This report published on Saturday, January 4, 2025 9:59:05 AM EST
"No home is perfect. Keep things in perspective. Do not kill your deal over things that do not matter. It is inappropriate to demand that a seller address deferred maintenance, conditions already listed on the seller's disclosure or nit-picky items."
The above is an excerpt from Sell Your Home For More by Nick Gromicko.
Acceptance of this report and/or relying on the information within constitutes acceptance of the real estate inspection agreement limits for the client listed above even if the agreement is not signed. Reliance on a home inspection report that was originally performed for a different home buyer removes warranties. Home Inspections are not a pass/fail. The purpose is to identify the condition of the home as much as can be done at the time of the inspection. It is out of the scope of the home inspection to give estimates for repairs. We recommend that contractors be utilized prior to closing to provide repair estimates.
If you are not the person identified as the client above then you need to attain permission from the client above and you need to have your own home inspection completed.
It is not typical to request to remedy those items which are small maintenance items. Your real estate agent will be your best source to help determine which items (if any) are appropriate to request for correction or improvement
The following items are excluded from this inspection: Elevator
1) Comment - The Basic Commercial Inspection was conducted according to International Standards of Practice for Inspecting Commercial Properties. The inspection, the Report, and its uses are strictly limited to the scope as described herein and as expressed in the agreement. The inspection is in no way intended to be a warranty or guarantee, express or implied, regarding the future use or operability of the building or its components.
2) Comment - The scope of service for this Basic Commercial Inspection includes the following: Walk-through survey to visually observe the subject property so as to obtain information on material systems and components for the purposes of providing a brief description and identifying physical deficiencies to the extent that they are easily visible and readily accessible. The focus is upon larger expense items, typically well above the $500-$1000 range
3) Comment - Photos are only a representative sample of conditions observed. There may be more than one area of concern not shown by photo
4) Comment - This is a reminder that inspections are not code inspections, zoning checks nor a check for permits. Most buildings more than only a few years old are not up to current codes due to codes changing over time. It is normal and expected for homes and buildings not to be "up to code". Codes themselves are subject to locations and interpretation.
Inspections are also not a pest/rodent inspection. It is not uncommon for critters to move into buildings when weather gets colder and/or there are food sources available. Keep food sources away and monitor always.
It is recommended that you get estimates for repairs prior to closing to fully understand the costs involved. Cost estimates are not part of the inspection. Our inspectors do not provide repairs so any estimate provided is very rough if given and should not be relied on due to large variations from contractors and materials.
Life expectancy of materials, appliances and systems is outside the scope of the inspection. Any information regarding this should not be relied upon due to variations of opinions from contractors and materials.
5) Comment - Issues that are considered cosmetic are not the goal of this report. For example, holes, stains, scratches, unevenness, not perfectly level or square, missing trim, paint and finish flaws or odors.
Inspections and inspection reports are not a guaranty of future performance or future functionality. The inspection company is not responsible for failure to properly maintain the property or damage that occurs or uncovered after taking possession.
6) Comment - Older building—We expect buildings to be built according to the standard practices and building codes, if any, that were in use at the date of construction. Older buildings often have areas or systems that do not comply with current building codes. While this inspection makes every effort to point out safety concerns, it does not inspect for building code compliance. It is common for buildings of any age to have had repairs done, and some repairs may appear less than standard. This inspection looks for items that are not functioning as intended. It does not grade the quality of the repairs. In older buildings, the inspector reviewed the structure from the standpoint of how it has fared through the years with the materials that were used. You can expect problems to become apparent as time passes. The inspector will not be able to find all deficiencies in and around a property, especially concerning construction techniques of the past.
7) Comment - The basement had fixed coverings such as walls and or ceilings. If excess moisture is present for long enough lengths of time mold is a possibility. Fixed coverings limit the amount of observable areas. It is beyond the scope of an inspection to tear open areas to expose concealed spaces.
Be aware that mold is naturally occurring and that "mold free" areas are not naturally occurring. If you have a concern about mold consider having a mold air samples and swab samples taken to help determine if elevated levels of mold exist.
Coverings also prevent direct observation of foundation.
8) Comment - Many windows, doors, walls, floors and/or ceiling surfaces were obscured by large amounts of furniture and/or stored items. Many areas couldn't be evaluated.
9) Comment - Additional Inspector(s):
Jim Troth
10) - The purpose of the Basic Commercial Inspection is to determine the current condition of the improvements located on a parcel of commercial real estate, by performing a walk-through survey and conducting research. The goal is to identify and communicate physical deficiencies to the user. The term physical deficiencies means the presence of conspicuous defects or material deferred maintenance of a subject property's material systems, components, or equipment as observed during the field observer's walk-through survey.
11) Safety, Repair/Replace, Evaluate - The parking area had significant cracks and/or deterioration/trip hazards in areas. A qualified contractor should evaluate and repair or replace driveway sections as necessary.
Photo 11-1 Photo 11-2
12) Safety, Repair/Replace, Evaluate - Stairs/walkways have settled. Recommend evaluation and repair. Consider slab jacking if possible as a repair method to ensure proper slope away from the building and to help remove any trip hazards.
13) Safety, Repair/Maintain, Evaluate - Trip hazards was/were found in sidewalk and/or patio sections due to cracks, settlement and/or heaving. A qualified contractor should evaluate and repair or replace sidewalk and/or patio sections as necessary to eliminate trip hazards.
Photo 13-1
14) Safety, Repair/Maintain - Trip hazard(s) existed at stairs due to non-uniform riser heights. Standard building practices call for riser heights not to vary more than 3/8 inch on a flight of stairs. At a minimum, the client(s) should be aware of this hazard, especially when guests who are not familiar with the stairs are present. Ideally a qualified contractor should evaluate and repair or replace stairs so all riser heights are within 3/8 inch of each other.
15) Safety, Repair/Maintain - Stairs with more than two risers had no handrail installed. This is a safety hazard. Handrails should be installed and be graspable handrails that your hand can completely encircle at stairs where missing.
Photo 15-1
16) Major Defect, Repair/Replace, Evaluate - Major cracks or areas of deterioration were found in multiple section(s) of brick/parapet wall. These are likely caused by significant movement of the foundation and/or walls. The client(s) are strongly advised to hire qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:
Foundation repair contractors who may prescribe repairs, and will give cost estimates for prescribed repairs
Masonry contractors who repair and/or replace brick sections
Geotechnical engineers who attempt to determine if settlement is ongoing, and what the cause of the settlement is
Structural engineers who determine if repairs are necessary, and prescribe those repairs
Photo 16-1 Photo 16-2
Photo 16-3 Photo 16-4
Photo 16-5 Photo 16-6
17) Repair/Replace, Evaluate - Sidewalks and/or patios have significant cracks and/or deterioration in areas. Recommend evaluation and repair or replace sidewalk and/or patio sections as necessary.
Photo 17-1
18) Repair/Replace, Evaluate - It appears that the buried drain lines are clogged/collapsed due to the lack of use of them. Consider evaluation and repair to better direct water away from the foundation.
Photo 18-1
19) Repair/Replace, Evaluate - Soffit boards were damaged or deteriorated in at least one area(s). Recommend evaluation and repairs as necessary.
Note that in these areas rafter "tails" are not visible.
Photo 19-1
20) Repair/Replace - The perimeter grading sloped towards the structure in areas and was too flat in other areas. This is a common find. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure. The grade should drop at least 6 inches within the first 10 feet. Correct any negative slope of brick/concrete areas as well to direct water away from structure. https://homeinspectionsinohio.com/negative-grading/
Where the site does not allow for the necessary fall away from the structure, drains or swales could be used.
21) Repair/Replace - Perimeter pavement/bricked area sloped towards structure in two area(s). This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Recommend having repairs made as necessary so all perimeter areas slope down and away from the structure.
22) Repair/Maintain, Minor Defect - At least two downspouts had no extensions, or had extensions that were ineffective. This is a common find that can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.
Photo 22-1 Photo 22-2
23) Repair/Maintain, Evaluate - Siding/flashing was damaged and/or deteriorated in small areas. Recommend evaluation and correction as necessary to help prevent water intrusion. Inspector is unable to determine condition of underlying material.
Photo 23-1 Photo 23-2
Photo 23-3
24) Repair/Maintain, Evaluate - Brick mortar was deteriorated and should be repaired to prevent further deterioration. Recommend having a qualified mason evaluate all bricks and repair as necessary. This will likely require repointing the mortar.
25) Repair/Maintain, Evaluate - Minor cracks were found in one section(s) of brick/stone. This is a commonly found item. Recommend repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.
Photo 25-1
26) Repair/Maintain, Evaluate - Fascia boards are damaged or deteriorated in at least one area. Recommend evaluation of all fascia areas and repairs made as necessary to help prevent precipitation and animal entry .
Be aware that most often fascia is largely not visible due to flashing materials or gutters blocking observation.
Photo 26-1
27) Repair/Maintain, Evaluate - Stone/brick mortar was deteriorated and should be repaired to prevent further deterioration. Recommend having a qualified mason evaluate all stone/brick and repair as necessary. This will likely require repointing the mortar.
28) Repair/Maintain - Bollard(s) were missing in areas that would benefit from the protection of them. Consider installing where needed.
Photo 28-1
29) Repair/Maintain - Drain pipe for the downspout was damaged. Recommend repairing to help ensure water is directed away from the foundation.
Photo 29-1
30) Repair/Maintain - Spray foam was observed as a sealant around wall penetration(s). Spray foam will deteriorate from the UV rays from the sun. Recommend replacing with an appropriate sealant.
Recommend evaluation for proper flashing
Photo 30-1 Photo 30-2
Photo 30-3
31) Maintain - Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
32) Maintain - The exterior finish in some areas was failing. Recommend prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain areas as needed.
Photo 32-1 Photo 32-2
33) Monitor - Stains were found in at least three area(s) on soffit boards, but no elevated moisture levels were found and the wood appears to be in good condition. Based on the appearance of the roof, these stains may be from past leaks. Recommend monitoring these areas in the future. If moisture is observed, a qualified contractor should evaluate and repair as necessary.
Photo 33-1 Photo 33-2
Photo 33-3
34) Comment - The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Exterior buildings such as sheds, barns and garages are not included unless specifically requested. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight. Inspector is unable to determine condition of underlying materials (see through solid objects) such as materials behind siding and facia positioned behind gutters or flashing for examples.
35) - The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, take measurements of plumbness, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
36) Safety, Major Defect, Repair/Replace, Evaluate - This building had solid-strand branch circuit aluminum wiring. This type of aluminum wiring can be a potential fire hazard. Problems due to expansion and contraction can cause overheating at connections between the wire and devices such as switches and receptacles, or at splices. The Consumer Products Safety Commission recommends either discontinuing use of circuits with aluminum wiring, or pigtailing copper wiring onto the ends of the aluminum wire. A qualified electrician should evaluate and repair or replace this wiring.
Kitchen panel
Photo 36-1
37) Safety, Repair/Replace, Evaluate - One overcurrent protection device was "double tapped", where 2 or more wires are clamped in a terminal that is designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. An electrician should evaluate and repair as necessary.
Kitchen panel
Photo 37-1
38) Safety, Repair/Replace, Evaluate - Neutral wires were doubled or bundled with other conductors on the neutral bus bar in the sub panel. Neutral wires should each have their own terminal and not placed together. This is unsafe due to the need to turn off multiple circuit breakers to work on any of the circuits using these wires. A qualified electrician should evaluate and repair as necessary.
If a neutral wire is bundled with a ground, it is considered a lesser concern and very common for buildings prior to 2002 typically.
In storage stairwell.
Photo 38-1
39) Safety, Repair/Replace, Evaluate - At least two open ground, three-pronged electric receptacles were found. This is a safety hazard due to the risk of shock. Recommend consulting with a qualified electrical contractor to determine alternatives to grounding the branch circuits in specific areas, and for bringing the receptacles into compliance with current safety standards. Some possibilities:
(1) Establishing a grounding connection for the circuits (rewiring is at times not practical) (2) Installation of ground-fault circuit interrupter (GFCI) protection at the branch circuits and affixing warning labels to the receptacles. (3) Replacing the improperly installed grounding-type receptacles with a 2-prong type receptacle.
Three prong receptacles without an equipment ground that are protected by a GFCI should be labeled as such and any receptacle downstream of the GFCI as well. A qualified electrician should always provide additional information to you and complete the repairs that involve wiring.
Grounding type receptacles began being required in structures during the 1960s. Based on the age of this structure an acceptable repair may be to simply replace the ungrounded 3-pronged receptacles with 2-pronged receptacles. However, the following appliances require grounding type receptacles: Computer hardware Refrigerators Freezers Air conditioners Clothes washers Clothes dryers Dishwashers Kitchen food waste disposers Information technology equipment Sump pumps Electrical aquarium equipment Hand-held motor-operated tools Stationary and fixed motor-operated tools Light industrial motor-operated tools Hedge clippers Lawn mowers
This list is not exhaustive. Grounded circuits and receptacles should be installed in locations where such appliances will be used.
40) Safety, Repair/Replace, Evaluate - One section of wiring that was not terminated was found. This is a potential safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. For example, cutting the wire to length and terminating the wire with wire nuts in a securely anchored, covered, properly sized junction box.
Photo 40-1
41) Safety, Repair/Replace, Evaluate - Wire splices were exposed due to not being contained in a covered junction box or in a box that had no cover. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes and/or cover plates where needed to contain wiring splices.
Photo 41-1
42) Safety, Repair/Maintain, Evaluate - Electric panel was located in the bathroom/kitchen, this is not recommended due to the risk of shock. Recommend repositioning the panel or at least protecting it well against moisture.
Up until approximately 1993 this was allowed for new construction and because of this it can be found on older properties.
Photo 42-1
43) Safety, Repair/Maintain, Evaluate - Relatively few electric receptacles are installed in interior rooms. This can result in "octopus" wiring with extension cords, which is a fire hazard if done. Consider installing additional receptacles as necessary and as per standard building practices.
Photo 43-1
44) Safety, Repair/Maintain - This property had at least one fuel burning appliance, and no permanently installed carbon monoxide alarms were visible. This is a safety hazard. Recommend installing carbon monoxide alarms as necessary and as per the manufacturer's instructions.
An insufficient number of smoke alarms were installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom.
45) Safety, Minor Defect - Screw(s) were missing from the main panel service panel cover and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.
Photo 45-1
46) Safety, Minor Defect - Cover plates were missing for one or more electric box(s), such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. Cover plates should be installed where missing.
Photo 46-1
47) Repair/Maintain, Evaluate - Electric panels were mounted higher than typically done. Often the max height for the highest breaker is 6'7". Consider having a licensed electrician evaluate and reposition the panel if needed/desired.
Photo 47-1
48) Serviceable, Comment - No observable concerns with the electric panel wiring.
Photo 48-1
49) Comment - The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring condition or materials; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch or outlet. Inspectors do not remove outlet covers and are unable to determine the type of wiring inside walls or in concealed spaces. Inspection are not code inspections.
Note: National safety standards require electrical panels to be weatherproof, readily accessible, and have a minimum of thirty-six inches of clear space in front of them for service. Also, they should have a main disconnect, and each circuit within the panel should be clearly labeled. Industry standards only require us to test a representative number of accessible switches, receptacles, and light fixtures. However, we attempt to test every one that is unobstructed, but if a building is furnished we will obviously not be able to test each one.
Manufacturer(s): Carrier, International Comfort Products
Estimated Furnace age: Unknown
Primary heating system energy source: Natural gas
Primary heat system type: Forced air
Distribution system: Sheet metal ducts
Manufacturer(s): Williamson
Filter location: Behind return air grill
Thermostat Location: Common area and in worship section
50) Safety, Repair/Replace, Evaluate - What appears to be asbestos was visible on some ductwork. It was significantly deteriorated in some areas, and if it is asbestos, it may pose a health hazard and require abatement. Recommend having this material tested at a qualified lab. If the material is found to contain asbestos, recommend consulting with a qualified asbestos abatement contractor or industrial hygenist. For information on asbestos hazards, visit https://www.cpsc.gov/safety-education/safety-guides/home/asbestos-home
51) Safety, Repair/Replace, Evaluate - The furnace or boiler flame(s) are yellow or orange rather than blue. This may be caused by inadequate combustion air and/or dirty or clogged burners. A qualified heating and cooling contractor should evaluate and repair as necessary.
Photo 51-1 Photo 51-2
52) Safety, Repair/Maintain - Amounts of debris, dirt and/or dust are visible in sections of supply and/or return air ducts. This can be an issue, especially for those with allergies or respiratory problems. At a minimum, the visible debris should be cleaned or hire a duct cleaning company clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit: http://www.epa.gov/iaq/pubs/airduct.html
53) Repair/Maintain, Minor Defect - Recommend replacing duct tape with metal tape designed for use on HVAC duct work. Regular duct tape becomes brittle and loses adhesiveness when exposed to heat. This can lead to unconditioned air entering the system and increase energy costs.
54) Repair/Maintain, Evaluate - Furnace was turned on, no flame and/or response from the furnace. Polite light was lit.
Photo 54-1
55) Maintain, Evaluate - The last service date of the heating and cooling systems appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than two years ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary prior to closing. This servicing should be performed every few years in the future, or as per the contractor's recommendations.
56) Maintain, Comment - The estimated useful life for air conditioning compressors is 8 to 15 years. This unit was at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.
Periodic maintenance will help ensure continued operation.
57) Maintain, Comment - The estimated useful life for forced air furnaces is 15 to 20 years. This furnace was at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.
Periodic maintenance will help ensure continued operation.
58) Maintain - The filter(s) for the heating/cooling system should be checked monthly and replaced or washed as necessary.
Also be aware that heating and cooling systems should have regular maintenance on them yearly to help ensure long life spans.
59) Monitor - Rust/stains observed in/on the furnace cabinet. Active leaking did not occur during time of inspection. Recommend monitoring for leaks from condensation.
If leaks do develop then get it evaluated and repaired to help prevent rusting/deterioration of the furnace.
Photo 59-1 Photo 59-2
Photo 59-3 Photo 59-4
60) Serviceable, Comment - The flames on the furnace looked good and the blower motor operated.
Photo 60-1 Photo 60-2
Photo 60-3 Photo 60-4
Photo 60-5
61) Comment - We check heating and cooling for basic function. Our inspection is not technically exhaustive. Our inspection of ducts is naturally limited to observable areas. Therefore large areas of ducts cannot be seen. Since dirt, dust, mold, even toys are commonly found in ducts we recommend that you have the ducts cleaned.
62) Comment - Be aware that window air conditioners and portable heating and cooling systems are not included in the scope of inspections.
65) Safety, Repair/Maintain - Temperature-pressure relief valve drain line for the water heater was too short. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. Recommend extending the drain line to 6 inches from the floor, or route it so as to drain outside.
Photo 65-1
66) Repair/Replace, Evaluate - Pin holes and/or corrosion were visible on one area(s) of copper water supply pipes. Leaks may result because of this. Recommend evaluate and replace water supply components as necessary.
Was not actively leaking at time of inspection.
Photo 66-1
67) Repair/Replace, Evaluate - One sink drain in kitchen had substandard repairs, such as tape, sealant and/or non-standard components. A qualified plumber should evaluate and repair as necessary.
Photo 67-1
68) Repair/Replace - A water heater is installed over or next to finished living spaces and has no catch pan and drain installed. Recommend having a qualified contractor install a catch pan and drain to prevent water damage to finished interior spaces below if/when the water heater develops a leak or is drained.
Photo 68-1
69) Repair/Maintain, Evaluate - Corrosion was visible at meter and/or on water service supply pipes. Leaks may result because of this. A qualified plumber should evaluate and replace water supply components as necessary.
Leak observed at/near the water meter/shut off valve. Recommend evaluation and repair.
Photo 69-1
70) Repair/Maintain - The plumbing vent still had a cap sealing it. Recommend removing it to help ensure venting of sewer gases.
caps are installed when plumbing is tested for leaks and sometimes it is forgotten to remove them.
Due to the age of this building ask sellers if this is cap due to past leaks.
Photo 70-1
71) Repair/Maintain - No sediment trap was installed on the water heater gas supply line. Sediment traps are intended to trap oil, scale, water condensation and/or debris from the gas supply lines before they reach and damage the water heater components. A qualified contractor should install one as per standard building practices.
Photo 71-1
72) Minor Defect, Comment - An expansion tank was not installed. These are recommended to help relieve pressure in water line from getting too high due to the heating of water. Too high of water pressure can result in plumbing issues such as a leaking TPR valve. Recommend checking with local plumber to determine if needed or required by the municipality.
73) Monitor, Comment - The estimated useful life for most water heaters is 8 to 12 years. This water heater was at this age range or older and may need replacing at any time. Recommend budgeting for a replacement in the near future. Monitor
74) Monitor - Corrosion was found on fittings and/or water supply lines for the water heater. No active leaking. Monitor
Photo 74-1
75) Monitor - Stains observed on pipes and/or fittings, apparently from past leaking. Active leaking not observed. Recommend monitoring. Also consider further evaluation to help ensure against leaks. Location(s) -women's and men's restroom
Photo 75-1 Photo 75-2
76) Comment - The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing materials / components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only.
Note that the inspector is not required to operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
77) Comment - "In accordance with industry standards, we do not normally test washing machines and their water connections and drainpipes if present. However, there are a few things of which you should be aware. The water supply to washing machines is usually left on, and their hoses can leak or burst under pressure and continue to flow. Therefore, we recommend replacing the rubber hose type with newer, braided, stainless steel ones that are much more dependable and that they be operated only during times you will be present. You should also be aware that the newer washing machines discharge a greater volume of water than many of the older drainpipes can handle, which causes the water to back up and overflow, and the only remedy would be to replace the standpipe and trap with one that is larger. Although not required, whenever structural damage may result from an overflow, we recommend a pan with a plumbed drain. An alternative is a flood or leak detection device that will terminate the water supply in a water pipe failure."
78) Comment - It is beyond the scope of the inspection to confirm if the structure uses a septic or a public sewer system. This includes determination or inspection of aerators designed for septic systems. Recommend confirming with seller if there is any questions regarding this. It is always a great idea to have the county health department inspect any septic system.
79) Comment - Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.
80) Comment - Your water meter and main water shut off location.
Photo 80-1
81) Comment - Image of water heater and data plate
Photo 81-1 Photo 81-2
82) Comment - The water heater was turned off at the time of the inspection. For example, circuit breaker turned off, gas supply turned off or pilot light turned off. The inspector was unable to fully evaluate the water heater.
Rainwater entering flues and mixing with combustion deposits, creating caustic chemicals which can corrode flues
Rainwater entering flues and causing damage to terracotta flue tiles from freeze-thaw cycles
Recommend installing screened cover(s) where missing. Screens should have holes 1/4 inch or larger.
Photo 83-1
84) Repair/Replace, Evaluate - The masonry chimney's mortar was deteriorated/had gaps and should be repaired to prevent further, significant deterioration. Recommend having a qualified chimney service contractor or mason evaluate chimney and repair as necessary. This will likely require repointing the mortar.
85) Comment - It is impossible for an inspection to determine with any degree of certainty whether the flue is free of defects. Also unable to determine the type of mortar used. In the 1990's it became standard for non-water soluble mortar be used.
In accordance with recommendations made by the National Fire Prevention Association (NFPA) it is recommended to have all chimneys inspected before buying a building, you should have a Level II inspection of the chimney flue prior to close of escrow. The typical fireplace inspection by an inspector is not a Level II inspection.
86) Comment - All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
87) Comment - Fireplace was blocked by personal items, stored items, and/or furniture. Fireplace was not evaluated.
Roof covering: Asphalt or fiberglass composition shingles, EPDM (ethylene-propylene-diene monomer)
Gutter & downspout material: Metal
Roof ventilation: None visible
88) Repair/Replace, Evaluate - One section(s) of roof flashing were deteriorated and/or rusted. Leaks may occur as a result. A qualified roofing contractor should evaluate and replace flashing where necessary.
Photo 88-1
89) Repair/Replace, Evaluate - Shingles were damaged, deteriorated and/or missing in area(s). Recommend evaluation by a roofer and replacement of any shingles in need to help prevent leaks.
Photo 89-1 Photo 89-2
Photo 89-3 Photo 89-4
Photo 89-5
90) Repair/Replace, Evaluate - Gaps were found in 4 roof surface seams. These may result in leaks. Recommend evaluation and repair/sealing as necessary.
Photo 90-1 Photo 90-2
Photo 90-3 Photo 90-4
Photo 90-5 Photo 90-6
91) Repair/Replace, Evaluate - Ceiling insulation was uneven in some areas. The ceiling insulation's R rating was also less than what's recommended for this area (R30). Recommend installing additional insulation as per standard building practices for better energy efficiency.
Older buildings often have R below 13 while recently built buildings have higher R factors of typically 36 to 49 as result of standards changing over time. We consider R factor of 30 to be the minimum. Adding additional insulation would be considered an upgrade and you should calculate the return on the investment as it will likely take several years to get a return.
Photo 91-1 Photo 91-2
Photo 91-3
92) Repair/Replace, Evaluate - Shingles had missing granules. Scraped /missing granules will shorten the life of those shingles. Recommend repair/replacing.
Photo 92-1 Photo 92-2
93) Repair/Replace, Evaluate - Sag/soft area was located. Recommend evaluation and repair/support as needed.
Photo 93-1 Photo 93-2
Photo 93-3
94) Repair/Replace, Evaluate - The membrane roof was bridging in areas. Bridging is where the rubber begins lifting (due to shrinking) and creating space between the membrane and vertical areas such as walls or platforms. This is an indication of an older membrane or inadequate installation. Recommend evaluation and repairs to relax the tension on the membrane to help prevent gaps from being created.
Photo 94-1 Photo 94-2
Photo 94-3 Photo 94-4
95) Repair/Replace, Evaluate - Ventilation was substandard in the attic. Inadequate attic ventilation may result in high attic and roof surface temperatures, reduce the life of the roof covering materials and increase cooling costs. High levels of moisture are also likely, and can be a conducive condition for wood destroying insects and organisms. Standard building practices require one square foot of vent area for 150 to 200 square feet of attic space. Vents should be evenly distributed between soffits, ridges and at corners to promote air circulation. Recommend correction/improvement.
96) Repair/Replace - The ceiling insulation's R rating was less than what's recommended for this area (at least R30). Recommend having a qualified contractor install additional insulation as per standard building practices for better energy efficiency.
Older buildings often have R below 13 while recently built buildings have higher R factors of typically 36 to 49 as result of standards changing over time. We consider R factor of 30 to be the minimum. Adding additional insulation would be considered an upgrade and you should calculate the return on the investment as it will likely take several years to get a return.
Photo 96-1 Photo 96-2
97) Repair/Replace - The roof access door was secured.Recommend repair.
Photo 97-1 Photo 97-2
98) Repair/Maintain, Minor Defect - Roofing nails in areas have loosened or backed out. Leaks may occur as a result. Recommend repair such as reseating nails and applying sealant.
Photo 98-1
99) Repair/Maintain, Evaluate - Heavy sealant usage indicates possible past leaks or substandard flashing. Consider evaluation and improvement. At minimum maintain sealants periodically. Inspector is unable to determine condition of underlying material.
Photo 99-1 Photo 99-2
100) Repair/Maintain - The caps for the parapet walls were rusted and would benefit from sealant and paint.
Photo 100-1 Photo 100-2
101) Maintain, Comment - Rubber membrane roofs require periodic maintenance typically every 4-5 years. Consider hiring a roofer to periodically inspect and do maintenance as needed.
102) Maintain - Debris such as leaves, needles, seeds, etc. had accumulated on the roof/gutters. This is a conducive condition for wood destroying insects and organisms since water may not flow easily off the roof, and may enter gaps in the roof surface. Leaks may occur as a result. Debris should be cleaned from the roof now and as necessary in the future.
Photo 102-1 Photo 102-2
Photo 102-3
103) Evaluate, Monitor - Stains were visible on the roof structure in area(s). These areas were dry at the time of the inspection (we compare moisture levels of the stains to other areas for comparison). The stains may be caused by a past leak. Recommend asking the property owner(s) about past leaks and repairs. The client(s) should monitor these areas in the future, especially after heavy rains, to determine if active leaks exist. If leaks are found, a qualified roofing contractor should evaluate and repair as necessary.
Dry stains are a common finding, especially in building older than 20 years
Photo 103-1 Photo 103-2
104) Comment - Be aware that lifting and or moving around insulation is beyond the scope of the inspection, therefore the areas directly buried and under insulation are not visible. Due to attic structures access to some areas are limited due to physical spaces and safety.
105) Comment - Some attic areas were inaccessible due to stored items, lack of permanently installed walkways, the possibility of damage to loose fill insulation, and/or low height. These areas are excluded from this inspection.
106) Comment - The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life nor any guarantee of roofs age, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice. We also recommend asking sellers for verification of roof covering age for all roof surfaces and/or checking building permits.
Insurance companies may or may not provide coverage due to a roofs age or other reasons of theirs. Recommend checking with your insurance provider regarding coverage. This is outside the scope for an inspector to know.
107) Comment - The plumbing vent type rubber boot(s) were in good condition.
108) Comment - Generally the roof covering was in useful condition. Be certain to have the concerns identified evaluated prior to closing
Photo 108-1 Photo 108-2
Photo 108-3 Photo 108-4
109) Comment - Past repairs observed. Recommend asking sellers for information. Common for when roofs age.
Photo 109-1 Photo 109-2
110) Comment - Images of the roof, above the (bell) tower.
111) Safety, Repair/Maintain, Evaluate - Inspected for exit signs at all exits and inspected for independent power sources such as batteries.
The presence of directional signs that were self powered where exit location was not obvious. Recommend evaluation and improvements as needed.
Emergency lighting not observed
Photo 111-1 Photo 111-2
Photo 111-3 Photo 111-4
Photo 111-5
112) Comment - Recommend asking building owner and or the person in charge of maintenance for the records of health and safety inspections from the local jurisdiction.
114) Safety, Repair/Maintain - Interior surface of the exhaust needs cleaning. Dust and grease buildup is a fire/safety hazzard. Recommend correction/cleaning.
115) Safety, Repair/Maintain, Comment - The headroom above the stair trend was lower than recommended in modern buildings. The headroom in all parts of a stairway typically are not less than 6 feet 8 inches. Spiral stairways should have headroom of at least 6 feet 6 inches.
Changing the structure to meet this standard may be difficult. Consider having it evaluated and improved if possible. At minimum be aware of the hazard.
Photo 115-1
116) Safety, Repair/Maintain - Treads and/or stringers were leaning and/or sagging in one or more areas. Recommend evaluation and repair all stair wells for safety reasons.
Photo 116-1
117) Safety, Repair/Maintain - Stairs with more than two risers had no handrail installed. This is a safety hazard. Handrails should be installed and be graspable handrails that your hand can completely encircle at stairs where missing.
Photo 117-1
118) Repair/Replace, Evaluate, Monitor - Evidence of prior water intrusion was found in at least one section of the basement. For example, water stains and/or efflorescence on the foundation or floor, water stains at bases of support posts, etc. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the basement. The inspector is unable to determine how much water may enter in the future. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:
Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
Improving perimeter grading
Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.
Photo 118-1 Photo 118-2
119) Repair/Replace, Evaluate, Comment - Organic growth /mold like substance observed. Unable to determine type of growth without lab testing. Recommend evaluation/ testing.
Photo 119-1 Photo 119-2
120) Repair/Replace, Evaluate - Areas of elevated moisture levels or wet areas were found in section(s) of the basement. Accumulated water is a conducive condition for wood destroying insects and organisms and though common, should not be present in the basement. Finished walls, fixtures, etc restrict observations. Recommend evaluation and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:
Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
Improving perimeter grading
Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.
Photo 120-1 Photo 120-2
121) Repair/Replace - Water supply pipes were uninsulated. Recommend insulating pipes as necessary for better energy efficiency and to help protect water pipes from freezing.
Area behind women's bathroom sinks
Photo 121-1
122) Repair/Maintain, Evaluate - Wood in foundation of the basement was rotten/damaged. Recommend repair to help reduce moisture intrusion.
Photo 122-1
123) Monitor - Moisture stains observed on stone foundation wall. This is common for this type of foundation. Excessive moisture not present.
Monitor and maintain proper grading, gutters and downspouts.
Photo 123-1
124) Comment - Many wall, floor, foundation walls, and/or ceiling surfaces were obscured by large amounts of furniture and/or stored items. Many areas couldn't be evaluated. Recommend asking sellers to clear areas for evaluation.
125) Safety, Repair/Replace, Evaluate - Guardrails were too low. This is a safety hazard due to the risk of falling. Standard building practices require that guardrails above drop-offs be a minimum of 36 inches high. Recommend evaluation and correction where necessary, and especially above drop-offs higher than 30 inches.
Photo 125-1
126) Safety, Repair/Replace, Evaluate - This structure was built prior to 1979 and may contain lead paint. Laws were enacted in 1978 in the US preventing the use of lead paint in residential structures. Lead is a known safety hazard, especially to children but also to adults. Numerous areas of the paint found in and around this structure are in poor condition (peeling, flaking, etc.). Recommend consulting with a qualified industrial hygenist to determine the safest and most cost-effective action to take regarding the paint. Testing and/or abatement may be necessary.
Photo 126-1
127) Safety, Repair/Replace, Comment - Asphalt-based asbestos floor tiles and plastic or vinyl-based asbestos flooring were popular in the U.S. in the 1940's - 1970's and were produced by some manufacturers (Armstrong) as late as 1980. Because of the age of the building tiles observed may be of this type. Tiles were significantly deteriorated in some areas, and if it is asbestos, it may pose a health hazard and require abatement. Recommend having this material tested at a qualified lab. If the material is found to contain asbestos, recommend consulting with a qualified asbestos abatement contractor or industrial hygienist. For information on asbestos, visit https://www.cpsc.gov/safety-education/safety-guides/home/asbestos-home
Basement closet across from kitchen
Photo 127-1
128) Safety, Repair/Maintain, Evaluate - Guardrails/handrails were missing from sections of elevated surfaces with "high" drop-offs. This is a safety hazard due to the risk of falling. Guardrails should be installed at drop-offs higher than 30 inches, but in some cases it is advised to install them at shorter drop-offs. Recommend installing as necessary.
Photo 128-1
129) Safety, Repair/Maintain - Stairs with more than two risers had no handrail installed. This is a safety hazard. Handrails should be installed and be graspable handrails that your hand can completely encircle at stairs where missing.
Photo 129-1 Photo 129-2
Photo 129-3
130) Safety, Comment - Asphalt-based asbestos floor tiles and plastic or vinyl-based asbestos flooring were popular in the U.S. in the 1940's - 1970's and were produced by some manufacturers (Armstrong) as late as 1980. Because of the age of the building, tiles observed may be of this type. However, they appeared to be intact and not significantly deteriorated. The client may wish to have this material tested at a qualified lab. For information on asbestos, visit https://www.cpsc.gov/safety-education/safety-guides/home/asbestos-home
Photo 130-1
131) Repair/Replace, Evaluate - Stains and elevated levels of moisture were found in at least two ceiling/wall area(s). The stain(s) appear to be due to roof leaks. A qualified contractor should evaluate and repair as necessary.
Areas were: room above stairwell, storage areas
Photo 131-1 Photo 131-2
Photo 131-3 Photo 131-4
Photo 131-5
132) Repair/Replace, Evaluate - Seals between double-pane glass in one window(s) had failed based on condensation or stains between at least one of the panes of glass. A qualified contractor should evaluate entire window and replace glass where necessary.
The client(s) should be aware that evidence of aging seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Windows or glass doors other than those that the inspector identified may also have failed seals and need glass replaced too.
133) Repair/Replace, Evaluate - Rot / deterioration observed on at least one or more windows. Recommend evaluation and repair/replacement as needed.
Photo 133-1
134) Repair/Maintain - Damage/cracks were found in walls and/or in other various areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.
Basement closet, women's bathroom, Kitchen windows (not pictured)
Photo 134-1 Photo 134-2
Photo 134-3
135) Repair/Maintain - Vinyl flooring is damaged and/or deteriorated in one or more areas. Recommend replace or repair the damaged flooring to help protect the flooring and for aesthetic reasons.
Photo 135-1
136) Repair/Maintain - Gaps existed in flooring where sections met. Consider improving for aesthetic reasons and to help protect the sub flooring.
138) Monitor - Stains were found in at least two or more ceiling area(s). However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks. Recommend asking the property owner(s) about this, and monitoring the stained area(s) in the future, especially after heavy or prolonged rain.
Photo 138-1 Photo 138-2
139) Comment - Minor cracks were found in ceiling in area(s). They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.
Cracks can form due to seasons and changes in temperature and humidity.
Photo 139-1 Photo 139-2
Photo 139-3 Photo 139-4
140) Comment - Minor cracks were found in walls in one area(s). They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.
Photo 140-1
IMPORTANT INFORMATION CONTINUES You should not regard this inspection and report as a guarantee or warranty of the property and its components. It is not. It is simply a report on the general condition of the property at a given point in time. Furthermore, as a homeowner, you should expect problems to occur; roofs will leak, drain pipes will become blocked, and components and systems will fail without warning. For these reasons, you should take into consideration the age of the house and its components and keep a comprehensive insurance policy current. If you have been provided with a home protection policy, read it carefully. Such policies usually only cover insignificant costs, such as that of rooter service, and the representatives of some insurance companies are very likely to charge you for a service call and then deny coverage on the grounds that a given condition was preexisting or not covered because of an alleged code violation or a manufacturers defect. Therefore, you should read such policies very carefully, and depend upon our company for any assistance and consultation that you may need. It is highly recommended that the suggested repairs, corrections, evaluations, etc be done prior to the end of your due diligence time period if possible or before closing. Evaluations and repairs can reveal issues not visible during a home inspection or beyond the scope of a home inspection.
It is beyond the scope of the inspection to confirm if the structure uses a septic or a public sewer system. Recommend confirming with seller.
Heating and Cooling systems Furnaces typically will last 15-20 years. With proper maintenance they can last longer. Air conditioners also have a typical life expectancy of 8-15 years. Heat pumps typically last 15-20 years. The estimated useful life for boiler system is 25-40 years. It is normal to have issues with systems as they age. Be sure to have regular maintenance done.
As of January 2006, air conditioning manufacturers are no longer allowed to manufacture products, or certain individual components (condensers, evaporator, compressors) for systems with less than a 13 SEER rating. As existing inventories of older efficiency style components are depleted, replacement of the A/C unit may be required in place of repairs.
Note: R22 has been the standard refrigerant used in air conditioners for many years. The problem with this refrigerant is that it is both less efficient and less environmentally friendly than R410a refrigerant. The government-mandated shift away from R22 refrigerant is an attempt to make homes more efficient and reduce the emissions of greenhouse gasses into the environment. As of 2010 R22 is no longer allowed to be used in newly-manufactured air conditioners. R-22 can not be added to current systems after Jan 2019. MO99 is a refrigerant that can be used to replace R-22. Identifying the type of refrigerant used in a system is not within the scope of the home inspection.
Crawl Spaces Crawl spaces should all be viewed periodically. Although not desirable it is common for moisture levels to be higher here than in other areas of the home. Recommend quarterly viewing so as to catch water intrusion and moisture related issues quickly.
Roof materials It is beyond the scope of the inspection to give the life expectation of roofing materials. There are many factors that effect the aging process such as color, angle, orientation, ventilation and type of material. Any mention of age is a rough estimate based upon experience and is in no way an guarantee of the actual age. We recommend asking seller if you want specific age information. It is also beyond the scope to determine if a roof has more than one layer of materials. lower layer can be concealed by drip edges and flashings.
Roofs are designed to shed water like an umbrella and are not “waterproof”. In events of wind driven rains, and periods of intense rain, water can sometimes blow into areas such as ridge vents, roof vents and valleys and present leaking conditions. This occurrence is rare, but can possibly happen in severe storm events. Unless it is raining at the time of inspection, some roof leaks may not be identified during the inspection process. As prescribed in the inspection authorization and agreement, this is a visual inspection only. Roofing life expectancies can vary depending on several factors. Any estimates of remaining life are approximations only.
Ceiling fans cannot be checked for proper mounting inside attic spaces where concealed by insulation.
The accuracy of breaker labeling is beyond the scope of the inspection.
Rodents Please be aware that inspecting for rodents is outside the scope of home inspections. If we see obvious indications of activity we will note it. If we note it that should not be taken that we conducted a pest inspection. It is also very common for mice and similar sized critters to enter all homes at sometime. Please do not be alarmed if you have such house guests at sometime.
What are Molds? Molds are simple, microscopic organisms, present virtually everywhere, indoors and outdoors. Molds, along with mushrooms and yeasts, are fungi and are needed to break down dead material and recycle nutrients in the environment. For molds to grow and reproduce, they need only a food source and any organic material, such as leaves, wood, paper, or dirt and moisture. Because molds grow by digesting the organic material, they gradually destroy whatever they grow on. Sometimes, new molds grow on old mold colonies. Mold growth on surfaces can often be seen in the form of discoloration, frequently green, gray, brown, or black but also white and other colors. Molds release countless tiny, lightweight spores, which travel through the air. Everyone is exposed to some mold on a daily basis without evident harm. It is common to find mold spores in the air inside homes, and most of the airborne spores found indoors come from outdoor sources. Mold spores primarily cause health problems when they are present in large numbers and people inhale many of them. This occurs primarily when there is active mold growth within home, office or school where people live or work. People can also be exposed to mold by touching contaminated materials and by eating contaminated foods. Molds produce health effects through inflammation, allergy, or infection. Allergic reactions (often referred to as hay fever) are most common following mold exposure. Typical symptoms that mold-exposed persons report (alone or in combination) include: Respiratory problems, such as wheezing, difficulty breathing, and shortness of breath Nasal and sinus congestion, Eye irritation (burning, watery, or reddened eyes) Dry, hacking cough, Nose or throat irritation, Skin rashes or irritation Headaches, memory problems, mood swings, nosebleeds, body aches and pains, and fevers are occasionally reported in mold cases, but their cause is not understood. Molds will grow and multiply whenever conditions are right and sufficient moisture is available and organic material is present. Be on the lookout in your home for common sources of indoor moisture that may lead to mold problems: If you suspect that you may have mold, contact a specialist.
When Things Go Wrong There may come a time that you discover something wrong with the house, and you may be upset or disappointed with your home inspection.
Intermittent Or Concealed Problems. Some problems can only be discovered by living in a house. They cannot be discovered during the few hours of a home inspection. For example, some shower stalls leak when people are in the shower, but do not leak when you simply turn on the tap. Some roofs and basements only leak when specific conditions exist. Some problems will only be discovered when carpets were lifted, furniture is moved or finishes are removed.
No Clues. These problems may have existed at the time of the inspection but there were no clues as to their existence. Our inspections are based on the past performance of the house. If there are no clues of a past problem, it is unfair to assume we should foresee a future problem.
We Always Miss Some Minor Things Some might say we are inconsistent because our reports identify some minor problems but not others. The minor problems that are identified were discovered while looking for more significant problems. We note them simply as a courtesy. The intent of the inspection is not to find the $200 problems; it is to find the $2,000 problems. These are the things that affect people's decisions to purchase.
Contractors' Advice The main source of dissatisfaction with home inspectors comes from comments made by contractors. Contractors' opinions often differ from ours. Don't be surprised when three roofers all say the roof needs replacement when we said that, with some minor repairs, the roof will last a few more years.
Last Man In Theory While our advice represents the most prudent thing to do, many contractors are reluctant to undertake these repairs. This is because of the "Last Man In Theory". The contractor fears that if he is the last person to work on the roof, he will get blamed if the roof leaks, regardless of whether the roof leak is his fault or not. Consequently, he won't want to do a minor repair with high liability when he could re-roof the entire house for more money and reduce the likelihood of a callback. This is understandable.
Most Recent Advice Is Best There is more to the "Last Man In Theory". It suggests that it is human nature for homeowners to believe the last bit of "expert" advice they receive, even if it is contrary to previous advice. As home inspectors, we unfortunately find ourselves in the position of "First Man In" and consequently it is our advice that is often disbelieved.
Why Didn't We See It Contractors may say "I can't believe you had this house inspected, and they didn't find this problem". There are several reasons for these apparent oversights:
1. Conditions During Inspection It is difficult for homeowners to remember the circumstances in the house, at the time of the inspection. Homeowners seldom remember that it was snowing, there was storage everywhere in the basement or that the furnace could not be turned on because the air conditioning was operating, et cetera. It's impossible for contractors to know what the circumstances were when the inspection was performed. Contractors also rarely understand the standards home inspectors are to follow.
2. The Wisdom Of Hindsight When the problem manifests itself, it is very easy to have 20/20 hindsight. Anybody can say that the basement is wet when there is 2 inches of water on the floor. Predicting the problem is a different story.
3. A Long Look If we spent 1/2 an hour under the kitchen sink or 45 minutes disassembling the furnace, we'd find more problems too. Unfortunately, the inspection would take several days and would cost considerably more.
4. We're Generalists We are generalists; we are not specialists. The heating contractor may indeed have more heating expertise than we do.
5. An Invasive Look Problems often become apparent when carpets or plaster are removed, when fixtures or cabinets are pulled out, and so on. A home inspection is a visual examination. We don't perform any invasive or destructive tests.
6. Taking advantage of a situation Contractors may be desperate or eager for extra work. Is is too tempting for some to attempt to get work approval asap by telling the home owner that someone else will be paying for it.
Not Insurance In conclusion, a home inspection is designed to better your odds. It is not designed to eliminate all risk. For that reason, a home inspection should not be considered an insurance policy. The premium that an insurance company would have to charge for a policy with no deductible, no limit and an indefinite policy period would be considerably more than the fee we charge. It would also not include the value added by the inspection.