This report published on Monday, March 13, 2023 12:04:12 PM PDT
Dear customer:
Thank you for choosing AREA Inspections to perform the following inspection on the property you wish to purchase. This report is the exclusive property of AREA Inspection and the individual/s paying for the inspection fee and report. Use of this report by any unauthorized persons is prohibited.
All findings should be made to AREA Inspections.
This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.
We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, see paint peeling off Walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.
While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.
This inspection report was prepared in a format specifically for the individual/s paying for the inspections fee and report and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the individual/s paying for inspections fee and report and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.
If you have any questions regarding this report, please feel free to call us.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety Concern
Poses a risk of injury
Repair/Replace
Recommend repairing or replacing
Repair/Maintain
Recommend repair and/or maintenance
Minor Defect
Correction likely involves only a minor expense
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Serviceable
Item or component is in serviceable condition
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Cool
Ground condition: Dry
Recent weather: Dry (no rain), Sunny
Overnight temperature: Cold
Inspection fee: $685.00
Payment method: Invoiced
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 2013
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: No
1) The General Property inspection is not an inspection for mold and the inspector specifically disclaims and assumes no responsibility for identifying the presence of mold fungi. Mold fungi are present in all property's and may be present at levels at which sensitive people may react physically to their presence, even at levels at which fungal colonies are not visible, or when fungal colonies are hidden in inaccessible portions of the home. If you are concerned with mold, the Inspector recommends that you hire a specialist to perform further testing
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of fences and gates: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wrought iron, Masonry
Condition of retaining walls: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of sidewalks and/or patios: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete, Paving stones
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open
2) Guardrails above retaining walls higher than 30 inches were missing. This is a safety hazard due to the risk of falling. At a minimum, the client should be aware of this hazard, especially when children are present. Recommend that a qualified contractor install or repair guardrails per standard building practices (e.g. minimum 3 feet high, no gaps wider than 4 inches, not climbable). Dense shrubbery or vegetation may be acceptable as a barrier, but only when mature enough to be effective.
Photo 2-1 Photo 2-2
3) Significant deterioration, leaning and/or bowing were found in one or more timber retaining walls. Recommend that a qualified contractor evaluate and repair or replace sections as necessary. Note that some retaining walls, based on their height or size, may require evaluation by a structural engineer.
Photo 3-1 Photo 3-2
4) Sidewalk(s) and/or patios were undermined in one or more areas, where soil has eroded out from beneath. Recommend that a qualified person repair as necessary to prevent further erosion and undermining.
Photo 4-1 Photo 4-2
Photo 4-3 Photo 4-4
Photo 4-5
5) Significant erosion was found in one or more areas. Recommend having a qualified person evaluate and make repairs as necessary to repair erosion, and to prevent erosion in the future.
Photo 5-1 Photo 5-2
Photo 5-3 Photo 5-4
Photo 5-5 Photo 5-6
Photo 5-7
6) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. It is a conducive condition for wood-destroying organisms. Recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo 6-1
7) One or more large tree stumps were close to the building exterior. Wood-destroying insects such as carpenter ants nest in such stumps and are more likely to infest the building as a result. Recommend that large tree stumps within a few feet of the building be removed by a qualified tree service contractor.
Photo 7-1
8) At the time of inspection it appears ongoing construction to the bearing wall was noted at the neighboring property. Recommend that the client review any documentation or recorded agreements regarding such walls, of the property owners involved, and easements permitting shared use or boundaries thereof.
Photo 8-1 Property line marker noted at curbside. Photo 8-2
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood, Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade, Concrete garage slab, Post tension slab and FTG do not cut or core
Foundation/stem wall material: Poured in place concrete, Concrete slab on grade
Footing material (under foundation stem wall): Poured in place concrete, Concrete slab
9) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo 9-1 Photo 9-2
10) Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture may enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco may become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo 10-1 Photo 10-2
Photo 10-3 Photo 10-4
11) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Viewed from ground with binoculars
Condition of roof surface material: Appeared serviceable
Roof surface material: Concrete tile
Roof type: Gable
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Limited evaluation due to little or no rainfall during and prior to the inspection
Gutter and downspout material: Not applicable, none installed
Gutter and downspout installation: None
12) No roof drainage system was installed or only a partial system was installed. Standard building practices call for gutters, downspouts and extensions to be installed at all lower roof edges to convey water well away from the building foundation. Without a drainage system, the crawlspace or basement below the house, if they exist, may accumulate water. Foundation footings are also more likely to settle or become undermined. Recommend consulting with a qualified contractor about installing a roof drainage system per standard building practices.
13) At the time of inspection it appears the roof was in serviceable condition except as noted
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Location of attic access point #A: Hallway, second floor
Attic access points that were opened and viewed, traversed or partially traversed: A
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Vermiculite insulation present: None visible
Vapor retarder: None visible
Condition of roof ventilation: None
Roof ventilation type: Closed cell
Attic exhaust fan condition: None visible
14) One or more support beam, engineered trusses or support lumber visible in the attic or garage attic appeared to have been repaired or sistered. Recommend asking the owners about such repairs, and or consulting with a qualified contractor.
Photo 14-1
15) One or more attic access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency. For more information, visit: http://www.reporthost.com/?ATTACC
Photo 15-1 Photo 15-2 Gaps were visible at the hatch seams.
16) No attic exhaust fan or vents was installed . However the inspector attempts to locate such devices when present. Therefore such systems are are not evaluated and are excluded from this report. Recommend asking the owners if one is installed and or consider having a qualified specialist or contractor fully evaluate and instal such systems if necessary and as per standard building practices. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist.
Unvented conditioned attics and roofs with spray foam insulation applied to the underside of the roof deck have been used since the mid-1990s. Open-cell spray polyurethane foam (ocSPF) or closed-cell spray polyurethane foam (ccSPF) insulation is sprayed along the underside of the roof sheathing to provide an unvented insulated and conditioned attic space or roof assembly that can be resilient, durable, and efficient in all climate zones. Wherever unvented conditioned attics or roofs are constructed, a means of moisture removal from the attic is necessary. The “conditioned” part of unvented conditioned attics or roofs is important.
17) At the time of inspection it appears the attic was in serviceable condition except as noted.
Photo 17-1 Photo 17-2
Photo 17-3 Photo 17-4
Photo 17-5 Photo 17-6
Photo 17-7 Photo 17-8
Photo 17-9 Photo 17-10
Photo 17-11 Photo 17-12
Photo 17-13
18) The attic roof deck assemblies were inaccessible because permanent polyurethane foam spray insulation was installed and therefore all rafter assemblies work was not visible. These areas were not evaluated and therefore are excluded from this inspection.
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Two, Attached Garages.
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core, Wood
Condition of exterior entry doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood
Condition of garage vehicle door(s): Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Type of garage vehicle door: Sectional, Sliding
Number of vehicle doors: 2
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of garage interior: Appeared serviceable, Required repair or evaluation (see comments below)
Garage ventilation: None visible
19) One or more gaps and/or holes were found in the attached garage walls or ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit: http://www.reporthost.com/?AGFR
Photo 19-1 Photo 19-2
20) Stains were found in one or more roof structure ceiling areas. The inspector was unable to determine if an active leak exists (e.g. recent dry weather, inaccessible height). Recommend asking the property owner about this, monitoring the stains in the future, and/or having a qualified contractor evaluate and repair if necessary.
Photo 20-1 Photo 20-2
21) Attic spaces greater than 30 inches in height appeared to exist in the garages, but no access points were found. Recommend that a qualified person install attic access points where missing and per standard building practices (e.g. adequate size, insulated, weatherstripped). A qualified person should fully evaluate these attic spaces and roof structures. These areas are excluded from this inspection.
Photo 21-1 Photo 21-2
22) Low to medium moisture intrusion was found at the garage ceiling above the exterior door and door jam. Recommend that a qualified contractor fully evaluate and repair as necessary after any leaks have been repaired. If moisture is present then concealed areas should be dried thoroughly.
Photo 22-1 Photo 22-2
Photo 22-3 Photo 22-4
Photo 22-5 Photo 22-6
23) Fungal rot was found at one or more exterior door jambs. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo 23-1 Photo 23-2
Photo 23-3 Photo 23-4
24) One or more walls ceilings were cracked. Recommend that a qualified person repair as necessary.
Photo 24-1 Photo 24-2
25) Significant gaps were found below or around one or more garage vehicle doors. Vermin and insects can enter the garage as a result. Recommend that a qualified person repair as necessary to eliminate or minimize gaps.
Photo 25-1
26) Weatherstripping at the sides and/or bottom of one or more garage vehicle doors was damaged, deteriorated and/or Warped. Recommend replacing or installing weatherstripping where necessary to prevent water and/or vermin intrusion.
Photo 26-1 Photo 26-2
Photo 26-3
27) At the time of inspection it appears the garage was in serviceable condition except as noted
Photo 27-1 Photo 27-2
Photo 27-3 Photo 27-4
Photo 27-5 Photo 27-6 Only one garage door had a battery back up system. Recommend reviewing and asking the owners about this and installing such back systems where necessary.
Photo 27-7 Photo 27-8
Photo 27-9 Photo 27-10
28) Minor cracks and or deterioration were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
Photo 28-1
29) The attic access in the garage was inaccessible and no hatch was installed. The inspector was unable to enter, view or traverse the attic space over the garage. This area is excluded from this inspection.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 200-240
Estimated service amperage: 225
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil, Cold water supply pipes
Condition of main service panel: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A: Building exterior
Location of main disconnect: At main disconnect panel outside
Condition of branch circuit wiring: Serviceable, Required repair, replacement and/or evaluation (see comments below)
Carbon monoxide alarms installed: No, recommend install
Smoke alarm power source(s): Hard wired
30) One or more cover plates installed outside were missing components. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair as necessary.
Photo 30-1
31) One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo 31-1 Photo 31-2
32) Carbon monoxide alarms were missing from one or more sleeping areas and/or on one or more levels. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit: http://www.reporthost.com/?COALRM
33) The front door's doorbell appeared to be inoperable. Recommend that a qualified person repair as necessary.
Photo 33-1
34) The front door's doorbell button was loose and/or damaged. Recommend that a qualified person repair as necessary.
Photo 34-1
35) One or more circuit breakers in panel(s) #A were in the off position. Consult with the property owner to determine why breakers were tripped or off, and that a qualified electrician evaluate and repair if necessary. Note that the inspector does not operate circuit breakers.
Photo 35-1
36) One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo 36-1 Photo 36-2
Photo 36-3 Photo 36-4
Photo 36-5 Photo 36-6
37) At the time of inspection it appears the electrical panels were on and in serviceable condition except as noted.
Photo 37-1 Photo 37-2
Photo 37-3
38) Equipment for a generator system was found. Generators, transfer switches and any associated wiring are excluded from this inspection. Recommend that the client consult with the property owner or review documentation to familiarize themselves with the operation of this system.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water meter: By street
Location of main water shut-off: Building exterior
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Location(s) of plumbing clean-outs: Building exterior
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: None visible
Sewage ejector pump installed: None visible
Condition of fuel system: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Visible fuel storage systems: Above ground
Location of main fuel shut-off valve: At gas meter, At building exterior
39) One or more flexible connectors used for gas supply lines passed through shelving and/or cabinets. Flexible connectors passing through walls, floors, ceilings, shelving or cabinets can be damaged, and leaks can occur. This is a potential explosion and/or fire hazard. Recommend that a qualified contractor repair per standard building practices.
Photo 39-1 Photo 39-2
Photo 39-3
40) One or more propane or natural gas supply terminations were unused (no appliance connected) and no cap was installed on the gas shut-off valve(s). Gas can flow directly out of the termination with the shut-off valve is opened. This is a potential fire hazard. Recommend that a qualified person install caps where missing per standard building practices.
Photo 40-1
41) The local gas shut-off valve for the gas-fired stove was inaccessible due to the location and surrounding objects or structures. This is a potential safety hazard when the appliance needs to be shut down quickly. Local shut-off valves should be readily accessible. Recommend that a qualified contractor repair per standard building practices.
Photo 41-1 Photo 41-2
42) Based on visible equipment or information provided to the inspector, this property appeared to have a yard irrigation (sprinkler) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. When this system is operated, recommend verifying that water is not directed at building exteriors, or directed so water accumulates around building foundations. Sprinkler heads may need to be adjusted, replaced or disabled. Consider having a qualified plumber verify that a backflow prevention device is installed per standard building practices to prevent cross-contamination of potable water. Recommend that a qualified specialist evaluate the irrigation system for other defects (e.g. leaks, damaged or malfunctioning sprinkler heads) and repair if necessary.
Photo 42-1 Photo 42-2
Photo 42-3 Photo 42-4 Broken sprinkler heads were found. Recommend that a qualified person repair and or replace as necessary.
Photo 42-5 Photo 42-6
Photo 42-7
43) Steel piping for the gas service located outside was significantly corroded. Gas leaks can result. Recommend evaluation by a qualified contractor to determine if piping needs replacing. If not, then a qualified person should prep and paint lines as necessary with a rust-preventative paint. Very corroded pipes should be replaced by a qualified contractor.
Photo 43-1
44) A fire suppression system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems normally require periodic inspection by a specialist to ensure correct operation. For example, checking for possible backflow contamination of the potable water system, or correct operation of valves and gauges. Recommend that a qualified specialist inspect this system in accordance with National Fire Prevention Association (NFPA) 25 standards.
Photo 44-1 Photo 44-2
Photo 44-3 Photo 44-4
Photo 44-5
45) At the time of inspection it appears the water and gas was on and in serviceable condition except as noted.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2013
Capacity (in gallons): 50
Manufacturer: Rheem
Model number: 22VR50FN
Location of water heater: Garage
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 115
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
46) Based on the location of the water heater and the visible venting, the water heater had a substandard source of combustion and/or dilution air. All gas appliances require adequate air (approximately 1 square inch per 1000 BTU) for combustion, dilution and ventilation. This is a potential safety hazard and can result in exhaust gases entering living spaces. A qualified contractor should evaluate and repair as necessary and per standard building practices.
Photo 46-1 Photo 46-2
47) At the time of inspection it appears the water heater was on and in serviceable condition except as noted.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Forced air furnace model #: GKS90905DXAF
Location of forced air furnace: Attic
Condition of furnace filters: Appeared serviceable, Required replacement
Location for forced air filter(s): At end of air handler, Behind return air grill(s)
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Type of combustion air supply: Vent(s) to exterior
Condition of cooling system and/or heat pump: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Cooling system and/or heat pump fuel type: Electric
Location: Exterior side
Type: Split system
Estimated age: Not determined
Manufacturer: Goodman
Heat pump or air conditioner model number: GSX160481FA
Condition of controls: Appeared serviceable
Condition of whole house fan: Appeared serviceable
24 hour automatic ventilation system present: Yes
48) Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.
Photo 48-1 Photo 48-2
49) Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo 49-1 Photo 49-2
Photo 49-3
50) At the time of inspection it appears the Furnace & A/C was in serviceable condition except as noted.
Photo 50-1 Photo 50-2
Photo 50-3 Photo 50-4
Photo 50-5 Photo 50-6
Photo 50-7 Photo 50-8
Photo 50-9 Photo 50-10
Photo 50-11 Photo 50-12
Photo 50-13 Photo 50-14
51) Air supply ports were installed. These are intended to improve indoor air quality in relatively air- tight structures by supplying fresh air to living spaces and by reducing moisture accumulation. Air supply ports should be kept open at all times.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Gas fireplace or stove type: Metal pre-fab fireplace
Fan or blower installed in gas-fired fireplace or stove: Not determined (inaccessible or obscured)
Condition of chimneys and flues: Appeared serviceable, wall exhaust only. No roof chimney structure.
Gas-fired flue type: B-vent
52) Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now.
Photo 52-1 Paint was stained on the metal screed. Photo 52-2 Excessive lint and dust was found at the pilot box.
Photo 52-3 Photo 52-4
53) At the time of inspection it appears the fireplaces was in serviceable condition except as noted.
Photo 53-1 Photo 53-2
Photo 53-3 No roof chimneys, only exterior wall exhaust.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of sinks and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of under-sink food disposal: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Range, cooktop or oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of built-in microwave oven: Appeared serviceable
Condition of hot water dispenser: N/A (none installed)
Condition of trash compactor: N/A (none installed)
54) The sink sprayer was damaged and/or deteriorated. Recommend that a qualified person repair or replace as necessary.
Photo 54-1 Photo 54-2
55) The under-sink food disposal was noisy or vibrated excessively. Recommend that a qualified contractor repair or replace as necessary.
Photo 55-1
56) 1 cooktop burner(s) were inoperable or difficult to operate. Recommend that a qualified person repair as necessary.
Photo 56-1 Photo 56-2
57) The clearance between the stove top and the base of the exhaust hood above was too low. While the recommended height varies per the hood manufacturer, standards usually call for a minimum of 24 inches of clearance. A low hood height can restrict visibility of the stove top. Recommend that a qualified contractor repair per standard building practices.
Photo 57-1 Photo 57-2
58) The refrigerator's ice maker was inoperable. Recommend that a qualified person repair as necessary.
Photo 58-1 Photo 58-2
59) Stains were found in the shelving or cabinets below the sink. Plumbing leaks may have occurred in the past. Consult with the property owner about this, and if necessary a qualified person evaluate and repair.
Photo 59-1 Photo 59-2
Photo 59-3 Photo 59-4
60) At the time of inspection it appears the available kitchen appliances were in serviceable condition except as noted.
Photo 60-1 Minor dents were found at the refrigerator doors. Photo 60-2
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, first floor
Location #B: Full bath, Master bath, first floor
Location #C: Full bath, second floor, Hallway two sinks
Location #D: Full bath, second floor, Jack and Jill
Location #E: Full bath, Master bath, second floor
Location #F: Laundry room/area, first floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Bathroom and laundry ventilation type: Windows, Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: No
61) The toilet lid and/or was loose or broken at location(s) #A and B. Recommend that a qualified plumber replace toilet(s) or components as necessary. Where cracks have resulted in leaks, additional repairs due to water damage may be needed.
Photo 61-1
62) A significant amount of water came out of the bathtub spout when the shower at location(s) #B, C and D was turned on. The diverter valve is likely defective, or may be encrusted with mineral deposits. Water will be wasted as a result. Recommend that a qualified plumber repair or replace components as necessary.
Photo 62-1 Photo 62-2
Photo 62-3
63) The clothes washer hook-ups were installed in a finished space or in an area where leaking can cause damage, and no catch pan or drain was installed. Catch pans and drains prevent water damage to finished interior spaces below if or when the washing machine leaks, overflows or is drained. If concerned, consult with a qualified contractor about installing these. Note that drain lines for catch pans may be difficult to install in an existing home unless the washer is located adjacent to an exterior wall.
Photo 63-1
64) The sink drain stopper mechanism at location(s) #C and D was inoperable or missing. Recommend that a qualified person repair or replace as necessary.
Photo 64-1 Photo 64-2
Photo 64-3
65) Gaps, no caulk, or substandard caulking were found between the bathtub and the floor at location(s) #D. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo 65-1 Photo 65-2
Photo 65-3
66) The exhaust fan or fan cover at location(s) #B, C and D needed cleaning. Dirty or clogged fans can result in moisture accumulation and subsequent mold, bacteria or fungal growth. Recommend cleaning fan covers or fans now and as necessary in the future.
Photo 66-1
67) Stains were found in the shelving or cabinets below the sink at location(s) #B and C. Plumbing leaks may have occurred in the past. Consult with the property owner about this, and if necessary that a qualified person evaluate and repair.
Photo 67-1 Photo 67-2
68) There were no washer nor dryer that were operated or evaluated therefore they have been excluded from this report.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood, Sliding glass
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Sliding, Single-hung
Condition of walls and ceilings: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable
69) Trim or jambs around one or more exterior sliding glass doors was damaged and/or deteriorated. Recommend that a qualified person repair, replace or install as necessary.
Photo 69-1 Photo 69-2
70) One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo 70-1
71) The sash-side spring mechanisms in one or more windows were broken, loose or disconnected. The window(s) were difficult to operate as a result, and not square in their frames or tracks. Recommend that a qualified contractor or service technician repair as necessary so windows open and close easily, and stay open without support.
Photo 71-1
72) Trim was damaged in one or more areas. Recommend that a qualified person repair as necessary.
Photo 72-1
73) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product: http://www.reporthost.com/?ECC
Limitations: We specifically exclude those items that we cannot fully observe such as areas within walls, behind walls, underground or other concealed or inaccessible areas. It is advisable to obtain all available documentation such as building permits, certificates of compliance, certificates of occupancy, construction documents such as plans or engineering, contracts, warranties, guarantees, receipts, instruction manuals or any other kind of pertinent information related to the plumbing system and its individual components. This report is intended to identify material defects only and act as a general guide to help the client make his or her own evaluation of the overall condition of the main sewer line, and is not intended to make any representation as to the advisability of purchase.
The report expresses the personal opinions of the inspector, based upon his visual impressions of the conditions that existed at the time of the inspection only. The inspection and report are not intended to be technically exhaustive, or to imply that every component was thoroughly inspected (this is not always possible as there are generally areas that are not accessible), or that every possible "defect" was discovered. No disassembly of equipment, opening of walls, moving of furniture, appliances or stored items, or excavation was performed. All components and conditions which by the nature of their location are concealed or camouflaged are excluded from the report. This inspection is specific to the main sewer line and any general comments about systems and conditions other than the main sewer line are informational only and do not represent an inspection of these areas. This is a specialty inspection of the main sewer line only (unless specified in the contract).
The main sewer line is that portion of the waste drainage piping system that is exterior to the structure and carries the building waste from the building drain (that portion of the waste drainage piping system that is under/interior to the structure) to the city sewer connection. The findings of this inspection are based on the opinions and education of the inspector and reflect the conditions discovered at the time of inspection only. As this is a non-invasive visual inspection AREA Inspections does not guarantee the ability of the main sewer line to fulfill its function in the future, as the outer wall of the sewer line is not visible and therefore beyond our view.
Condition of sewer line: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
System type: Conventional gravity
Were past service records available during the inspection: No
Have prior repairs been made to this system: No
Number of bedrooms in the dwelling: 5
Number of bathrooms in the dwelling: 4
Number of current residents in the dwelling: Not applicable, dwelling vacant
Number of future residents expected in dwelling: Not determined
Food disposal installed: Yes
Condition of lid(s): Appeared serviceable
Clean-out lid type: Riser with secured lid at or near grade
74) At the time of inspection it appears the lateral lines have minor root intrusion, minor cracks or accumulated debris. Recommend that a qualified plumbing contractor perform maintenance by means of jetting and clearing the main line and fully evaluate as necessary and prescribe repairs and/or maintain in the future.
Photo 74-1 Located at approx. 10 meters Photo 74-2
Photo 74-3
75) At the time of inspection it appears the lateral lines have excessive build up and scale at the inner walls pipe. Recommend that a qualified plumbing contractor perform maintenance by means of jetting and clearing the main line and maintain in the future.
Photo 75-1 Photo 75-2 Located at approx. 13 meters
Photo 75-3 Photo 75-4
Photo 75-5
76) At the time of inspection it appears the lateral lines have (offsets) misalign joints. Recommend that a qualified plumbing contractor perform maintenance by means of jetting and clearing the main line to further evaluate and prescribe repairs if necessary and maintain in the future.
Photo 76-1 Located at approx. 13 meters Photo 76-2
77) At the time of inspection it appears the sewer line was in serviceable condition except as noted. *No backing up was visible when a functional flow test was performed. Access to the main sewer clean out was located at the front of the house, S/W corner of the Garage. Lateral line traveled southbound towards street. *Public in-line sewer connection was confirmed at approx. 25 meters. *Anti-back-flow insert located at the main clean-out. Recommend clean up and maintain in the future. *Recommend jetting and clearing as need now and and having a qualified plumber fully evaluate and prescribe repairs if necessary and maintain in the future.
Photo 77-1 Photo 77-2
Photo 77-3 Photo 77-4 Anti-backflow insert.
Photo 77-5 Approx 56 Feet to curbside. Photo 77-6
Photo 77-7 Plastic to clay transition located at approx. 17 meters Photo 77-8
Photo 77-9 In-line sewer municipal connect located at approx. 25 meters Photo 77-10
Photo 77-11 Photo 77-12 Sewer clean-out access located in driveway not confirmed due to back fill with sand. Recommend asking the owners about this and or having a qualified person fully evaluate and prescribe repairs if necessary.
Photo 77-13
1.1. A Home Inspection is a non-invasive, visual examination of a residential dwelling, performed for a fee, which is designed to identify observed material defects within specific components of said dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or other essential systems or portions of the home, as identified and agreed to by the Client and Inspector, prior to the inspection process.
I. A home inspection is intended to assist in evaluation of the overall condition of the dwelling. The inspection is based on observation of the visible and apparent condition of the structure and its components on the date of the inspection, and not the prediction of future conditions.
II. A home inspection will not reveal every concern that exists or ever could exist, but only those material defects observed on the day of the inspection.
III. A home inspection can include a survey and/or analysis of energy flows and usage in a residential property if the client requests it. 1.2. A Material Defect is a condition of a residential real property, or any portion of it, that would have a significant, adverse impact on the value of the real property, or that involves an unreasonable risk to people on the property. The fact that a structural element, system or subsystem is near, at or beyond the end of the normal useful life of such a structural element, system or subsystem is not by itself a material defect.
1.3. An Inspection Report shall describe and identify, in written format, the inspected systems, structures, and components of the dwelling, and shall identify material defects observed. Inspection reports may contain recommendations regarding conditions reported or recommendations for correction, monitoring or further evaluation by professionals, but this is not required.
A complete copy of the STANDARDS OF PRACTICE we adhere to can be found at the following link: http://www.nachi.org/sop.htm