Home Inspection Report
Client(s): Proper T Solutions LLC
Property address: 2166 Harriet
Inkster, MI
Inspection date: 4-19-05
This report published on 4/20/2005 1:32:48 PM EDT


How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and shown in bold type. Items of concern follow descriptive information and are shown as follows:
SafetyPoses a risk of injury or death 
Major defectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 
Concern items are sorted by the types listed above. Click here for a glossary of building construction terms.

Table of Contents
Exterior
Porch
Detached garage or carport
Bedroom/s
Roof
Plumbing and laundry
Heating and air conditioning
Electric service
Kitchen/Interior rooms
Water heater
Attic
Crawl space
General information


Exterior Return to table of contents  
Footing material: Masonry
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Metal, Asbestos-based shingles
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel
1) One or more trip hazards were found in the sidewalk due to cracks and/or settlement. Recommend having a qualified paving contractor repair or replace sidewalk section(s) as necessary to eliminate trip hazards.

Photo 11
 
2) While I am not qualified to positively identify the presence of asbestos, the exterior siding on this house does appear to be a type of asbestos containing shingle. A test by a qualified individual would have to be performed to make a positive identification.
http://www.oldhouseweb.com/stories/Detailed/10470.shtml

http://www.nachi.org/tips/1805.gif

Photo 2
 
3) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.
4) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Recommend making repairs as necessary such as repairing or installing splash blocks or tie-ins to underground drain lines so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.
http://www.nachi.org/tips/1910.gif

Photo 3

Photo 4

Photo 5
 
5) One or more gutters are damaged. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Recommend having a qualified contractor replace or repair gutters where necessary.

Photo 6

Photo 7
6) Moderate wood rot was viewed at the front door threshold. Proper maintenance or replacement is required to prevent further damage to this section of wood. Also note the small hole to the left of the porch. This is a potential rodent entry point and should be repaired.

Photo 10
 
7) The exterior finish in some areas is failing. Recommend having a qualified painting contractor prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain areas as needed and as per standard building practices.
8) Siding is missing in some areas. This should be replaced to prevent water entry and damage to the wall structure. It appears, in this photo, as though the fascia is water damaged. Other damage resulting from this defect was not visible during the time of the inspection.
http://www.nachi.org/tips/1813.gif

Photo 9
 
9) One or more outside faucets were not evaluated due to their being winterized with covers, and are excluded from this inspection.
10) No outside outlets were seen on the exterior of the house. At leas two outside outlets should be located on your home. One on the front and one on the rear. They must be located within 6'6" of grade level , be readily accessible, and be GROUND FAULT CIRCUIT INTERRUPTER protected(GFCI).
 
Porch Return to table of contents  
11) The front porch was covered by exterior carpeting preventing a full view of its surface. The viewable area appeared in general good condition. Minor damage was viewed at the bottom right CMU mortar.
12) The rear porch is in good condition.
13) Metal window awnings appear in good condition.
14) Metal porch covers appear solid and in good condition.
 
Detached garage or carport Return to table of contents  
Footing material: Poured in place concrete
Foundation material: Poured in place concrete
Apparent wall structure: Wood frame
Wall covering: Vinyl
Exterior door material: N/A
Roof inspection method: Viewed from ground with binoculars
Roof type: Hipped
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: Unknown
Gutter & downspout material: Aluminum
Roof ventilation: None visible
15) It appears as though electricity was provided at one point but has been removed. This photo shows an abandoned electrical entry point. A qualified electrical would have to be contacted to determine whether or not this is a usable source of electricity.

Photo 25
 
16) There are no outlets provided in the garage. Outlets should be installed with at least one being GFCI.
17) Anchor bolts (photo 23), used to secure the garage to the foundation, are improperly installed resulting in wall movement (photo 24). A qualified building contractor should be contacted to make necessary repairs.
http://www.nachi.org/tips/0278.gif

Photo 23

Photo 24
18) Moderate water damage was viewed at several areas of the garage. This is caused by non water treated lumber used for the construction. It appears as though this garage was constructed by an individual not licensed in the building trades. I recommend a qualified building contractor make the necessary repairs/modifications. It would be wise to see if a permit was pulled for the construction of this garage.

Photo 22
 
19) The garage vehicle door is damaged and does not close all the way without considerable force. Recommend having a qualified garage door contractor repair vehicle door(s) as necessary.
20) Surface cracking was viewed throughout the garage slab. The area cracking appears to be a secondary application used to cover the original slab.
21) Firewood is stored so that it's either in contact with the structure or very close to it. The is a conducive condition for wood destroying insects. Recommend storing firewood outdoors in an open area, as far away from the house as practical, to keep away insects. For more information visit http://ohioline.osu.edu/hyg-fact/2000/2065.html
 
Bedroom/s Return to table of contents  
22) Front bedroom widows fall when in the open position. Double hung and single hung windows have spiral balances, block & tackle balances, counter balances, jambliners or sash ropes on both sides which serves as the mechanism that allows the windows to open and close freely and to remain at any desire position. These mechanisms have springs or cords that maybe broken or loose which could result from normal wear and tear causing the windows not to stay up. Adjustment or replacement of the mechanism maybe required to allow the windows to open and close freely. Surface cracking was viewed throughout the garage slab. The area cracking appears to be a secondary application used to cover the original slab.
23) Rear bedroom widows fall when in the open position. Double hung and single hung windows have spiral balances, block & tackle balances, counter balances, jambliners or sash ropes on both sides which serves as the mechanism that allows the windows to open and close freely and to remain at any desire position. These mechanisms have springs or cords that maybe broken or loose which could result from normal wear and tear causing the windows not to stay up. Adjustment or replacement of the mechanism maybe required to allow the windows to open and close freely. Surface cracking was viewed throughout the garage slab. The area cracking appears to be a secondary application used to cover the original slab.
24) Rear bedroom door and closet door do not close properly. The door mechanisms do not work and should be replaced to allow for proper function.
25) When walking near the side window in the rear bedroom, see photo, I could hear the ductwork under the house buckle. After inspecting this area in the crawlspace, it appears as though the ductwork installed moves a little with the flooring system. This is not a major concern just a nuisance.

Photo 15
 
 
Roof Return to table of contents  
Roof inspection method: Viewed from ground with binoculars
Roof type: Cross-hipped
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: Unknown
Gutter & downspout material: Aluminum
Roof ventilation: Inadequate
26) The roof appears to be in good condition. I recommend asking the seller when it was installed to get a general idea when your next replacement will need to take place.
27) The television antenna is mounted to the chimney. This places stress on the chimney and is not a recommended method of installation.
 
Plumbing and laundry Return to table of contents  
Location of main water shut-off valve: Laundry
Location of main water meter: Laundry
Location of main fuel shut-off: Rear of home
Water service: Public
Service pipe material: Copper, Galvanized steel
Supply pipe material: Copper, Galvanized steel
Vent pipe material: Galvanized steel
Drain pipe material: Galvanized steel, Copper
Waste pipe material: Cast iron, Copper
28) This leaking main waste line, located in the crawl space, is an environmental hazard and should be repaired by a licensed plumber. This may be a contributing factor in the presence of moisture in the crawl space area.

Photo 41
 
29) Some, most, or all of the water supply pipes in this structure are made of galvanized steel. Based on the age of this structure, these pipes may be nearing or may have exceeded their estimated useful life of 40 and 60 years. Internal corrosion and rust can reduce the inside diameter of these pipes over time, resulting in reduced flow and eventually, leaks. The inspector performed a "functional flow test" during the inspection where multiple fixtures were run simultaneously, and found the flow to be adequate. For example, the shower flow didn't decrease substantially while the toilet was flushed. Despite this, and given their apparent age, these pipes may need replacing at any time.
http://www.nachi.org/tips/1504.gif
30) A plumbing leak was viewed at the plumbing closet, located in the rear bedroom. The circle in this photo shows the active leak. Note also the damage to the sheet rock as a result of past or present water leaks.

Photo 27
 
31) Improper main waste line was viewed in the crawlspace. A proper support should be installed to secure the waste line and prevent damage form failure of current support. I recommend a qualified plumber make necessary repairs/replacement.

Photo 35
 
32) While they were once an acceptable method of plumbing trap, drum traps are no longer used as they do not provide a proper water trap. This trap should be replaced by a licensed plumber for updating.
http://www.nachi.org/tips/1637.gif

Photo 36
 
 
Heating and air conditioning Return to table of contents  
Heating system energy source: Natural gas
Heat system type: Forced air
A/C energy source: N/A
Distribution system: Sheet metal ducts
Brand & model: GSD-75-MHN 75,000 BTU
Location of filter(s): Top of Furnace
33) Because of the age and/or condition of this furnace, recommend that a qualified heating and cooling technician inspect the heat exchanger and perform a Carbon Monoxide test when it's serviced.
34) A significant has leak was detected at the drip leg on the furnace. I turned the gas of to this unit. I recommend a qualified HVAC tech make necessary repairs to this gas line to prevent damage to the property and other persons.

Photo 17
 
35) The estimated useful life for forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time.
36) Last service date of this system is more than one year ago or is unable to be determined. Recommend asking seller when it was last serviced. If unable to determine or if more than one year ago, recommend that this system be inspected, cleaned, serviced and repaired if necessary by a qualified heating and cooling technician. Recommend that this servicing be made annually in the future.
37) This system is equipped with throw-away filter(s). They appear to be dirty. Recommend replacing filter(s) now and every 2 months in the future if the thermostat's fan position is set to "Auto", or monthly if it's set to "On".
 
Electric service Return to table of contents  
Primary service type: Overhead
Primary service overload protection type: Fuses
Service amperage (amps): 100
Service voltage (volts): 120-240
Location of main service panel: Laundry
Location of main disconnect: Breaker at top of main panel
Service conductor material: Aluminum, Copper
Main disconnect rating (amps): 60
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: Can't verify
Smoke detectors present: No
38) Service drop wires are less than 10 feet above ground or walkways. Recommend having a qualified, licensed electrician and/or the utility company evaluate and repair.

Photo 8
 
39) One or more circuit breakers are "double tapped", where 2 or more wires are clamped in a circuit breaker terminal, and the circuit breaker is only designed for 1 wire. This is a safety hazard since wires may loosen and cause arcing, sparking and fires. Recommend having a qualified, licensed electrician evaluate and repair.

Photo 21
 
40) This panel is outdated and should be replaced to meet current standards. A qualified electricial will have to make the necessary changes to the main panel.
41) No smoke detectors are visible. Recommend installing smoke detectors as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html
42) One or more smoke detectors is damaged or missing, and an insufficient number of smoke detectors are installed. Recommend replacing inoperable smoke detectors as necessary, and installing additional smoke detectors as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html
43) Inadequate clearance exists to the main service panel. Recommend having a qualified, licensed electrician make modifications as necessary so:

  • An area 3" wide by 3' deep exists in front of the panel
  • The panel is at least 5 1/2 feet above the floor
  • There's at least 6'3" of headroom
  • The wall below the panel is clear to the floor
  • 44) One or more bushings are missing from where wires enter holes in the main service panel. This is a safety hazard since the wiring insulation can be cut or abraded on the metal edge of the hole(s). Recommend having a qualified, licensed electrician install bushings where missing.

    Photo 19
     
    45) Ground and neutral wires should be isolated under their own screw and separate bus bar. This photo shows both ground and neutral conductors under the same screw and on the same bus bar. This is common practice in older outdated panels.

    Photo 20
     
    46) Improperly secured conductors were viewed in the attic area. To prevent damage to these conductors, they should be properly secured by a licensed electrician.

    Photo 29
     
    47) This photo shows a two prong ungrounded outlet located close to the shower area. This should be removed by a licensed electrical to prevent possible electrical shock.

    Photo 16
     
    48) The conductors in this photo are located in the rear bedroom closet. This conductor should be installed behind the wall to prevent damage to it and to prevent possible electrical shock to persons coming in contact with damaged sheathing.

    Photo 14
     
    49) One or more screws are missing from the main service panel cover. Recommend replacing missing screws.

    Because live wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws don't come in contact with wiring inside the panel when they're installed.
      50) A false ground was detected, using a SureTest Circuit Analyzer, at most outlets throughout the home. This is a common defect found when the receptacles have been updated to include a ground source but the homes outdated wiring does not provide a means of grounding.

    Photo 12
     
     
    Kitchen/Interior rooms Return to table of contents  
    51) This home was built before 1978, when laws were enacted in the US preventing the use of lead paint in residential structures. Lead paint may be present, and is a known safety hazard, especially to children but also to adults. It may cause brain damage and retarded mental and physical development, among other things. The paint found in and around this structure appeared to be intact and and most likely encapsulated by more recent layers of paint that's not lead-based. However, recommend following precautions as described in the following links to Consumer Products Safety Commission website articles regarding possible lead paint.

    What You Should Know About Lead Based Paint in Your Home: Safety Alert - CPSC Document #5054

    CPSC Warns About Hazards of "Do lt Yourself" Removal of Lead Based Paint: Safety Alert - CPSC Document #5055
    52) Sink drains slowly. Recommend clearing drain on left side of kitchen sink.
    53) Damage to the windows on the side wall of the living room was viewed. This is consistent with water entry. These windows are also lacking a locking device.

    Photo 13
     
    54) One or more light fixtures are inoperable. This may be due to burnt out bulbs. Recommend having a qualified electrician evaluate and repair or replace fixture(s) as necessary.
    55) Walking on some sections of the floor results in squeaking or creaking noises. This is usually the result of substandard construction practices where the subfloor decking isn't adequately fastened (insufficient glue) to the framing below. In most cases, this is an annoyance only rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on there being finished hardwood floors, carpeting over the subfloor, and/or clear access to the underside of the subfloor. Recommend having a qualified contractor evaluate and repair as necessary.
    56) Screen(s) missing in one or more windows. Window(s) may not provide ventilation during months when insects are active. Recommend installing screens.
    57) One or more doors don't latch when closed. Recommend making repairs as necessary such as adjusting latch plates or lockset mechanisms.
    58) One or more doors bind in their jambs. Recommend making repairs as necessary so they close easily.
    59) Vinyl floor tiles are installed in some rooms that are "wet areas" (kitchen, bathrooms, laundry room, etc.). This is a poor choice of floor material since water can seep through the cracks and infiltrate the wooden subfloor beneath. Recommend replacing vinyl floor tiles with a waterproof floor such as sheet vinyl where necessary. No exterior drain was viewed at the laundry room
    60) Window(s) in the living room do not have a locking mechanism.
    61) Caulk needs repair around the base one or more tub faucets. Recommend applying a bead of caulk around the base of tub faucets where necessary.
    62) Recommend caulking around the base of the tub faucet to prevent water damage to wall materials.
    63) The range did not respond to normal controlls. If this unit is included with the house, you may want to ask the seller about removing/replacing it.
    64) One or more faucets are reverse-plumbed, where hot water flows when what should be the cold water faucet is operated, or when the single faucet is set to the cold setting, and vica versa.
    65) Minor cracks found in ceiling. These are only a cosmetic concern. No action is recommended.
     
    Water heater Return to table of contents  
    Estimated age: Unknown
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Brand & model: Bradford White
    66) This water heater requires a 6" clearance from combustibles at the top. The gas lines are installed to close to this unit and should be properly installed by a qualified HVAC technician.

    Photo 18
     
    67) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be approaching this age. Recommend budgeting for a replacement in the near future.
     
    Attic Return to table of contents  
    Inspection method: Traversed
    Ceiling structure: Attic Structure
    Insulation material: Rockwool loose fill, Cellulose roll or batt
    Insulation depth: 4"
    68) Non-metallic sheathed wiring is unsupported or inadequately supported. This type of wiring should be attached to runners or to solid backing with fasteners at intevals of 4 1/2 ft. or less. Recommend having a qualified electrician evaluate and repair as necessary.
    69) Insulation in attic is substantially less than an R30 rating. Recommend installing additional insulation for better energy efficiency.

    Photo 31
     
    70) Several gaps were viewed from inside the attic area. This is consistent with improperly/damaged roof flashing and a potential water entry point. This should be evaluated by a qualified roofing contractor for repairs.

    Photo 30
     
    71) Insulation is missing or uneven in some areas. Recommend installing additional insulation where necessary.
      72) This photo shows an improper support. You can see this wood member is under a significant amount of stress and unable to properly support this section of the roof. I recommend a licensed builder for repairs/replacement.

    Photo 28
     
     
    Crawl space Return to table of contents  
    Inspection method:
    Insulation material underneath floor above: None visible
    Pier or support post material: Concrete
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    Vapor barrier present: No
    73) A jack is being used to support the section directly under the house furnace. This is not only an improper supporting means, the wood the jack is resting on is severely water damaged and not able to support the weight of this unit. This should be evaluated by a licensed HVAC technician.

    Photo 37
     
    74) Cover plate(s) are missing from one or more electric receptacle boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard and poses a risk of both fire and shock. Recommend installing cover plates over receptacle boxes where missing.

    Photo 40
     
    75) No insulation under floor in crawl space. Recommend installing R19 or better (6" thick fiberglass batt) insulation below floor for energy efficiency.
    76) Vapor barrier is missing. Recommend installing 6 mil polyethylene with seams overlapped at least 24" so no soil is exposed in the crawlspace.
    77) The water supply pipes in the crawl space are uninsulated. Recommend insulating these pipes for better energy efficiency and to prevent water pipes from freezing.
    78) The heating and/or cooling ducts in the crawl space are uninsulated. Recommend installing R19 insulation or better on ducts for better energy efficiency.
    79) Unconventional methods of supporting the heating ductwork were viewed in the attic area. This should be repaired by a qualified HVAC technician.

    Photo 38

    Photo 39
    80) Moisture is present throughout the crawlspace. Also mortar damage was viewed in several areas. This is consistent with damage caused by improperly installed downspouts.

    Photo 32

    Photo 42
    81) Moisture damage to this section is being caused by excessive moisture present in the crawlspace.

    Photo 33
     
    82) Low head clearance prevented me from completing a thorough inspection of the crawlspace area.

    Photo 34
     
     
    General information Return to table of contents  
    Overview: Be sure to ask the seller about the range and the age of the roof. Also remember to find out if a permit was pulled when constructing the garage.
    Structures inspected: House and Garage
    Report number: 106
    Time started: 10:00 am
    Time finished: 1:15 pm
    Inspection Fee: 200.00 PAID
    Present during inspection: N/A
    Occupied: No
    Age of building: Unknown
    Type of building: Single family
    Weather conditions: Clear
    Temperature: Warm
    Ground condition: Dry
    Foundation type: Crawlspace
    The following items are excluded from this inspection: Items listed in contract.
    The following contract is completed prior to the inspection.
    www.stepbystepinspections.com

    THIS CONTRACT LIMITS OUR LIABILITY?PLEASE READ CAREFULLY

    Address _______________________________________________________________ Report# ___________

    Client: __________________________________________________________________________________

    I (Client) hereby request a visual inspection of the structure at the above address to be conducted by: ______________________

    For my sole use and use and benefit. I warrant that I will read the following agreement carefully. I understand that I am bound by all the terms of this contract.
    Initial Here _________ _________

    SCOPE OF INSPECTION
    The scope of the inspection and report is a limited visual inspection of the general systems and components of the home to identify any system or components listed in the report which may be in need of immediate major repair. The inspection will be performed in compliance with generally accepted standards of practice, a copy of which is ╬ available upon request ╬ included with this report. The scope of the inspection is limited to the items listed within the content of this report.

    OUTSIDE THE SCOPE OF THE INSPECTION
    Any area which is not exposed to view, is concealed, or is inaccessible because of soil, walls, floors, carpets, ceilings, furnishing, or any other thing is not included in the scope of this inspection.
    This inspection does not include any destructive testing or dismantling. Client agrees to assume all the risk for all conditions which are concealed from view at the time of the inspection.
    This is not a home warranty, guarantee, insurance policy or substitute for real estate transfer disclosures which may be required by law.
    Whether or not they are concealed, the following ARE OUTSIDE THE SCOPE OF THIS INSPECTION.
    ?Building code or zoning ordinance violations.
    ?Geological stability or soils condition.
    ?Structural stability or engineering analysis.
    ?Termites, pests or other wood destroying organisms.
    ?Asbestos,radon,formaldehyde,lead,water/air quality, electromagnetic radiation or any environmental hazards.
    ?Building value appraisal or cost estimates.
    ?Condition of detached buildings.
    ?Pools or spas bodies and underground piping.
    ?Specific components noted as being excluded on the individual system inspection forms.
    ?Private water of private sewage systems.
    ?Saunas, steam baths, or fixtures and equipment.
    ?Radio-controlled devices, automatic gates, elevators, lifts, dumbwaiters and thermostatic or time clock controls.
    ?Water softener/purifier systems or solar heating systems.
    ?Furnace heat exchangers, freestanding appliances, security alarms or personal property.
    ?Adequacy of efficiency of any system or component.
    ?Prediction of life expectancy of any item.
    (Some of the above items may be included in this inspection for additional fees. Check with your inspector)

    Your inspector is a home inspection generalist and is not acting as a licensed engineer or expert in any craft or trade. If your inspector recommends consulting other specialized experts, client must do so at client?s expense.

    I have read and agree to the above Scope of Inspection.

    Initial Here ___________ ___________
    ARBRITRATION: Any dispute concerning the interpretation of this agreement or arising from this inspection and report, except one for inspection fee payment, shall be resolved informally between the parties or by arbitration conducted in accordance with the rules of the recognized Arbitration Association except- Page 1of2

    that the parties shall select an arbitrator who is familiar with the home inspection industry. The Arbitrator shall conduct summary judgment motion and enforce full discovery rights as a court would as provided in civil proceeding by legal code.

    I have read and agree to the above arbitration clause: _______ ________

    CONFIDENTIAL REPORT: The inspection report to be prepared for Client is solely and exclusively for Client?s own information and may not be relied upon by any other person. Client agrees to maintain the confidentially of the inspection report and agrees not to disclose any part of it to any other person. Client may distribute copies of the inspection report to the seller and the real estate agents directly involved in this transaction, but said persons are not specifically intended beneficiaries of this Agreement or the inspection report. Client and Inspector do not in any way intend to benefit said seller or the real estate agents directly or indirectly through this Agreement or the inspection report. Client agrees to indemnify, defend, and hold Inspector harmless from any third party claims arising out of Client?s unauthorized distribution of the inspection report.
    ATTORNEY?S FEES: The prevailing party in any dispute arising out of this agreement, the inspection, or report(s) shall be awarded all attorneys? fees, arbitrator and other costs.

    SEVERABILITY: Client and Inspector agree that should a Court of Competent Jurisdiction determine and declare that any portion of this contract is void, voidable able or unenforceable, the remaining provisions and portions shall remain in full force and effect.

    DISPUTES: Client understands and agrees that any claim for failure to accurately report the visually discernible condition at the Subject Property, as limited herein above, shall be made in writing and reported to the Inspector within ten business days of discovery, Client understands and agrees that any failure to notify the inspector as stated above shall constitute a waiver of any and all claims for said failure to accurately report the condition in question.

    LIMITATION ON LIABILITY
    INSPECTOR?S LIABILITY FOR MISTAKES OR OMISSIONS IN THIS INSPECTION REPORT IS LIMITED TO A REFUND OF THE FEE PAID FOR THIS INSPECTION AND REPORT. THE LIABILITY OF INSPECTOR?S PRINCIPALS, AGENTS, AND EMPLOYEES IS ALSO LIMITED TO THE FEE PAID. THIS LIMITATION APPLIES TO ANYONE WHO IS DAMAGED OR HAS TO PAY EXPENSES OF ANY KIND BECAUSE OF MISTAKES OR OMISSIONS IN THIS INSPECTION AND REPORT. THIS LIABILITY LIMITATION IS BINDING ON CLIENT AND CLIENT?S SPOUSES, HEIRS, PRINCIPALS, ASSIGNS AND ANYONE ELSE WHO MAY OTHERWISE CLAIM THROUGH CLIENT. CLIENT ASSUMES THE RISK OF ALL LOSSES GREATER THAN THE FEE PAID FOR THE INSPECTION. CLIENT AGREES TO IMMEDIATELY ACCEPT A REFUND OF THE FEE AS FULL SETTLEMENT OF ANY AND ALL CLAIMS WHICH MAY EVER ARISE FROM THIS INSPECTION.

    LIMITED LIABILITY INSPECTION FEE $______________