-2
Photo 83-3 Photo 83-4
Photo 83-5
84) The lock mechanisms on one or more sliding glass doors were difficult to operate. Recommend that a qualified person repair as necessary.
Photo 84-1 Photo 84-2
Photo 84-3 Photo 84-4
85) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product: https://www.reporthost.com/?ECC
86) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
87) One or more rooms or hallways had ceilings that were too low. Standards vary for minimum ceiling heights, but generally they should be at least 7 feet high except in areas with sloped ceilings where at least half of the area should have 7 foot or higher ceilings. This may pose a safety hazard to tall people.
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of past wood-destroying insects: Yes
Visible evidence of conditions conducive to wood-destroying organisms: Yes
Evidence of prior treatment of wood-destroying insects: Termite bait stations located in various areas along the outside perimeter of the foundation. Recommend a licensed exterminator to further access the property for any wood destroying organisms.
Location #A: Basement boiler area. Along foundation and entrance into boiler area.
88) Evidence of past infestation of termites was found at location(s) # in the form of mud tubes with . Recommend the following:
Correct any conducive conditions for wood-destroying organisms mentioned in this report.
Consult with the property owner about any history of infestation.
Have a state-licensed pest control operator evaluate further and treat as necessary.
Photo 88-1 Mud tubes from prior termite infestation. Photo 88-2
Photo 88-3 Termite bait station. Photo 88-4
Photo X-1 This area if the front porch over hang felt spongy. Recommend a qualified contractor to evaluate. Photo X-2 Grade is too high. Water and snow can find its way inside. Recommend a qualified contractor to evaluate and repair.
Photo X-3 Drain for washing machine was inaccessible. Photo X-4 Front door. Wood is deteriorating and should be replaces. Grade is too high. Water and snow can find its way inside. Recommend a qualified contractor to evaluate and repair.