Heartland Commercial Property Inspections LLC

https://heartlandcommercialpropertyinspections.com
(614) 286-5229
Inspector: Jim Troth
Title picture Title picture

Warehouse/Manufacturing Inspection Report
Unofficial version!

Client(s): Business Client
Property address: Any City, OH 43232-4302
Inspection date: Friday, November 22, 2024

This report published on Saturday, January 4, 2025 9:39:34 AM EST

"No home is perfect. Keep things in perspective. Do not kill your deal over things that do not matter. It is inappropriate to demand that a seller address deferred maintenance, conditions already listed on the seller's disclosure or nit-picky items."

The above is an excerpt from Sell Your Home For More by Nick Gromicko.

Acceptance of this report and/or relying on the information within constitutes acceptance of the real estate inspection agreement limits for the client listed above even if the agreement is not signed. Reliance on a home inspection report that was originally performed for a different home buyer removes warranties. Home Inspections are not a pass/fail. The purpose is to identify the condition of the home as much as can be done at the time of the inspection. It is out of the scope of the home inspection to give estimates for repairs. We recommend that contractors be utilized prior to closing to provide repair estimates.

If you are not the person identified as the client above then you need to attain permission from the client above and you need to have your own home inspection completed.

It is not typical to request to remedy those items which are small maintenance items. Your real estate agent will be your best source to help determine which items (if any) are appropriate to request for correction or improvement

Table of Contents

General information
Exterior and Foundation
Electric service and Branch Wiring
Heating and cooling
Plumbing, Toilets, Water Heater
Warehouse and Office Space
Warehouse rolling doors
Attic/Roof
Commercial Life Safety
View summary

General informationTable of contents
Type of building: Office and Warehouse
Year built: 1962
Present during inspection: Client(s)
Occupied: No
Weather conditions: Cloudy
Temperature: 30's
Foundation type: Slab
1) Safety, Comment -  Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygenists, professional labs and/or abatement contractors for this type of evaluation.
2) Comment -  The Basic Commercial Inspection was conducted according to International Standards of Practice for Inspecting Commercial Properties. The inspection, the Report, and its uses are strictly limited to the scope as described herein and as expressed in the agreement. The inspection is in no way intended to be a warranty or guarantee, express or implied, regarding the future use or operability of the building or its components.
3) Comment -  The scope of service for this Basic Commercial Inspection includes the following:
Walk-through survey to visually observe the subject property so as to obtain information on material systems and components for the purposes of providing a brief description and identifying physical deficiencies to the extent that they are easily visible and readily accessible. The focus is upon larger expense items, typically well above the $500-$1000 range
4) Comment -  Photos are only a representative sample of conditions observed. There may be more than one area of concern not shown by photo
5) Comment -  This is a reminder that inspections are not code inspections, zoning checks nor a check for permits. Most buildings more than only a few years old are not up to current codes due to codes changing over time. It is normal and expected for homes and buildings not to be "up to code". Codes themselves are subject to locations and interpretation.

Inspections are also not a pest/rodent inspection. It is not uncommon for critters to move into buildings when weather gets colder and/or there are food sources available. Keep food sources away and monitor always.

It is recommended that you get estimates for repairs prior to closing to fully understand the costs involved. Cost estimates are not part of the inspection. Our inspectors do not provide repairs so any estimate provided is very rough if given and should not be relied on due to large variations from contractors and materials.

Life expectancy of materials, appliances and systems is outside the scope of the inspection. Any information regarding this should not be relied upon due to variations of opinions from contractors and materials.
6) Comment -  Issues that are considered cosmetic are not the goal of this report. For example, holes, stains, scratches, unevenness, not perfectly level or square, missing trim, paint and finish flaws or odors.

Inspections and inspection reports are not a guaranty of future performance or future functionality. The inspection company is not responsible for failure to properly maintain the property or damage that occurs or uncovered after taking possession.
7) Comment -  Additional Inspector(s):

Jim Troth
8)   -  The purpose of the Basic Commercial Inspection is to determine the current condition of the improvements located on a parcel of commercial real estate, by performing a walk-through survey and conducting research. The goal is to identify and communicate physical deficiencies to the user. The term physical deficiencies means the presence of conspicuous defects or material deferred maintenance of a subject property's material systems, components, or equipment as observed during the field observer's walk-through survey.
Exterior and FoundationTable of contents
Footing material: Not visible
Foundation material: Concrete block
Apparent wall structure: Concrete block
Wall covering: Stucco
Sidewalk material: Poured in place concrete
9) Safety, Major Defect, Repair/Replace, Evaluate -  Cracks, deterioration, leaning and/or bowing were found in retaining walls. Because of the height or proximity to foundations or property lines, a qualified structural engineer should evaluate to determine what repairs are necessary. Repairs should be made by a qualified contractor.
Photo
Photo 9-1 
10) Safety, Major Defect, Repair/Replace -  Loading docks/ ramps were damaged. Recommend evaluation and securing all loading docs to help ensure safety.
Photo
Photo 10-1 
Photo
Photo 10-2 
Photo
Photo 10-3 
Photo
Photo 10-4 
Photo
Photo 10-5 
Photo
Photo 10-6 
11) Safety, Major Defect, Evaluate -  Observed damaged foundation / walls and supports in various areas. Recommend evaluation and repair/replacement to help ensure proper foundation support. Recommend evaluation prior to closing.

Cables used for diagonal bracing were also damaged
Photo
Photo 11-1 
Photo
Photo 11-2 
Photo
Photo 11-3 
Photo
Photo 11-4 
Photo
Photo 11-5 bowing
Photo
Photo 11-6 
Photo
Photo 11-7 bowing
12) Safety, Repair/Replace -  Vehicle restraint systems were not observed for all but one in the rear of the building. These help to prevent trailers from pulling away unexpectedly. Recommend installing to help prevent loading dock accidents.
https://www.ritehite.com/en/am/products/vehicle-restraints
Photo
Photo 12-1 The only trailer lock system observed.
13) Safety, Repair/Maintain, Evaluate -  Stairs/walkways have settled. Recommend evaluation and repair. Consider slab jacking as a repair method to ensure proper slope away from the building and to help remove any trip hazards.

Article explaining slab jacking https://homeinspectionsinohio.com/understanding-slab-jacking-a-cost-effective-solution-for-sunken-concrete/
14) Safety, Repair/Maintain, Evaluate -  Guardrails were loose and/or wobbly in one area(s). This is a safety hazard. Recommend evaluation and repairs as necessary, such as installing new fasteners or hardware, installing additional fasteners and/or installing additional railing components as necessary so they are securely attached.
Photo
Photo 14-1 
15) Safety, Repair/Maintain -  Stairs with more than two risers had no handrail installed. This is a safety hazard. Handrails should be installed and be graspable handrails that your hand can completely encircle at stairs where missing.
16) Major Defect, Repair/Replace, Evaluate -  Major crack / bowing (more than 3/4 inch wide) was found in the foundation / wall. These appear to be a structural concern, and may indicate that settlement is ongoing. The client(s) are strongly advised to hire qualified contractors and/or engineers as necessary for further evaluation of all areas of foundation. Such contractors may include:
  • Foundation repair contractors who may prescribe repairs, and will give cost estimates for prescribed repairs
  • Masonry contractors who repair and/or replace brick veneer
  • Geotechnical engineers who attempt to determine if settlement is ongoing, and what the cause of the settlement is
  • Structural engineers who determine if repairs are necessary, and prescribe those repairs
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
17) Repair/Replace, Evaluate -  Moderate cracking and / or bowing in was found in the foundation/wall. This may be a structural concern, and an indication that settlement is ongoing. The client(s) should consider hiring qualified contractors and/or engineers as necessary for further evaluation of all areas of the foundation. Such contractors may include:
  • Foundation repair contractors who may prescribe repairs, and will give cost estimates for prescribed repairs
  • Masonry contractors who repair and/or replace brick veneer
  • Geotechnical engineers who attempt to determine if settlement is ongoing, and what the cause of the settlement is
  • Structural engineers who determine if repairs are necessary, and prescribe those repairs
Photo
Photo 17-1 
Photo
Photo 17-2 
Photo
Photo 17-3 
Photo
Photo 17-4 
Photo
Photo 17-5 
Photo
Photo 17-6 
18) Repair/Replace, Evaluate -  There are indications of past foundation repair. However, there are some significant signs of subsequent movement. Recommend a structural engineer and/or drainage specialist be consulted for re-evaluation and/or possible repairs.
Photo
Photo 18-1 
Photo
Photo 18-2 
Photo
Photo 18-3 
Photo
Photo 18-4 
Photo
Photo 18-5 
19) Repair/Replace, Evaluate -  Support columns had dents. Recommend evaluation and repairs if needed.
Photo
Photo 19-1 
Photo
Photo 19-2 
20) Repair/Replace -  The perimeter grading sloped towards the structure in areas. This is a common find. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure. The grade should drop at least 6 inches within the first 10 feet. Correct any negative slope of brick/concrete areas as well to direct water away from structure.
https://homeinspectionsinohio.com/negative-grading/

Where the site does not allow for the necessary fall away from the structure, drains or swales could be used.
21) Repair/Replace -  One downspout was dented, damaged and/or crushed. This can restrict the water flow and result in clogging and overflowing gutters. Water may accumulate around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Damaged downspouts should be repaired or replaced as necessary.
22) Repair/Replace -  The cushions to help seal the "connection" between the back of a truck and the structure was missing or significantly deteriorated. Recommend installing.
23) Repair/Replace -  One gutter(s) was/were damaged/missing. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Recommend replacing or repairing gutters where necessary.
24) Repair/Replace -  Bumper designed to protect the dock was missing and deteriorated in area. Recommend installing to help absorb vehicle impacts to protect the docks.
Photo
Photo 24-1 
Photo
Photo 24-2 
Photo
Photo 24-3 
Photo
Photo 24-4 
25) Repair/Maintain -  Minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to help prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply.
  • Resilient caulks (easy to apply).
  • Epoxy sealants (both a waterproof and structural repair).

Note: small cracks can be the result of normal drying and shrinking of cement and mortar along with settling.
Photo
Photo 25-1 
Photo
Photo 25-2 
26) Repair/Maintain -  One downspout was missing. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms and may also cause the foundation to settle and possibly fail over time. A qualified contractor should install downspout(s) where missing. Also recommend installing extensions such as splash blocks or tie-ins to underground drain lines as necessary to carry rainwater away from the structure.
27) Repair/Maintain -  Gutters were leaking during the inspection. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Recommend repairing gutters where necessary.
28) Repair/Maintain -  Bollard(s) were missing in areas that would benefit from the protection of them. Consider installing where needed.
Photo
Photo 28-1 
Photo
Photo 28-2 
29) Comment -  The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Exterior buildings such as sheds, barns and garages are not included unless specifically requested. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight. Inspector is unable to determine condition of underlying materials (see through solid objects) such as materials behind siding and facia positioned behind gutters or flashing for examples.
30) Comment -  There are indications of past foundation repair such as installed I-beams, straps, anchors, etc. We recommend you refer to any structural engineer's report if available for further information of repairs, any warranties and proper maintenance of the foundation.
Photo
Photo 30-1 
Photo
Photo 30-2 
Photo
Photo 30-3 
Photo
Photo 30-4 
Photo
Photo 30-5 
Photo
Photo 30-6 
31)   -  The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, take measurements of plumbness, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Electric service and Branch WiringTable of contents
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200, 200, 200,400
Service voltage (estimated): 3 phase, 4 wire, 120/208
Location of Main Service Switch: Warehouse
Location of Sub panel: Warehouse, office
Location of main disconnect: Warehouse
Service entrance conductor material: Copper
System ground: Ground rod(s) in soil
Branch circuit wiring type: Conduit, metallic cable
32) Safety, Repair/Replace, Evaluate -  Significant amounts of contaminants or foreign material such as dirt and/or debris were found in the main service panel. No approved method exists for cleaning contaminants from panel interiors or components such as bus or terminal bars. The panel and/or components inside may need replacing. A qualified electrician should evaluate and repair or replace components as necessary.
Photo
Photo 32-1 
Photo
Photo 32-2 
33) Safety, Repair/Replace, Evaluate -  Loose conductors were found in the main service panel had bare ends and were not connected to circuit breakers or fuses. This is a safety hazard due to the risk of fire if the bare conductors come into contact with other components in the panel. An electrician should evaluate and repair as necessary. For example, removing wires that aren't terminated or installing wire nuts.

Panel 2,11,5
Photo
Photo 33-1 
Photo
Photo 33-2 
Photo
Photo 33-3 
Photo
Photo 33-4 
Photo
Photo 33-5 
34) Safety, Repair/Replace, Evaluate -  Neutral wires were doubled or bundled with other conductors on the neutral bus bar in the Panel 12,5. Neutral wires should each have their own terminal and not placed together. This is unsafe due to the need to turn off multiple circuit breakers to work on any of the circuits using these wires. A qualified electrician should evaluate and repair as necessary.

If a neutral wire is bundled with a ground, it is considered a lesser concern and very common for buildings prior to 2002 typically.
Photo
Photo 34-1 
Photo
Photo 34-2 
35) Safety, Repair/Replace, Evaluate -  One open ground, three-pronged grounding type receptacle(s) were found. This is a safety hazard due to the risk of shock. An electrician should evaluate and make repairs as necessary.

Grounding type receptacles were first required in structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.
Photo
Photo 35-1 
36) Safety, Repair/Replace, Evaluate -  Two electric receptacle had reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. An electrician should evaluate and make repairs as necessary.

identified with blue dot(s) with "H&N"
Photo
Photo 36-1 
37) Safety, Repair/Replace, Evaluate -  At least three sections of wiring that was not terminated was found. This is a potential safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. For example, cutting the wire to length and terminating the wire with wire nuts in a securely anchored, covered, properly sized junction box.
Photo
Photo 37-1 
Photo
Photo 37-2 
Photo
Photo 37-3 
38) Safety, Repair/Replace, Evaluate -  Wire splices were exposed due to not being contained in a covered junction box or in a box that had no cover. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes and/or cover plates where needed to contain wiring splices.
Photo
Photo 38-1 
Photo
Photo 38-2 
Photo
Photo 38-3 
39) Safety, Repair/Replace, Evaluate -  Interlocking three single-pole breakers together to create a "3-pole" breaker is generally not considered acceptable practice as it could be an electrical safety hazard and potentially compromise the circuit protection. If one of the "3 pole breakers" circuits were to trip, that one breaker may not be strong enough to trip the other two.

Recommend a qualified licensed electrician install a proper three pole breaker that is designed for that type of 3 phase circuit, and/or removing if not needed any longer.
Photo
Photo 39-1 
Photo
Photo 39-2 
40) Safety, Repair/Maintain, Evaluate -  Three electric receptacle(s) and/or the boxes they are installed in were loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
Photo
Photo 40-1 
Photo
Photo 40-2 
Photo
Photo 40-3 
41) Safety, Repair/Maintain, Evaluate -  Non-metallic sheathed wiring was routed so it is subject to damage, such as on wall or ceiling surfaces. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. This is a safety hazard due to the risk of shock and fire. Recommend improving as necessary. For example, rewire using conduit, or re-routing through wall cavities.
Photo
Photo 41-1 
42) Safety, Minor Defect -  Knockout(s) had been removed inside the main service panel where no wires and bushings are installed, and no cover(s) have been installed to seal the hole(s). This is a safety hazard. Recommend installing knockout covers where missing.
Photo
Photo 42-1 
Photo
Photo 42-2 
Photo
Photo 42-3 
Photo
Photo 42-4 
43) Safety, Minor Defect -  Pointed and/or too-long screws were used to fasten the cover to several panels. These types of screws are more likely to come into contact with wiring inside the panel than stock screws from the manufacturer, and can damage wiring insulation. This is a safety hazard due to the risk of shock and/or fire. Long and/or pointed crews should be replaced as necessary with the correct screws.
Photo
Photo 43-1 
Photo
Photo 43-2 
Photo
Photo 43-3 
44) Safety, Minor Defect -  Cover plates were missing for at least two electric box(s), such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. Cover plates should be installed where missing.
Photo
Photo 44-1 
45) Safety, Minor Defect -  Cover plate(s) were broken at three electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be replaced where necessary.
Photo
Photo 45-1 
Photo
Photo 45-2 
Photo
Photo 45-3 
46) Safety, Minor Defect -  Conduit for protecting wires were not loose or not secured properly at the ends. Consider improving to help protect wires. Typically conduit should be secured with in 3 feet of panels/ends.
Photo
Photo 46-1 
Photo
Photo 46-2 
Photo
Photo 46-3 
47) Repair/Replace, Evaluate -  Office areas electric receptacle(s) did not have power. Recommend asking the property owner(s) about this. Switches may need to be operated to make some receptacles energized. If necessary, a qualified electrician should evaluate and make repairs as necessary.

identified with blue dot(s)
Photo
Photo 47-1 
48) Serviceable, Comment -  No observable concerns with the electric panel wiring.
Photo
Photo 48-1 
Photo
Photo 48-2 
Photo
Photo 48-3 
Photo
Photo 48-4 
Photo
Photo 48-5 
Photo
Photo 48-6 
49) Comment -  The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring condition or materials; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch or outlet. Inspectors do not remove outlet covers and are unable to determine the type of wiring inside walls or in concealed spaces. Inspection are not code inspections.

Note: National safety standards require electrical panels to be weatherproof, readily accessible, and have a minimum of thirty-six inches of clear space in front of them for service. Also, they should have a main disconnect, and each circuit within the panel should be clearly labeled. Industry standards only require us to test a representative number of accessible switches, receptacles, and light fixtures. However, we attempt to test every one that is unobstructed, but if a building is furnished we will obviously not be able to test each one.
Heating and coolingTable of contents
Estimated Condenser age: 1995. 1995
Manufacturer(s): Lennox
Primary heating system energy source: Natural gas
Primary heat system type: Forced air
Primary A/C energy source: Electric
Primary Air conditioning type: Split system
Distribution system: Sheet metal ducts
Estimated Furnace age: 1995,1995,1995
50) Safety, Repair/Replace, Evaluate -  The furnace or boiler flame(s) are noisy (roaring) and/or "dancing" over the burner(s). This may be caused by an improper gas-air mixture flow velocity and may result in Carbon Monoxide due to incomplete combustion. A qualified heating and cooling contractor should evaluate and repair as necessary.
Photo
Photo 50-1 
Photo
Photo 50-2 
51) Repair/Replace, Evaluate -  The cooling fins on air handler's evaporator coils are bent, damaged and/or deteriorated. This may result in reduced efficiency and higher energy costs. A qualified heating and cooling contractor should evaluate and repair as necessary.
Photo
Photo 51-1 
Photo
Photo 51-2 
52) Repair/Replace, Evaluate -  One furnace did not respond when its controls were operated. This system was not fully evaluated. The client(s) should consult with the property owner(s) as to how it operates and have a qualified heating and cooling contractor evaluate and make repairs if necessary.
Photo
Photo 52-1 
53) Maintain, Evaluate, Comment -  The estimated useful life for forced air furnaces is 15 to 20 years. This furnace was at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future. Recommend also servicing and prior to closing.

Periodic maintenance will help ensure continued operation.
54) Maintain, Comment -  The estimated useful life for air conditioning compressors is 8 to 15 years. This unit was at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.

Periodic maintenance will help ensure continued operation.
55) Maintain -  The filter(s) for the heating/cooling system should be checked monthly and replaced or washed as necessary.

Also be aware that heating and cooling systems should have regular maintenance on them yearly to help ensure long life spans.
56) Monitor, Comment -  Stains observed on the exhaust vent. It appears that there may have been repairs such as sealing any gaps on the exterior. It is also possible that the stains can be caused by the exhaust fumes cooling and condensing. Monitor.
Photo
Photo 56-1 
57) Monitor -  Rust/stains observed in/on the furnace cabinet. Active leaking did not occur during time of inspection. Recommend monitoring for leaks from condensation.

If leaks do develop then get it evaluated and repaired to help prevent rusting/deterioration of the furnace.
Photo
Photo 57-1 
Photo
Photo 57-2 
58) Comment -  We check heating and cooling for basic function. Our inspection is not technically exhaustive.
Our inspection of ducts is naturally limited to observable areas. Therefore large areas of ducts cannot be seen. Since dirt, dust, mold, even toys are commonly found in ducts we recommend that you have the ducts cleaned.
59) Comment -  Image(s) of furnace
Photo
Photo 59-1 
Photo
Photo 59-2 
Photo
Photo 59-3 
Photo
Photo 59-4 
Photo
Photo 59-5 
Photo
Photo 59-6 
60)   -  Image(s) of condenser.
Photo
Photo 60-1 
Photo
Photo 60-2 
Photo
Photo 60-3 
Photo
Photo 60-4 
Photo
Photo 60-5 
Photo
Photo 60-6 
Photo
Photo 60-7 
Photo
Photo 60-8 
Plumbing, Toilets, Water HeaterTable of contents
Location of main water shut off: Warehouse
Location of main water meter: Warehouse
Location of main fuel shut off: Exterior
Water service: Public
Service pipe material: Polyethelene
Apparent supply pipe material(s): Copper, CPVC
Drain pipe material: Not visible
Waste pipe material: Not visible
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Manufacturer: Bradford White
61) Repair/Maintain, Evaluate -  Drain line was not capped or was capped in a non standard manner. Recommend improving to help prevent sewer gases from escaping.

Odor of sewer gas in the was noted. Recommend evaluation and corrections made as needed by a plumber.
Photo
Photo 61-1 
62) Comment -  The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing materials / components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only.

Note that the inspector is not required to operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
63) Comment -  "In accordance with industry standards, we do not normally test washing machines and their water connections and drainpipes if present. However, there are a few things of which you should be aware. The water supply to washing machines is usually left on, and their hoses can leak or burst under pressure and continue to flow. Therefore, we recommend replacing the rubber hose type with newer, braided, stainless steel ones that are much more dependable and that they be operated only during times you will be present. You should also be aware that the newer washing machines discharge a greater volume of water than many of the older drainpipes can handle, which causes the water to back up and overflow, and the only remedy would be to replace the standpipe and trap with one that is larger. Although not required, whenever structural damage may result from an overflow, we recommend a pan with a plumbed drain. An alternative is a flood or leak detection device that will terminate the water supply in a water pipe failure."
64) Comment -  It is beyond the scope of the inspection to confirm if the structure uses a septic or a public sewer system. This includes determination or inspection of aerators designed for septic systems. Recommend confirming with seller if there is any questions regarding this. It is always a great idea to have the county health department inspect any septic system.
65) Comment -  Your water meter and main water shut off location.
Photo
Photo 65-1 
66) Comment -  Image of water heater and data plate
Photo
Photo 66-1 
Photo
Photo 66-2 
Warehouse and Office SpaceTable of contents
67) Repair/Replace, Evaluate -  Deteriorated raised concrete floor sections observed. Recommend correction to help remove trip hazards.
Correct any conditions that could lead to settlement.
Photo
Photo 67-1 
Photo
Photo 67-2 
68) Repair/Replace, Evaluate -  Seals between double-pane glass in one window(s) had failed based on condensation or stains between at least one of the panes of glass. A qualified contractor should evaluate entire window and replace glass where necessary.

The client(s) should be aware that evidence of aging seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Windows or glass doors other than those that the inspector identified may also have failed seals and need glass replaced too.

https://homeinspectionsinohio.com/broken-seals
Photo
Photo 68-1 
69) Repair/Replace -  Active roof leaks were observed recommended repair
70) Repair/Replace -  Active roof leaks were observed throughout. Recommended repair
Photo
Photo 70-1 
Photo
Photo 70-2 
Photo
Photo 70-3 
Photo
Photo 70-4 
71) Repair/Maintain, Evaluate -  Ceiling panel/tile was deteriorated/damaged. Recommend evaluation and repairs/replacements as needed.
Photo
Photo 71-1 
Photo
Photo 71-2 
Photo
Photo 71-3 
Photo
Photo 71-4 
Photo
Photo 71-5 
72) Repair/Maintain -  Damage/cracks were found in walls in areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.
Areas:
Photo
Photo 72-1 
Photo
Photo 72-2 
73) Minor Defect, Maintain, Comment -  Minor cracks were found in the concrete slab. However, they don't appear to be a structural concern and no trip hazards were found. This is common for large sections of cement. Recommend sealing to help prevent water infiltration and for aesthetic reasons.
Photo
Photo 73-1 
Photo
Photo 73-2 
Photo
Photo 73-3 
Photo
Photo 73-4 
74) Minor Defect, Maintain -  The weatherstrip around the entry door was missing/deteriorated or had gaps to allow air leakage or water infiltration. Weatherstrip should be installed where missing and/or replaced where needed.
Photo
Photo 74-1 
75) Monitor -  Stains were found in drop ceiling area(s). However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks. Recommend asking the property owner(s) about this, and monitoring the stained area(s) in the future, especially after heavy or prolonged rain.
Photo
Photo 75-1 
Photo
Photo 75-2 
Photo
Photo 75-3 
Photo
Photo 75-4 
Warehouse rolling doorsTable of contents
76) Repair/Replace -  The vehicle doors were damaged or deteriorated. A qualified contractor should evaluate and repair or replace the doors as necessary.

Door D H
Photo
Photo 76-1 
Photo
Photo 76-2 
Photo
Photo 76-3 
77) Repair/Maintain, Minor Defect -  One roller was out of the track, repair/reposition to help ensure smooth and proper operation.

Door d
78) Repair/Maintain, Evaluate -  The vehicle doors were not balanced. The doors won't stay in place when it's partially opened. Recommend correction/tightening of the spring/tension-er.

https://www.youtube.com/watch?v=E58p206j16o

Doors B C E F G H

All the unlabeled doors were also not balanced
79) Repair/Maintain -  The track for the garage door was damaged/bent. Recommend evaluation and repairs as needed.

Door c
Photo
Photo 79-1 
80) Repair/Maintain -  Weatherstrip at the sides and/or bottom of the vehicle doors were damaged and/or deteriorated. They should be replaced where necessary to prevent water and small animal intrusion.
81) Repair/Maintain -  Bollard was damaged / loose. Recommend repairing to help protect the the opening space edges.
Photo
Photo 81-1 
82) Minor Defect, Monitor, Comment -  The garage vehicle door had some small areas of deterioration/dents. Still operational, monitor.
Attic Inspection method: Viewed from hatch
Roof structure type: Trusses, Rafters
Roof type: Flat
Roof covering: EPDM (ethylene-propylene-diene monomer), TPO
Estimated age of roof material: 20+
Gutter & downspout material: Metal
83) Major Defect, Repair/Replace, Evaluate -  The roof surface material is beyond or at the end of its service life and needs replacing now. The client(s) should consult with a qualified roofing contractor to determine replacement options and costs.
84) Repair/Replace, Evaluate -  Ventilation was substandard in the attic. Inadequate attic ventilation may result in high attic and roof surface temperatures, reduce the life of the roof covering materials and increase cooling costs. High levels of moisture are also likely, and can be a conducive condition for wood destroying insects and organisms. Standard building practices require one square foot of vent area for 150 to 200 square feet of attic space. Vents should be evenly distributed between soffits, ridges and at corners to promote air circulation. Recommend correction/improvement.
85) Repair/Replace, Evaluate -  Standing water was found on the flat roof. It should evaporate within 48 hours after it rains. If standing water remains after 48 hours, then the roof installation is likely substandard. A qualified roofing contractor should evaluate and repair if necessary to prevent prolonged standing water.
Photo
Photo 85-1 
Photo
Photo 85-2 
Photo
Photo 85-3 
Photo
Photo 85-4 
Photo
Photo 85-5 
Photo
Photo 85-6 
86) Repair/Replace, Evaluate -  Flashings at parapet walls were deteriorated and/or substandard. These may result in leaks. A qualified roofing contractor should evaluate and repair as necessary.
Photo
Photo 86-1 
Photo
Photo 86-2 
87) Repair/Replace, Evaluate -  Area(s) of the roof structure over the bathrooms was wet or had elevated levels of moisture at the time of the inspection. This indicated an active leak in the roof or structure exterior. A qualified contractor should evaluate and repair as necessary.
Photo
Photo 87-1 
Photo
Photo 87-2 
88) Repair/Replace, Evaluate -  Ceiling insulation above the bathroom was uneven in some areas. The ceiling insulation's R rating was also less than what's recommended for this area (R30). Recommend installing additional insulation as per standard building practices for better energy efficiency.

Older buildings often have R below 13 while recently built buildings have higher R factors of typically 36 to 49 as result of standards changing over time.
We consider R factor of 30 to be the minimum. Adding additional insulation would be considered an upgrade and you should calculate the return on the investment as it will likely take several years to get a return.
Photo
Photo 88-1 
Photo
Photo 88-2 
Photo
Photo 88-3 
89) Repair/Replace, Evaluate -  Truss/rafter has been bent/damaged. These should not be altered without a structural engineer approval of the changes. Recommend evaluation and repair.
Photo
Photo 89-1 
Photo
Photo 89-2 
Photo
Photo 89-3 
90) Repair/Replace, Evaluate -  Sag/soft areas were located. Recommend evaluation and repair/support as needed.
Photo
Photo 90-1 
91) Repair/Replace, Evaluate -  Gaps were found in many roof surface seams. These may result in leaks. Recommend evaluation and repair/sealing as necessary.
Areas of previous repairs are in poor condition and should be evaluated for likely replacement.
Photo
Photo 91-1 
Photo
Photo 91-2 
Photo
Photo 91-3 
Photo
Photo 91-4 
Photo
Photo 91-5 
92) Repair/Replace -  Rubber roof had damaged in several areas. Recommend repair/patching to help prevent water infiltration.
Photo
Photo 92-1 
Photo
Photo 92-2 
Photo
Photo 92-3 
Photo
Photo 92-4 
Photo
Photo 92-5 
Photo
Photo 92-6 
Photo
Photo 92-7 
Photo
Photo 92-8 
Photo
Photo 92-9 Ventilation cap held down with bungee cord.
Photo
Photo 92-10 
Photo
Photo 92-11 
93) Repair/Replace -  Ventilation cap was missing. Replace or repair the roof as needed.
Photo
Photo 93-1 
94) Evaluate, Comment -  Unable to estimate insulation level due to design. Recommend asking sellers for information.
95) Evaluate -  There were indications of a fire occurring. Recommend asking sellers for information and for any reports regarding this.
Photo
Photo 95-1 
Photo
Photo 95-2 
Photo
Photo 95-3 
Photo
Photo 95-4 
Photo
Photo 95-5 
96) Comment -  Be aware that lifting and or moving around insulation is beyond the scope of the inspection, therefore the areas directly buried and under insulation are not visible. Due to attic structures access to some areas are limited due to physical spaces and safety.
97) Comment -  No accessible attic spaces were found or inspected at this property for most of the building
98) Comment -  The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life nor any guarantee of roofs age, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice. We also recommend asking sellers for verification of roof covering age for all roof surfaces and/or checking building permits.

Insurance companies may or may not provide coverage due to a roofs age or other reasons of theirs. Recommend checking with your insurance provider regarding coverage. This is outside the scope for an inspector to know.
Commercial Life SafetyTable of contents
99) Safety, Repair/Replace -  Fire extinguishers were missing.

Recommend correction.
Photo
Photo 99-1 
100) Safety, Repair/Maintain, Evaluate -  Inspected for exit signs at all exits and inspected for independent power sources such as batteries.

The presence of directional signs that were self powered where exit location was not obvious. Recommend evaluation and improvements as needed.
Photo
Photo 100-1 
101) Comment -  Recommend asking building owner and or the person in charge of maintenance for the records of health and safety inspections from the local jurisdiction.
102) Comment -  A fire sprinkler system was present. These systems should be inspected annually.
Photo
Photo 102-1 
Photo
Photo 102-2 
103)   -  Slow leak observed at fire suppression system.
Zone 3
Photo
Photo 103-1 
Photo
Photo 103-2 
104)   -  Damaged exit sign
Photo
Photo 104-1 


Photo
Photo X-1 
Photo
Photo X-2 
Photo
Photo X-3