Summary

Client(s):  Jim & Jill Home Buyer
Property address:  123 Work From Home Lane
Green Mountain Views, VT
Inspection date:  Sunday, July 4, 2021

This report published on Thursday, November 4, 2021 11:25:54 AM EDT

NOTICE TO THIRD PARTIES: This Report is the exclusive property of Covered Bridge Professional Home Inspections, LLC and the Client(s) listed above and is not transferable to any third parties or subsequent buyers.Our inspection and this Report have been performed with a written contract agreement that limits its scope and usefulness. Unauthorized recipients are therefore advised not to rely upon this Report, but rather to retain the services of an appropriately qualified home inspector of their choice to provide them with their own inspection and report.

Concerns are shown and sorted according to these types:
Concern typeSafetySafety concern needs to be corrected, icon is reserved for more immediate issues
Concern typeEvaluateFurther review and or evaluation by a specialist prior to the end of the inspection contingency
Concern typeRepair/ReplaceRepair or replacement needed
Concern typeRepair/MaintainRepair or maintenance needed
Concern typeMinor DefectCorrection likely minor expense or repair
Concern typeMaintainRequires on - going maintenance
Concern typeEnergy / Cost SavingsEnergy and / or cost savings option
Concern typeMonitorMonitor now and in future
Concern typeAdequateAppears adequate / satisfactory (capable of function will show normal wear)
Concern typeCommentFor your information / Inspector's recommendation


General Information
1) The purpose of a home inspection is to identify major visually observable defects that are present at the time of the inspection and to provide information regarding the condition of the home's systems and components. The inspection is non-invasive. The inspection is intended to provide information that can be used to prevent further deterioration of the property and increase the safety of the home by recommendations of the inspector. Whenever such conditions exist it is recommended that a qualified contractor be consulted for any necessary repairs.

Any recommendation made for further evaluation or repair/replace action (icons or text ) by a specialist should be investigated prior to the close of the transaction so that the client possesses a clear understanding of the magnitude of the condition, repair options, and repair costs.

The inspection is limited to readily accessible areas of the property. The inspection shall not be considered a code compliance inspection. We are generalists, not specialists holding licenses of each discipline needed to construct a home.
The inspection is a snapshot in time of the home's condition on the day of inspection. The inspection and report shall not be construed to constitute a home warranty, insurance policy, or guarantee of any kind.

The inspection is supplemental to the Sellers property information (SPIR) report, where all known defects are supposed to be fully disclosed and documented by the seller.

Overview / Our Opinion
16) Overview - The home appeared relatively well-maintained overall.

The most significant concerns were: grading, vegetation, 25-year-old roof wear: attic mold/mildew-like substance: aging water heater review /repair, CSST gas line bonding; rusty pressure tank; non-functional kitchen range hood, garage water damage repairs; smoke/CO detection,

Safety, preventive maintenance, and thermal recommendations rounded out this report.
17) Hi folks,
We normally get a chance to talk with clients on-site about our inspection process, you were not able to attend, completely understandable. What I would have discussed is our reporting/inspection process is very detailed. Don't be shocked by the number of items, this is typical of our process.

Many additional photos likely have been added to give you a better "visual" experience from not being able to attend. Our overall opinion is in the "Overview " section. Please take your time to read over the report in its entirety and call or email with any questions you might have and we will follow up with you.

The electronic report is best supported verbally to ensure proper conveyance of the report findings. We are requesting the opportunity to go over the entire report (if that is what's needed) with you if, at all possible, it's very important to us and the overall process of the inspection. Please give us a call to set up a review time so we can converse and go over any questions you might have.

Exterior
20) One or more trip hazards were found in the sidewalk and/or patio sections due to cracks, settlement, and/or heaving. A qualified contractor should evaluate and repair or replace sidewalk and/or patio sections as necessary to eliminate trip hazards.

One or more flights of stairs with more than two risers have no handrail installed. This is a safety concern. A qualified contractor should install graspable handrails that your hand can completely encircle at stairs where missing per standard building practices. See image:
https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/S095-Deck-Stair-Handrail-Grip-Size-640x480.jpg

Guardrails are missing from one or more sections of stairwells with high drop-offs. This is a safety concern. Standard building practices require guardrails to be installed at drop-offs higher than 30 inches. A qualified contractor should evaluate and install guardrails as necessary and as per standard building practices.
https://www.nachi.org/gallery/?level=picture&id=520
Photo
Photo 20-1 Missing guardrails at back stairs.
Photo
Photo 20-2 Recommend handrails at steep stone step areas for added safety.
21) Windows overall appeared in satisfactory condition overall. Some repair, maintenance is needed. Recommend repairs as needed by a qualified contractor. Please see photos for more information.
Photo
Photo 21-1 Dining area.
Seals between double-pane glass in one or more windows appear to have failed based on condensation or stains between the panes of glass. Recommend review and repairs or replacement as needed by a qualified contractor.

The client(s) should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Windows or glass doors other than those that the inspector identified may also have failed seals and need glass replaced too.
Photo
Photo 21-2 Additional gaskets/weatherstripping at some windows may be an indication of air gaps. Recommend review/repair as necessary by a qualified contractor.
Photo
Photo 21-3 A few windows would not open. May be humidity or otherwise. Recommend review/repair as/if necessary by a qualified contractor.
Photo
Photo 21-4 Second floor front bedroom.
Awning window hardware was loose. Recommend repair by a qualified contractor.
Photo
Photo 21-5 Screen(s) in many windows are missing. The client(s) should ask the property owner(s) about this. Screens are often removed for window cleaning or during winter months, they may be stored somewhere. If not, then recommend installing screens where missing.
Photo
Photo 21-6 Some screens noted in the basement.
Photo
Photo 21-7 Second floor.
One or more windows drop or slide down when opened, sash side tension is worn, and or is in need of repair or replacement. Recommend a qualified contractor review and repair / replace as needed.
22) Overall the exterior finish was adequate however, some areas are peeling or have decay. A qualified contractor should evaluate areas of decay, repair, prep (pressure wash, scrape, sand, prime caulk, etc.), and repaint or re-stain areas as needed replacing all rotten wood per standard building practices.
Photo
Photo 22-1 Some peeling paint/decay was noted at some window trim areas. Many appeared to be recently painted over. Recommend repairs as needed replacing all rotten wood by a qualified contractor.
Photo
Photo 22-2 Fans vent outside.
Photo
Photo 22-3 
Photo
Photo 22-4 
23) The substructure of the deck and or porch was not fully evaluated due to no access. The inspection was via camera under the skirting. What could be seen appeared to be in good condition
Recommend all decks be reviewed annually for, pier movement, levelness, separation, loose railings/handrails, decay, etc. and repaired as needed by a qualified contractor.
Deck safety, http://www.safestronghome.com/resources/video-hsc-deck.asp

Some recommendations made. Please see photos.
Photo
Photo 23-1 
Photo
Photo 23-2 Handrail(s) at some stairs are ungraspable and are a safety concern. Handrails should be sized and shaped so your hand can encircle them. A qualified contractor should make repairs or modifications as necessary. For example, replacing existing handrails or installing additional handrails. See image;https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/S095-Deck-Stair-Handrail-Grip-Size-640x480.jpg
Photo
Photo 23-3 Concrete piers noted.
Photo
Photo 23-4 No access under the porch, camera only inspection in the gap at the base of the skirting.
Photo
Photo 23-5 Structure appeared adequate with camera only inspection under the skirting.
Photo
Photo 23-6 
24) One or more gutters are damaged. This can result in water accumulating around the structure's foundation. A qualified contractor should replace or repair gutters where necessary.
https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/B158-Grading-Gutters-Downspouts.jpg
Photo
Photo 24-1 Some seams appeared deteriorated at copper gutters.
Photo
Photo 24-2 Some gaps noted at seams.
25) The perimeter grading slopes toward the structure in some areas or appeared negative to flat. This can result in water accumulating around the structure's foundation. Accumulated water is a conducive condition to wood destroying insects and organisms. Recommend grading soil so it slopes down and away from the structure.

Original grade - https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2019/02/1885.jpg
Settled grade - http://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2019/02/1887.jpg
Photo
Photo 25-1 Grading appeared negative/pitched toward the home at the back.
26) Recommend finding day-lighted basement drains, perimeter, and or gutter drain pipe (if present) to ensure water is running from it in heavy rains/wet months. Clean out (snake out or Roto Router) as/if needed in the future.
Maintaining drainpipe areas will help keep the water table around the home lower, if it becomes plugged, the water table could rise and cause basement water and or moisture when there was none before.
Image of a footing drain / grading:http://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2019/02/1885.jpg

Some recommendations made. Please see photos.
Photo
Photo 26-1 Perimeter drainage pipes appeared damaged and/or missing sections at back stairs. Recommend review/repair by a qualified contractor.
Photo
Photo 26-2 Left side entrance location.
27) Vegetation such as trees, shrubs, and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood-destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one-foot clearance between it and the structure's exterior.

Trees are overhanging roofs and are within 10 feet of the roof vertically. Trees should be pruned so they are at least 10 feet above the roof, or don't overhang the roof.

http://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2019/02/1928.jpg
Photo
Photo 27-1 Ivy growing at chimney area.
Photo
Photo 27-2 Cut back vegetation to allow sun and air in to dry the siding.

Roof
37) The roof surface material appeared to be in satisfactory condition overall with wear/repairs noted. Granular loss, cupping/curling shingle, ridge cap shingle repairs needed. The client(s) should budget for a replacement roof surface in the near future simply due to age. See photos for more information.
Defect images:
https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/R048C-Worn-Asphalt-Shingles.jpg

See photos for more infromation.
Photo
Photo 37-1 Lower standing seam metal roofing appeared adequate.
Photo
Photo 37-2 The steel roof is installed. Typically snow will not stay on it as long as an asphalt roof surface, a good maintenance feature keeping weight off the roof structure. It will however have larger than normal snow piles next to the home in the winter months. Recommend keeping the lower part of siding and or wooden trim work in these areas painted more often than the rest of the home to repel water/snow. Add snow guards/cleats where needed over entrances, roof penetrations, etc. if needed by a qualified roofing contractor. Sample of snow guards/cleats :
https://www.alpinesnowguards.com/
http://snoblox-snojax.com/
Photo
Photo 37-3 West side.
Main home asphalt roofing.
Photo
Photo 37-4 Some cupping and curling beginning to show in shingles. Recommend repairs as necessary by a qualified contractor.
Photo
Photo 37-5 25-year-old roof wear noted.
Loose shingles and one large area of missing shingles at the center of the ridge cap. Potential for water intrusion/hidden decay.
The ridge cap is damaged in one or more areas, recommend a qualified contractor review and repair.
Photo
Photo 37-6 The ridge cap is deteriorated and or has missing shingles in one or more areas and is in need of repair and or replacement. Recommend a qualified roofer review and repair as needed.
Photo
Photo 37-7 East side.
Granular wear noted to the shingles in many areas. Monitor repair/replace as needed in the future.
Photo
Photo 37-8 

Attic
41) A mold/mildew like surface material is present in the attic space. Recommend a qualified mold contractor evaluate, test, and repair as needed, and repairs are made to the root cause by a qualified contractor to prevent it from coming back. Some recommendations made. Please see photos.

For more information on mold/mildew removal please see the following link;
https://www.epa.gov/mold
https://www.fastmoldremoval.com/
http://www.concrobium.com/
http://www.cleanertoday.com/Mold-Cleaner-p/moldstat32.htm

For more information on adding ventilation to the attic space please see:
http://www.doityourself.com/stry/h2addatticvent
Photo
Photo 41-1 Roof sheathing had a mildew-like substance on it that was widespread. This appeared to be caused by a lack of ventilation and or heat loss.
For an image of an attic system with soffit venting please see this link: https://res.cloudinary.com/internachi/image/upload/f_auto,q_auto:best/gallery-images/insulation_and_energy/general/attic-eave-loose-fill-insulation.jpg
Photo
Photo 41-2 As noted in the roofing section - A missing ridge vent shingle area on the roof was seen from the attic as well. Air is supposed to flow out the cap.
Photo
Photo 41-3 Ridge and soffit venting noted.
Photo
Photo 41-4 Ventilation may have been upgraded to prevent further mildew growth. Recommend asking owners about any attic upgrades. Soffit baffle vents present. Air flows in from the soffit area.

Electric Service
45) Panel(s) appeared in satisfactory overall condition.

Main over-current protection devices (circuit breakers) was "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety concern since the bolt or screw may tighten securely against one wire, but leave others loose. Very common items found during home inspections. A qualified electrician should evaluate and repair as necessary.


Electric panel(s) were noted in either a bathroom and or closet area. Standard practices state they should not be located in these areas. Recommend a qualified electrician for further review, advisement, and repairs per standard practices.

Some recommendations were made. Please see the photos.
Photo
Photo 45-1 The basement panel was in a bedroom closet.
Photo
Photo 45-2 
Photo
Photo 45-3 Appeared to be a surge protector connected to the main lug, recommend reviewing and installation per manufactures instructions by a qualified electrician.
Photo
Photo 45-4 Surge protector taps at main lugs.
Photo
Photo 45-5 Neutral wires are doubled or bundled together on the neutral bar. This is unsafe due to the need to turn off multiple circuit breakers to work on any of the circuits using these wires. A qualified electrician should evaluate and repair as necessary.
Photo
Photo 45-6 Neutral and equipment ground conductors are combined at one or more subpanels. This should only occur in the main service panel and is a safety concern. Neutral conductors should be attached to a "floating" neutral bar not bonded to the panel while grounding conductors should be attached to a separate grounding bar bonded to the subpanel. A qualified electrician should evaluate and repair as necessary per standard practices.
Photo
Photo 45-7 Meters were not labeled. The assumption was made that the meter at left was assigned to the home, but recommend confirmation and labeling as needed.
Photo
Photo 45-8 Main service disconnect switch. 100 amp.
46) Non-metallic sheathed wiring is routed in one or more areas so it is subject to damage, such as on wall or ceiling surfaces. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. A qualified electrician should evaluate and repair as necessary per standard building practices. For example, rewire using a decorative surface conduit, or re-routing through wall cavities.

Flexible lamp or extension cords were being used for permanent wiring in one or more areas. They should only be used for portable equipment on a temporary basis. Cords should be removed as necessary if used permanently, and or a qualified electrician should evaluate and make repairs as necessary. For example, installing additional circuits and/or electric receptacles.
Image: https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/E086C-Extension-Cord-Problems.jpg
Photo
Photo 46-1 Kitchen light cord was stapled under the cabinet.
Photo
Photo 46-2 Track light wire was surface run in the kitchen.

Water Heater
49) The tankless hot water system was delivering hot water to all intended areas on the day of inspection. Recommend maintenance per manufacturer's recommendations by a qualified heating contractor as needed.
Regular maintenance is important to keep your tankless water heater performing well.
Keep the area around the exterior vent exhaust free of snow and ice.

Tankless water heaters typically are rated to last 15-20 years. Consult the owner's manual for more information. Clients should budget for a replacement in the future.

No visible temperature-pressure relief valve is installed on the water heater. This is a potential safety concern. A qualified plumber should install a temperature-pressure relief valve and drain line as per standard building practices/manufacturer's instructions. For more information, visit: http://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2019/02/1599.jpg

Some recommendations made. Please see photos.
Photo
Photo 49-1 17 year old Takagi gas/tankless water heater.
Photo
Photo 49-2 Heat shielding noted at the joist. Recommend review of combustion clearances per manufacturers instructions by a qualified contractor.
Photo
Photo 49-3 Rust/heat markings noted at vent area. Recommend review/repair as necessary by a qualified contractor.
Photo
Photo 49-4 No visible TPR valve at the water heater. TPR valve may be an internal device. Recommend review and installation as necssary per manufacturer's instruction by a qualified contractor.

Heating & Cooling
53) The newer boiler was operational, delivering hot water to baseboards and radiant floor heat the day of inspection. Recommend annual maintenance per manufacturers instructions.

No drain line is installed for the relief valve. This is a potential safety concern due to the risk of scalding if someone is standing next to the boiler when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor. Minor repair.
For more information, visit http://www.wattsreg.com/default.htm?/t&p/installation.htm
Photo
Photo 53-1 2-year-old high effiecny IBC gas boiler.
Photo
Photo 53-2 
Photo
Photo 53-3 Thermostats were operated, but no heat noted at baseboards in the home.
Photo
Photo 53-4 
Photo
Photo 53-5 Missing drain line.
54) The gas manifold and CSST flexible gas lines are not bonded to the electrical system. Typically a ground wire is run directly to the electric panel to the steel manifold. The purpose is to prevent damage to CSST during lighting strikes. Recommend a qualified electrician review and bond/ground gas lines per standard practice.
For more information see:http://csstsafety.com/Images/CSST-Direct-Bonding-Tech-Bulletin.pdf

Regardless of any findings we discover, we recommend a licensed gas contractor review all connections for leaks, material types of plumbing, exhausts, gas pressures, regulators, tanks, shutoffs, bonding, etc. This is to ensure up to date materials and codes are present and have been reviewed by a licensed gas contractor. We do not quote gas codes, per VT & NH Rules. Quoting code is not a part of this inspection. We are generalists, not specialists holding licenses of each discipline needed to construct a home.
Photo
Photo 54-1 CSST gas line was not bonded, should be a minor fix.
Photo
Photo 54-2 Regulator and shut off valve at the East side.
Photo
Photo 54-3 LP gas underground tank riser.
Photo
Photo 54-4 Main LP gas shut off valve.

Plumbing & Laundry
57) The kitchen sink drains slowly. Drain(s) should be cleared as necessary, and by a qualified plumber if necessary.
Photo
Photo 57-1 

Water Supply
63) The estimated useful life well equipment is as follows:
* Well pump 15 to 20 years.
* Steel pressure tanks 15 to 25 years.
Both were operational on the day of inspection.
Image of a drilled well: http://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2019/02/1527.0.jpg
Image of a pressure tank: https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2019/02/1528-640x480.jpg
https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/P080-Well-Tank-with-Bladder.jpg

Some recommendations made. Please see photos.
Photo
Photo 63-1 Pressure tank and main water shut-off valve. It was operational and is getting older.
Photo
Photo 63-2 Rust noted at pressure tank.
The estimated useful life for most steel pressure tanks is 15 to 25 years. This tank appeared to be approximately this age and will need eventual replacement. Clients should budget for replacement.

Basement
65) Guardrails are missing from one or more sections of stairwells with high drop-offs. This is a safety concern. Standard building practices require guardrails to be installed at drop-offs higher than 30 inches. A qualified contractor should evaluate and install guardrails as necessary and as per standard building practices.
https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/S093-Deck-Stair-Railing.jpg
Photo
Photo 65-1 

Fireplaces, Woodstoves & Chimneys
73) The chimney(s) and flue(s) were inspected from very limited vantage points. Not all areas could be seen visibly, limiting the inspection. What could be seen appeared adequate.
We recommend a certified chimney service contractor (preferably with a video scope) perform an inspection for a more comprehensive evaluation.
Resources - https://www.csia.org/

The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device (if present).

Image of possible chimney defects;
https://coveredbridgeprofessionalhomeinspections.com/blog/wp-content/uploads/2020/04/F052C-Masonry-Chimney-Defects-Above-Roof-640x480.jpg

Some recommendations made. Please see photos.
Photo
Photo 73-1 A metal liner for the woodstove is present. Insulation contact. Denting/damage noted. Recommend review and repair by a qualified chimney professional.
Photo
Photo 73-2 Chimney appeared adequate from what was visible.
Photo
Photo 73-3 Vegetation on the brick chimney can cause moisture damage, recommend removal.
Photo
Photo 73-4 

Kitchen
75) The range hood fan was inoperable. We checked breakers etc. A qualified contractor should evaluate and repair or replace the fan or the range hood as necessary.
Photo
Photo 75-1 

Bathrooms
80) The water stopper mechanism is not sealing, missing, or needs adjustment or repair to hold water. Stopper mechanisms should be installed where missing and/or repairs should be made so stoppers function properly.
Photo
Photo 80-1 Upstairs tub

Interior Rooms
85) Smoke alarms appeared battery-operated, hard-wired smoke detection has been required since 1994 (1996 home). Recommend a qualified electrician review and repair per VT's standards.
For more information see the links below.
Please see the following links for more information on VT smoke detector requirements:

For more information see below.
Matrix - http://firesafety.vermont.gov/sites/firesafety/files/files/Documents/dfs_codesheet_residental_smoke_alarms_matrix.pdf
General info - http://firesafety.vermont.gov/sites/firesafety/files/pdf/Code%20Info%20Sheets/2012_Residental%20Smoke%20Alarms.pdf
http://www.nfpa.org/public-education/by-topic/smoke-alarms

CO's should be near all bedrooms. Recommend additional units be added as needed by a qualified contractor to reflect the VT Dept. of Fire & Safety rules.
For more information on VT Division of Fire and Safety standards please see:
http://firesafety.vermont.gov/sites/firesafety/files/files/Documents/dfs_codesheet_co_alarm_matrix.pdf
http://firesafety.vermont.gov/sites/firesafety/files/files/Documents/dfs_codesheet_co_alarms.pdf
Photo
Photo 85-1 10-year lithium battery operated smoke detection.
Photo
Photo 85-2 
Photo
Photo 85-3 CO detector at second floor hall appeared to be 10 year lithium battery but not written on data plate. No visible CO detector near the basement bedroom.
86) One or more light fixtures appear to be inoperable. Recommend further evaluation by replacement of bulb(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.
Photo
Photo 86-1 Some track light fixtures were inoperable/dead bulbs.
Photo
Photo 86-2 
Photo
Photo 86-3 Lights in some closets were inoperable. Appeared to be battery operated. Recommend review/repair as necessary.
87) One or more handrails had no "returns" installed, where ends of handrails turn and connect to adjacent walls so objects or clothing will not catch on the open ends. This is a safety concern. Recommend that a qualified person install returns per standard building practices. Image - http://www.hammersmith.com.au/images/productimages/Internal_Components/Mono_Rail/JH062R%20lge.jpg
Photo
Photo 87-1 Main and basement stairwells hand no handrail returns.
88) This door will not shut or close easily. Repairs should be made by a qualified contractor if necessary.
Photo
Photo 88-1 Boiler room door.

Garage
92) The garage overall structure appeared to be adequate with good quality structural components, however,
water damage and decay were noted near the second-floor sliding door and window area. Recommend a qualified contractor review this area, find the root cause, repair, and replace all rotten wood.
Photo
Photo 92-1 
Photo
Photo 92-2 Water damage near siding door which was sealed/ locked off. Significant water staining and decay were noted inside.
Photo
Photo 92-3 Weak floor, decay in this area only. The rest of the garage was fine.
Photo
Photo 92-4 
Photo
Photo 92-5 
93) Siding and or trim areas of the garage have peeling and or decay in one or more areas.
Windows appeared in poor condition.
Recommend repairs as needed by a qualified contractor.
Photo
Photo 93-1 2 windows need repair/ replacement.
Photo
Photo 93-2 
94) One or more exterior entrance doors are damaged and/or deteriorated and should be repaired or replaced by a qualified contractor.
Photo
Photo 94-1