Inspector: Scott Knudson
NACHI ID NUMBER: NACHI09070813

       

Home Inspection Report
Client(s): Joe Smith
Property address: 1234 Elm Street
Anytown, USA
Inspection date: Tuesday, August 04, 2009
This report published on Saturday, February 11, 2012 1:06:47 PM PST

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Click here for a glossary of building construction terms. Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Basement
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 1017
Inspector's name: Scott Knudson
Structures inspected: House
Type of building: Single Family
Age of building: 20 to 25 years old
Time started: 15:30
Time finished: 18:30
Inspection Fee: 275.00
Payment method: Invoiced, Escrow
Occupied: No
Weather conditions: Clear
Temperature: Hot
Ground condition: Dry
Front of structure faces: North
Main entrance faces: North
Foundation type: Unfinished basement
The following items are excluded from this inspection: Irrigation system, Water softener system
1) Safety, Repair/Replace - This property has one or more fuel burning appliances, and no carbon monoxide alarms are visible. This is a safety hazard. Recommend installing one or more carbon monoxide alarms as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
 
Exterior Return to table of contents
Footing material: Not visible
Foundation material: Poured in place concrete
Apparent wall structure: Wood frame
Wall covering: Brick veneer, Metal
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel, Sliding glass
2) Safety, Repair/Replace, Evaluate - One or more trip hazards were found in sidewalk and/or patio sections due to cracks, settlement and/or heaving. A qualified contractor should evaluate and repair or replace sidewalk and/or patio sections as necessary to eliminate trip hazards.

Photo 10  
Trip hazard located near garage vehicle door.
 

3) Safety, Repair/Replace, Evaluate - One or more sets of stairs are wobbly. A qualified contractor should evaluate and repair as necessary, such as installing additional supports and/or diagonal bracing.

Photo 15  
Rear steps are wobbly and should be painted or stained to improve lifespan.
 

4) Safety, Repair/Replace - One or more flights of stairs with more than two risers have no handrail installed. This is a safety hazard. A qualified contractor should install graspable handrails that your hand can completely encircle at stairs where missing, and as per standard building practices.

Photo 9  
Handrail recommended on steps with 3 or more risers.
 

5) Repair/Replace - One or more fence gates are difficult to open, close and/or latch, or are damaged and/or deteriorated. Repairs should be made as necessary, and by a qualified contractor if necessary, so gates operate easily.

Photo 12  
East gate needs repair for normal operation.
 

6) Repair/Replace - The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.

Photo 20  
Recommend improving grade of slope around home in various locations.
 

7) Repair/Replace - One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

Photo 11  
Downspout extensions recommended.
 

8) Repair/Replace - One or more outside faucets are missing handles. Recommend installing handles where missing.

Photo 18  
Hose bib missing handle on Southwest corner of home.
 

9) Repair/Maintain - Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.

Photo 14  
Recommend cutting back trees from home.
 

10) Maintain - Trees and/or shrubs are in contact with or are close to the roof edge(s) in one or more areas. Damage to the roof may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.

Photo 17  
Recommend cutting back trees from home.

Photo 21  
Recommend cutting back trees from home.

11) Maintain - Recommend cleaning rear steps and treating with a preservative claiming to waterproof, block ultraviolet light, and stop mildew. Consumer Reports recommends these products:

  • Cabot Decking Stain and PTW Stain
  • Olympic Water Repellent Deck Stain
  • Thompson's House and Deck Stain
  • Wolman PTW Deck Stain
  • Akzo Sikkens Cetol DEK
  • Benjamin Moore Moorwood Clear Wood Finish
  • DAP Woodlife Premium
  • Olympic Natural Look Protector Plus
    12) Evaluate - One or more light fixtures (rear garage entry and front entry) appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.
    13) Comment - Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
     
    Roof Return to table of contents
    Roof inspection method: Traversed
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 20 to 25 years old
    Gutter & downspout material: Aluminum
    Roof ventilation: Adequate
    14) Repair/Replace - One or more "rubber boot" flashings are damaged or deteriorated and may result in leaks or vermin intrusion. A qualified contractor should replace flashings where necessary.

    Photo 23  
    Rubber boot flashing around plumbing vents on roof are cracking and should be repaired to avoid roof leaks.
     

    15) Maintain - Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

    Photo 22  
    Gutters need cleaning.
     

    16) Maintain - Trees and/or shrubs are in contact with or are close to the roof edge(s) in one or more areas. Damage to the roof may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.

    Photo 7  
    Recommend cutting back trees from home.
     
     
    Garage Return to table of contents

    17) Safety, Repair/Replace, Evaluate - One or more wall and/or ceiling surfaces between the attached garage and interior living spaces have gaps, holes, or missing or inadequate surface materials. These surfaces are intended to prevent vehicle fumes from entering living spaces, and to slow the spread of fire from the garage to living spaces. A qualified contractor should evaluate and make repairs as necessary so the attached garage wall and ceiling surfaces that adjoin living spaces are tightly sealed and fire rated as per standard building practices. Typically these surfaces require a one-hour fire rating.

    Photo 25  
    Garage firewall has been breached.

    Photo 26  
    Garage firewall is negated due to deteriorating seams.

    18) Safety, Repair/Replace, Evaluate - The automatic door closing device (sprung hinges, etc.) on the garage-house door needs adjustment, repair or replacing. The door doesn't close and latch easily and/or completely via the force of the automatic closing device. This door is intended to prevent vehicle fumes from entering living spaces and to slow the spread of fire from the garage to living spaces. A qualified contractor should evaluate and make repairs as necessary.
    19) Safety, Repair/Replace, Evaluate - The auto-reverse mechanism on the vehicle door opener is inoperable or requires too much force to activate. This is a safety hazard, especially for small children. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
    http://www.cpsc.gov/cpscpub/pubs/523.html
    http://www.ohdstl.com/safety.html

    20) Safety, Repair/Replace - No infrared "photo eye" devices are installed for the vehicle door's electric door opener. They've been required on all vehicle door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit:
    http://www.cpsc.gov/cpscpub/pubs/523.html
    http://www.ohdstl.com/safety.html

    21) Safety, Repair/Replace - One or more flights of stairs with more than two risers have no handrail installed. This is a safety hazard. A qualified contractor should install graspable handrails that your hand can completely encircle at stairs where missing, and as per standard building practices.

    Photo 24  
    Handrail recommended on steps with 3 or more risers.
     

    22) Repair/Replace - The weatherstrip around one or more exterior entry doors is missing and/or deteriorated. Weatherstrip should be installed where missing and/or replaced where deteriorated, and by a qualified contractor if necessary.
    23) Comment - The interior perimeter of the garage is excluded from this inspection due to lack of access from stored items.
     
    Attic Return to table of contents
    Inspection method: Viewed from hatch
    Roof structure type: Trusses
    Ceiling structure: Trusses
    Insulation material: Cellulose loose fill
    Insulation depth: 10 to 15 inches
    Insulation estimated R value: 35
    24) Comment - Some attic areas were inaccessible due to lack of permanently installed walkways, the possibility of damage to insulation, low height and/or stored items. These areas are excluded from this inspection.
    25) Comment - No recommendations.

    Photo 46  
    Attic.
     
     
    Electric service Return to table of contents
    Primary service type: Underground
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 100
    Service voltage (volts): 120/240
    Location of main service switch: South side of home
    Location of sub panels: South exterior
    Location of main disconnect: Middle
    Service entrance conductor material: Copper
    System ground: Cold water supply pipes, Copper
    Main disconnect rating (amps): 100
    Branch circuit wiring type: Copper
    Solid strand aluminum branch circuit wiring present: No
    Smoke detectors present: Yes
    26) Comment - No recommendations.

    Photo 16  
    Main eletrical panel on South side of home.
     
     
    Water heater Return to table of contents
    Estimated age: 0 to 5 years old
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Manufacturer: Rheem
    Model: 22V40-36F1
    Water temperature (degrees Fahrenheit): 105
    27) Safety, Repair/Replace - The water heater does not have seismic straps or struts installed. This is a potential safety hazard since movement can cause leaks in the gas supply lines or damage wiring. Leaks may also occur in water supply pipes. A qualified contractor should install seismic straps or struts as necessary and as per standard building practices.

    Photo 35  
    Water heater.
     

    28) Safety, Repair/Replace - No drain line is installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

    Photo 38  
    Extension tube missing on water heater.
     

    29) Repair/Maintain - Drafter hood should be better secured to unit and recommend replacing gas line with flexible gas line.

    Photo 37  
    Recommend updating gas connection to a flexible gas connection.

    Photo 40  
    Water heater draft hood should be better secured to unit.
     
    Heating and cooling Return to table of contents
    Estimated age: 20 to 25 years old
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air, Standard efficiency
    Primary A/C energy source: N/A
    Primary Air conditioning type: N/A
    Distribution system: Sheet metal ducts
    Manufacturer: Whirlpool
    Model: NUGG075DF01
    Filter location: At the base of the furnace
    Last service date: Unknown
    30) Repair/Maintain, Evaluate - The last service date of this system appears to be more than two years ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than two years ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed every few years in the future, or as per the contractor's recommendations.
    31) Maintain - Air handler filter(s) are dirty and should be replaced now. They should be checked monthly in the future and replaced as necessary.
    32) Maintain - Air handler filter(s) should be checked monthly in the future and replaced or washed as necessary.
    33) Evaluate - The furnace or boiler flame(s) "roll out" of the combustion chamber. This is a fire hazard due to the possibility of excessive heat damaging heating components, controls and wiring. A qualified heating and cooling contractor should evaluate and repair as necessary.
    34) Monitor, Comment - The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.

    Photo 36  
    Furnace.
     
     
    Plumbing and laundry Return to table of contents
    Water pressure (psi): 75
    Location of main water shut-off valve: Front wall of Basement
    Location of main water meter: Unknown
    Location of main fuel shut-off: West side of home
    Water service: Public
    Service pipe material: Copper
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
    35) Repair/Replace, Evaluate - Pin holes and/or corrosion were visible on one or more areas of copper water supply pipes. This most often occurs with acid water with a pH of less than 6.5. Leaks may result because of this. A qualified plumber should evaluate and replace water supply components as necessary. The client(s) should consult with a qualified plumber regarding the possibility of acidic water, and what solutions may be available to neutralize the pH.

    Photo 39  
    Minor corrosion noted on supply piping near main water shut off.
     

    36) Repair/Replace - The washing machine is installed over a finished living space and has no catch pan or drain installed. These are not commonly installed, but they are recommended to prevent water damage to finished interior spaces below if or when the washing machine leaks, overflows or is drained. Recommend having a qualified contractor install both a catch pan and drain.

    Photo 41  
    Laundry room.
     

    37) Evaluate - The inspector was not able to find the water meter. Recommend that the client(s) attempt to find the water meter by consulting with the property owner(s), searching for it themselves, or consulting with the local water municipality. It is especially important to find the meter if no main shut-off valve is found because the meter may be the only way to turn off the water supply in the event of an emergency, such as when a supply pipe bursts.
     
    Basement Return to table of contents
    Insulation material underneath floor above: None visible
    Pier or support post material: Wood, Bearing wall
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    38) Safety, Repair/Replace, Evaluate - Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 32  
    Abandoned wiring noted in basement.

    Photo 33  
    Junction box in basement needs cover.

    39) Safety, Minor Defect - Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 45  
    Outlets in basement bedroom need covers.
     
     
    Kitchen Return to table of contents

    40) Safety, Repair/Replace, Evaluate - One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
    41) Safety, Repair/Replace, Evaluate - One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
    42) Comment - One or more kitchen appliances appear to be near, at, or beyond their intended service life of 10 to 15 years. Recommend budgeting for replacements as necessary.

    Photo 42  
    Kitchen.
     
     
    Bathrooms Return to table of contents

    43) Repair/Replace, Evaluate - One or more sink drains (master bathroom) have an active leak. For example, at pipe fittings and/or junctions between pipe and sink. A qualified plumber should evaluate and repair as necessary.

    Photo 30  
    Sink waste pipe leaks in master bathroom.
     

    44) Repair/Replace - One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
    45) Repair/Replace - One or more bathtub drains (upstairs hallway bathroom) are clogged or drain slowly. Drain(s) should be cleared as necessary, and by a qualified plumber if necessary.
     
    Interior rooms Return to table of contents

    46) Safety, Repair/Replace, Evaluate - One or more electric receptacles (bedrooms) have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
    47) Safety, Repair/Replace - Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
    http://www.google.com/search?q=old+smoke+alarms

    48) Repair/Replace, Evaluate - Screen(s) in one or more windows are missing. The client(s) should ask the property owner(s) about this. Screens are often removed for window cleaning and they may be stored somewhere. If not, then recommend installing screens where missing.
    49) Repair/Replace, Evaluate - The lock mechanisms on one or more sliding glass doors are inoperable and/or difficult to operate. A qualified contractor should evaluate and repair as necessary.

    Photo 28  
    Rear sliding door locked needs repair.
     

    50) Repair/Replace, Evaluate - Seals between double-pane glass in one or more sliding glass doors appear to have failed based on condensation or stains between the panes of glass. A qualified contractor should evaluate and replace glass where necessary.

    The client(s) should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Glass doors or windows other than those that the inspector identified may also have failed seals and need glass replaced too.

    51) Repair/Replace - Screen(s) in one or more windows are torn or have holes in them. Screens should be replaced where necessary.
    52) Evaluate - One or more light fixtures (stairway) appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.
     

    Photo 8  
    Window well covers recommended for safety and to keep water and debris out.

    Photo 19  
    Window well covers recommended for safety and to keep water and debris out.

    Photo 27  
    Garage.

    Photo 29  
    Restricted access to gas meter shut off. Recommend improving access.

    Photo 31  
    Older thermostat. Recommend updating to digital set back thermostat for improved energy savings.

    Photo 34  
    Floors cracks common in basements noted.

    Photo 43  
    Master bathroom.

    Photo 44  
    Main floor hallway bathroom.

     
    All of our inspections require a signed inspection agreement signed by the client. If this agreement is not signed prior to your receiving the report, it is important to understand that we take no liability whatsoever for information contained in this report. Our legal responsibilities and liabilities are described within the inspection agreement and only apply once the agreement is signed and we have a copy in our office. THIS REPORT IS NOT VALID UNLESS WIND RIVER PROPERTY LLC HAS SIGNED AGREEMENT ON FILE IN ITS OFFICE. All components designated for inspection in the ASHI Standards of Practice are inspected, except as may be noted in the “Limitations of Inspection” sections within this report. It is the goal of the inspection to put a home buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered a guarantee or warranty of any kind. This inspection is visual only. A representative sample of building components are viewed in areas that are accessible at the time of the inspection. No destructive testing or dismantling of building components is performed. Please refer to the pre-inspection contract for a full explanation of the scope of the inspection.