This report published on Tuesday, August 11, 2020 2:49:53 PM PDT
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
photos not showing defects are included to show scope of inspection.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open
Condition of decks, porches and/or balconies: Appeared serviceable
Condition of stairs, handrails and guardrails: Appeared serviceable
2) Guardrails at one or more locations with drop-offs higher than 30 inches were loose, and pose a fall hazard. Recommend that a qualified person repair guardrails as necessary.
Photo 2-1 Photo 2-2
3) Fungal rot was found in decking boards, support posts and/or Trim at one or more decks or porches. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.
Photo 3-1 Photo 3-2
Photo 3-3 B Photo 3-4
Photo 3-5 B Photo 3-6
Photo 3-7 Photo 3-8
Photo 3-9 Photo 3-10 B
Photo 3-11 Photo 3-12
4) Fungal rot and/or insect damage was found in support posts and/or Trim at one or more structures covering decks, patios and/or porches. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo 4-1 Photo 4-2
Photo 4-3 A Photo 4-4
Photo 4-5
5) Grounds photos
Photo 5-1 Photo 5-2
Photo 5-3 Photo 5-4
Photo 5-5 Photo 5-6
Photo 5-7 Photo 5-8
Photo 5-9 Photo 5-10
Photo 5-11 Photo 5-12 caulk all seams to prevent water damage and conditions conducive to wood destroying organisms
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Cement fiber
Condition of foundation and footings: Appeared serviceable
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
6) Soil was in contact with or less than 6 inches from siding, trim or structural wood. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. If not possible, then recommend replacing untreated wood with rot resistant pressure-treated lumber. Since even pressure-treated materials can eventually decay, plan to periodically check the condition of any wood that is in contact with earth. Note that damage from fungal rot and/or insects may be discovered when soil is removed, and further repairs and wood replacement may be necessary.
Photo 6-1 C Photo 6-2 C
Photo 6-3 Photo 6-4
Photo 6-5 Photo 6-6
Photo 6-7
7) "Honeycombing" was found in one or more sections of the concrete foundation. This occurs when aggregate and sand in the concrete mixture bunches into clusters and fails to mix with the cement paste. This can be caused because the concrete mix was too stiff, by inadequate consolidation (insufficient use of a mechanical concrete vibrator) and/or pouring the concrete from too high of an elevation. In many cases honeycombing is only a cosmetic issue, but it does make concrete susceptible to water infiltration. Where honeycombing is accessible, recommend that a qualified person fill voids with an approved material such as hydraulic cement or non-shrinking grout.
When honeycombing is visible, it may also exist in hidden areas. Honeycombing can result in mold growth in absorbent flooring materials (e.g. carpeting and mortar joints), and can cause rigid flooring materials to warp and buckle.
Photo 7-1 sw corner of home.
8) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo 8-1 Photo 8-2 D
Photo 8-3 Photo 8-4
9) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
do to these areas staying shaded and the moist air, some mildew like staining appears. Recommend treating/cleaning with mildew inhibitor and repaint with mildew resistant paint.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.
The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Condition of floor substructure above: Appeared serviceable
Condition of insulation underneath floor above: Appeared serviceable
Condition of vapor barrier: Appeared serviceable
Condition of crawl space ventilation: Appeared serviceable
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Hipped
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
12) Roof photos
Photo 12-1 Photo 12-2
Photo 12-3 Photo 12-4
Photo 12-5 Photo 12-6
Photo 12-7 Photo 12-8
Photo 12-9 Photo 12-10
Photo 12-11 Photo 12-12
Photo 12-13 Photo 12-14
Photo 12-15 Photo 12-16
Photo 12-17 Photo 12-18
13) Roof age appears to be the same as the home, aprox. 15 years. Roof should last the rest of its expected service life(25) with proper maintenance. 10 more years.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Approximate attic insulation R value (may vary in areas): R-38
Vapor retarder: Installed
Condition of roof ventilation: Appeared serviceable
14) Attic photos
Photo 14-1 Photo 14-2
Photo 14-3 Photo 14-4
Photo 14-5 Photo 14-6
Photo 14-7 Photo 14-8
Photo 14-9 Photo 14-10
Photo 14-11 Photo 14-12 since knobs block attic stairs, I did not want to risk damage. I did not close hatch. Hatch was open when I arrived so I left it the way I found it.
Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Condition of door between garage and house: Appeared serviceable
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: None visible
15) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 200
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Carbon monoxide alarms installed: Yes, but not tested
17) One or more electric receptacles at the kitchen, dining room, living room, den, hallway(s) and/or laundry area had no visible arc fault circuit interrupter (AFCI) protection, or the inspector was unable to determine if AFCI protection was present. This is a potential safety hazard. Recommend that a qualified electrician evaluate and install AFCI protection if necessary and per standard building practices. General guidelines for AFCI-protected receptacles include the following locations:
Bedrooms (since 1999)
Kitchens, laundry areas, family rooms, dining rooms, living rooms, parlors, libraries, dens and recreation rooms, sunrooms, closets and hallways (since 2014)
AFCI in box are for bedrooms only. box meets afci requirments at time of construction
Photo 17-1
18) Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Consult Sellers disclosure on the purpose for this unusual use. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo 18-1 electrical cord used for ?.... there was nothing on the other side of the wall that explained this.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: Garage
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PVC plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Sewage ejector pump installed: No
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable, Near, at or beyond service life
Type: Tank
Estimated age: 2005/ 15 yrs
Capacity (in gallons): 65
Temperature-pressure relief valve installed: Yes
Location of water heater: Laundry room
21) The water heater's earthquake reinforcement was substandard. For example, struts were used rather than straps, substandard fasteners were used, or they may allow significant movement. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines leaking if gas-fired, or electric wiring being damaged if powered by electricity. Water leaks may also occur. Recommend that a qualified person repair or replace existing earthquake reinforcement per standard building practices. Typically 2 straps are required, the upper being located 1/3 of the way down from the top, and the lower being 1/3 of the way up from the bottom. If the water heater isn't located against a wall, blocking should be installed between it and the wall so the straps can be adequately tightened.
Photo 21-1 requires 2 straps
22) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo 22-1 The letter B in the serial number verifies this water heater was manufactured in 2005 it is 15 years old.. The age of the house.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Location of forced air furnace: Garage, Mechanical room
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At top of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of controls: Appeared serviceable
24) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit: https://www.reporthost.com/?ANFURINSP
25) The furnace heating system was not fully evaluated because the access panel was taped shut . Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that the inspector does not operate shut-off valves, pilot lights or circuit breakers, or any controls other than normal controls (thermostat).
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Gas fireplace or stove type: Metal pre-fab fireplace
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: B-vent
27) The glass front on the gas fireplace had a hazy film. This is typically a mineral residue left from water vapor as the gas burns. It may be possible to clean this fogging by removing the glass from the fireplace and using a gas appliance ceramic glass cleaner, available through gas fireplace and stove distributors and installers. Ammonia-based products, such as common glass cleaners, should not be used since they can cause damage or etching to the glass, or make the haze permanent. It may be possible for a homeowner to remove the glass for cleaning, if the instructions for the fireplace are available and if the homeowner is experienced in such repairs. Consult with a qualified specialist for more information, or to have them do the cleaning.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Electric, Induction
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
29) Kitchen photos
Photo 29-1 Photo 29-2
Photo 29-3 Photo 29-4
Photo 29-5 Photo 29-6
Photo 29-7 Photo 29-8
Photo 29-9 Photo 29-10
Photo 29-11 Photo 29-12
Photo 29-13 Photo 29-14
Photo 29-15 Photo 29-16
Photo 29-17 Photo 29-18
Photo 29-19 Photo 29-20
Photo 29-21 Photo 29-22 refrigerated drawers were used for storage and not tested for temp.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: 3/4 bath
Location #B: Master bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
30) Bath, laundry, sink photos
Photo 30-1 Photo 30-2
Photo 30-3 Photo 30-4
Photo 30-5 monitor and maintain edge of wood. Likely spot for water intrusion. Photo 30-6
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of stairs, handrails and guardrails: N/A
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood decay fungi: Yes
Visible evidence of past wood-destroying insects: Yes
Visible evidence of past wood decay fungi: Yes
Visible evidence of damage by wood-destroying insects: Yes
Visible evidence of damage by wood decay fungi: Yes
Visible evidence of conditions conducive to wood-destroying organisms: Yes
Location #A: South deck post
Location #B: Deck boards
Location #C: Exterior earth wood contact
Location #D: Exterior vegetation contact
32) WDO photos A,B,C,D
Photo 32-1 A Photo 32-2 D
Photo 32-3 C Photo 32-4 C
Photo 32-5 B Photo 32-6 B
Photo 32-7 B
Thank you. If you have any questions, please do not hesitate to call 541-272-7538.