This is an actual home inspection report published in 20 minutes, starting from the time the report was uploaded from the ReportHost Pro software to the ReportHost website. The 20 minute time included resizing and uploading digital pictures, spell checking and publishing.
An example of a report that took 10 minutes can be found here.

Website: http://www.allpointinspections.com/
Phone:
(XXX) XXX-XXXX
XXXXXXXXX
Poulsbo, WA
98370
Inspector: Jim Gallant
Full General Home Inspection and
Structural Pest Inspection WA State Dept. Agriculture ICN#
XXXXXXXXX |
Client(s): |
XXXX XXXXXXX |
Property address: |
XXXX XXXXXXX XX XXXXXX, XX |
Inspection date: |
XX/XX/XXXX |
This report published on XX/XX/XXXX XX:XX:XX PM PDT
View
summary page
This report is the exclusive property of this inspection
company and the client(s) listed in the report title. Use of this report by any
unauthorized persons is prohibited.
WAC 16-228-2045 requires that a
diagram be prepared for WDO (Wood Destroying Organism) inspection reports. A
copy is available upon request.
For information on follow-up
inspections, please see the bottom section of this report.
Thank you
for choosing All Point Home Inspections. We've made every effort to provide you
with a thorough, high quality inspection, and hope that the information in this
report proves to be valuable in your consideration of this property. If for any
reason you are unsatisfied with this report, or have questions after reviewing
it, please don't hesitate to call us. If you are satisfied, please tell your
friends about us.
This inspection complies with the American Society of Home Inspectors' (ASHI) Standards of Practice
and the National
Association of Home Inspectors' (NAHI) Standards of Practice. This report is
intended to identify major defects within a structure that significantly affect
its habitability or that cost in excess of $500 to repair, although minor
defects may be noted in the report. Cosmetic items such as damaged molding,
trim, doors, cabinets, interior paint or carpet are generally excluded from this
report.
Home inspection reports by nature focus on defects and may seem
negative in tone. Some features of this property may be in excellent condition
and of high quality but have not been mentioned, or been deemed adequate in the
report. This is not meant to downplay this property's assets, but to focus on
alerting you to potentially expensive problems. Bear in mind that all homes,
regardless of their age, have some number of defects.
Areas of the
property that are excluded due to lack of access are vulnerable to infestation
and damage from wood destroying insects and organisms.
How to Read this
Report
This report is organized by the property's
functional areas. Within each functional area, descriptive information is
listed first and is shown in bold type. Items of concern follow
descriptive information. Concerns are shown and sorted according to these types:
 |
Safety |
Poses a risk of injury or death |
 |
Major defect |
Correction likely involves a significant
expense |
 |
Repair/Replace |
Recommend repairing or replacing |
 |
Repair/Maintain |
Recommend repair and/or maintenance |
 |
Minor defect |
Correction only involves a minor
expense |
 |
Maintain |
Recommend ongoing maintenance |
 |
Evaluate |
Recommend evaluation by a specialist |
 |
Monitor |
Recommend monitoring in the future |
 |
Comment |
For your information |
Structural Pest Inspection Concerns
Items of concern relating to
the structural pest inspection are shown as follows:
 |
WDO/WDI Infestation |
Evidence of infestation of wood destroying
insects or organisms (Live or dead insect bodies, fungal growth,
etc.) |
 |
WDO/WDI Damage |
Damage caused by wood destroying insects or
organisms (Rot, carpenter ant galleries, etc.) |
 |
WDO/WDI Conducive conditions |
Conditions conducive for wood destroying insects
or organisms (Wood-soil contact, shrubs in contact with siding, roof or
plumbing leaks, etc.) |
Click
here for a glossary of building construction terms.
Contact your inspector if there are terms that you do not
understand, or visit the glossary of construction terms at
http://www.reporthost.com/glossary.asp
Table of Contents
General
Information
Grounds
Exterior
/ Foundation
Roof /
Attic
Garage /
Carport
Electric
Plumbing
/ Fuel Systems
Water
Heater
Heating
Fireplaces
/ Stoves / Chimneys
Kitchen
Bathrooms
/ Laundry / Sinks
Interior
Rooms / Areas
Structural
Pest Findings
Report number:
xxxxxx
Time started:
9:00 AM
Time finished:
11:00 AM
Present during
inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions: Partly cloudy
Temperature: Cool
Ground condition: Damp
Inspection fee: $XXX
Payment method: Check
Type of building: Single family
Buildings inspected:
One house
Age of building(s):
XXXX
Source for building age:
Client
Front of building faces:
East
Main entrance faces:
East
Occupied: Yes
1) 
Structures built prior to 1980 may contain
lead-based paint and/or asbestos in various building materials such as
insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are
known health hazards. Evaluating for the presence of lead and/or asbestos is not
included in this inspection. The client should consult with specialists as
necessary, such as industrial hygienists, professional labs and/or abatement
contractors for this type of evaluation. For information on lead, asbestos and
other hazardous materials in homes, visit:
http://www.epa.gov/
http://www.cpsc.gov/
http://www.cdc.gov/
2)
Some wall and floor surfaces were obscured
by furniture, stored items and couldn't be fully evaluated.
Limitations:
The following items are not included in this inspection:
swimming pools, spas, hot tubs, water features and related equipment;
playground, recreation or leisure equipment; landscape lighting; areas below
exterior structures with less than three feet of vertical clearance; irrigation
systems; invisible fencing; sea walls, docks and boathouses. Any comments made
regarding these items are as a courtesy only. Note that the inspector does not
test or determine the adequacy of drainage systems for grounds, walkways,
below-grade stairs and roof downspouts. The inspector does not provide an
evaluation of geological conditions and/or site stability, compliance of pool or
spa fencing with municipal requirements, or determination that deck, balcony
and/or stair membranes are watertight.
The following
items are excluded from this inspection: Shed
Condition of fences and gates:
Required repairs, replacement and/or evaluation (see
comments below)
Fence and gate material: Wood
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material:
Poured in place concrete, Gravel
Condition of sidewalks and/or patios: Appeared
serviceable
3)
Fences were damaged or
deteriorated in some areas. A qualified person should repair or replace sections
as necessary.
 Photo
9 |
|
4)
Vegetation such as trees, shrubs and/or vines was in contact with or less than
one foot from the building exterior. Vegetation can serve as a conduit for wood
destroying insects and may retain moisture against the exterior after it rains.
Vegetation should be pruned and/or removed as necessary to maintain a one foot
clearance between it and the building exterior.
 Photo
2 |
 Photo
3 |
5)
Minor cracks, settlement, heaving and/or
deterioration were found in one or more sidewalk or patio sections. However they
don't appear to be a structural concern and no trip hazards were found. No
immediate action is recommended, but the client may wish to have repairs made or
have cracked sections replaced for aesthetic reasons.
Limitations:
The following items are not included in this inspection:
below-grade foundation walls and footings, or those obscured by vegetation or
building components; exterior building surfaces or components obscured by
vegetation, stored items or debris. Any comments made regarding these items are
as a courtesy only. Some amount of cracking is normal in concrete slabs and
foundation walls due to shrinkage and drying. Note that the inspector does not
determination the adequacy of sump pumps, seismic reinforcement, nor determine
if support posts, columns, beams, joists, studs, trusses, etc. are of adequate
size, spanning or spacing.
Condition of wall covering:
Appeared serviceable
Apparent
wall structure: Wood frame
Wall
covering: Wood fiber
Condition of
foundation and footings: Appeared
serviceable
Foundation type: Crawlspace
Foundation material: Poured in place concrete
Footing material:
Poured in place concrete
Anchor
bolts for seismic reinforcement: Not
determined
Shear panels for seismic reinforcement:
Not determined
Condition of floor
substructure: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: 2x6 tongue and groove
Condition of crawl
space: Appeared serviceable
Crawl
space inspection method: Partially
traversed
Insulation material underneath floor above:
Fiberglass roll or batt
Ventilation: Appears serviceable
Vapor barrier present: Yes
6) 
The exterior finish over the entire
structure was failing. A qualified painting contractor should prep (pressure
wash, scrape, sand, prime caulk, etc.) and repaint or restain the entire
structure as per standard building practices.
 Photo
6 |
|
7) 

This property was clad with
composition wood fiber siding. Many brands of this type of siding by different
manufacturers are known to deteriorate and/or fail prematurely due to moisture
penetration. Failure is typically visible in the form of swelling, cracking and
delamination, especially at the bottom edges. Class action lawsuits have been
filed or are being filed against most manufacturers of this material.
Some areas of siding on this structure showed the symptoms described
above and need replacement and/or maintenance. For example on the south side.
Some manufacturers (Louisiana Pacific) recommend a repair process for this
siding where affected areas are sealed with "Permanizer Plus", a flexible primer
made by Pittsburgh Paint, followed by two coats of 100% acrylic latex paint.
This sealant must be applied to the bottom edges using a brush. The face of the
siding can be sprayed. The "Permanizer Plus" sealer isn't required for edges
that aren't swollen, cracked or deteriorated, but the acrylic latex should still
be brushed on these edges.
A qualified contractor should evaluate and
replace siding as necessary, and/or seal and repaint as necessary and as
described above, or by other methods specified by the siding's
manufacturer.
For more information, visit:
http://www.ppg.com/ppgaf/pl1198.htm - Pittsburgh Paints, PRIMERS
-THE FOUNDATION FOR A TOP QUALITY JOB
http://www.siding4u.com/failing_siding_help.htm - Failing LP
Siding Help Page
 Photo
7 |
 Photo
8 |
8) 

Evidence of prior water intrusion was
found in one or more sections of the crawl space. For example, sediment stains
on the vapor barrier or foundation, and/or efflorescence on the foundation.
Accumulated water is a conducive condition for wood destroying insects and
organisms and should not be present in the crawl space. The client should review
any disclosure statements available and ask the property owner about past
accumulation of water in the crawl space. The crawl space should be monitored in
the future for accumulated water, especially after heavy and/or prolonged
periods of rain. If water is found to accumulate, a qualified contractor who
specializes in drainage issues should evaluate and repair as necessary. Typical
repairs for preventing water from accumulating in crawl spaces include:
Repairing, installing or improving rain run-off systems (gutters, downspouts
and extensions or drain lines)
Improving perimeter grading
Repairing, installing or improving underground footing and/or curtain
drains
Ideally, water should not enter crawl spaces, but if water must be
controlled after it enters the crawl space, then typical repairs include
installing trenches, gravity drains and/or sump pump(s) in the crawl space.
 Photo
47 |
|
9)
One or more unlined wooden planter boxes are attached to the side of the
building. Wood soil contact exists in such boxes and is a conducive condition
for wood-destroying insects and organisms. Recommend either removing them, or
modifying them so that no wood-soil contact exists (install plastic or metal
liners), and so that they are well drained.
 Photo
5 |
|
10)
Caulk was deteriorated around windows, around doors, at siding-trim junctions. A
qualified person should repair or replace as necessary. For more information,
visit:
http://www.reporthost.com/_docs/FPL_Caulking_Ins_Outs.pdf
 Photo
11 |
|
Limitations:
The following items or areas are not included in this
inspection: areas that could not be traversed or viewed clearly due to lack of
access; areas and components obscured by insulation; solar roofing components;
any comments made regarding these items are as a courtesy only. Note that the
inspector does not determination if rafters, trusses, joists, beams, etc. are of
adequate size, spanning or spacing. The inspector does not provide an estimate
of remaining roof surface life, does not determine that the roof has absolutely
no leaks at the time of the inspection, and does not determine that the roof
won't leak in the future. Only active leaks and evidence of past leaks observed
during the inspection are reported on as part of this inspection. To absolutely
determine than no leaks exist, complete access to all roof structure areas must
be available during a wide variety of weather conditions, including prolonged
heavy rain, high wind from varying directions, heavy accumulations of snow
and/or ice, and melting snow and ice.
Condition of roof
structure: Appeared serviceable
Roof type: Gable
Condition of shingle and/or shake roof surface materials: Appeared serviceable
Roof surface material:
Asphalt or fiberglass composition shingles
Apparent number of layers of roof surface material: Two
Condition of gutters, downspouts and
extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation:
Full
Condition of attic:
Appeared serviceable
Attic
inspection method: Viewed from hatch(es)
Roof structure type: Trusses
Ceiling structure: Trusses
Ceiling insulation material: Mineral wool loose
fill
Ceiling insulation depth: 10
inches
Ceiling insulation rating: R 28
Roof ventilation: Appears serviceable
11) 
One or more exhaust fan ducts in the
attic were missing. This is a conducive condition for wood destroying insects
and organisms due to increased moisture levels in the attic from the exhaust
air. A qualified person should evaluate and make permanent repairs as necessary
and as per standard building practices, so all exhaust air is vented outside.
 Photo
36 |
|
12)
The ceiling insulation in some
areas of the attic was uneven. This may result in increased heating or cooling
costs due to decreased energy efficiency. A qualified person should repair,
replace or install insulation as necessary. For more information, visit:
http://www.eere.energy.gov/consumer/tips/insulation.html
 Photo
37 |
|
13)
Moss was growing on the roof. As a
result, shingles may lift or be damaged. Leaks may result and/or the roof
surface may fail prematurely. This is a conducive condition for wood destroying
insects and organisms. Efforts should be taken to kill the moss during its
growing season (wet months). Typically zinc-based chemicals are used for this,
and must be applied periodically. For information on various moss treatment
products and their pros and cons, visit:
http://bryophytes.science.oregonstate.edu/page24.htm
 Photo
12 |
|
14)
This asphalt or fiberglass composition
roof surface had two or more layers of roofing materials. When this roof is
replaced, recommend a complete "tear off", where all existing layers of roofing
are removed before installing new roofing materials. For 20-year rated
composition shingles, additional layers of material reduce the new roof
material's lifespan as follows:
16-20 years - First roof
12-16 years - Second layer on existing roof
Removing existing roofing
materials will significantly increase the cost of the next roof.
15)
All attic and roof structure sections more
than 10 feet from the access hatch(es) were inaccessible due to possible damage
to insulation, limited height. These areas are excluded from the inspection.
Limitations:
The inspector does not determine the adequacy of firewall
ratings. Requirements for ventilation in garages varies between
municipalities.
Type: Attached,
Garage
Condition of garage: Required repair, replacement and/or evaluation (see comments
below)
Type of garage: Solid
core
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments
below)
Garage vehicle door type: Sectional
Number of vehicle doors:
1
Condition of garage floor:
Appeared serviceable
Condition of
garage interior: Required repair or evaluation (see
comments below)
16) 

The self-closing device on the
garage-dwelling door needs adjustment repair or replacing. This door is intended
to prevent vehicle fumes from entering living spaces and to slow the spread of
fire from the garage to living spaces. A qualified person should evaluate and
make repairs as necessary.
 Photo
14 |
|
17) 

The threshold at the base of the
garage-dwelling door was missing. This door, and a threshold below, are intended
to prevent vehicle fumes from entering living spaces and to slow the spread of
fire from the garage to living spaces. A threshold prevents flammable materials
such as carpeting from being installed under the door. A qualified contractor
should evaluated and repair or replace the threshold as necessary.
 Photo
16 |
|
18) 

Safety containment cables were missing for
one or more vehicle door springs. This is a safety hazard. Safety containment
cables prevent springs from snapping free and causing damage or injury. A
qualified contractor should evaluate and make repairs or replace components as
necessary. For more information on garage door safety issues, visit:
http://www.cpsc.gov/cpscpub/pubs/523.html
http://www.ohdstl.com/safety.html
 Photo
18 |
|
19) 

The walls between the attached garage and
interior living spaces had holes. These surfaces are intended to prevent vehicle
fumes from entering living spaces, and to slow the spread of fire from the
garage to living spaces. A qualified contractor should evaluate and make repairs
as necessary so the attached garage wall and ceiling surfaces that adjoin living
spaces are tightly sealed and fire rated as per standard building practices.
Typically these surfaces require a one-hour fire rating.
 Photo
30 |
|
20) 
Weatherstrip around or at the base of
the garage-dwelling door was missing. A qualified person should repair or
replace as necessary to prevent vehicle fumes from entering living spaces.
 Photo
15 |
|
21) 
Hardware on the garage vehicle door was
loose. A qualified person should evaluate and repair as necessary.
 Photo
19 |
|
22)
Some wall and floor areas were obscured by
and couldn't be evaluated. These areas are excluded from the inspection.
 Photo
17 |
|
23)
Modifications were made, such as
installing interior walls and/or shelving, and limit or reduce the parking space
originally available in the garage.
 Photo
31 |
|
Limitations:
The following items are not included in this inspection:
generator systems, surge suppressors, inaccessible or concealed wiring;
underground utilities and systems; low voltage lighting or lighting on timers or
sensors. Any comments made regarding these items are as a courtesy only. Note
that the inspector does not determine the adequacy of grounding or bonding, does
not determine if this system has an adequate capacity for the client's specific
needs, nor determine if this system has any reserve capacity for additions or
expansion. The inspector does not operate circuit breakers as part of the
inspection, install or change light bulbs, nor determine the operability of
every wall switch.
Electric service condition:
Required repair, replacement and/or evaluation (see
comments below)
Primary service type: Overhead
Service voltage (volts): 120
Service amperage (amps): 200
Primary service overload protection type:
Circuit breakers
Service entrance
conductor material: Aluminum
Main
disconnect rating (amps): Not applicable, no single main
disconnect
System ground: Ground
rod(s) in soil
Condition of main service panel:
Required repair, replacement and/or evaluation (see
comments below)
Condition of sub: Required repair, replacement and/or evaluation (see comments
below)
Location of main service panel #A: Garage
Location of sub panel #B: Below main panel in garage
Location of main
disconnect: Top bank of breakers in main service panel
(split bus)
Branch circuit wiring type: Nonmetallic sheathed
Condition of branch
circuit wiring: Serviceable
Solid
strand aluminum branch circuit wiring present: None
visible
Smoke detectors present: Yes
Carbon monoxide detectors present:
No
24) 


This property had one or more Federal
Pacific Electric brand main service or sub panels that use "Stab-Lok" circuit
breakers (panel #B). Both double and single pole versions of these circuit
breakers are known to fail by not tripping when they are supposed to. This is a
potential but serious fire hazard. Recommend having a qualified electrician
replace any and all Federal Pacific panels. For more information, visit: http://www.inspect-ny.com/fpe/fpepanel.htm
If the Federal
Pacific panel(s) are not replaced, then a qualified electrician should
thoroughly evaluate the panel(s) and make repairs as necessary. Recommend
installing smoke detectors above Federal Pacific panels.
 Photo
22 |
|
25) 


This property had one or more Zinsco brand
main service or sub panels (panel #A). These panels and their circuit breakers
have a variety of problems including:
Bus bars made from aluminum that tend to oxidize and corrode
Breakers that don't trip under normal overload conditions
Breakers that appear to be tripped when they're not
These problems
are a safety hazard due to the risk of fire. Recommend having a qualified
electrician replace any and all Zinsco brand panels.
If the Zinsco
panel(s) are not replaced, then a qualified electrician should thoroughly
evaluate the panel(s) and components within and make repairs as necessary.
Recommend installing smoke detectors above Zinsco panels.
For more
information, visit:
http://www.inspect-ny.com/electric/Zinsco.htm
 Photo
21 |
|
26) 

Some wiring was loose, unsupported, or
inadequately supported (in garage). Standard building practices require
non-metallic sheathed wiring to be trimmed to length, attached to runners or to
solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should
be installed within 12 inches of all enclosures. A qualified, licensed
electrician should evaluate and repair as necessary. For example, trim wire to
length and/or install staples as needed.
 Photo
26 |
|
27) 

Wire splices were exposed due to not being
contained in a covered junction box. For example, in the garage. This is a
safety hazard due to the risk of shock and fire. A qualified electrician should
evaluate and make repairs as necessary. For example, install securely mounted
junction boxes with cover plates where needed to contain wiring splices.
 Photo
23 |
 Photo
27 |
28) 

One or more electric baseboard heaters
were installed with an electric receptacle located above. Insulation on
appliance cords in contact with the heater(s) may be damaged by the heat. This
is a safety hazard due to the risk of shock and fire. A qualified electrician
should evaluate and make repairs as necessary. For example, converting
receptacles to junction boxes, moving receptacles and/or moving baseboard
heaters.
 Photo
33 |
|
29) 

Some electric receptacles had
reverse-polarity wiring, where the hot and neutral wires are reversed. This is a
safety hazard due to the risk of shock. A qualified electrician should evaluate
and make repairs as necessary. (one in garage)
 Photo
20 |
|
30) 

One or more electric receptacles at the
following "wet" locations appeared to have no ground fault circuit interrupter
(GFCI) protection: kitchen, bathroom(s). This is a safety hazard due to the risk
of shock. Recommend having a qualified electrician evaluate to determine if GFCI
protection exists, and if not, repair as necessary. For more information,
visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
 Photo
41 |
|
31) 
One or more bushings were missing from
where wires enter holes in panel #B. This is a safety hazard since the wiring
insulation can be cut or abraded on the metal edge of the hole(s). A qualified
electrician should install bushings where missing.
 Photo
25 |
|
32) 
Energized equipment was exposed at
panel #B due to missing closure covers. This is a safety hazard due to the risk
of shock. A qualified person should repair as necessary.
 Photo
24 |
|
33) 
Based on the age of this structure and
the appearance of existing smoke alarms, the alarms may be older than 10 years
old. According to National
Fire Protection Association, aging smoke alarms don't operate as efficiently
and often are the source for nuisance alarms. Older smoke alarms are estimated
to have a 30% probability of failure within the first 10 years. Newer smoke
alarms do better, but should be replaced after 10 years. Unless you know that
the smoke alarms are new, replacing them when moving into a new residence is
also recommended by NFPA. For more information, visit this article: NFPA urges replacing home smoke alarms after 10 years.
 Photo
32 |
|
34) 
Smoke detectors were missing from
bedrooms. Additional smoke detectors should be installed as necessary so a
functioning one exists in each hallway leading to bedrooms, in each bedroom, and
one each level of the building. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
35) 
This property had one or more fuel
burning appliances and/or an attached garage, and no carbon monoxide detectors
were visible. This is a safety hazard. Recommend installing one or more carbon
monoxide detectors as necessary and as per the manufacturer's instructions. For
more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
Limitations:
The following items are not included in this inspection:
private wells and sewage disposal systems; main, side and lateral sewer lines;
gray water systems; pressure boosting systems; incinerating or composting
toilets; fire suppression sprinkler systems; water softeners, conditioners or
filtering systems; plumbing components concealed within the foundation or
building structure, or in inaccessible areas such as below tubs; underground
utilities and systems; overflow drains for tubs and sinks; backflow prevention
devices. Any comments made regarding these items are as a courtesy only. Note
that the inspector does not operate water supply or shut-off valves due to the
possibility of valves leaking or breaking when operated. The inspector does not
test for lead in the water supply, the water pipes or solder, does not determine
if plumbing and fuel lines are adequately sized, and does not determining the
existence or condition of underground or above-ground fuel
tanks.
Condition of service and main line: Appeared serviceable
Location of main water
meter: Hatch in driveway
Location
of main water shut: Not located
Water service: Public
Water pressure (psi): 65 psi
Service pipe material: Not
determined
Condition of supply lines: Appeared serviceable
Supply pipe material:
Copper
Condition of waste lines:
Appeared serviceable
Waste pipe
material: Plastic
36) 
One or more outside faucets were missing
backflow
prevention devices. These devices reduce the likelihood of polluted or
contaminated water entering the potable water supply. This condition can occur
when an outside faucet is left in the "on" position with a hose connected and
the sprayer head turned off. When pressure in the system fluctuates, water can
be drawn back into the water supply pipes from the building. If a chemical
sprayer is being used with the hose, those chemicals can enter the water supply
pipes.
Recommend installing backflow prevention devices on all exterior
hose bibs where missing. They are available at most home improvement stores and
are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
 Photo
4 |
|
37) 
Copper water supply pipes in buildings
built prior to 1986 may be joined with solder that contains lead. Lead is a
known health hazard, especially for children. Laws were passed in 1985
prohibiting the use of lead in solder, but prior to that solder normally
contained about 50 percent lead. The client should be aware of this, especially
if children will be living in this structure. Evaluating for the presence of
lead in this structure is not included in this inspection. The client should
consider having a qualified lab test for lead, and if necessary take steps to
reduce or remove lead from the water supply. Various solutions such as these may
be advised:
Flush water taps or faucets. Do not drink water that has been sitting in the
plumbing lines for more than six hours.
Install appropriate filters at points of use.
Use only cold water for cooking and drinking. Hot water dissolves lead more
quickly than cold water.
Use bottled or distilled water.
Treat well water to make it less corrosive.
Have a qualified plumbing contractor replace supply pipes and/or plumbing
components as necessary.
For more information visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
http://www.epa.gov/safewater/lead/index.html
 Photo
45 |
|
38)
Most water supply pipes in the
crawl space were uninsulated. Recommend insulating pipes as per standard
building practices for better energy efficiency and to prevent water pipes from
freezing.
 Photo
46 |
|
39)
A drain line at the west side
of the crawl space was sagging. It mat not drain properly. A qualified person
should repair as necessary. For example, install one or more Straps,
 Photo
44 |
|
40)
The inspector was not able to find the
main water shut-off valve. The client should consult with the property owner to
determine if a shut-off valve exists, find it themselves, or hire a qualified
plumber if necessary to find it. If no shut-off valve is found for the
structure, then recommend having a qualified plumber install one to more easily
allow the water supply to be turned off in the event of an emergency, such as
when a supply pipe bursts.
41)
One or more outside faucets (one on west
side) were not evaluated due to their being winterized with covers, and are
excluded from this inspection.
Limitations:
The following items are not included in this inspection:
solar water heating systems; circulation systems. Any comments made regarding
these items are as a courtesy only. Note that the inspector does not provide an
estimate of remaining life on water heaters, does not determine if water heaters
are appropriately sized, or perform any evaluations that require a pilot light
to be lit.
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: 2002
Energy source: Electricity
Capacity (in gallons):
50
Manufacturer: U.S. Craftmaster
Location of water heater:
Garage
42) 

The temperature/pressure relief valve
drain line was sloped upwards. This is a potential safety hazard due to the risk
of explosion from restricted flow. A qualified plumber should evaluate and
repair as necessary so the drain line complies with the temperature-pressure
relief valve manufacturer's installation instructions. For more information,
visit: http://www.reporthost.com/_docs/TPvalve.pdf
 Photo
28 |
|
43) 
The water heater did not have seismic
straps or struts installed. This is a potential safety hazard. Leaks may also
occur in water supply pipes. A qualified person should install seismic straps or
struts as necessary and as per standard building practices.
44)
The temperature-pressure
relief valve was leaking. A qualified plumbing contractor should replace this
valve.
 Photo
10 |
|
45)
A permanently installed insulated jacket
was installed on the water heater. It obscured the manufacturer's information
label and most of the water heater. The inspector was unable to fully evaluate
the water heater.
 Photo
29 |
|
Limitations:
The following items are not included in this inspection:
humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired
heat systems; thermostat or temperature control accuracy and timed functions;
heating components concealed within the building structure or in inaccessible
areas; underground utilities and systems; safety devices and controls (due to
automatic operation). Any comments made regarding these items are as a courtesy
only. Note that the inspector does not provide an estimate of remaining life on
heating system components, does not determine if heating systems are
appropriately sized, or perform any evaluations that require a pilot light to be
lit. It is beyond the scope of this inspection to determine if furnace heat
exchangers are intact and free of leaks.
Condition of
heating system: Required repair, replacement and/or
evaluation (see comments below)
Heating type:
Radiant, Baseboard
Fuel type:
Electric
46) 
One or more electric baseboard heaters
were inoperable (bathroom and NW bedroom). A qualified person should evaluate
and repair or replace as necessary.
Limitations:
The following items are not included in this inspection:
coal stoves, gas logs, chimney flues (except where visible). Any comments made
regarding these items are as a courtesy only. Note that the inspector does not
determine the adequacy of drafting or sizing in fireplace and stove flues, nor
determine if prefabricated or zero clearance fireplaces are installed in
accordance with the manufacturer's specifications. The inspector does not
perform any evaluations that require a pilot light to be lit.
Location #A: Wood store in living
room
Stove type: Freestanding
Fuel type: Wood
Condition of chimneys: Appeared serviceable
Chimney type:
Metal
47) 

A significant amount of creosote (1/8 inch
or more) was visible in flue(s) at location # A. A qualified contractor should
inspect, clean, and repair if necessary now and annually in the future.
 Photo
13 |
|
Limitations:
The following items are not included in this inspection:
free-standing or portable appliances such as dishwashers, trash compactors,
refrigerators, freezers, ice makers; specialty appliances such as hot water
dispensers, water filters and trash compactors; appliance timers, clocks, cook
functions, self and/or continuous cleaning operations, thermostat or temperature
control accuracy, and lights. Any comments made regarding these items are as a
courtesy only. Note that the inspector does not provide an estimate of the
remaining life of appliances, and does not determine the adequacy of operation
of appliances such as dishwashers, garbage disposals, trash compactors, ovens,
broilers, etc.
Condition of counters: Appeared serviceable
Condition of cabinets:
Appeared serviceable
Condition of
sinks and related plumbing: Appeared
serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type:
Electric
Condition of
refrigerator: Appeared serviceable
Limitations:
The following items are not included in this inspection:
overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam
generators, clothes washers, clothes dryers. Any comments made regarding these
items are as a courtesy only. Note that the inspector does not determine the
adequacy of washing machine drain lines, washing machine catch pan drain lines,
or clothes dryer exhaust ducts. The inspector does not operate water supply or
shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the
possibility of valves leaking or breaking when operated. The inspector does not
determine if shower pans or tub and shower enclosures are water tight, or
determine the completeness or operability of any gas piping to laundry
appliances.
Location #A: Hallway
bath
Location #B: Laundry area in
garage
Condition of counters: Appeared serviceable
Condition of cabinets:
Appeared serviceable
Condition of
sinks and related plumbing: Appeared
serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and
related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments
below)
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments
below)
48) 
The exhaust fan at location #A was
noisy or vibrates excessively. Moisture may accumulate as a result. A qualified
person should evaluate and repair or replace as necessary.
49) 
The shower diverter valve at location #A
was defective. A significant amount of water came out of the bathtub spout when
the shower was turned on. Water will be wasted as a result. A qualified plumber
should evaluate and replace components or make repairs as necessary.
 Photo
42 |
|
50)
The sink drain at location #A
used flexible drain pipe. This type of drain pipe is more likely to clog than
smooth wall pipe. Recommend having a qualified plumber replace this pipe with
standard plumbing components (smooth wall pipe) to prevent clogged drains.
 Photo
40 |
|
Limitations:
The following items are not included in this inspection:
security, intercom and sound systems; communications wiring; central vacuum
systems; elevators and stair lifts; sources of obnoxious odors; cosmetic
deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and
coverings, or in equipment; deficiencies relating to interior decorating; low
voltage and gas lighting systems. Any comments made regarding these items are as
a courtesy only. Note that the inspector does not evaluate any areas or items
which require moving stored items, furnishings, debris, equipment, floor
coverings, insulation or similar materials. The inspector does not test for
asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any
other toxic substance. Some items such as window operability are tested on a
sampled basis. The client should be aware that paint may obscure wall and
ceiling defects, floor coverings may obscure floor defects, and furnishings may
obscure wall, floor and floor covering defects. If furnishings were present
during the inspection, recommend a full evaluation of walls, floors and ceilings
that were previously obscured when possible. Determining the cause of odors is
not within the scope of this inspection.
Exterior door
material: Wood, Sliding glass
Condition of exterior entry doors: Appeared
serviceable
Condition of interior doors: Appeared serviceable
Type of windows:
Aluminum, Multi, Sliding
Condition of windows: Required repair,
replacement and/or evaluation (see comments below)
Wall
type or covering: Drywall
Condition of walls: Appeared
serviceable
Ceiling type or covering: Drywall, Acoustic spray
Condition of ceilings:
Appeared serviceable
Flooring
type or covering: Carpet, Vinyl
Condition of flooring: Appeared
serviceable
51) 

Many ceiling areas in this structure had
ceiling texture possibly installed prior to 1980. This material may contain
asbestos, which is a known carcinogen and poses a health hazard. Laws were
passed in the United States in 1978 prohibiting use of asbestos in residential
structures, but stocks of existing materials have been known to be used for some
time thereafter. The client may wish to have this ceiling material tested by a
qualified lab to determine if it does contain asbestos.
In most cases,
when the material is intact and in good condition, keeping it encapsulated with
paint and not disturbing it may reduce or effectively eliminate the health
hazard. If the client wishes to remove the material, or plans to disturb it
through remodeling, they should have it tested by a qualified lab and/or consult
with a qualified industrial hygienist or asbestos abatement specialist. For more
information, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/453.html
 Photo
34 |
|
52) 
Screens in some windows are deteriorated.
A qualified person should evaluate and repair or replace as necessary.
 Photo
35 |
|
53)
Deadbolts on one or more
exterior doors were inoperable (handle spun freely at front door). A qualified
person should repair as necessary.
 Photo
39 |
|
54)
Lock mechanisms on many
windows were damaged. A qualified person should repair as necessary.
 Photo
43 |
|
55)
Vinyl flooring was
deteriorated in some (kitchen) areas. A qualified person should repair or
replace as necessary.
 Photo
38 |
|
Limitations:
This report only includes findings from accessible and
visible areas on the day of the inspection. In addition to the inaccessible
areas documented in this report, examples of other inaccessible areas include:
sub areas less than 18 inches in height; attic areas less than five feet in
height, areas blocked by ducts, pipes or insulation; areas where locks or
permanently attached covers prevent access; areas where insulation would be
damaged if traversed; areas obscured by vegetation. All inaccessible areas are
subject to infestation or damage from wood destroying organisms. The inspector
does not move furnishings, stored items, debris, floor or wall coverings,
insulation, or other materials as part of the inspection, nor perform
destructive testing. Wood destroying organisms may infest, reinfest or become
active at anytime. No warranty is provided as part of this
inspection.
Visible evidence of active wood destroying
insects: No
Visible evidence of
active wood decay fungi: No
Visible evidence of past wood destroying insects: No
Visible evidence of past wood decay fungi:
No
Visible evidence of damage by
wood destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to
wood destroying organisms: Yes
FOLLOW-UP INSPECTION
POLICY
Generally we discourage follow-up inspections for these
reasons
1. Quality of repairs
If repairs are made to a property
based on the results of an inspection, the work should be performed by qualified
contractors, not the seller. By qualified, we mean licensed, bonded,
state-certified where applicable and with a reasonable amount of experience.
Contractors providing repairs should provide legible documentation in the form
of work orders and/or receipts. If repairs are made in this way, then there's
generally no need for a follow-up inspection. Additionally, it may be better to
negotiate a lower price on your home and have repairs made by contractors you
choose rather than the seller making repairs as cheaply as
possible.
2. Pest inspections required for some follow-up
inspections
On occasion, some follow-up inspections may require a
complete, new structural pest inspection. Examples include:
Evaluating a crawl space after carpenter ant infestation was found
Evaluating numerous items throughout a structure after a significant amount
of time has passed (original inspection in winter, follow-up in
summer)
Our fees for follow-up inspections are as follows:
Follow-up inspection: $150
Follow-up inspections with a structural pest (WDO/WDI) inspection:
$250
Additional charges usually apply for travel outside of
Kitsap County
SCOPE AND LIMITATIONS OF THIS INSPECTION
This inspection is
limited to a visual observation of the exposed and readily accessible areas of
the home. The concealed and inaccessible areas are not included. The following
locations are considered inaccessible due to limited height and excluded from
this inspection unless otherwise stated:
Crawl space areas less than 18 inches in height
Attic spaces less than 5 feet in height
Spaces under outdoor decks less than 5 feet high
Observation includes
operation of the systems or components by means of the normal user controls.
Dismantling of equipment, and destructive testing is not included. Some specific
items are also excluded, and these are listed in the following section. If you
feel there is a need for evaluation of any of these items, then you will need to
arrange for specific inspections.
Items not Included
- Recreational, leisure, playground or decorative equipment or appliances
including but not limited to pools, hot tubs, saunas, steam baths, landscape
lighting, fountains, shrubs, trees, and tennis courts;
- Cosmetic conditions (wallpapering, painting, carpeting, scratches,
scrapes, dents, cracks, stains, soiled or faded surfaces on the structure or
equipment, soiled, faded, torn, or dirty floor, wall or window coverings
etc.);
- Noise pollution or air quality in the area;
- Earthquake hazard, liquefaction, flood plain, soil, slide potential or any
other geological conditions or evaluations;
- Engineering level evaluations on any topic;
- Existence or non-existence of solder or lead in water pipes, asbestos,
hazardous waste, radon, urea formaldehyde urethane, lead paint or any other
environmental, flammable or toxic contaminants or the existence of water or
airborne diseases or illnesses and all other similar or potentially harmful
substances (although the inspector may note the possible existence of asbestos
in ceiling texture and furnace duct tape);
- Zoning or municipal code (e.g. building, fire, housing (existing
buildings), mechanical, electrical, plumbing, etc. code) restrictions or other
legal requirements of any kind;
- Any repairs which relate to some standard of interior decorating;
- Cracked heat exchangers or similar devices in furnaces;
- Any evaluation which requires the calculation of the capacity of any
system or item that is expected to be part of the inspection. Examples include
but are not limited to the calculation of appropriate wattage or wiring of
kitchen appliances, appropriate sizing of flues or chimneys, appropriate
ventilation to combustion-based items (e.g. furnaces, water heaters,
fireplaces etc.), appropriate sizing, spacing and spanning of joists, beams,
columns, girders, trusses, rafters, studs etc., appropriate sizing of plumbing
and fuel lines, etc.;
- Washers and dryers;
- Circuit breaker operation;
- Specialty evaluations such as private sewage, wells, solar heating
systems, alarms, intercom systems, central vacuum systems, wood and coal
stoves, pre-fab and zero clearance fireplaces, space heaters, sprinkler
systems, gas logs, gas lights, elevators and common areas unless these have
been specifically added to the inspection description above but only to the
degree that the inspector is capable of evaluating these items;
- Items that are not visible and exposed including but not limited to
concealed wiring, plumbing, water leaks, under bathtubs and shower stalls due
to faulty pans or otherwise, vent lines, duct work, exterior foundation walls
(below grade or covered by shrubs or wall/paneling, stored goods etc.) and
footings, underground utilities, and systems and chimney flues;
- Evaluations involving destructive testing;
- Evaluation which requires moving personal goods, debris, furniture,
equipment, floor covering, insulation or like materials;
- Design problems and adequacy or operational capacity, quality or
suitability;
- Fireplace drafting;
- To prevent damages to units, air conditioning when outside temperature
below 60 degrees F or if the unit has not been warmed up or on for at least 24
hours prior to inspection;
- Any evaluation which would involve scraping paint or other wall
coverings;
- Heating system accessories (e.g. humidifiers, electronic air cleaners
etc.);
- Legal description of property such as boundaries, egress/ingress,
etc.;
- Quality of materials;
- Conformance with plan specifications or manufacturers specifications;
- Flood conditions or plains;
- Any other characteristics or items which are generally not included in a
building inspection report on a regular basis.
As a part of our
service, we sometimes provide approximate, cost of repair estimates for
particular items. These estimates should be considered as background information
only. It is beyond the scope of this inspection and report to supply you with
accurate repair costs. Such estimates should be supplied by contractors who
specialize in this type of work. Our estimates should be used only as
guidelines. If you intend to negotiate the price of this property based on
defects found during this inspection, we strongly suggest you obtain one or more
written bids from a licensed contractor(s). It is a conflict of interest for All
Point Home Inspections to recommend any specific contractor.
Evaluations
are made as to the present age, and remaining economic life of an item, i.e.
water heaters, roofs, plumbing, furnaces, etc. These evaluations are based on
visual observation, industry averages and prior experience. THEY ARE NOT OFFERED
AS A WARRANTY OR CERTIFICATION OF REMAINING LIFE.
Disclaimer
In
some cases we may recommend your consulting a specialist such as a structural
engineer or licensed electrician. Hiring a specialist can be a prudent means of
providing some protection of your financial investment in this property. WE DO
NOT MAKE ANY TYPE OF WARRANTY OR GUARANTEE AS TO THE CONDITION OF THE PROPERTY.
SOME THINGS MAY REMAIN HIDDEN OR BECOME DEFECTIVE AFTER THE INSPECTION. IT IS
NOT POSSIBLE TO DETECT EVERY DEFECT WITHIN A BUILDING DURING THE COURSE OF A
GENERAL INSPECTION. THIS REPORT SHOULD BE USED IN CONJUNCTION WITH, AND NOT A
REPLACEMENT FOR , A PRE-CLOSING WALK-THROUGH BY THE CLIENT.
THIS INSPECTION
IS NOT AN INSURANCE POLICY AGAINST HIDDEN DEFECTS, OR CONDITIONS THAT ARE NOT
VISIBLE AND READILY APPARENT AT THE TIME OF INSPECTION.
THE COST OF THIS
INSPECTION DOES NOT ENTITLE YOU TO ANY TYPE OF PROTECTION FROM HIDDEN FLAWS AND
DEFECTS. THIS INSPECTION DOES NOT TRANSFER YOUR ULTIMATE RESPONSIBILITY TO ALL
POINT HOME INSPECTIONS.