StepByStep Home Services LC
Home Inspection Report
Client(s): xxxxxxxxx
Property address: xxxxxxx
xxxxxx, MI
Inspection date: Thursday, May 31, 2007
This report published on 4/16/2008 6:35:44 PM EDT

Duty to the Public
1. The NACHI Inspector shall abide by the Code of Ethics and substantially follow the NACHI Standards of Practice.
2. The NACHI inspector will not engage in any practices that could be damaging to the public or bring discredit to the home inspection industry.
3. The NACHI Inspector shall be fair, honest, impartial, and act in good faith in dealing with the public.
4. The NACHI Inspector will not discriminate in any business activities on the basis of race, color, religion, sex, national origin, familial status, sexual orientation, or handicap and shall comply with all federal, state and local laws concerning discrimination.
5. The NACHI Inspector shall be truthful regarding his/her services & qualifications.
6. The NACHI Inspector will have no undisclosed conflict of interest with the client, nor will the NACHI Inspector accept or offer any undisclosed commissions, rebates, profits, or other benefit.
7. The NACHI Inspector shall always act in the interest of the client, unless doing so violates a law, statute, or this Code of Ethics.
8. The NACHI Inspector shall use a written contract that specifies the services to be performed, limitations of services, and fees.
9. The NACHI Inspector shall comply with all government rules and licensing requirements of the jurisdiction where he/she conduct business.
10. The NACHI Inspector shall not offer to perform repairs on the property that was inspected for a period of 12-months from the time of the initial inspection.
Duty to Continue Education
1. The NACHI Inspector will comply with NACHI's current Continuing Education Requirements.
2. The NACHI Inspector shall pass the NACHI's Online Inspector Exam once every calendar year.
Duty to the Profession and NACHI
1. The NACHI Inspector will strive to improve the Home Inspection Industry by sharing his/her lessons and/or experiences for the benefit of all. This does not preclude the Inspector from copyrighting or marketing his/her expertise to other Inspectors or the public in any manner permitted by law.
2. The NACHI Inspector shall assist the NACHI leadership in disseminating and publicizing the benefits of NACHI membership.
3. The NACHI Inspector will not engage in any act or practice that could be deemed damaging, seditious, or destructive to NACHI, fellow NACHI members, NACHI employees, leadership or directors. Member(s) accused of acting or deemed in violation of such rules shall be reviewed by the Ethics committee for possible sanctions and/or expulsion from NACHI.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Exterior
Roof
Garage
Electric Service
Water Heater
Heating
Cooling
Plumbing and Laundry
Fireplaces, woodstoves and chimneys
Kitchen
Breakfast Nook
Living Room
Interior Rooms
Master Bathroom
Bedroom 3
Bathroom 1 Off Laundry
Bathroom 2 Upstairs
Basement
Attic
Crawl Space
 
General Information Return to table of contents
Report number: 53107
Structures inspected: Home/Garage
Type of building: Single family
Age of building: 1964
Property owner's name:
Report number: 53106
Structures inspected: Home/Garage
Type of building: Single family
Age of building: 1964
Property owner's name: Unknown
Time started: 12:00
Time finished: 6:00
Inspection Fee: 379.00
Payment method: Check
Present during inspection: Client(s), Realtor(s)
Occupied: No
Weather conditions: Clear
Temperature: Hot
Ground condition: Dry
Foundation type: Unfinished basement, Finished basement, Crawlspace
The following items are excluded from this inspection: Items listed in the NACHI SOP as outside the scope of the home inspections.


1) One or more leaks were found in gas supply lines, fittings and/or valves at the hot water heater. This is a safety hazard due to the risk of explosion. A qualified contractor and/or the gas utility company should evaluate and make repairs as soon as possible. I turned the gas off at the exterior of the home.

Photo 73  

Photo 74  

2) Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
     
    Exterior Return to table of contents
    Foundation material: Poured in place concrete
    Apparent wall structure: Wood frame
    Wall covering: Brick veneer, Vinyl
    Driveway material: Poured in place concrete
    Sidewalk material: Brick
    Exterior door material: Solid core steel
    3) One or more trip hazards were found in the driveway due to cracks, settlement and/or heaving. Recommend having a qualified contractor evaluate and repair or replace driveway sections as necessary to eliminate trip hazards.

    Photo 2  
     

    4) One or more wall-mounted exterior light fixtures have wiring that's subject to water intrusion due to caulk not being installed around the light fixture's back plate. Caulk should be applied around the perimeter of back plates where missing. A gap should be left at the bottom for condensation to drain out.

    Photo 6  
     

    5) One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.

    Photo 4  
     

    6) The drain tile at the exterior downspout of sump drain is crushed and no longer functional. Recommend repairs by a licensed contractor.

    Photo 102  
     

    7) Moderate cracks and/or deterioration found in one or more sections of brick veneer. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar, replacing bricks and/or sections of veneer.

    The brick in several areas is below grade where the soil and mulch is covering the bricks. This condition will cause the mortar and bricks to deteriorate. Recommend removing mulch and soil from those areas while being sure to maintain a proper slope away from the home. Several areas of brick that were not visible at the time of the inspection may need to be replaced once the soil and mulch is removed revealing the bricks.

    Photo 17  

    Photo 18  

    8) Minor cracks were found in one or more sections of brick veneer. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.

    Photos taken at the right side of the home off the garage.

    Photo 22  

    Photo 23  

    9) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.

    Photo 8  

    Photo 9  

    Photo 12  

    Photo 13  

    10) A shutter at the front of the home is loose where the fastener is not long enough to attach it to the brick. Recommend installing a longer fastener or using an epoxy to attach the shutter to the wall. These gaps are typical areas for bees or hornets nests.

    Photo 7  
     

    11) An outside faucet handle at the rear of the home is not properly attached. Recommend installing a new handle to allow for proper function.

    Photo 11  
     

    12) One or more downspouts are dented, damaged and/or crushed. This can restrict the water flow and result in clogging and overflowing gutters. Water may accumulate around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Damaged downspouts should be repaired or replaced as necessary, and by a qualified contractor if necessary.

    Photo 14  
     

    13) The front porch is cracked and should be patched with cement or hydraulic cement to prevent further deterioration. This crack does not present a trip hazard.

    Photo 3  
     

    14) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.

    Photo 10  

    Photo 19  

    Photo 20  

    Photo 21  

    Photo 25  
     

    15) Window glazing putty at one or more windows is missing and/or deteriorated. Putty should be replaced and/or installed where necessary. For more information on replacing window putty, visit: http://www.oldhouseweb.com/stories/Detailed/12216.shtml

    Photo 5  
     

    16) Several areas at the right side of the home has what appears to be a type of fungus growing on it. Recommend using a siding cleaner such as Siding OX and stiff brush available at your local hardware store.

    http://www.cleanertoday.com/Vinyl_Siding_cleaner_Quick_Simple_Effective_s/7.htm

    Photo 24  

    Photo 35  

    Photo 36  

    Photo 37  
     
    Roof Return to table of contents
    Roof inspection method: Traversed
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 6 Years over garage / 8 years over the home
    Gutter & downspout material: Aluminum
    Roof ventilation: Inadequate
    17) A section of the roof near the chimney dips and may prevent water from shedding off the surface. Recommend repairs such as replacing sheathing to allow for a proper slope and water flow.

    Photo 32  

    Photo 34  

    18) A downspout over the garage terminates directly on the surface. This can cause the shingles in this area to deteriorate quickly by washing the granuals off the shingles. Recommend extending the downspout to the gutter below.

    Photo 31  
     
     
    Garage Return to table of contents

    19) One or more open ground, three-pronged electric receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. For example, replacing receptacles or correcting wiring circuits.

    Grounding type receptacles began being required in residential structures during the 1960s. Based on the age of this structure and the presence of 2-pronged receptacles in some areas of this structure, an acceptable repair may be to simply replace the ungrounded 3-pronged receptacles with 2-pronged receptacles. However the following appliances require grounding type receptacles:

  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

    This list is not exhaustive. Grounded circuits and receptacles should be installed in locations where such appliances will be used.

    Photo 27  
     

    20) Minor cracks were seen at the garage slap. Recommend sealing cracks with concrete of hydraulic cement.

    Photo 26  
     

    21) Hardware that fastens the garage door opener to the roof structure is missing a bolt. Recommend installing a bolt where is is connected to the truss bottom cord.

    Photo 28  
     
     
    Electric Service Return to table of contents
    Primary service type: Underground
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main service switch: Basement
    Location of main disconnect: Breaker at top of main service panel
    System ground: Cold water supply pipes
    Main disconnect rating (amps): 200
    Branch circuit wiring type: Non-metallic sheathed
    Solid strand aluminum branch circuit wiring present: No
    Smoke detectors present: Yes Recommend installing smoke and CO detectors in each bedroom.
    22) Conductors that are connected to circuits should be marked black or red to identify them as hot conductors. This photo shows a white (typically neutral) conductor conned directly to a circuit. Recommend marking conductor with red or black marker or tape.

    Photo 72  
     

    23) Insulation on conductors should not extend more than one inch into the main panel. Recommend removing insulation so that is does not extend too far into the panel.

    Photo 71  
     
     
    Water Heater Return to table of contents
    Estimated age: 1995
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 76
    Manufacturer: A.O. Smith
    Model: FXG
    Water temperature (degrees Fahrenheit): 160 - taken at an upstairs bathroom.
    24) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    25) Corrosion was found in one or more areas on the water heater where the dielectric union is damaged or installed improperly. Recommend repairs to prevent further corrosion and possible water leaks.

    Photo 75  
     
     
    Heating Return to table of contents
    Estimated age: 1993
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air
    Distribution system: Sheet metal ducts
    Manufacturer: Carrier
    Model: WEATHERMAKER 8000
    Filter location: In return air duct below furnace
    26) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    27) Air handler filter(s) is damaged and should be replaced now. This type of filter generally lasts up to 10 months. Recommend checking the filter every three months and replacing when excessively dirty in the future.

    Photo 76  
     

    28) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
    29) Because of the excessive gas leak at the hot water heater I was unable to test the furnace flames. The furnace heating was not evaluated.
     
    Cooling Return to table of contents
    Estimated age: 2002
    Primary A/C energy source: Electric
    Primary Air conditioning type: Split system
    Distribution system: Sheet metal ducts
    Manufacturer: Tech 2000
    Model: Silencer System
    30) Vegetation such as trees, shrubs and/or vines are too close to the outdoor condensing unit. Standard building practices require that there be at least 12 inches of clearance on all sides and at least four to six feet above. Inadequate clearances around the condensing unit can result in reduced efficiency, increased energy costs and/or damage to equipment. Vegetation should be pruned and/or removed as necessary to maintain these clearances.

    Photo 16  
     
     
    Plumbing and Laundry Return to table of contents
    Water pressure (psi): 82
    Location of main water shut-off valve: Basement
    Location of main water meter: Basmement
    Location of main fuel shut-off: Exterior Left
    Water service: Public
    Service pipe material: Copper
    Supply pipe material: Copper
    Vent pipe material: Cast iron
    Drain pipe material: Plastic
    Waste pipe material: Plastic, Cast iron
    31) The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

    Photo 55  
     

    32)   The water supply pressure is greater than 80 psi. Pressures above 80 psi may void warranties for some appliances such as water heaters or washing machines. Flexible supply lines to washing machines are more likely to burst with higher pressures. Typically the pressure cannot be regulated at the water meter. Recommend having a qualified plumber evaluate and make modifications to reduce the pressure below 80 psi. Installing a pressure reducing valve on the main service pipe is a common solution to this problem. If one exists, then it should be adjusted for lower pressures.

    Water pressure taken at the exterior left and was at 83 psi.

    Photo 77  
     
     
    Fireplaces, woodstoves and chimneys Return to table of contents
    Fireplace type: Masonry
    Chimney type: Masonry
    33) A significant amount of creosote (1/8 inch or more) is visible in the fireplace flue. A qualified chimney service contractor should clean now and annually in the future.

    Photo 50  

    Photo 51  

    Photo 52  

    Photo 53  

    34) The fireplace doors are loose where a bolt is either not properly secured or stripped. Recommend repairs to allow for proper function.

    Photo 54  
     

    35) The masonry chimney's mortar is deteriorated and should be repaired to prevent further, significant deterioration. Recommend having a qualified chimney service contractor or mason evaluate chimney and repair as necessary. This will likely require repointing the mortar.

    Photo 38  

    Photo 39  

    36) Flashing at the base of the chimney is not in contact with the brick causing a gap. Recommend repairs such as adding caulk to prevent water from entering the attic area.

    Photo 33  
     
     
    Kitchen Return to table of contents

    37) The range can tip forward, and no anti-tip bracket appears to be installed. This is a safety hazard since the range may tip forward when weight is applied to the open door, such as when a small child climbs on it, or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free standing ranges since 1985. An anti-tip bracket should be installed to eliminate this safety hazard. For more information, visit http://www.hgtv.com/hgtv/remodeling/article/0,1797,HGTV_3659_2017492,00.html
    38) The bottom door on the range is loose where the hardware is loose or bent. Recommend repairs such as bending hardware back into place or replacing.

    Photo 45  
     

    39) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

    Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.

    Photo 40  
     

    40) The window in front of the sink does not open all the way and catches on the overhang flashing at the exterior. Recommend repairing the flashing to allow for proper function.

    Photo 42  

    Photo 43  

    41) Hardware such as hinges, latches or pulls are loose and/or missing on one or more cabinets. Repairs should be made and/or hardware should be replaced as necessary, and by a qualified contractor if necessary.

    Photo 41  
     

    42) Caulk is missing and/or deteriorated where countertops meet backsplashes in wet areas, such as around sinks. Caulk should be replaced where deteriorated and/or applied where missing to prevent water damage.

    Photo 44  
     
     
    Breakfast Nook Return to table of contents

    43) Evidence of a past water leak was seen at the ceiling. This area was tested with a Wagner MMC moisture meter and was dry at the time of the inspection.

    Photo 48  
     

    44) One or more doors will not latch when closed. Repairs should be made as necessary, and by a qualified contractor if necessary. For example, aligning strike plates with latch bolts and/or replacing locksets or adjusting hinges.

    Photo 46  

    Photo 47  
     
    Living Room Return to table of contents

    45) Lock mechanisms on one or more windows or patio doors are missing and/or damaged so that they are inoperable or loose. Repairs should be made by a qualified contractor or service technician so that windows lock and unlock easily.

    Photo 49  
     
     
    Interior Rooms Return to table of contents

    46) Two-pronged electric receptacles rather than three-pronged, grounded receptacles are installed in one or more interior rooms. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:

  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

    This list is not exhaustive. A qualified electrician should evaluate and install grounded receptacles as per the client(s)' needs and standard building practices.
    47) Hardware such as hinges, latches or pulls are loose and/or missing on one or more cabinets. Repairs should be made and/or hardware should be replaced as necessary, and by a qualified contractor if necessary.

    Photo taken in the laundry room.

    Photo 56  
     

    48) One or more light fixtures are damaged and/or deteriorated. A qualified electrician should evaluate and repair or replace light fixtures where necessary.

    Photo taken in the laundry room.

    Photo 59  
     

    49) One or more windows that were built to open, will not open, or open only minimally due to their being painted shut, damaged and/or deteriorated in some way. Repairs should be made as necessary, and by a qualified contractor if necessary so windows open fully, and open and close easily.

    Photo taken in the laundry room.

    Photo 57  
     

    50) Glass in one or more windows is broken. A qualified contractor should replace glass where necessary.

    Photo taken in the laundry room.

    Photo 58  
     

    51) Minor cracks were found in walls in one or more areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.
     
    Master Bathroom Return to table of contents

    52) One or more light fixtures are loose or installed in a substandard way. A qualified contractor or electrician should evaluate and make repairs as necessary so light fixtures are securely mounted and installed in accordance with the manufacturer's installation instructions.

    The conductors sparked when the fixture was moved so I turned tripped the circuit in the basement. Recommend repairs such as replacing the conductors where damaged.

    Photo 93  
     

    53) Grout around the shower floor/wall is damaged or deteriorated.Recommend repairs such as applying caulk to prevent water from entering behind the shower pan and deteriorating the flooring.

    Photo 61  

    Photo 62  

    54) One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
     
    Bedroom 3 Return to table of contents

    55) The cover plate is missing where cable enters this room. Recommend installing a proper cable plate.

    Photo 65  
     
     
    Bathroom 1 Off Laundry Return to table of contents

    56) Grout is cracked on the tiles near the toilet. Recommend repairs such as regrouting tiles to prevent water entry.

    Photo 60  
     
     
    Bathroom 2 Upstairs Return to table of contents

    57) Caulk is missing or deteriorated along the hot and cold water fixtures. Recommend applying caulk to prevent water entry.

    Photo 64  
     

    58) One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
    59) The bathtub drain does not prevent the water from draining when in the up position. Recommend adjusting the drain for proper function.

    http://www.homerepairforum.com/images/uploads/2005-8-28_Tub_Stopper_Linkage_w550.JPG

    60) The shower plate is not securely fasted to the wall and moves around when the shower valve is operated. Recommend repairs such as tightening the screw to allow for a firm attachment to the shower wall.

    Photo 63  
     
     
    Basement Return to table of contents
    Insulation material underneath floor above: Fiberglass roll or batt
    Pier or support post material: Steel
    Beam material: Steel
    Floor structure above: Solid wood joists
    61) An organic growth was seen at two areas of the basement. Recommend evaluation by a certified mold specialist to determine what type of growth it is and how to remove it.

    Refer to my previous email for several contacts.

    Photo 69  

    Photo 70  

    62) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains and/or efflorescence on the walls where rod holes are leaking. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.

    Photo 66  

    Photo 67  

    Photo 68  
     

    63) The basement is partially finished preventing a full evaluation of those walls and ceiling areas obstructed by drop ceiling and panels.
     
    Attic Return to table of contents
    Inspection method: Traversed
    Roof structure type: Trusses
    Ceiling structure: Trusses
    Insulation material: Mineral wool roll or batt
    Insulation depth: 7"
    Insulation estimated R value: 19
    64) The roofs sheathing has a dip or sag over the garage and home. This can be the result of several things such as inadequate ventilation causing the sheathing to buckle, sheathing that is undersized for the truss span of 24" or sheathing that is installed without a proper gap or H clips. When the roof covering (shingles) are replaced I recommend the sheathing be replaced throughout to prevent this dip in the sheathing.
    65) Sheathing at the drip edge of the garage is rotten and not properly fastened to the roof causing an excessive dip where the roof is lower in the middle and high at the ends. Sheathing in this area should be replaces and properly fastened. Recommend evaluation and repairs by a licensed contractor.
    66) Most of the roofs sheathing is water damaged and buckles causing the roof to dip in several areas. Recommend repairs or replacement over the entire roof structure.
    67) Sheathing is damaged in the garage and home attic. Recommend replacement of damaged sheathing by a qualified contractor to prevent further damaged which may be caused by snow accumulation.


    Some areas of the sheathing appear to have been replaced.

    Photo 29  

    Photo 97  

    Photo 98  

    Photo 99  

    68) The ceiling insulation's R rating is significantly less than what's recommended for this area. Recommend having a qualified contractor install additional insulation (three inches) as per standard building practices for better energy efficiency.

    Photo 101  
     

    69) One or more attic vents are blocked by insulation and/or debris. This can reduce air flow through the attic, reduce the life of the roof surface because of high temperatures, and/or increase moisture levels in the attic. Repairs should be made as necessary, such as moving insulation or debris, so vents are unobstructed.

    Photo 95  

    Photo 96  

    70) Stains were visible on the roof structure at the home and garage. These areas were dry at the time of the inspection. The stains may be caused by a past leak. Recommend asking the property owner(s) about past leaks. The client(s) should monitor these areas in the future, especially after heavy rains, to determine if active leaks exist. If leaks are found, a qualified roofing contractor should evaluate and repair as necessary.

    Photo 30  
     

    71) The roofs sheathing is missing H clips and does not have a gap between each panel. While H clips were not used in the 60's a gap should have been maintained to allow for expansion and contraction. When the roof sheathing is replaced H clips should be installed to allow for a proper gap and additional support.
     
    Crawl Space Return to table of contents
    Inspection method: Traversed
    Insulation material underneath floor above: Foam
    Pier or support post material: Steel
    Beam material: Steel
    Floor structure above: Solid wood joists
    Vapor barrier present: Yes
    72) The crawlspace has a deep trench where the soil was not backfilled during construction. Backfilling allows for support to the basement walls and adds strength to the structure. Recommend adding soil and gravel to the area of the crawlspace that is not backfilled. A licensed contractor should perform this to ensure the soil is properly graded and gravel is added.

    Photo 88  

    Photo 89  

    Photo 90  
     

    73) Steel support posts are not securely fastened to the footing below. This is a safety hazard since they can separate during a seismic event. A qualified contractor should evaluate and make repairs as necessary, such as installing a properly sized support.

    Photo 80  

    Photo 81  

    74) Evidence of prior water intrusion was found in one or more sections of the crawl space substructure. These areas tested try at the time of the inspection however the floor structure is damaged or deteriorated and in need of replacement by a licensed contractor.

    Photo 86  

    Photo 87  

    75) The stove vent is excessively long and touching the crawl floor. This may cause the vent to deteriorate from moisture. Recommend trimming foil vent by a licensed contractor using proper connectors and clamps.

    Photo 84  
     

    76) One or more crawl space vent screens are blocked by soil, debris, insulation, stored items or removable panels. This restricts ventilation in the crawl space and may result in increased levels of moisture inside. Materials or items blocking vents should be removed.

    Photo 82  

    Photo 83  

    77) The vapor barrier needs repair. Exposed soil was found in some areas. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should make repairs as necessary so no exposed soil exists. Standard building practices require the following:

  • The soil below the vapor barrier should be smooth and free from sharp objects.
  • Seams should overlap a minimum of 12 inches.
  • The vapor barrier should lap up onto the foundation side walls.

    Better building practices require that:

  • Seams and protrusions should be sealed with a pressure sensitive tape.
  • The vapor barrier should be caulked and attached tightly to the foundation side walls. For example, with furring strips and masonry nails.

    Photo 78  
     

    78) An opening was seen at the sump pump discharge line where it exits the home. Recommend sealing hole to prevent mice from entering the crawlspace.

    Photo 91  
     

    79) Insulation on air supply vents is deteriorated and/or missing in one or more areas. Recommend repairing or installing insulation on vent pipes where necessary for better energy efficiency.

    Photo 79  

    Photo 85  

    Photo 92  
     
     

    Photo 15  

    Photo 94  

    Photo 100  
     

     
    The following contract is completed prior to the inspection.
    www.stepbystepinspections.com

    The address of the property is: ________________________________________________Fee for the home inspection is $____________________.
    INSPECTOR acknowledges receiving a deposit of $_________________ from CLIENT.

    THIS AGREEMENT made this _____________ day of _______________________________________________________, 200__, by and between

    ______________________________________________ (Hereinafter INSPECTOR) and the undersigned (hereinafter CLIENT), collectively referred to herein as the parties. The Parties Understand and Voluntarily Agree as follows:

    1. INSPECTOR agrees to perform a visual inspection of the home/building and to provide CLIENT with a written inspection report identifying the defects that INSPECTOR both observed and deemed material. INSPECTOR may offer comments as a courtesy, but these comments will not comprise the bargained-for report. The report is only supplementary to the sellers disclosure.
    2. Unless otherwise inconsistent with this Agreement or not possible, INSPECTOR agrees to perform the inspection in accordance to the current Standards of Practice of the National Association of Certified Home Inspectors posted at http://www.nachi.org/sop.htm. CLIENT understands that these standards contain certain limitations, exceptions, and exclusions.
    3. The inspection and report is solely and exclusively for Clients own information and may not be relied upon by any other person. Client agrees to maintain the confidentially of the inspection report and agrees not to disclose any part of it to any other person. Client may distribute copies of the inspection report to the seller and the real estate agents directly involved in this transaction, but said persons are not specifically intended beneficiaries of this Agreement of the inspection report. Client and inspector do not in any way intend to benefit said seller or the real estate agents directly or indirectly through this Agreement or the Inspection report. Client agrees to indemnify, defend, and hold Inspector harmless from any third party claims arising out of Client?s unauthorized distribution of the inspection report.

    4. INSPECTOR assumes no liability for the cost of repair or replacement of unreported defects or deficiencies either current or arising in the future. CLIENT acknowledges that the liability of INSPECTOR, its agents, employees, for claims or damages, costs of defense or suit, attorneys fees and expenses and payments arising out of or related to the INSPECTORS negligence or breach of any obligation under this Agreement, including errors and omissions in the inspection or the report, shall be limited to liquidated damages in an amount equal to the fee paid to the INSPECTOR, and this liability shall be exclusive. CLIENT waives any claim for consequential, exemplary, special or incidental damages or for the loss of the use of the home/building even if the CLIENT has been advised of the possibility of such damages. The parties acknowledge that the liquidated damages are not intended as a penalty but are intended (i) to reflect the fact that actual damages may be difficult and impractical to ascertain; (ii) to allocate risk among the INSPECTOR and CLIENT; and (iii) to enable the INSPECTOR to perform the inspection at the stated fee.

    5. INSPECTOR does not perform engineering, architectural, plumbing, or any other job function requiring an occupational license in the jurisdiction where the inspection is taking place, unless the inspector holds a valid occupational license, in which case he/she may inform the CLIENT that he/she is so licensed, and is therefore qualified to go beyond this basic home inspection, and for additional fee, perform additional inspections beyond those within the scope of the basic home inspection. Any agreement for such additional inspections shall be in a separate writing or noted here: ______________________________________________________________________________________________________________________.

    6. In the event of a claim against INSPECTOR, CLIENT agrees to supply INSPECTOR with the following: (1) Written notification of adverse conditions within 14 days of discovery, and (2) Access to the premises. Failure to comply with the above conditions will release INSPECTOR and its agents from any and all obligations or liability of any kind.
    7. The parties agree that any litigation arising out of this Agreement shall be filed only in the Court having jurisdiction in the County in which the INSPECTOR has its principal place of business. In the event that CLIENT fails to prove any adverse claims against INSPECTOR in a court of law, CLIENT agrees to pay all legal costs, expenses and fees of INSPECTOR in defending said claims.
    8. If any court declares any provision of this Agreement invalid or unenforceable, the remaining provisions will remain in effect. This Agreement represents the entire agreement between the parties. All prior communications are merged into this Agreement, and there are no terms or conditions other than those set forth herein. No statement or promise of INSPECTOR or its agents shall be binding unless reduced to writing and signed by INSPECTOR. No change or modification shall be enforceable against any party unless such change or modification is in writing and signed by the parties. This Agreement shall be binding upon and enforceable by the parties and their heirs, executors, administrators, successors and assignees. CLIENT shall have no cause of action against INSPECTOR after one year from the date of the inspection.
    9. Payment of the fee to INSPECTOR (less any deposit noted above) is due upon completion of the on-site inspection. The CLIENT agrees to pay all legal and time expenses incurred in collecting due payments, including attorney?s fees, if any. If CLIENT is a corporation, LLC, or similar entity, the person signing this Agreement on behalf of such entity does personally guaranty payment of the fee by the entity.