Bottom to Top Home Inspections

76 Crescent Dr 
East Hartford CT 06118-2714
Inspector: Robert Repass
Title picture

Property Inspection Report
Unofficial version!

Client(s): Brad Stowe
Property address: 109 Buckingham St
Meriden CT 06451-3915
Inspection date: Thursday, December 14, 2023

This report published on Tuesday, December 26, 2023 12:38:20 PM EST

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings
View summary

General InformationTable of contents
Time started: 5:00
Time finished: 7:00
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Cold
Inspection fee: 450
Payment method: Check
Buildings inspected: One detached garage
Age of main building: 1928
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: No
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Brick
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Concrete
1)  Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 1-1 
Photo
Photo 1-2 
Photo
Photo 1-3 
2)   SERVICE WALKS & DRIVEWAYS Spalling concrete cannot be patched with concrete because the new will not bond with the old. Water will freeze between the two layers, or the concrete will break apart from movement. Replacement of damaged sections is recommended. Walks our driveways close to the property should be properly pitched away to direct water away from the foundation. Asphalt drive be kept sealed and large cracks be filled to prevent damaged from frost. PATIOS should also be properly pitched away. Improperly pitched patios are one source of wet basements. EXTERIOR WOOD SURFACES All surfaces of untreated wood need regular applications of paint or special chemicals to prevent resist damage. Porch or deck columns and fence post buried in the ground and made of untreated wood will become damaged in a year or two . Decks should always be nailed with galvanized,stainless steel or aluminum nails. Decks not painted or stained should be treated with a water sealer. GRADING AND DRAINAGE Any system of drainage or landscaping that creates positive drainage [moving water away from the foundation walls.] will help to keep the basement or crawlspace dry. Where negative grade exists additional back fill is suggested. Dirt should be approximately six inch below top of foundation wall and should not touch wood surfaces. Flower beds, loose mulched areas, railroad ties and other such landscaping items close to the foundation trap moisture and contribute to wet basements. To establish a positive grade, a proper slope away from the house is 1 inch per foot for about 5-6 feet ROOF AND SURFACE WATER CONTROL Roof and surface water must be controlled to maintain a dry basement and crawlspace. This means keeping gutters clean and aligned, extending downspouts. installing splashblocks, and building up the grade so that roof and surface water is diverted away from the building. WINDOW WELLS The amount of water which enters a window well from falling rain is generally light but water will accumulate in window wells if yard is improperly graded. Plastic window well covers are useful in keeping out leaves and other debris. RETAINING WALLS Retaining walls deteriorate because of excessive pressure build up from behind them generally because of water accumulation. Conditions can often be improved byby excavating trench behind the wall and filling it with coarse gravel. Drain holes in the wall will then be able to relieve the water pressure. Retaining walls sometime suffer from tree root pressure or from general movement from topsoil down the slope. Normally, these conditions require rebuilding the retaining wall. RAILINGS It is recommended that railings be installed for any stairway over 3 steps and porches over 30 inches for safety reasons . Balusters for porches balconies and stairs should be close enough to assure children cannot squeeze thru.
Exterior and FoundationTable of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Metal
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
Condition of interior foundation: Satisfactory
3)  Basement window needs repairs. Recommend a qualified contractor service as needed
Photo
Photo 3-1 
4)  Missing window well covers
Photo
Photo 4-1 
Photo
Photo 4-2 
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Bearing wall
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
5)  No under-floor insulation was installed in the unheated basement. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.
Photo
Photo 5-1 
6)   Indicates that the walls have stress cracks, but little movement has occurred. In our opinion, the cracks should be filled with mortar and the walls monitored for further movement and cracking. If additional movement or cracking occurs, reinforcing may be necessary.
7)   Any basement/crawlspace that has cracks or leaks is technically considered to have failed. Most basement/crawlspace have step cracks in various areas. If little or no movement has occurred and the step cracks are uniform, this is considered acceptable. Horizontal cracks in the third or fourth block down indicate the block has moved due to outside pressure. They can be attributed to many factors such as improper grading, improperly functioning downspouts and gutter system,etc Normally if little or no movement has taken place and proper downspouts and grading exists,this is considered acceptable. If the wall containing the stress crack has moved considerably, this will require some method of reinforcement. Basements/crawlspace that have been freshly painted or tuck pointed should be monitored for movement. This will be indicated by by cracks reopening

MOISTURE
Basement/crawlspace dampness is frequently noted in houses and in most cases the stains or moisture present is a symptom denoting a problem exist outside the home. Usual causes are improper downspouts extensions , leaky gutters or improper grading at the perimeter of house. A proper slope away from the house is one inch per foot for 5 to 6 feet.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One, Not determined (inaccessible or obscured)
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
Age of roof: 10 to 15 years old
8)  Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 8-1 
9)  One or more gutters were leaking. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 9-1 
10)  Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 10-1 
Photo
Photo 10-2 
11)   VALLEYS AND FLASHING that are covered with shingles and or tar or any other are considered not visible and are not part of the inspection.

TAR AND GRAVEL ROOFS - This type of covering on a pitched roof requires ongoing annual maintenance. We recommened that a roofing contractor evaluate this type of roof.

Flat roofs are very vulnerable to leaking. It is very important to maintain proper drainage to prevent ponding of water.

ROOF TYPE LIFE EXPECTANCY REMARKS

Asphalt 20-25 yrs Used on 80% of roofs today
shingles

arch. asphalt 30-40 yrs heavier and more durable.

Asphalt roll roofing 10 yrs used on low slope roofs.

wood shingles 20-40 yrs treat with preservative every 5 yrs

Clay tiles 20 + yrs durable, fireproof but not watertight

Slate shingles 30-100 yrs very durable but brittle and costly

Metal roofing 20-40 yrs comes sheets and shingles should be
well grounded and needs painting.
Attic and Roof StructureTable of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-25
Vermiculite insulation present: Yes
Vapor retarder: Installed, None in some areas
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents
12)  What appeared to be vermiculite insulation was found in the attic. Vermiculite produced prior to 1991 may contain asbestos, less so if mined after 1991. When vermiculite insulation is present in attics, the EPA recommends that it be left undisturbed and that the attic not be used for storage, and that people (especially children) should not enter the attic. If the client is concerned about this material posing a safety hazard, then consult with a qualified asbestos abatement specialist or industrial hygienist. For more information, visit:
http://www.reporthost.com/?VERMINS
http://www.reporthost.com/?AITH
Photo
Photo 12-1 
13)  One or more exhaust ducts (e.g. bathroom fan, clothes dryer) in the attic have come apart, were loose or have fallen down. This can result in increased moisture levels inside the structure and is a conducive condition for wood-destroying organisms. Recommend that a qualified person make permanent repairs as necessary.
Photo
Photo 13-1 
Garage or CarportTable of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Detached
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 2
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): No
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Exists
14)  Garage wall pushed back and split the bottom 2x4.
Photo
Photo 14-1 
15)  Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Photo
Photo 15-1 
16)   OVERHEAD DOOR OPENERS
We recommend that a separate receptacle be provided for all openers. Openers that do not have a safety reverse are considered a safety hazard . Small children and pets are especially vulnerable . We recommend that switches are placed high enough so that children can't reach them

BURNERS
Any appliance such as a water heater, furnace etc. should have the flame at least 18'' above the floor. any flame below 18'' is considered a safety hazard.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Main disconnect rating (amps): 200
System ground: Cold water supply pipes
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
17)  One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
Photo
Photo 17-1 
18)  One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 18-1 Basement light for the stairs
Photo
Photo 18-2 Light in rear porch
19)   Every effort has been made to evaluate the size of the service. Three wires going in to house indicate 240 volts. The total amperage can be difficult to determine. We highly recommend that ground fault interrupters [GFCI] be connected to all receptacles around water. This device automatically shuts the circuit off when senses a current leak to ground. This device can be purchased at any hardware store. GFCI'S are recommended by all receptacles located near water, outside receptacles,or garage receptacles. Pool receptacles should also be protected with a GFCI. If you do have GFCI's it is recommended that you test and reset them monthly When you push the test button,the reset button should pop out,shutting off the circuit. If it doesn't,the breaker is not working properly. If you don't test them monthly the buttons have a tendency to stick and may not protect you when needed. Knob and tube wiring found in older homes should be checked by an electrician to ensure the wire covering is in good condition. Under no circumstances should this wire be covered with insulation. Recessed lighting should have a baffle around them so that they are not covered with insulation. Newer recessed lighting will turn off if they overheat. Federal Pacific Stab Lok Electrical panels may be unsafe. See www.google.com (Federal Pacific) . Aluminum wiring in general lighting circuits have a history of overheating with a potential of fire. If this type of wiring exists ,a licensed electrical contractor should evaluate the whole system. . ARC FAULTS In some areas arc Faults are required for bedrooms in new homes starting in 2002. In some areas arc faults are required for all 120 volt circuits that are not GFCI protected in new homes starting in 2009. Upgrade is desired for enhanced safety. . REVERSE POLARITY A common problem in many homes that surfaces is reverse polarity. This is a potentially hazardous situation on which the hot and neutral wires are reversed at the receptacle, thereby allowing the appliance to be incorrectly connected. this is an inexpensive item to correct. . Each receptacle has a brass and a silver screw. The black wire should be wired to the brass screw and the white wire should go to the silver screw. When these wires are switched, this is called "reverse polarity". Turning off the power and switching these wires will correct the problem. . Main service wiring for housing typically 240 volts. The minimum capacity for newer homes is 100 amps though many older homes still have 60 amp service. Main service wiring may be protected by one or more circuit breakers or fuses. While most areas allow up to six main turnoffs, expanding from these panels is generally not allowed.
COOLING Testing A/C Systems and heat pumps. The circuit breakers to A/C should be on for a minimum of 24 hours and the outside temperature be at least 65 degrees for the past 24 hours or an A/C system can not be operated without possible damage to the compressor. Check the instructions in your A/C manual or on the outside compressor before starting up in the summer. Heat pump can only be tested in the mode it's running in. Outside temperature should be at least 65 degrees for the past 24 hrs to run in cooling mode.

A/C CONDENSER COIL They should not become overgrown with foliage. Clearance requirements vary, but 2' on all sides should be considered minimal with up to 6' of air discharge desirable. If a clothes dryer vent is within five to ten feet either relocate the dryer vent or do not run when A/C is running. The lint will quickly reduce the efficiency of the A/C unit.
Plumbing / Fuel SystemsTable of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic, Galvanized steel
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Galvanized steel
Vent pipe condition: Appeared serviceable
Vent pipe material: Galvanized steel
Sump pump installed: No
Sewage ejector pump installed: No
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: oil tank
Location of main fuel shut-off valve: At oil tank
20)   WELLS Examination of wells is not included in this visual inspection. It is recommended that you checked for purity by the local health authorities , and if possible,a check on the flow of the well during periods of drought. A well pit should have a locked cover on it to prevent anyone from falling into the pit.

SEPTIC
The check of septic systems is not included in our visual inspection. You should have the local health authorities or other qualified experts check the condition of the septic system.

In order for the septic system to be checked, the house must have been occupied within the last 30 days.

WATER PIPES
Galvanized water pipes rust from the inside out and may have to be replaced within 20 to 30 years. This is usually done in two stages: horizontal piping in the basement first, and vertical pipes throughout the house later as needed.

Copper pipes usually have more life expectancy and may last as long as 60 years before needing to be replaced.

HOSE BIBS
During the winter months it is necessary to make sure the outside faucets are winterized. This can be done by means of a valley located in the basement. Leave the outside faucets open to allow any water standing in the pipes to drain, preventing them from freezing. Hose bibs cannot be tested when winterized.

WATER HEATER
The life expectancy of a water heater is 5-10 years. Water heaters generally need not be replaced unless they leak. It is good maintenance practice to drain 5-10 gallons from the heater several times a year. Missing relief valves or improper extension present a safety hazard.

WATER SOFTENERS
During a visual inspection it is not possible to determine if water is being properly softened.

PLUMBING
The temperature/pressure valve should be tested several times a year by lifting the valve's handle. Caution: very hot water will be discharged. If no water comes out, the valve is defective and must be replaced.

SHUT-OFF VALVES
Most shut-off valves have not been operated for long periods of time. We recommend operating each shut-off valve to: toilet bowl, water heater, under sinks, main shut-off, hose faucets, and all others. We recommend you have a plumber do this, as some of the valves may need to be repacked or replaced. Once the valves are in proper operating order, we recommend opening and closing these valves several times a year.

POLYBUTYLENE PIPING
This type of piping has a history of problems and should be examined by a licensed plumber and repaired or replaced as necessary.

MECHANICAL DEVICES MAY OPERATE AT ONE MOMENT AND LATER MALFUNCTION; THEREFORE,LIABILITY IS SPECIFICALLY LIMITED TO THOSE SITUATIONS WHERE IT CAN BE CONCLUSIVELY SHOWN THAT THE MECHANICAL DEVICE INSPECTED WAS INOPERABLE OR IN IMMEDIATE NEED OF REPAIR OR NOT PREFORMING THE FUNCTION FOR WHICH IS IT WAS INTENDED AT THE TIME OF INSPECTION.
Water HeaterTable of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2008
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
21)  Inspector could not hot water from old water heater because the pilot light was out. Recommend a qualified contractor evaluate and service as needed
Photo
Photo 21-1 
22)  The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be near this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 22-1 
Heating, Ventilation and Air Condition (HVAC)Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Boiler
General heating distribution type(s): Pipes and radiators
Last service date of primary heat source: 1-18-21
Source for last service date of primary heat source: Property owner
Condition of burners: Appeared serviceable
Type of combustion air supply: Vent(s) to exterior, No dedicated source visible, uses room air
Condition of venting system: Appeared serviceable
Condition of controls: Appeared serviceable
23)  The last service date of the gas or oil fired boiler appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
Photo
Photo 23-1 
24)  The estimated useful life for most cast iron boilers is 40 to 50 years. This boiler appeared to manufactured in 1997.
Photo
Photo 24-1 
Photo
Photo 24-2 
25)   HEATING AND AIR CONDITIONING units have normal lives. normal lives are;

GAS FIRED HOT AIR 15-25 YRS

0IL-FIRED HOT AIR 20-30 YRS

CAST IRON BOILER 30-50 YRS +

STEEL BOILER 30-40 YRS +

COPPER BOILERS 10-20 YRS

CIRCULATING PUMP (hot water) 10-15 YRS

AIR CONDITIONING COMPRESSOR 8 -12 YRS

HEAT PUMP 8 - 12 YRS


Gas fired units that are close to or beyond their normal lives have the potential of becoming a source of carbon monoxide in your home. You my want to have such a unit checked annually to assure yourself the unit is still intact. Of course a unit of such age is a candidate for replacement with a new high efficiency furnace. The fuel savings alone can be very attractive.

Boilers and there systems may require annual attention. If you are not familiar system, have heating contractor come out in the fall to show you how to do some necessary thing

Forced air systems should have their filters changed every 30-60 days during the heating and cooling seasons. This is especially true if you have central air conditioning. A dirty air system can lead to premature failure to your compressor- a $1,500 machine

Oil-fired boilers and furnaces should be serviced every year by a service professional. most experts agree you will pay for the service cost in fuel saved each year by having a well tuned burner.

Heat exchangers cannot be examined nor their condition be determined without being disassembled. Since this is not possible during a visual inspection. you may want to obtain a service on the unit or contact a furnace technician regarding a more thorough examination.
Fireplaces, Stoves, Chimneys and FluesTable of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry
Condition of wood-burning fireplaces, stoves:
Condition of gas-fired fireplaces or stoves: Required repair, replacement and/or evaluation (see comments below)
Gas fireplace or stove type: Converted wood-burning fireplace
26)  Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit:
http://www.reporthost.com/?ANGFINSP
Photo
Photo 26-1 
27)  The brick chimney was moderately deteriorated. For example, loose or missing mortar, cracked, broken, loose or spalled bricks. Loose bricks can pose a safety hazard, and deteriorated masonry can allow water to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary.
Photo
Photo 27-1 
Photo
Photo 27-2 
28)  The glass front on the gas fireplace had a hazy film. This is typically a mineral residue left from water vapor as the gas burns. It may be possible to clean this fogging by removing the glass from the fireplace and using a gas appliance ceramic glass cleaner, available through gas fireplace and stove distributors and installers. Ammonia-based products, such as common glass cleaners, should not be used since they can cause damage or etching to the glass, or make the haze permanent. It may be possible for a homeowner to remove the glass for cleaning, if the instructions for the fireplace are available and if the homeowner is experienced in such repairs. Consult with a qualified specialist for more information, or to have them do the cleaning.
29)   Chimneys built of masonry will eventually need tuck pointing. A cracked chimney top that allows water to get behind the surface brick will accelerate the deterioration. Moisture will also deteriorate the clay flue liner. Periodic cleaning will keep you apprised of the chimneys condition.the flashing around the chimney may need resealing and should be inspected every couple years or so. Unlined chimneys should be evaluated by a chimney technician.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of walls: Satisfactory
Condition of ceiling: Satisfactory
30)  The microwave oven was inoperable. Recommend that a qualified person evaluate and repair or replace as necessary.
Photo
Photo 30-1 
31)  The refrigerator was Old. Recommend that a qualified person repair as necessary. The refrigerator may need replacing.
Bathrooms, Laundry and SinksTable of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Central exhaust fan
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
Condition of walls: Satisfactory
Condition of ceiling: Satisfactory
32)  The exhaust fan at location(s) #A was weak or slow. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.

Photo
Photo 32-1 
33)   STALL SHOWERS
The metal shower pan in a stall shower has a potential or probable life of 10-20 years depending on the quality of the pan installed. Although a visual inspection is made to determine if the shower pan is leaking, it cannot be stated with certainty that no defect is present or that one may not soon develop. Shower pan leaks often do not show except when shower is in actual use.

CERAMIC TILE

Bathroom tile installed in a mortar bed is excellent. It is still necessary to keep the joints between the tile and the tub/shower caulked or sealed to prevent water from leaking through and damaging the ceiling below.

Ceramic tile is often installed in mastic. It is important to keep the gaps between the tile caulked so water won't seep behind and deteriorate the wall board. Special attention should be paid area around facets and other penetrations.

EXHAUST FANS

Bathrooms with a shower should have exhaust fans when possible. This helps to remove excess moisture from the room, preventing damage to the walls ceiling and wood finishes.
The exhaust fan should not be vented into the attic. The proper way to vent fans is to the outside. Running a vent pipe horizontally and venting into a soffit is preferred.

SLOW DRAINS on sinks, tubs, and showers are usually due to build up of hair and soap scum. Most sink popups can be easily removed for cleaning. Some tubs have a spring attached to the closing lever that acts as a catch for hair. It may require removing a couple of screws to disassemble. If you can't mechanically remove the obstruction, be kind to your pipes. Don't use a caustic cleaner. There are several bacteria drain cleaners available. This drain cleaners take a little longer to work but are safe on your pipes.
Interior, Doors and WindowsTable of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Wood, Double-hung
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
34)  One or more exterior doors had double-cylinder deadbolts installed, where a key is required to open them from both sides. This can be a safety hazard in the event of an emergency because egress can be obstructed or delayed. Recommend replacing double-cylinder deadbolts with single-cylinder deadbolts where a handle is installed on the interior side.
Photo
Photo 34-1 
35)  Floors in one or more areas were not level. This can be caused by foundation settlement or movement of the foundation, posts and/or beams. Significant repairs may be needed to make floors level. Recommend that a qualified contractor and/or engineer evaluate further. Repairs should be performed by a qualified contractor.
Photo
Photo 35-1 
36)  One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo
Photo 36-1 
37)  Glass in one or more windows was cracked, broken and/or missing. Recommend that a qualified contractor replace glass where necessary.
Photo
Photo 37-1 
38)  Lock mechanisms on one or more windows were inoperable and/or difficult to operate. This can pose a security risk. Recommend that a qualified person repair as necessary.
Photo
Photo 38-1 
Photo
Photo 38-2 
Photo
Photo 38-3 
39)   WINDOW FRAMES AND SILLS Window frames and sills are often found to have surface deterioration due condensation that has run off the window and damaged the varnish. Usually this can be repaired with a solvent style of refinisher and fine steel wool. thus is sometimes a sign of to much humidity in the house. FIREPLACES It is important that a fireplace be cleaned on a regular basis to prevent creosote build up in the flue, which can cause a chimney fire. Masonry fireplace chimneys are normally required to have terra cotta flue liner or 8 inches of masonry surrounding each flue to be consider safe. During visual inspections, it is not uncommon to be unable to detect the absence of a flue liner either because of stoppage at the firebox,a defective damper or lack of access from the roof. WOOD BURNERS Once installed,it can be difficult to determine proper clearances for wood burning stoves. Manufacturers specifications are usually unavailable to the inspector to determine proper installation. VENTILATION Ventilation is recommended at the rate of one sq. ft.of vent area to 300 sq. ft. of attic floor space, this being divided between soffit and rooftop. Power vents should ideally have both humidistat and a thermostat, since ventilation is needed to remove both winter moisture and summer heat. Evidence of condensation such as blacken roof sheathing is an indication that ventilation may have been blocked or is blocked orinadequate. INSULATION The recommended insulation in the attic is R-38 If insulation is added, it is important that the ventilation is proper. SMOKE DETECTORS Smoke detectors should be tested monthly. At least one detector should be installed on each level. CO detectors are not required by most states, but for safety reasons, are highly recommended. VAPOR BARRIERS The vapor barrier should be on the heated side of the surface. Most older homes were built without vapor barriers. if the vapor barrier is towards the cold side of the surface it should be sliced or removed. Most vapor barriers in the attic are covered by the insulation and therefore not visible. INSULATED GLASS Broken seal in thermopane/insulated windows are not always visible nor detectible due to humidity and temperature changes during the day. Other factors such as window covering,dirty windows,and lack of accessibility, personal property placed in front of the windows all effect the view of the windows at the time of the inspection
Wood Destroying Organism FindingsTable of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: No


Photo
Photo X-1