Inspector: Vince Santos

 

Home Inspection Report
Client(s): Charles D.
Property address: 16312 Ironstone Lane
Romulus, MI
Inspection date: Saturdday, April 15, 2006
This report published on 4/16/2006 3:15:05 PM EDT

Thank you for allowing me to serve your inspection needs Chan. If you have any questions give me a call.


How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and shown in bold type. Items of concern follow descriptive information and are shown as follows:
SafetyPoses a risk of injury or death 
Major defectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 
Concern items are sorted by the types listed above.  Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Kitchen
Living Room
Interior rooms
Master Bedroom
Master Bath
Bedroom 2
Bathroom 2
Basement Bathroom 3
Basement


General information Return to table of contents  
Report number: 41506
Structures inspected: Home/Attached Garage
Type of building: Single family
Age of building: 1992
Time started: 10:15
Time finished: 1:10
Inspection Fee: 150.00 PAID
Payment method: Cash
Present during inspection: Client(s), Realtor(s)
Occupied: No
Weather conditions: Clear
Temperature: Warm
Ground condition: Dry
Front of structure faces: East
Main entrance faces: East
Foundation type: Finished basement
The following items are excluded from this inspection: Irrigation systemItems listed as outside the scope in the NACHI SOP.
1)
2) The natural gas service was turned off. As a result, some appliances such as water heater(s), forced air furnace(s), gas fireplace(s), stove(s), range(s) and/or gas supply lines weren't fully evaluated. The inspector was unable to test for gas leaks.
 
Exterior Return to table of contents  
Footing material: Not visible
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Vinyl
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel
3) One or more trip hazards were found in sidewalk and/or patio sections due to cracks, settlement and/or heaving. A qualified contractor should evaluate and repair or replace sidewalk and/or patio sections as necessary to eliminate trip hazards.

Photo 34  
4) One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Outlet at the rear of the home.

Photo 1  
5) One or more gutters are poorly sloped so that significant amounts of water accumulate in them rather than draining through the downspouts. This can cause gutters to overflow, especially when organic debris such as leaves or needles have accumulated in them. A qualified contractor should evaluate and make repairs as necessary, such as correcting the slope in gutters or installing additional downspouts and extensions if necessary.
6) Fascia boards are damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.

Photo 6  
7) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.

Photo 2  

Photo 38  
8) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

Photo 4  

Photo 37  
9) One or more gutters are damaged. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. A qualified contractor should replace or repair gutters where necessary.

Photo 36  
10) One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply. See http://www.quickrete.com/catalog/HydraulicWater-StopCement.html for an example.
  • Resilient caulks (easy to apply). See http://www.quickrete.com/catalog/GrayConcreteRepair.html for an example.
  • Epoxy sealants (both a waterproof and structural repair). See http://www.mountaingrout.com/ for examples of these products.

    Photo 5  
  • 11) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.

    Photo 35  
    12) Minor cracks were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
     
    Roof Return to table of contents  
    Roof inspection method: Traversed
    Roof type: Cross-hipped
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 1992
    Gutter & downspout material: Plastic
    Roof ventilation: Adequate
    13) The roof surface material is beyond or at the end of its service life and needs replacing now. The client(s) should consult with a qualified roofing contractor to determine replacement options and costs.

    Photo 7  

    Photo 8  

    Photo 9  

    Photo 10  

    Photo 11  
    14) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

    Photo 7  

    Photo 12  
     
    Garage Return to table of contents  
    15) No infared "photo eye" devices are installed for the vehicle door's electric door opener. They've been required on all vehicle door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
    16) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 13  
      17) An excessive voltage drop was found at one outlet in the garage. A qualified electrician should make repairs as necessary.

    For more information on voltage drop, please visit the following site.

    http://www.psihq.com/iread/faqvolt.htm

    Photo 14  
     
    Attic Return to table of contents  
    Inspection method: Traversed
    Roof structure type: Trusses
    Ceiling structure: Trusses
    Insulation material: Fiberglass roll or batt
    Insulation depth: 6.5"
    Insulation estimated R value: R19
    18) The ceiling insulation's R rating is significantly less than what's recommended for this area. Recommend having a qualified contractor install additional insulation as per standard building practices for better energy efficiency.
     
    Electric service Return to table of contents  
    Primary service type: Underground
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 100
    Service voltage (volts): 120/240
    Location of main service switch: Basement
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Aluminum
    System ground: Cold water supply pipes
    Main disconnect rating (amps): 100
    Branch circuit wiring type: Non-metallic sheathed
    Solid strand aluminum branch circuit wiring present: No
    19) One or more overcurrent protection devices (circuit breakers or fuses) are "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.

    Photo 31  
    20) One or more clamps that secure the electric service's grounding electrode and/or bonding conductor(s) to pipe(s) are improperly installed. Grounding and/or bonding may be inadequate as a result and may be a safety hazard for shock. A qualified electrician should evaluate and repair as necessary.

    Photo 25  
     
    Water heater Return to table of contents  
    Estimated age: 1997
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Manufacturer: Kenmore
    21) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    22) The temperature-pressure relief valve is leaking. A qualified plumbing contractor should replace this valve.

    Photo 28  
    23) The water heater was turned off at the time of the inspection. For example, circuit breaker turned off, gas supply turned off or pilot light turned off. The inspector was unable to fully evaluate the water heater.
     
    Heating and cooling Return to table of contents  
    Estimated age: 1997- Be sure to ask seller about exact age.
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air
    Primary A/C energy source: Electric1992
    Primary Air conditioning type: Split system
    Distribution system: Sheet metal ducts
    Manufacturer: Bryant
    Filter location: At the base of the furnace
    Last service date: Unknown
    24) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit: http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
    25) The estimated useful life for air conditioning compressors is 8 to 15 years. This unit appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    26) The outside condensing unit is not level. Damage may occur if it is more than ten degrees off from level. A qualified contractor should evaluate and make repairs as necessary, such as replacing the pad that the condensing unit is installed on.

    Photo 3  
    27) The outdoor air temperature was below 60 degrees Fahrenheit during the inspection. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
    28) The furnace was shut off at the time of the inspection. For example, the gas supply was shut off, the pilot light was out, and/or the electric supply was turned off. As a result, the inspector was unable to fully evaluate this unit.
     
    Plumbing and laundry Return to table of contents  
    Location of main water shut-off valve: Basement
    Location of main water meter: Basement
    Location of main fuel shut-off: Exterior Left
    Water service: Public
    Service pipe material: Copper
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
    29) The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
    30) Stains were found in one or more sections of drain and/or waste pipes. Recommend monitoring these areas in the future, and if leaks are found, have a qualified plumber evaluate and repair as necessary. Alternatively, the client(s) may wish to have a qualified plumber evaluate now and repair if necessary.

    This leak is directly under the hallway bathroom toilet.

    Photo 30  
     
    Fireplaces, woodstoves and chimneys Return to table of contents  
    Fireplace type: Masonry
    Chimney type: Metal
    31) A significant amount of creosote (1/8 inch or more) is visible in the fireplace flue. A qualified chimney service contractor should inspect, clean, and repair if necessary now and annually in the future.
    32) All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.

    Photo 17  
     
    Kitchen Return to table of contents  
    33) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.

    Photo 16  
    34) The range can tip forward, and no anti-tip bracket appears to be installed. This is a safety hazard since the range may tip forward when weight is applied to the open door, such as when a small child climbs on it, or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free standing ranges since 1985. An anti-tip bracket should be installed to eliminate this safety hazard. For more information, visit http://www.hgtv.com/hgtv/remodeling/article/0,1797,HGTV_3659_2017492,00.html
    35) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

    Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.
     
    Living Room Return to table of contents  
    36) No smoke alarms are visible. This is a safety hazard. A qualified electrician should install smoke alarms as per standard building practices (functioning one exists in hallways leading to bedrooms, and in each bedroom, etc.). For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    37) An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    38) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    39) Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the subfloor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering, and the access to the underside of the subfloor. Recommend having a qualified contractor evaluate and repair as necessary.
    40) Lock mechanisms on one or more windows are missing and/or damaged so that they are inoperable. Repairs should be made by a qualified contractor or service technician so that windows lock and unlock easily.
     
    Interior rooms Return to table of contents  
    41) One or more doors have no lockset installed. Locksets should be installed where missing.

    Photo 15  
     
    Master Bedroom Return to table of contents  
    42) Lock mechanisms on one or more windows are missing and/or damaged so that they are inoperable. Repairs should be made by a qualified contractor or service technician so that windows lock and unlock easily.

    Photo 18  
     
    Master Bath Return to table of contents  
    43) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.

    Photo 19  
    44) The door hinge screws are loose and preventing the door from closing properly. Recommend tightening the screws to allow for proper function.

    Photo 20  
     
    Bedroom 2 Return to table of contents  
    45) The closet doors appear to be improperly installed. While the doors stay in place, they are difficult to operate and require the proper hardware and adjustment for proper function.
     
    Bathroom 2 Return to table of contents  
    46) No ground fault circuit interrupter (GFCI) protection device is visible for the electric supply to the jetted tub. If no GFCI protection exists, then this is a safety hazard due to the risk of shock. A qualified electrician should evaluate and install GFCI protection if none is installed.

    Photo 33  
    47) One or more toilets are loose. A qualified contractor should remove the toilet(s) for further evaluation and repairs if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
    48) The toilet handle is missing and should be repaired or replaced as necessary.

    Photo 32  
     
    Basement Bathroom 3 Return to table of contents  
    49) Water damage and organic growth was found on the walls throughout the bathroom walls. Recommend further tests be conducted by a mold specialist to determine proper removal and repairs necessary.

    Photo 26  
    50) The bathroom door did not close due to warped trim. This damage appears to be caused by moisture swelling the trim. Recommned repairs by a licensed contractor.

    Photo 27  
     
    Basement Return to table of contents  
    Insulation material underneath floor above: None visible
    Pier or support post material: Not visible
    Beam material: Steel
    Floor structure above: Solid wood joists
    51) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains and/or efflorescence on the foundation or floor, water stains at bases of support posts, etc. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.

    Water damage and organic growth was found on the walls throughout the basement walls. Recommend further tests be conducted by a mold specialist to determine proper removal and repairs necessary.

    Photo 24  

    Photo 26  

    Photo 29  
  • 52) The floor structure was not visible due to ceiling tiles being installed preventing an inspection of the floor system and plumbing.
    53) Standing water and/or wet areas were found in one or more sections of the basement. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. A qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.

    Photo 23  
  • 54) One or more electric receptacles appear to have no power. Recommend asking the property owner(s) about this. Switches may need to be operated to make some receptacles energized. If necessary, a qualified electrician should evaluate and make repairs as necessary.

    Photo 21  

    Photo 22  
     
    The following contract is completed prior to the inspection.
    www.stepbystepinspections.com

    THIS CONTRACT LIMITS OUR LIABILITY?PLEASE READ CAREFULLY

    The address of the property is: ______________________________________________________________________________________________.

    Fee for the home inspection is $____________________. INSPECTOR acknowledges receiving a deposit of $_________________ from CLIENT.

    THIS AGREEMENT made this _____________ day of _______________________________________________________, 200__, by and between

    __________________________________________________________ (Hereinafter INSPECTOR) and the undersigned (hereinafter CLIENT), collectively referred to herein as the parties. The Parties Understand and Voluntarily Agree as follows:

    1. INSPECTOR agrees to perform a visual inspection of the home/building and to provide CLIENT with a written inspection report identifying the defects that INSPECTOR both observed and deemed material. INSPECTOR may offer comments as a courtesy, but these comments will not comprise the bargained-for report. The report is only supplementary to the seller’s disclosure.
    2. Unless otherwise inconsistent with this Agreement or not possible, INSPECTOR agrees to perform the inspection in accordance to the current Standards of Practice of the National Association of Certified Home Inspectors posted at http://www.nachi.org/sop.htm. CLIENT understands that these standards contain certain limitations, exceptions, and exclusions.
    3. The inspection and report are performed and prepared for the use of CLIENT, who gives INSPECTOR permission to discuss observations with real estate agents, owners, repairpersons, and other interested parties. INSPECTOR accepts no responsibility for use or misinterpretation by third parties. INSPECTORS inspection of the property and the accompanying report are in no way intended to be a guarantee or warranty, express or implied, regarding the future use, operability, habitability or suitability of the home/building or its components. Any and all warranties, express or implied, including warranties of merchantability and fitness for a particular purpose, are expressly excluded by this Agreement.

    4. INSPECTOR assumes no liability for the cost of repair or replacement of unreported defects or deficiencies either current or arising in the future. CLIENT acknowledges that the liability of INSPECTOR, its agents, employees, for claims or damages, costs of defense or suit, attorneys fees and expenses and payments arising out of or related to the INSPECTORS negligence or breach of any obligation under this Agreement, including errors and omissions in the inspection or the report, shall be limited to liquidated damages in an amount equal to the fee paid to the INSPECTOR, and this liability shall be exclusive. CLIENT waives any claim for consequential, exemplary, special or incidental damages or for the loss of the use of the home/building even if the CLIENT has been advised of the possibility of such damages. The parties acknowledge that the liquidated damages are not intended as a penalty but are intended (i) to reflect the fact that actual damages may be difficult and impractical to ascertain; (ii) to allocate risk among the INSPECTOR and CLIENT; and (iii) to enable the INSPECTOR to perform the inspection at the stated fee.

    5. INSPECTOR does not perform engineering, architectural, plumbing, or any other job function requiring an occupational license in the jurisdiction where the inspection is taking place, unless the inspector holds a valid occupational license, in which case he/she may inform the CLIENT that he/she is so licensed, and is therefore qualified to go beyond this basic home inspection, and for additional fee, perform additional inspections beyond those within the scope of the basic home inspection. Any agreement for such additional inspections shall be in a separate writing or noted here: ______________________________________________________________________________________________________________________.

    6. In the event of a claim against INSPECTOR, CLIENT agrees to supply INSPECTOR with the following: (1) Written notification of adverse conditions within 14 days of discovery, and (2) Access to the premises. Failure to comply with the above conditions will release INSPECTOR and its agents from any and all obligations or liability of any kind.
    7. The parties agree that any litigation arising out of this Agreement shall be filed only in the Court having jurisdiction in the County in which the INSPECTOR has its principal place of business. In the event that CLIENT fails to prove any adverse claims against INSPECTOR in a court of law, CLIENT agrees to pay all legal costs, expenses and fees of INSPECTOR in defending said claims.
    8. If any court declares any provision of this Agreement invalid or unenforceable, the remaining provisions will remain in effect. This Agreement represents the entire agreement between the parties. All prior communications are merged into this Agreement, and there are no terms or conditions other than those set forth herein. No statement or promise of INSPECTOR or its agents shall be binding unless reduced to writing and signed by INSPECTOR. No change or modification shall be enforceable against any party unless such change or modification is in writing and signed by the parties. This Agreement shall be binding upon and enforceable by the parties and their heirs, executors, administrators, successors and assignees. CLIENT shall have no cause of action against INSPECTOR after one year from the date of the inspection.
    9. Payment of the fee to INSPECTOR (less any deposit noted above) is due upon completion of the on-site inspection. The CLIENT agrees to pay all legal and time expenses incurred in collecting due payments, including attorneys fees, if any. If CLIENT is a corporation, LLC, or similar entity, the person signing this Agreement on behalf of such entity does personally guaranty payment of the fee by the entity.
    CLIENT HAS CAREFULLY READ THE FOREGOING, AGREES TO IT, AND ACKNOWLEDGES RECEIPT OF A COPY OF THIS AGREEMENT.

    _________________________ _________________________
    FOR INSPECTOR CLIENT OR REPRESENTATIVE