| Home Inspection Report | |
| Client(s): | Gary Wolf |
| Property address: | 413 S. 4th Street |
| Inspection date: | Sunday, April 30, 2006 |
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
![]() | Safety | Poses a risk of injury or death |
![]() | Major defect | Correction likely involves a significant expense |
![]() | Repair/Replace | Recommend repairing or replacing |
![]() | Repair/Maintain | Recommend repair and/or maintenance |
![]() | Maintain | Recommend ongoing maintenance |
![]() | Evaluate | Recommend evaluation by a specialist |
![]() | Monitor | Recommend monitoring in the future |
![]() | Comment | For your information |
Click here for a glossary of building construction terms.
Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.aspTable of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Crawl space
Basement
Kitchen
Bathrooms
Interior rooms
| General information | Return to table of contents |

Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygenists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:| Exterior | Return to table of contents |
No ground fault circuit interrupters on exterior of the house, all outlet that are accessible from grade level should have GFCI installed.


One or more major cracks (more than 3/4 inch wide) were found in the foundation. These appear to be a structural concern, and may indicate that settlement is ongoing. The client(s) are strongly advised to hire qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:
Vent area on the back side of the house is damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.
![]() Photo 1 Vent enclosure is pulled away from the roof, so it's possible that moisture and animals could get in and cause damage.
|
One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.
![]() Photo 3 Down spout has no extension to get water away from the footing.
Also the crawl space vent , fits loose and there is no screen behind it. |
One or more outside faucets aren't anchored securely to the structure's exterior. Fasteners should be installed or replaced as necessary so faucets are securely anchored to prevent stress on plumbing supply lines and possible leaks.

One or more moderate cracks (1/8 inch to 3/4 inch) were found in the foundation. These may be a structural concern, or an indication that settlement is ongoing. The client(s) should consider hiring qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:
Soil is in contact with or less than six inches from siding and/or trim. This is a conducive condition for wood destroying insects and organisms. Soil should be graded and/or removed as necessary so there are at least six inches of space between the siding and trim and the soil below.
![]() Photo 2 Bottom plate is at ground level.
|
Decking boards are spaced closer together than 3/8 inch with accumulated organic debris (leaves, fir needles, etc.). This is a conducive condition for wood destroying insects and organisms. Debris should be cleaned as necessary to prevent accumulation and resultant rot. If or when the deck boards are replaced, recommend spacing boards so they're at least 3/8 inch apart to allow debris to fall through the cracks rather than accumulate in them.
![]() Photo 6 Deck needs some attention where it is sagging.
|
Window glazing putty at one or more windows is missing and/or deteriorated. Putty should be replaced and/or installed where necessary. For more information on replacing window putty, visit: http://www.oldhouseweb.com/stories/Detailed/12216.shtml
![]() Photo 4 Trim needs sanding and painting.
|
| Roof | Return to table of contents |


One or more plumbing vent pipes terminate less than one foot from vertical surfaces such as exterior walls. Debris or snow is more likely may block these openings, and may result in sewer gases entering living spaces. A qualified contractor should evaluate and make repairs as necessary so vent pipes terminate at least one foot from vertical surfaces.

Composition tabbed shingles are installed on one or more roof sections with a slope less than 3/12 (three inches rise for every 12 inches run). Most shingle manufacturers won't warranty composition shingles if used on a roof with a slope less than 3/12. At a minimum, the client(s) should consult with a qualified roofing contractor regarding this and monitor these roof section(s) and interior spaces below for leaks in the future. Ideally, or if leaks occur, a qualified roofing contractor should replace the roof surface with materials intended for low slopes such as a "torch down" roof.
![]() Photo 14 Flashing is coming loose needs to be fixed. Also shows an area where trim needs sanding and painting.
|
| Garage | Return to table of contents |

The garage-house door isn't equipped with an automatic closing device such as sprung hinges. This door should close and latch automatically to prevent vehicle fumes from entering living spaces and/or to slow the spread of fire from the garage to living spaces. A qualified contractor should install automatic closing device(s) as necessary, and as per standard building practices, so this door closes and latches automatically.

No infared "photo eye" devices are installed for the vehicle door's electric door opener. They've been required on all vehicle door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html

No ground fault interrupter circuits were found in the garage. GFIC should be installed for all outlets except ones where a freezer or other appliance is plugged in.
Garage apron is broken up and there are loose pieces of concrete on the floor.
Much of the garage, include areas around the interior perimeter and in the center are excluded from this inspection due to lack of access from stored items.
| Attic | Return to table of contents |


Paper facing on batt insulation is oriented towards open spaces, rather than against interior space surfaces. This occurs when newer, fiberglass batt insulation with paper facing on one side is installed backwards or upside down, or when older batt insulation wrapped on both sides with paper is installed. The paper facing is flammable. Newer insulation usually has a warning label indicating this on the facing.

What appears to be vermiculite insulation was found in the attic. This material may contain asbestos, which is a known carcinogen, and may pose a health hazard. However even if this material does contain asbestos, it may not pose a health hazard since it's not in a living space. The client(s) may wish to have this material tested for asbestos by a qualified lab and/or consult with a qualified industrial hygenist or remediation specialist, and should definitely do so if they plan to remove it or disturb it through remodeling. For more information on asbestos use in homes, visit: http://www.cpsc.gov/CPSCPUB/PUBS/453.html
Post wiring was found in the attic going to the ceiling lights in the bedroom.
| Electric service | Return to table of contents |



The main service panel uses older style, screw-in fuses. This type of fuse allows anyone to install incorrectly rated fuses, possibly resulting in damage to wiring. Based on the age and/or appearance of the panel(s) using fuses, and/or deterioration of the panels or components inside, recommend having a qualified electrician replace this panel with a modern panel and circuit breakers. If the panel isn't replaced, then a qualified electrician should evaluate and make repairs as necessary.
![]() Photo 8 Shows larger main panel and sub panel at left.
|
![]() Photo 9 Another Sub panel in basement about 10 feet to the left of the others.
|


One or more overcurrent protection devices (circuit breakers or fuses) are "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.


This property has "knob and tube" wiring, which was commonly installed prior to 1950. It is ungrounded, and considered unsafe by today's standards. Over time, the wires insulation may become brittle and fall apart or wear thin, resulting in exposed conductors and a risk of shock and/or fire. This wiring is also easily damaged by covering it with insulation (a common practice), and incorrectly tapping new wiring into it.

The service drop wires are less than three feet above one or more sections of roof with a slope of 3/12 (three inches vertical for every 12 inches horizontal) or more. This is a safety hazard for shock since people on the roof may come into contact with the service drop wires. The utility company and/or a qualified electrician should evaluate and repair as necessary.

No bonding was seen around water meter in the basement - grounding that uses water line as ground must be bonded around water meter.


The electric service to this property appears to be rated at substantially less than 200 amps, and may be inadequate for the client(s) needs. Recommend consulting with a qualified electrician about upgrading to a 200 amp service.
![]() Photo 7 100 Amp service
|

The legend for overcurrent protection devices (breakers or fuses) in the main service panel is missing, unreadable or incomplete. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.
| Water heater | Return to table of contents |

Corrosion was found on fittings and/or water supply lines for the water heater. Leaks may exist. A qualified plumbing contractor should evaluate and repair as necessary.
| Heating and cooling | Return to table of contents |
No carbon monoxide detector was seen in the area of the furnance

The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
| Plumbing and laundry | Return to table of contents |
Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.
A sump pump is installed on the premises. This may indicate that water accumulates inside or below the structure. Recommend asking the property owners how often the sump pump operates and for how long at different times of the year. Also, the clients should be aware that the service life of most sump pumps is between five and seven years, and that the pump may need replacing soon depending on its age and how much it operates.
![]() Photo 12 This sump pump pit needs a safety cover.
|
| Fireplaces, woodstoves and chimneys | Return to table of contents |

One or more chimney flue openings do not have a screen installed. Screens prevent the following:
One or more chimney flues do not have a rainproof cover installed. They prevent the following:
Chimney in the basement has a unused hole that should be sealed off to prevent heat loss from basement.
| Crawl space | Return to table of contents |


One or more pier or foundation footings are undermined, where soil has either eroded out from underneath, or has been excavated too close to the footing. Structural engineers typically require undisturbed soil to extend at least a foot horizontally out from the edge of footings, and then slope down no more steeply than 45 degrees. Otherwise soil may collapse from beneath the footing(s). A qualified structural engineer should evaluate and determine what repairs if any should be made. If repairs are prescribed, then a qualified contractor should perform them in accordance with the engineer's recommendations.
Some crawl space areas were inaccessible due to low height (less than 18 inches), ductwork or pipes blocking, standing water, and/or stored items. These areas are excluded from this inspection.
![]() Photo 10 |
![]() Photo 11 Old cast iron waste pipe not being used .
|
| Basement | Return to table of contents |

Gaps larger than four inches were found in one or more guardrails. This is a safety hazard, especially for small children. A qualified contractor should make modifications as necessary so gaps in guardrails do not exceed four inches. For example, installing additional balusters or railing components.
No ground fault interrupter circuits were found in the basement.
![]() Photo 13 Boiler, water heater and electrical panel. Located in basement.
|
| Kitchen | Return to table of contents |


One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
| Bathrooms | Return to table of contents |


One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
| Interior rooms | Return to table of contents |


One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.


Two-pronged electric receptacles rather than three-pronged, grounded receptacles are installed in one or more interior rooms. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:
Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html

This structure was built prior to 1979 and may contain lead paint. Laws were enacted in 1978 in the US preventing the use of lead paint in residential structures. Lead is a known safety hazard, especially to children but also to adults. The paint found in and around this structure appeared to be intact and may be encapsulated by more recent layers of paint that are not lead-based. Regardless, recommend following precautions as described in the following links to Consumer Products Safety Commission website articles regarding possible lead paint.
The doorbell appears to be inoperable. Recommend having a qualified electrician evaluate and repair as necessary.

Floors in one or more areas are not level. Significant repairs may be needed to make floors level, such as repairs to the foundation. A qualified contractor should evaluate and make repairs as necessary.
Glass in one or more windows is broken. A qualified contractor should replace glass where necessary. Down stairs bedroom.
One or more locksets are loose and should be tightened, repaired and or replaced as necessary.
The weatherstrip around one or more exterior entry doors is missing and/or deteriorated. Weatherstrip should be installed where missing and/or replaced where deteriorated, and by a qualified contractor if necessary.
Minor cracks were found in walls in one or more areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.