Shawford Property Inspections, LLC

Website: http://www.shawfordhomeinspections.com
Email: denny@shawfordhomeinspections.com
Phone: (404) 374-7070

 

Property Inspection Report
Client(s): Sample
Property address: Atlanta, Ga
Inspection date: June 2009
This report published on 7/7/2009 11:12:27 AM EDT

View summary page

This report is the exclusive property of Shawford Property Inspections, LLC and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Grounds
Exterior
Roof
Attic
Electric service
Water heater
Heating and cooling
Crawl/Unfinished Basement
Plumbing and laundry
Downstairs Bath
Upstairs Bath
Kitchen
Interior rooms

 
General information Return to table of contents
Inspector: Denny Ford
Type of building: Single family
Time started: 09:00
Inspection Fee: 250.00
Occupied: No
Weather conditions: Clear
Temperature: Warm
Ground condition: Dry
Front of structure faces: East
Main entrance faces: East
Foundation type: Crawlspace
1)   This property has one or more fuel burning appliances, and no carbon monoxide alarms are visible. This is a safety hazard. Recommend installing one or more carbon monoxide alarms as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
2)   Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
    3)   The water service wasn't turned on during the inspection. As a result, plumbing supply, drain and waste lines, fixtures, and some appliances such as water heaters weren't fully evaluated.
     
    Grounds Return to table of contents
    Footing material: Not visible
    Foundation material: Concrete block
    Driveway material: Asphalt
    Sidewalk material: None
    4) One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks.

    Photo 4  
     

    5) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.

    Photo 6  

    Photo 9  

    Photo 11  
     

    6)   Unable to locate the foundation drain outlet; therefore, visual inspectiion not made.
     
    Exterior Return to table of contents
    Wall covering: Composition wood clapboard
    Apparent wall structure: Wood frame
    Exterior door material: Solid core wood
    7)   One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.

    Photo 7  
     

    8)   One or more light fixtures are loose or installed in a substandard way. A qualified contractor or electrician should evaluate and make repairs as necessary so light fixtures are securely mounted and installed in accordance with the manufacturer's installation instructions.

    Photo 12  
     

    9)   Ceiling fan located on screened porch in "wet" or "damp" location has no visible rating for use in wet locations. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and replace fan fixture as necessary and as per standard building practices.

    Photo 13  
     

    10)   Trip hazard(s) exist at stairs due to non-uniform riser heights. Standard building practices call for riser heights not to vary more than 3/8 inch on a flight of stairs. At a minimum, the client(s) should be aware of this hazard, especially when guests who are not familiar with the stairs are present. Ideally a qualified contractor should evaluate and repair or replace stairs so all riser heights are within 3/8 inch of each other.

    Photo 1  
     

    11) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

    Photo 8  
     

    12) The gutter is missing on the front corner of the house. This can result in water accumulating around the structure's foundation, or in the crawl spaces. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. A qualified contractor should install gutters and downspouts where missing. Also, extensions such as splashblocks or tie-ins to underground drain lines should be installed as necessary to carry rain water away from the house.

    Photo 5  
     

    13)   Gaps exist at one or more openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and entry by vermin.

    Photo 10  
     

    14)   One or more crawl space vent screens are missing. Animals such as vermin or pets may enter the crawl space and nest, die and/or leave feces and urine. A qualified contractor should install screens where missing using screen material such as "hardware cloth" with 1/4 inch minimum gaps.

    Photo 3  
    Screen by AC condenser. Most of the vent screens on the house are not adequate
     

     
    Roof Return to table of contents
    Roof inspection method: Viewed from ground with binoculars
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Gutter & downspout material: Aluminum
    Roof ventilation: Inadequate
    15)   The siding on one or more exterior walls above lower roof sections is in contact with or has less than a one inch gap between it and the roof surface below. A gap of at least one inch is recommended so water isn't wicked up into the siding from the shingles below, and also to provide room for additional layers of roofing materials when the current roof surface fails. Recommend having a qualified contractor make repairs as necessary, such as trimming siding, so at least a one inch gap exists between the siding and the roofing below where necessary.

    Photo 15  

    Photo 16  

    16) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.
    17) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.

    Photo 2  
     

    18) Composition tabbed shingles are installed on one or more roof sections with a slope less than 3/12 (three inches rise for every 12 inches run). Most shingle manufacturers won't warranty composition shingles if used on a roof with a slope less than 3/12. At a minimum, the client(s) should consult with a qualified roofing contractor regarding this and monitor these roof section(s) and interior spaces below for leaks in the future. Ideally, or if leaks occur, a qualified roofing contractor should replace the roof surface with materials intended for low slopes such as a "torch down" roof.

    Photo 14  
     

     
    Attic Return to table of contents
    Inspection method: Not inspected
    19)   The attic access hatch was inaccessible due the hatch being permanently closed. The inspector was unable to evaluate the attic, and it's excluded from this inspection. Recommend modifying the hatch as necessary to allow periodic evaluation of attic spaces.
     
    Electric service Return to table of contents
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Service entrance conductor material: Aluminum
    20)   One or more pointed and/or too-long screws are used to fasten the cover to the main service panel. These types of screws are more likely to come into contact with wiring inside the panel than stock screws from the manufacturer, and can damage wiring insulation. This is a safety hazard due to the risk of shock and/or fire. Long and/or pointed crews should be replaced as necessary with the correct screws, and if necessary by a qualified electrician.
    21)   One or more screws are missing from the main service panel cover and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.

    Photo 21  
     

     
    Water heater Return to table of contents
    Estimated age: 1 year
    Type: Tank
    Energy source: Electric
    Capacity (in gallons): 50
    Manufacturer: Rheem
     
    Heating and cooling Return to table of contents
    Estimated age: 2 years
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air
    Primary A/C energy source: Electric
    Primary Air conditioning type: Split system
    Distribution system: Flexible ducts
    Manufacturer: Carrier
    Model: CNRHP3617ACAAAAA
    Filter location: In return air duct below furnace
    Last service date: Unknown
    22)   The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
    23)   Air handler filter(s) are dirty and should be replaced now. They should be checked monthly in the future and replaced as necessary.
     
    Crawl/Unfinished Basement Return to table of contents
    Inspection method: Traversed
    Insulation material underneath floor above: None visible
    Pier or support post material: Concrete block
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    Vapor barrier present: Partial
    24)   One or more pier or foundation footings are undermined, where soil has either eroded out from underneath, or has been excavated too close to the footing. Structural engineers typically require undisturbed soil to extend at least a foot horizontally out from the edge of footings, and then slope down no more steeply than 45 degrees. Otherwise soil may collapse from beneath the footing(s). A qualified structural engineer should evaluate and determine what repairs if any should be made. If repairs are prescribed, then a qualified contractor should perform them in accordance with the engineer's recommendations.

    Photo 23  
     

    25)   Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 26  
     

    26) Standing water was found in one or more sections of the crawl space. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the crawl space. A qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:

    Water appears to have come from the ice maker line not being turned off before being disconnected.

    Photo 24  

    Photo 25  

    27) No vapor barrier is installed in some areas. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should install a vapor barrier where missing. Standard building practices require the following:

  • The soil below the vapor barrier should be smooth and free from sharp objects.
  • Seams should overlap a minimum of 12 inches.
  • The vapor barrier should lap up onto the foundation side walls.

    Better building practices require that:

  • Seams and protrusions should be sealed with a pressure sensitive tape.
  • The vapor barrier should be caulked and attached tightly to the foundation side walls. For example, with furring strips and masonry nails.
     
    Plumbing and laundry Return to table of contents
    Location of main water shut-off valve: Crawlspace
    Location of main water meter: Street
    Location of main fuel shut-off: North side of house
    Visible fuel storage systems: None
    Water service: Public
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
     
    Downstairs Bath Return to table of contents

    28) Tile and/or grout in one or more showers is damaged and/or deteriorated. For example, deteriorated or missing grout, cracked, missing or loose tiles, etc. A qualified contractor should evaluate and repair tile and/or grout as necessary.

    Photo 22  
     

     
    Upstairs Bath Return to table of contents

    29)     GFCI outlet in this bathroom is controlled by GFCI in downstairs bath. This outlet should be a standard outlet.
     
    Kitchen Return to table of contents

    30)   One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.

    Photo 18  
     

    31)   One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 17  
     

    32)   No range hood is installed over the range or cook top. Ventilation and/or lighting may be inadequate and moisture may accumulate indoors. Recommend having a qualified contractor install a vented and lighted range hood, with the exhaust fan configured so as to vent outdoors.
     
    Interior rooms Return to table of contents

    33)   One or more open ground, three-pronged electric receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. For example, replacing receptacles or correcting wiring circuits.

    Grounding type receptacles began being required in residential structures during the 1960s. Based on the age of this structure and the presence of 2-pronged receptacles in some areas of this structure, an acceptable repair may be to simply replace the ungrounded 3-pronged receptacles with 2-pronged receptacles. However the following appliances require grounding type receptacles:

  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

    This list is not exhaustive. Grounded circuits and receptacles should be installed in locations where such appliances will be used.

    Photo 19  
     

    34)   Minor cracks were found in ceilings in one or more areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.

    Photo 20  
    Dining room ceiling
     

     