Property Inspection Report
Client(s): Sample
Property address: Atlanta, Ga
Inspection date: 2008
This report published on 7/10/2008 9:55:21 AM EDT

View summary page

This report is the exclusive property of Shawford Property Inspections, LLC and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Basement
Grounds
Exterior
Roof
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Inspector: Denny Ford
Positive Comments: Decks are new and well attached, missing only the flashing. There appears to have been extensive work and money put into the remodel on the upper floors. All electric, plumbing and HVAC appear to have been updated (except for missing condenser units).
Structures inspected: 567 Boulevard, Atlanta, Ga 30312
Type of building: Single family
Age of building: 88
Time started: 12:30
Time finished: 3:00
Inspection Fee: 300.00
Payment method: Cash
Present during inspection: Client(at times), Realtor(at beginning)
Occupied: No
Weather conditions: Clear
Temperature: Warm
Ground condition: Damp
Front of structure faces: East
Main entrance faces: East
Foundation type: Semi-Finished Basement
Type of building: Single family


1)   House was in a state of partial remodel, with most of the upstairs completed except for painting and other finishes.

The basement had significant water damage and existing drywall had be cut off to eliminate the water and allow the area to dry.

2)   The natural gas service was turned off. As a result, some appliances such as water heater(s), forced air furnace(s), gas fireplace(s), stove(s), range(s) and/or gas supply lines weren't fully evaluated. The inspector was unable to test for gas leaks.
3)   The water service wasn't turned on during the inspection. As a result, plumbing supply, drain and waste lines, fixtures, and some appliances such as water heaters weren't fully evaluated.
4)   Electricity was not available during the inspection (service turned off or not fully installed, main disconnect tripped, etc.). As a result, branch circuit wiring, fixtures such as lights and fans, switches, ground fault circuit interrupter (GFCI) devices, arc fault circuit interrupter (AFCI) devices, and some appliances such as water heaters, forced air furnaces, heat pump or air conditioning units, and kitchen appliances weren't fully evaluated.
 
Basement Return to table of contents
Insulation material underneath floor above: None
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Solid wood joists
5)   The basement has water damage and an effort has been made to remove the damaged material, thus exposing the brick foundation.

It appears that the foundation has significant damage and should be referred to a structural engineer to determine whether or not this can be fixed and to what extent it impacts the structure.

Photo 6  

Photo 7  

Photo 8  

Photo 9  

6) Standing water and/or wet areas were found in one or more sections of the basement. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. A qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.

    Photo 13  

    Photo 14  

     
    Grounds Return to table of contents
    Footing material: Not visible
    Foundation material: Brick; Some concrete block was present, and in one place, framing was being used for foundation
    Driveway material: Poured in place concrete
    Sidewalk material: Brick
    7)   Cracks, deterioration, leaning and/or bowing were found in one or more retaining walls. Because of the height or proximity to foundations or property lines, a qualified structural engineer should evaluate to determine what repairs are necessary. Repairs should be made by a qualified contractor.

    Retaining wall on North side of house has a significant lean and has been 'repaired' by using a steel band.

    Photo 1  
     

    8) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.

    Photo 12  
     

    9)   Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.
    10)   Minor cracks were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
     
    Exterior Return to table of contents
    Wall covering: Wood clapboard
    Apparent wall structure: Wood frame
    Exterior door material: Solid core steel
    11) Flashing is missing from above one or more deck ledger boards. This can cause moisture to accumulate between the ledger board(s) and the structure. Rot may result in this area and cause the ledger board fasteners to fail. The deck may separate from the structure in this event and poses a significant safety hazard. A qualified contractor should install flashing above ledger board(s) where necessary. For more information on installing deck ledger boards visit: http://www.hometime.com/Howto/projects/decks/deck_4.htm

    And for more information on building safe decks in general, visit: http://www.thisoldhouse.com/toh/knowhow/exteriors/article/0,16417,212625,00.html

    12)   Cover plate(s) are broken at one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be replaced where necessary.

    Photo 5  
     

    13)   One or more exterior disconnect switches, such as for a heat pump or air conditioner compressor unit, have exposed wiring or components when the cover is opened or removed. This is a safety hazard due to the risk of shock, especially for children. Because these boxes rarely need to be opened (usually only for maintenance), recommend installing a lock on box cover(s) to reduce the risk of shock.
    14) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

    Photo 4  
     

    15) There are gaps in the siding in someplaces. Gaps allow the entrance of water and unwanted pests. Evaluation and repair by a qualified professional is recommended.

    Photo 11  
     

    16) Recommend cleaning deck(s) and railing(s) and treating with a preservative claiming to waterproof, block ultraviolet light, and stop mildew. Consumer Reports recommends these products:

  • Cabot Decking Stain and PTW Stain
  • Olympic Water Repellent Deck Stain
  • Thompson's House and Deck Stain
  • Wolman PTW Deck Stain
  • Akzo Sikkens Cetol DEK
  • Benjamin Moore Moorwood Clear Wood Finish
  • DAP Woodlife Premium
  • Olympic Natural Look Protector Plus
     
    Roof Return to table of contents
    Roof inspection method: Viewed from ground with binoculars
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 10 years
    Gutter & downspout material: Aluminum
    Roof ventilation: Adequate
    17) Trees overhanging and touching roof. Should be trimmed by a qualfied professional.

    Photo 2  
     

     
    Attic Return to table of contents
    Inspection method: Viewed from hatch
    Roof structure type: Rafters
    Ceiling structure: Ceiling beams
    Insulation material: Fiberglass loose fill
     
    Electric service Return to table of contents
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main service switch: Outside - South Wall
    Location of sub panels: Front Bedroom, Basement West wall
    Service entrance conductor material: Aluminum
    System ground: Cold water supply pipes
    Main disconnect rating (amps): 200
    Branch circuit wiring type: Non-metallic sheathed
    Solid strand aluminum branch circuit wiring present: Can't verify
    Smoke detectors present: Yes
    18)   One or more screws are missing from the main service panel cover and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.
    19)   Many outlets open. House is still in a state of remodel. Unable to verify grounding or GFCI, although some were present.
     
    Water heater Return to table of contents
    Estimated age: New
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Manufacturer: General Electric
    Number of water heaters: 2
    20)   Gas flue for water heaters (2) and rurnace were run in such a way that part of the run was downhill. This could result in a CO problem.
    21) The temperature-pressure relief valve drain line is routed so as to empty into the crawl space. Water may accumulate in the crawl space if the valve develops a leak. A qualified plumber should re-route the drain line so as to drain outside.
    22)   The water heater was turned off at the time of the inspection. For example, circuit breaker turned off, gas supply turned off or pilot light turned off. The inspector was unable to fully evaluate the water heater.
     
    Heating and cooling Return to table of contents
    Estimated age: New
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air
    Primary A/C energy source: Electric
    Primary Air conditioning type: Split system
    Distribution system: Flexible ducts
    Number of air handlers: 3
    23)   Electric and Gas were turned off. Was not possible to determine working condition of the furnaces.

    The condenser units were missing (stolen?) and will have to be replaced.

    New pads for the condensers should be installed to provide a supportable and level location for the condenser units.

    Photo 3  
     

     
    Plumbing and laundry Return to table of contents
    Location of main water shut-off valve: Basement - East wall of house
    Location of main water meter: Street
    Location of main fuel shut-off: SouthEast corner of house
    Water service: Public
    Service pipe material: Copper
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
    24)   Water supply was off, therefore the inspector could not evaluate the plumbing equipment.

    It should be noted the supply pipe and waste pipe appeared to be new.

     
    Kitchen Return to table of contents

    25)   No appliances, electric, gas or water.
     
    Bathrooms Return to table of contents

    26)   Bathrooms have been recently redone.

    No electric or water present and could not evaluate.

     
    Interior rooms Return to table of contents

    27)   Master bedroom floor had several humps. The basement ceiling was finished and the inspector was unable to determine the exact cause of the floor issues. The floor did not appear to give, but it is recommended that the floor be evaluated by a qualified professional.

    Photo 10  
     

     