Bishop Property Inspections

PO Box 3595 
Sequim WA 98382-5039
Inspector: Chuck Bishop
Inspector's email: chuck@bishoppropertyinspections.com
Inspector's phone: (360) 461-0170
Title picture

Property Inspection Report
Unofficial version!

Client(s): Buffie Earley-Carpentier
Property address: 522 E 8th St
Port Angeles WA 98362-6222
Inspection date: Friday, December 5, 2025

This report published on Saturday, December 6, 2025 11:30:55 AM PST

This report is the exclusive property of this inspection company and the client listed in the report title. Use of this report by any unauthorized persons is prohibited.

How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information
Concern typeDamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Life Safety
Grounds
Exterior and Foundation
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Restrooms, Bathrooms, Laundry and Sinks
Offices, Interior, Doors and Windows
Wood Destroying Organism Findings
View summary

General InformationTable of contents
Report number: 5275
Time started: 9:00 AM
Time finished: 10:30 AM
Present during inspection: Client
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Rain
Temperature during inspection: Cool
Inspection fee: $400.00
Payment method: Check
Primary use of building(s) and property: Beauty Salon
Age of main building: 1953
Front of building faces: North
Main entrance faces: North
Occupied: Yes
1)  The property was older and may not meet many generally-accepted current building standards. Older properties are inspected within the context of the time period in which they were built, taking into account the generally-accepted building practices of that period. This report may comment on unsafe conditions, but problems will be described as defects at the inspector's discretion.

Properties are not required to be constantly upgraded to comply with newly-enacted building codes, and are only required to comply with building codes or generally-accepted standards which existed at the time of original construction.
An exception may exist when a property is remodeled, depending on the scope of work.

This inspection is not a building code-compliance inspection, but an inspection for safety and system defects. This report may comment on and identify as problems, systems, components and/or conditions which may violate building codes. However confirmation of compliance with any building code or identification of any building code violation is not the goal of this inspection or report, and lies beyond the scope of this inspection.
Fire suppression system installed: No
Fire alarm system installed: Yes
2)  Exit signs near emergency exits were missing. This is a potential safety hazard. A qualified person should repair, replace or modify exit signs as necessary, and per National Fire Protection Association (NFPA) 101 standards.
3)  A fire alarm system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist.
Photo
Photo 3-1 
Site profile: Level
Condition of parking areas and driveways: Appeared serviceable
Parking areas and driveways material: Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Exterior and FoundationTable of contents
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade
Foundation/stem wall material: Concrete slab on grade
Footing material (under foundation stem wall): Poured in place concrete
Anchor bolts or hold downs for seismic reinforcement: None visible
Shear panels for seismic reinforcement: None visible
4) Damage Deterioration was found at fascia. Recommend that a qualified contractor repair as necessary. All deteriorated wood should be replaced.
Photo
Photo 4-1 
5)  Some sections of siding were loose or cracked. Recommend that a qualified person repair or replace siding as necessary.
Photo
Photo 5-1 
Photo
Photo 5-2 
6) Conducive conditions Soil (gravel) was in contact with or less than 6 inches from siding, trim or structural wood. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be discovered when soil is removed, and further repairs and wood replacement may be necessary.
Photo
Photo 6-1 
Photo
Photo 6-2 
7) Conducive conditions The paint finish over much of the entire structure was failing (e.g. peeling, faded). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep and repaint the entire building exterior per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
Photo
Photo 7-4 
Photo
Photo 7-5 
Roof inspection method: Traversed
Condition of roof surface material: Near, at or beyond service life
Roof surface material: Torch down (modified bitumen)
Roof type: Flat or low slope
Apparent number of layers of roof surface material: Not determined (inaccessible or obscured)
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
8) Conducive conditions The roof surface was significantly deteriorated and appeared to be at or beyond its service life. It needs replacing now. This is a conducive condition for wood-destroying organisms. Consult with a qualified contractor to determine replacement options. Note that some structural repairs are often needed after old roof surfaces are removed and the structure becomes fully visible. Related roofing components such as flashings and vents should be replaced or installed as needed and per standard building practices. Per client, a bid has been received, and roofing will be replaced in the near future. Roof signage and chimney to be removed.
Photo
Photo 8-1 
Attic and Roof StructureTable of contents
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Not determined (inaccessible or obscured)
Vapor retarder: None visible
9)  Ceiling insulation or insulation at roof level was not observed. Client may wish to have a qualified contractor install insulation at time of reroofing for better energy efficiency and per standard building practices.
10)  No accessible attic spaces were found or inspected at this property. The inspector attempts to locate attic access points and evaluate attic spaces where possible. When a structure is occupied, such access points may be obscured by stored items or furnishings. Inspectors typically don't move stored items, furnishings or personal belongings. If such access points are found in the future and/or made accessible, a qualified person should fully evaluate those attic spaces and roof structures.
11)  The roof structure had no visible venting.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Back room
Location of sub-panel #F: Back room
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: armor clad (AC), metal clad (MC) or flexible metal conduit (FMC)
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke detectors installed: Yes, but not tested
Carbon monoxide detectors installed: No, recommend install
12)  Plastic water supply pipes were installed, and the electric service appeared to rely on metal water supply pipes for a grounding electrode. The plastic pipes may have compromised the grounding system and may pose a safety hazard for shock. Recommend that a qualified electrician evaluate and repair if necessary.
Photo
Photo 12-1 
Photo
Photo 12-2 
13)  Electric receptacles at locations where required had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
Photo
Photo 13-4 
14)  No carbon monoxide detectors were found on the property. This is a potential safety hazard. Modern standards call for placement of CO detectors on every habitable level and in every HVAC zone of buildings. CO detectors must be distinct from fire alarms and other devices. CO detectors are typically integrated with central fire alarm systems where installed. A qualified contractor should evaluate and install CO detectors per standard building practices. Existing detectors may detect CO, but could not be verified.
15)  A wire showed signs of over-heating. A qualified electrician should evaluate and make repairs or replace components as necessary.
Photo
Photo 15-1 Subpanel
16)  The service mast extended above the roof surface and the guy wires were substandard. This is a potential shock hazard. Recommend that a qualified electrician repair per standard building practices.
Photo
Photo 16-1 
17)  Several ground fault circuit interrupter (GFCI) type receptacles had an open ground. Open ground GFCI receptacles will trip, but they won't provide a grounded electric supply for appliances that need them. This is a potential shock hazard. Client may wish to have a qualified electrician upgrade wiring per standard building practices.
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
18)  Smoke detectors were found in buildings. However requirements for smoke detectors vary by occupancy type and in some cases by municipality. It is beyond the scope of this inspection to determine all required locations for smoke detectors. A qualified contractor should evaluate buildings on this property and install and/or replace smoke detectors per standard building practices. Smoke detectors are typically integrated with fire alarm systems where installed.
Photo
Photo 18-1 
Plumbing / Fuel SystemsTable of contents
Condition of service and main line: Appeared serviceable
Water service: Public
Service pipe material: Galvanized steel, Plastic
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, Galvanized steel, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic, Galvanized steel
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Galvanized steel, Cast iron
Location(s) of plumbing clean-outs: Not determined (obscured, inaccessible or none found)
Vent pipe condition: Appeared serviceable
Vent pipe material: Cast iron
Sump pump installed: Yes
Condition of sump pump: Appeared serviceable
Condition of fuel system: Not determined (gas service off or no fuel oil)
Visible fuel storage systems: None visible
19)  The inspector was unable to locate the main sewer clean-out, and unable to verify that one exists. Such clean-outs can help determine if the main line versus a fixture drain line is clogged, and make clearing out the sewer line easier and less expensive. Without a main sewer clean-out, a plumber's drain clearing machine will need to be run through an internal fixture (e.g. a toilet) or through a vent pipe typically located on the roof. Consult with the property owner, or have a qualified plumber evaluate if necessary, to determine if a clean-out exists. If one is not installed, then recommend that a qualified plumber install one per standard building practices.
20)  Per client, some drain pipes have a substandard slope. Clogging or leaks can occur as a result. Drain and waste pipes should be sloped 1/4 inch per foot of length if less than 3 inches in diameter, or 1/8 inch per foot of length for larger diameters. At this point, client needs to snake said pipes periodically. Client may wish to consult with a qualified electrician to determine if other alternatives exist.
21)  A plumbing vent pipe terminated less than 6 inches above the roof surface below. Debris and/or snow can block vent pipe openings with such short pipes. Blocked vent pipes can cause sewer gases to enter living spaces. Recommend that a qualified person repair by extending pipe to terminate at least 8 inches above the roof surface.
Photo
Photo 21-1 
22)  The inspector was unable to determine the output location for the sump pump's discharge pipe. Consult with the property owner or evaluate further to determine the location of the sump pump discharge pipe. Discharge pipes should terminate well away from foundations to soil sloping down and away so water doesn't accumulate around the foundation or in crawl spaces or basements. If it does terminate close to the foundation, recommend that a qualified person repair per standard building practices.
Photo
Photo 22-1 
Water HeaterTable of contents
Condition of water heater: Appeared serviceable
Type: Tankless
Energy source: Electricity
Capacity (in gallons): Not applicable, 12 amp draw per manf.
Temperature-pressure relief valve installed: Yes
Manufacturer: Bosch
Model number: ES8-1MWIR
Serial number: 7 738 004 998
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 111 degrees
Heating, Ventilation and Air Condition (HVAC)Table of contents
General heating system type(s): Heat pump, Electric heaters
General heating distribution type(s): None, individual heaters
Condition of electric heaters (not forced air): Appeared serviceable
Electric heater type (not forced air): Wall mounted, fan-assisted
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Electric
Estimated age of forced air furnace: 2015
Forced air heating system manufacturer: Daikin
Forced air furnace model #: FTX18NMVJU
Forced air furnace serial number: G005418
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): Behind return air grill(s)
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: Building exterior
Type: Split system, Heat pump
Estimated age of heat pump or air conditioning unit: 2015
Manufacturer of cooling system and/or heat pump: Daikin
Heat pump or air conditioner model number: RX18NMVJU
Heat pump or air conditioner serial number: G004129
Condition of controls: Appeared serviceable
23)  The last service date of the forced air heating/cooling system appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor service this system and make repairs if necessary. Because this system has a compressor and refrigerant system, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the contractor when it's serviced.
24)  The outdoor air temperature was below 65 degrees Fahrenheit during the inspection. Air conditioning systems can be damaged if operated during such low temperatures. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
Restrooms, Bathrooms, Laundry and SinksTable of contents
Location #A: Unisex restroom
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
25)  The clothes dryer was equipped with a vinyl or mylar, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. They can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow and cause overheating. Recommend that such ducts be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary.
26)  A sink drained slowly. Recommend clearing drain and/or having a qualified plumber repair if necessary.
Photo
Photo 26-1 
Offices, Interior, Doors and WindowsTable of contents
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Metal, Multi-pane, Single-pane, Fixed, Jalousie
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Tiles
Condition of flooring: Appeared serviceable
Flooring type or covering: Vinyl, linoleum or marmoleum
27) Conducive conditions Stains and elevated levels of moisture were found ceiling/wall areas. One wall area appears to be an active leak. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 27-1 
28)  There was a hole in a wall. Recommend that a qualified person repair as necessary.
Photo
Photo 28-1 Bathroom
Wood Destroying Organism FindingsTable of contents
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: No