Brown Home Inspections LLC

409 Mamie 
Hattiesburg, MS 
39401
Inspector: Jason Brown

Property Inspection Report

Client(s):  Emily Ladner
Property address:  203 Hamilton
Petal, MS
Inspection date:  Tuesday, October 9, 2018

This report published on Tuesday, October 16, 2018 2:52:58 PM CDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating
Cooling / Heat Pump
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas
Wood Destroying Organism Findings

View summary

General Information
Table of contents
Time started: 3:00 PM
Time finished: 4:30 PM
Inspector: Jason Brown
Present during inspection: Client, Property owner, Contractor
Client present for discussion at end of inspection: Yes
Weather conditions: Partly cloudy, Rain
Temperature: Warm
Ground condition: Damp
Inspection fee: 250.00
Buildings inspected: Single Family Home
Age of building(s): 60+ years
Source for building age: Inspector's estimate
Front of building faces: North
Occupied: No
1) Structures built prior to 1980 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.epa.gov
http://www.cpsc.gov
http://www.cdc.gov
2) The natural gas service was turned off. As a result, some appliances such as water heater(s), forced air furnace(s), gas fireplace(s), stove(s), range(s) and/or gas supply lines weren't fully evaluated. The inspector was unable to test for gas leaks.
Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Chain link
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Concrete
Condition of exterior stairs: Appeared serviceable
Exterior stair material: Masonry
3) Handrails at one or more flights of stairs were missing. This is a safety hazard. Standard building practices require that handrails be:
  • Installed at stairs with four or more risers
  • Sized and shaped so your hand can encircle them
  • Permanently and securely attached, and able to withstand a 200 pound force in any direction at any point
  • Continuous and extend for the entire flight of the stairs
  • Located between 30 and 38 inches above the leading edge of the stair treads

A qualified person should repair, replace or install as necessary and as per standard building practices.
4) Fences were damaged or deteriorated in some areas. A qualified person should repair or replace sections as necessary.
Photo
Photo 4-1 
Photo
Photo 4-2 
Exterior / Foundation
Table of contents
Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Condition of foundation and footings: Required repairs, replacement and/or evaluation (see comments below)
Foundation type: Crawlspace
Pier or support post material: Masonry
Beam material: Solid wood
Floor structure: Solid wood joists
Crawl space inspection method: Traversed
Insulation material underneath floor above: None visible
Ventilation: Appears serviceable
Vapor barrier present: No
5) Cracks or deterioration were found in one or more sections of brick veneer. This may relate to water/pest damage at sub floor. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.
Photo
Photo 5-1 
Photo
Photo 5-2 
Photo
Photo 5-3 
Photo
Photo 5-4 
6) Rot or water damage was found at one or more sections of floor sheathing, joists and/or beams. A qualified contractor should evaluate and repair as necessary. All rotten wood should be replaced.

Pest damage present at these areas.

Left and left front areas of sub structure

10-16-2018 New pictures with notes in comments below pictures.
Photo
Photo 6-1 water damage under kitchen sink
Photo
Photo 6-2 some joists have been "scabbed onto" to repair the scabs have also been damaged
Photo
Photo 6-3 
Photo
Photo 6-4 
Photo
Photo 6-5 water/insect damage under bathroom
Photo
Photo 6-6 visible deflection at den floor
Photo
Photo 6-7 10-16-2018 Area under bathroom. New beam is improper size/material/orientation. No piers and or footings present to provide vertical support.
Photo
Photo 6-8 10-16-2018 Original rotten beam under bathroom still in place.
Photo
Photo 6-9 10-16-2018 Improper beam/footing material at area under den. Improper bearing of joists to beam.
Photo
Photo 6-10 
Photo
Photo 6-11 10-16-2018 Improper beam material/orientation. Improper pier material at area under den.
Photo
Photo 6-12 10-16-2018 New joists have been installed at area under den. Old joists are still present.
Photo
Photo 6-13 10-16-2018 Improper bearing on new beam.
Photo
Photo 6-14 
Photo
Photo 6-15 10-16-2018 Main central beam and ledger are deteriorated. This ledger is already compressing with weight of new joist. Consider new pier/beam/footings at these locations.
Photo
Photo 6-16 10-16-2018 No repairs have occurred at area under kitchen. Need new pier/footings, and beams at this location.
7) No vapor barrier was installed in the crawl space. This is a conducive condition for wood destroying organisms due to the likelihood of water evaporating into the building from the soil. A qualified person should install a vapor barrier as per standard building practices.

10-16-2018 A vapor barrier was installed.
Photo
Photo 7-1 
8) The crawl space access hatch was missing. A qualified person should repair, replace or install as necessary to prevent water and vermin intrusion.
9) Some crawl space vent screens were missing. Animals such as vermin or pets may enter the crawl space and nest, die and/or leave feces and urine. A qualified person should replace damaged or deteriorated screens where necessary using screen material such as "hardware cloth" with 1/4 inch minimum gaps.
Photo
Photo 9-1 
10) Additional piers/footings should be installed at this beam for proper support and bearing.

10-16-2018 See item 6 for update.
Photo
Photo 10-1 
Roof / Attic
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Appeared serviceable
Roof type: Hipped
Age of roof surface(s): 1 year
Source for building age: Inspector's estimate
Roof inspection method: Traversed
Condition of shingle and/or shake roof surface materials: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Condition of exposed flashings: Appeared serviceable
Condition of attic: Appeared serviceable
Attic inspection method: Traversed
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Ceiling insulation material: Fiberglass roll or batt
Ceiling insulation depth: 8 inches
Ceiling insulation rating: 20
Roof ventilation: Appears serviceable
Garage / Carport
Table of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
Type: Attached, Carport
Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Service voltage (volts): 120
Service amperage (amps): 60
Primary service overload protection type: Circuit breakers
Condition of main service panel: Appeared serviceable
Condition of sub: Appeared serviceable
Branch circuit wiring type: Non-metallic sheathed
Condition of branch circuit wiring: Serviceable
11) Relatively few electric receptacles were installed in one or more areas. This can result in "octopus" wiring with extension cords, which is a fire hazard. A qualified electrician should evaluate and install additional receptacles as necessary and as per standard building practices.

No outlets at bathrooms.

10-16-2018 New GFCI outlets have been installed.
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
12) Two-pronged electric receptacles rather than three-pronged, grounded receptacles were installed in one or more areas. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:
  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

This list is not exhaustive. A qualified electrician should evaluate and install grounded receptacles as per the client's needs and standard building practices.

10-16-2018 A grounded outlet has been installed at laundry location.
Photo
Photo 12-1 
Photo
Photo 12-2 
Photo
Photo 12-3 
13) One or more electric receptacles at the kitchen had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
14) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.
Photo
Photo 14-1 
15) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
Photo
Photo 15-1 
16) The legend for overcurrent protection devices (breakers or fuses) in panel #A and B was missing. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.

10-16-2018 A legend was installed at the sub panel.
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
17) One or more flexible gas supply connectors were routed through a metal cabinet. Standard building practices require that solid iron pipe be used where gas supply lines are routed through holes in metal cabinets. Continued vibration from this equipment may cause the edge of the metal cabinet to wear through the flexible connector, resulting in gas leaks. This is a safety hazard. A qualified heating and cooling contractor should evaluate and make repairs and/or modifications as necessary.
Photo
Photo 17-1 
18) Insulation on one or more water supply pipes in the crawl space was missing. A qualified person should replace or install insulation as per standard building practices for better energy efficiency and to prevent water pipes from freezing.
19) Based on the age of this structure, recommend that a qualified plumber inspect the waste lines using a video scope device to determine if they need repair or replacement. Property owners are usually responsible for repairs to the side sewer and publicly owned lateral lines. Such repairs can be expensive.
Photo
Photo 19-1 
Water Heater
Table of contents
Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Near, at or beyond service life
Type: Tank
Estimated age: 23 years
Energy source: Natural gas
Capacity (in gallons): 40
Manufacturer: U.S. Craftmaster
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
20) No drain line was installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices.

10-16-2018 A drain extension was installed at this valve.
Photo
Photo 20-1 
Photo
Photo 20-2 
21) The outer flame shield for the water heater combustion chamber was missing. This is a potential fire hazard. A qualified person should repair or replace as necessary.
Photo
Photo 21-1 
22) A water heater was installed over finished living spaces and had no catch drain installed. Recommend having a qualified contractor install a drain to prevent water damage to finished interior spaces below if/when the water heater develops a leak or is drained.

10-16-2018 A drain was installed at this pan.
Photo
Photo 22-1 
Photo
Photo 22-2 
23) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Appeared serviceable
Location of heating system: Closet
Heating type: Forced air
Fuel type: Natural gas
24) The furnace heating system was not fully evaluated because the gas supply was off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that as per the standards of practice for NACHI (http://www.nachi.org) and ASHI (www.ashi.org), the inspector is not required to operate shut-off valves, pilot lights or overcurrent protection devices, or any controls other than "normal controls".
Cooling / Heat Pump
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Appeared serviceable
Type: Split system
Estimated age: 23+ years
Approximate tonnage: 3 tons
Manufacturer: Goodman
Condition of distribution system: Appeared serviceable
Condition of controls: Appeared serviceable
Condition of air filters: Required repair, replacement and/or evaluation (see comments below)
25) The system's air handler was installed in an interior space, and no auxiliary condensate drain line or water sensor were installed. Primary condensate drain lines often clog. When they do, water can overflow into finished living spaces below and cause damage. Recommend having a qualified contractor evaluate and install an auxiliary drain line and/or water sensor as per standard building practices.
Photo
Photo 25-1 
26) The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.
27) The estimated useful life for most cooling systems and heat pumps is 10 to 15 years. This system appears to be near this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
28) One or more air filters were dirty. A qualified person should replace filter(s) as necessary. Filters should be checked monthly and maintained as necessary in the future.
Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type: Electric
29) Replace "bake on" light at stove.
Photo
Photo 29-1 
30) One or more sink drains had an active leak. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 30-1 
31) The clearance between the stove top and the base of the exhaust hood above was substandard. While the recommended height varies per the hood manufacturer, standards usually call for a minimum of 24" of clearance. A low hood height can restrict visibility of the stove top. The client should consider having a qualified contractor raise the exhaust hood as per the manufacturer's installation instructions, or as per standard building practices.
Photo
Photo 31-1 
32) Repair loose microwave.
Photo
Photo 32-1 
33) Some counters showed minor deterioration.
Photo
Photo 33-1 seal gaps at counters
Bathrooms / Laundry / Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Master
Location #B: Guest
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Condition of laundry facilities: Appeared serviceable
34) The clothes dryer exhaust duct terminated in the crawl space. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Damage to building components may result. A qualified person should install, repair or replace as necessary so the duct terminates outdoors, as per standard building practices. For more information, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

10-16-2018 A vent was installed to the exterior.
Photo
Photo 34-1 
Photo
Photo 34-2 
35) Repair leaking shower head at guest shower.
Photo
Photo 35-1 
Interior Rooms / Areas
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
Exterior door material: Wood, Glass
Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Type of windows: Aluminum, Single pane
Condition of windows: Appeared serviceable
Wall type or covering: Drywall
Condition of walls: Appeared serviceable
Ceiling type or covering: Drywall
Condition of ceilings: Appeared serviceable
Flooring type or covering: Carpet, Wood, Tile
36) Repair water damage window frames.

ie at rear bedroom
Photo
Photo 36-1 
37) Carpeting in one or more areas was stained or soiled. Recommend having carpeting professionally cleaned as necessary.
Photo
Photo 37-1 
38) Minor cracks and/or holes were found in walls in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
Photo
Photo 38-1 
39) Many windows used single-pane glass. Single-pane windows are one of the largest sources of heat loss in winter and heat gain in the summer due to their low insulating ability and high air leakage rates. They're estimated to be responsible for 25 to 50 percent of the energy used to heat and cool homes. The client should consider replacing single-pane windows with new, multi-pane windows.
Photo
Photo 39-1 
40) Stains were found in one or more ceiling areas. However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks. Recommend asking the property owner about this, and monitoring the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, a qualified contractor should evaluate and repair as necessary.
Photo
Photo 40-1 at den ceiling
Wood Destroying Organism Findings
Table of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than five feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood destroying organisms may infest, reinfest or become active at anytime. No warranty is provided as part of this inspection.
41) Several areas of the sub structure showed evidence of pest activity and damage and beams and joists mainly in the left/left front quadrant of the sub structure. These areas should be treated. All affected areas of joists/beams/sub flooring should be replaced.
Photo
Photo 41-1 
Photo
Photo 41-2 
Photo
Photo 41-3 
Photo
Photo 41-4 
Photo
Photo 41-5 
Photo
Photo 41-6 
Photo
Photo 41-7 
Photo
Photo 41-8 
Photo
Photo 41-9 
Photo
Photo 41-10 
Photo
Photo 41-11 at storage room

Please contact Jason Brown if you have any questions regarding this report.