This report published on Sunday, November 5, 2023 11:35:13 AM EST
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
Safety
Poses a safety hazard
Repair/Replace
Recommend repairing or replacing
Maintain
Recommend ongoing maintenance
Evaluate
Recommend evaluation by a specialist
Monitor
Recommend monitoring in the future
Comment
For your information
Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Hot
Inspection fee: 0
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Source for main building age: Client
Occupied: Yes
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit: https://www.reporthost.com/?EPA https://www.reporthost.com/?CPSC https://www.reporthost.com/?CDC
2) As per the owner built circa 1928, and additions were made circa 2010.
Photo 2-1 Photo 2-2
3) 3BD 2BA
4) Balloon framing original construction
5) Dutch gable gambrel roof
6) Mini split disconnect not in sight of heat pump in rear of the house. Recommend further evaluation by licensed hvac technician or electrician.
7) Heat pump condensation lines not draining away from the house
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level. Recommend grading property slope away from house.
Condition of driveway: Appeared serviceable
Driveway material: Asphalt, Brick
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete, Paving stones
Condition of deck, patio and/or porch covers: Appeared serviceable
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
9) Rear deck gate rubs on the decking. Recommend further evaluation by a qualified individual.
Photo 9-1
10) Wood along the foundation is touching the earth. Wood should never come in direct contact with the soil or concrete. This could lead to a pest problem in the future. Recommend further evaluation by a licensed contractor and exterminator.
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Wall covering: Vinyl, Solid brick (not veneer)
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space, Finished basement
Foundation/stem wall material: Concrete block
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)
11) One or more holes or gaps were found in the siding or trim. Vermin, insects, or water may enter the structure. I would recommend that a qualified person repair as necessary.
Photo 11-1
12) The chimney appears to be original and in need of repointing. I recommend a second evaluation by a licensed chimney professional.
Photo 12-1
13) Wood rot was found at the threshold of the side/basement entrance. Bare wood should never be in contact directly with cement or dirt. This door is also at ground level, which can lead to water intrusion if the driveway is graded improperly. Door thresholds should be a minimum of 4 inches above ground level. Recommend repair or replacement by a qualified individual.
Photo 13-1
14) The rear deck stairs do not seem to be attached to the deck structure. Recommend further evaluation by a qualified contractor.
Photo 14-1
15) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo 15-1 Photo 15-2
Photo 15-3
16) One of the crawlspace vents appeared to be blocked. Recommend further evaluation by a qualified contractor.
Photo 16-1
17) One crawl space vents appear to be at grade. This can result in water intrusion during rainfall. All vents and door ways should be at least 4 inches above grade.
Photo 17-1
18) Multiple siding intrusions. Monitor for leaking—further evaluation by a licensed contractor.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.
The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
19) Inspector could not access the crawl space. Recommend access be available and inspected by a qualified individual prior to closing.
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.
Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
20) Loose wiring hanging from the ceiling. Recommend further evaluation by a licensed electrician.
Photo 20-1
21) Partially finished basement. Inspector was unable to verify parts of the foundation due to wall and ceiling covering and debris.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable, Shed, Gambrel
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
22) Extensions such as splash blocks or drain pipes for one or more downspouts were . Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo 22-1
23) The gutter above the bow window has a complex flashing scenario. This could lead to leaks int he future. Recommend a second evaluation by a licensed roofer or window contractor for further evaluation.
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Condition of roof structure: Could not be determined due to finished attic
24) Inspector could not fully evaluate Attic and Roof Structure due to sheetrock. The attic is partially finished with no apparent ventilation. Recommend further evaluation by a licensed contractor to determine the proper soffit and ridge venting installed. Lack of proper ventilation may shorten the life of the roof. Gable vent has been replaced by a window as displayed below.
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
25) Multiple breakers inside the panel box had more than one circuit. The wiring visible in the basement, is not properly secured. Multiple outlets are missing grounds, and or loose. Switches appear to be sunken into walls, and one outlet outside is low to the ground and not operable. Recommend further evaluation by a licensed electrician PRIOR to closing.
Photo 25-1 Photo 25-2
Photo 25-3 Photo 25-4
Photo 25-5 Photo 25-6
Photo 25-7 Photo 25-8 Exterior outlets should be at least 18" above ground level.
Photo 25-9 Photo 25-10
Photo 25-11 Photo 25-12
Photo 25-13 Photo 25-14
26) Electrical Service might be less than 36" away from the window. This can be a safety hazard. Recommend further evaluation by a licensed electrician.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
House Trap: The main house trap could not be located. Recommend further evaluation by a licensed plumber PRIOR to closing.
Fuel Type: Natural Gas
27) Multiple sump pumps were found in the basement. The one next to the water heater was missing its cover and had standing water at the bottom. Unable to verify if they were operating.
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Furnace, Heat pump
General heating distribution type(s): Ducts and registers
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Hydronic (hot water), Circulating pump, Radiators
Hydronic or steam heat fuel type: Natural gas
Owner Statement: Heat Pumps installed January of 2023.
Heat Pump on Side Sizer: The heat pump located at ground level is 1.5 tons.
29) Heat Pump should be on a cement pad or mounted to the home. Recommend further evaluation by a licensed HVAC technician.
Photo 29-1
30) The heating system was not fully evaluated because the . Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that the inspector does not operate shut-off valves, pilot lights or circuit breakers, or any controls other than normal controls (thermostat).
31) The heat pump or air conditioner condensing unit was not fully evaluated because the . Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that the inspector does not operate or replace overcurrent protection devices, or operate any controls other than normal controls (thermostat).
32) The estimated useful life for most steel boilers is 20 years. This boiler appeared to be near this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Recommend having serviced by a licensed HVAC technician before operating.
Photo 32-1 Photo 32-2
Photo 32-3
33) Multiple Heating and Cooling Systems. Heat Pump Mini Splits, Radiators, and Hydronic Steam Radiators.
The systems were unable to be fully evaluated. Recommend further evaluation by a licensed HVAC technician to determine if the systems are adequate for the living space.
34) One disconnect on the heat pump in the rear of the home is not "in sight" of the unit. It wraps around the side. Recommend further evaluation by a licensed electrician.
Photo 34-1
35) Unable to verify the size of all heat pump/AC units due to their location.
Photo 35-1 Photo 35-2
Photo 35-3
36) Heat Pump Condenser drain lines should drain six feet away from the house.
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Note from Owner: Owner states they closed up fireplace on the interior but did not remove chimney. Unable to verify the chimney due to no access.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Owner Statement: All bathrooms renovated in January of 2023.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Window Types: Single Hung, Double Hung, Vinyl Clad Windows, Casement Windows, Picture Windows, and Bow Windows.
37) One broken window was found. Recommend replaced by a licensed contractor.