Property Inspection Report

Client(s):  Paul Ortiz
Property address:  901 South 6th Ave Space# 290, Hacienda Heights, CA 91745
Inspection date:  Monday, July 25, 2016

This report published on Tuesday, July 26, 2016 7:21:50 PM PDT

Dear Customer:

Thank you for choosing R.B.Inspections to perform the following inspection on the property you wish to purchase. This report is the exclusive property of R.B.Inspections and the individual(s) paying for the inspection fee and report. Use of this report by any unauthorized persons is prohibited.

All findings should be made to R.B.Inspections.

This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.

We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, see paint peeling off walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.

While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.

This inspection report was prepared in a format specifically for the individual/s paying for the inspections fee and report and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the individual/s paying for inspections fee and report and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.

No warranty, guarantee, or insurance by R.B.Inspections is expressed or implied. This report does not include inspection for wood destroying insects, mold, lead or asbestos. A representative sampling of the building components is viewed in areas that are accessible at the time of the inspection. No destructive testing or dismantling of components is performed. Not all defects will be identified during this inspection. Unexpected repairs should be anticipated.

The person conducting your inspection is not a licensed structural engineer or other professional whose license authorizes the rendering of an opinion as to the structural integrity of a building or its other component parts.

You are advised to seek two professional opinions and acquire estimates of repair as to any defects, comments, improvements or recommendations mentioned in this report. We recommend that the professional making any repairs inspect the property further, in order to discover and repair related problems that were not identified in the report. We recommend that all repairs, corrections, and cost estimates be completed and documented prior to closing or purchasing the property. Feel free to hire other professionals to inspect the property prior to closing, including HVAC professionals, electricians, plumbers, engineers, or roofers.

If you have any questions regarding this report, please feel free to call us.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeServiceableItem or component is in servicable condition
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings


General Information
Return to table of contents

Time started: 9:40am
Time finished: 12:35pm
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Warm
Inspection fee: 250.00
Payment method: Check
Type of building: Single family, Mobile home
Buildings inspected: Mobile Home
Number of residential units inspected: 1
Age of main building: 2000
Source for main building age: Realtor
Front of building faces: East
Main entrance faces: South
Occupied: No

1)   What Really Matters




by Nick Gromicko (Founder of InterNACHI)

Buying a home? The process can be stressful. A home inspection is supposed to give you peace of mind, but often has the opposite effect. You will be asked to absorb a lot of information in a short time. This often includes a written report, a checklist, photographs, environmental reports, and what the inspector himself says during the inspection. All this, combined with the seller's disclosure and what you notice yourself, makes the experience even more overwhelming. What should you do?

Relax. Most of your inspection will be maintenance recommendations, life expectancies for various systems and components, and minor imperfections. These are useful to know about. However, the issues that really matter will fall into four categories:

1. major defects. An example of this would be a structural failure;
2. things that lead to major defects, such as a small roof-flashing leak, for example;
3. things that may hinder your ability to finance, legally occupy, or insure the home; and
4. safety hazards, such as an exposed, live buss bar at the electrical panel.

Anything in these categories should be addressed. Often, a serious problem can be corrected inexpensively to protect both life and property (especially in categories 2 and 4).
Most sellers are honest and are often surprised to learn of defects uncovered during an inspection. Realize that sellers are under no obligation to repair everything mentioned in the report. No home is perfect. Keep things in perspective. Do not kill your deal over things that do not matter. It is inappropriate to demand that a seller address deferred maintenance, conditions already listed on the seller's disclosure, or nit-picky items.
Photo
Photo 1-1
 

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete, Brick
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood, Carpet
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Plastic fiber

2) Guardrails at one or more locations with drop-offs higher than 30 inches had gaps that were too large. This poses a safety hazard for children (e.g. falling, getting stuck in railing). Guardrails should not have gaps or voids that allow passage of a sphere equal to or greater than 4 inches in diameter, or 6 inches in diameter at triangular spaces between stair edges and guardrails. At a minimum, the client should be aware of this hazard. Recommend that a qualified contractor repair or replace guardrails per standard building practices.
Photo
Photo 2-1
 

3) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 3-1
 

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Not applicable, slab, manufactured or mobile home

4) Some sections of siding and/or trim were deteriorated, loose and/or damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 4-1
Photo
Photo 4-2

5) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 5-1
 

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Steel
Beam material: Steel
Condition of insulation underneath floor above: Appeared serviceable

6) One or more support posts were not positively secured to the beam above. Recommend that a qualified contractor repair per standard building practices. For example, by installing metal plates, plywood gussets or dimensional lumber connecting posts and beams.
Photo
Photo 6-1
 

7) The screens for one or more crawl space vents were missing. Vermin or pets can enter the crawl space and nest, die and/or leave feces and urine. Vermin often damage under-floor insulation too. Recommend that a qualified person install or replace screens where necessary using 1/8-inch to 1/4-inch wire mesh.
Photo
Photo 7-1
Photo
Photo 7-2

8) Cellulose material such as scrap wood, form wood, cardboard forms and/or cardboard or paper was found in the crawl space. This is a conducive condition for wood-destroying organisms. Recommend removing all cellulose-based debris or stored items.
Photo
Photo 8-1
Photo
Photo 8-2

9) At the time of inspection the crawl space appeared to be serviceable, except as noted.
Photo
Photo 9-1
Photo
Photo 9-2
Photo
Photo 9-3
Photo
Photo 9-4
Photo
Photo 9-5
Photo
Photo 9-6
Photo
Photo 9-7
Photo
Photo 9-8
Photo
Photo 9-9
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable

10) Extensions such as splash blocks or drain pipes for one or more downspouts were damaged. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 10-1
 

11) One or more downspouts were damaged. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 11-1
 

12) Debri such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Photo
Photo 12-1
Photo
Photo 12-2

13) At the time of inspection the roof covering appeared to be in serviceable condition, except as noted.
Photo
Photo 13-1
Photo
Photo 13-2
Photo
Photo 13-3
Photo
Photo 13-4
Photo
Photo 13-5
Photo
Photo 13-6

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Carport
Condition of garage floor: Appeared serviceable

14) One or more deck, patio and/or porch covers had a small hole. Water can leak through. Recommend that a qualified person repair as necessary.
Photo
Photo 14-1
Photo
Photo 14-2

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 100
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Building exterior
Location of main service panel #B: Laundry room
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: copper

15) One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the exterior wouldn't trip when tested. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 15-1
 

16) One or more electric receptacles at the bathroom(s) and/or exterior had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 16-1
Photo
Photo 16-2
Photo
Photo 16-3
Photo
Photo 16-4

17) One or more cover plates installed outside were not rated for exterior use. This is a potential shock and fire hazard. Recommend that a qualified electrician repair per standard building practices.
Photo
Photo 17-1
 

18) One or more knockouts were missing from panel(s) #B. Holes in panels are a potential fire hazard if a malfunction ever occurs inside the panel. Rodents can also enter panels through holes. Recommend that a qualified person install knockout covers where missing and per standard building practices.
Photo
Photo 18-1
 

19) Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 19-1
 

20)   Location of main service panel #A: Building exterior

Photo
Photo 20-1
 

21)   Location of main service panel #B: Laundry room
Photo
Photo 21-1
Photo
Photo 21-2
Photo
Photo 21-3
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable, Near, at or beyond service life
Water service: Public
Water pressure (psi): 50psi
Location of main water shut-off: Building exterior, North
Condition of supply lines: Appeared serviceable
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground
Location of main fuel shut-off valve: At gas meter, North

22)   Water pressure (psi): 50psi

Photo
Photo 22-1
 

23)   Main water shut-off.

Photo
Photo 23-1
 

24)   Main fuel shut-off valve: At gas meter.
Photo
Photo 24-1
 

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2015
Capacity (in gallons): 30
Temperature-pressure relief valve installed: Yes
Location of water heater: Closet, Exterior
Hot water temperature tested: Yes

25) Drain line was installed for the temperature-pressure relief valve, but is not terminated properly. Recommend that a qualified person evaluate and repair as necessary.
Photo
Photo 25-1
 

26) The water heater's earthquake straps or struts were substandard. For example, they may allow significant movement or use substandard fasteners. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person repair or replace existing earthquake reinforcement per standard building practices.
Photo
Photo 26-1
Photo
Photo 26-2

27) The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD
Photo
Photo 27-1
 

28) At the time of inspection the water heater appeared to be in serviceable condition, except as noted.
Photo
Photo 28-1
 

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Location of forced air furnace: Laundry room
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): Behind return air grill(s)
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: north
Type: Split system

29) The cooling fins at the air handler evaporator coils were damaged. Recommend that a qualified HVAC contractor repair fins as necessary.
Photo
Photo 29-1
 

30) Condensate line terminated improperly
High-efficiency furnace exhaust products condensate fluid which must be properly discharged.
The condensate line for the high-efficiency furnace discharged improperly and should corrected by a qualified person.

Terminated in crawl space.
Photo
Photo 30-1
 

31) The estimated useful life for most heating and air conditioning units is 10-15 years. These units appeared to be at this age and/or its useful lifespan and may need servicing, replacing or repairs at any time. Recommend budgeting for a replacement in the near future.

Both appeared to have an estimated age of year 2000.

Both were in serviceable condition except as noted.
Photo
Photo 31-1
Photo
Photo 31-2
Photo
Photo 31-3
Cold air temp.
Photo
Photo 31-4
Photo
Photo 31-5
Photo
Photo 31-6
Photo
Photo 31-7
Hot air temp.
 

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Metal pre-fab
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Metal

32) One or more fireplace dampers were inoperable. Recommend that a qualified contractor repair or replace dampers as necessary.

Wouldn't open.
Photo
Photo 32-1
 

33) At the time of inspection the fire place was in serviceable condition except as noted.
Photo
Photo 33-1
 

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas
Type of ventilation: Hood or built into microwave over range or cooktop

34) One or more filters for the cooktop exhaust fan were damaged and/or dirty. Recommend replacing filters as necessary.
Photo
Photo 34-1
 

35) The light in the exhaust hood was inoperable. Recommend replacing light bulb(s) or that repairs be made by a qualified person if necessary.
Photo
Photo 35-1
 

36) At the time of inspection the kitchen appliances, flooring, cabinets and countertops pictured below were evaluated and appeared to be in serviceable condition, except as noted.
Photo
Photo 36-1
Photo
Photo 36-2
Photo
Photo 36-3
Photo
Photo 36-4
Photo
Photo 36-5
Photo
Photo 36-6
Photo
Photo 36-7
Photo
Photo 36-8
Photo
Photo 36-9
Photo
Photo 36-10

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Master bath
Location #B: Full bath, Hallway
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans

37) The hot and/or cold water supply flow for the bathtub at location(s) #A was low or inoperable. Recommend that a qualified plumber evaluate and repair as necessary.
Photo
Photo 37-1
 

38) The clothes dryer exhaust duct terminated in the crawl space. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person install, repair or replace the duct as necessary so it terminates outdoors, and per standard building practices. For more information, visit:
http://www.reporthost.com/?DRYER
Photo
Photo 38-1
Photo
Photo 38-2

39) Gaps, no caulk, or substandard caulking were found between the bathtub and the floor at location(s) #B. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 39-1
Photo
Photo 39-2

40) Recommend cleaning and sealing the grout at countertops at location(s) #B now and in the future as necessary to prevent staining and to improve waterproofing.
Photo
Photo 40-1
Photo
Photo 40-2

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal, Glass panel
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall, Plaster
Ceiling type or covering: Drywall, Plaster
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products, Tile

41) One or more interior doors wouldn't close flush. Recommend a qualified person evaluating and repairing as necessary.


Photo
Photo 41-1
 

42) Floor guides were missing at one or more sliding closet doors.
Photo
Photo 42-1
 

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.

1.1. A Home Inspection is a non-invasive, visual examination of a residential dwelling, performed for a fee, which is designed to identify observed material defects within specific components of said dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or other essential systems or portions of the home, as identified and agreed to by the Client and Inspector, prior to the inspection process.

I. A home inspection is intended to assist in evaluation of the overall condition of the dwelling. The inspection is based on observation of the visible and apparent condition of the structure and its components on the date of the inspection, and not the prediction of future conditions.

II. A home inspection will not reveal every concern that exists or ever could exist, but only those material defects observed on the day of the inspection.

III. A home inspection can include a survey and/or analysis of energy flows and usage in a residential property if the client requests it.
1.2. A Material Defect is a condition of a residential real property, or any portion of it, that would have a significant, adverse impact on the value of the real property, or that involves an unreasonable risk to people on the property. The fact that a structural element, system or subsystem is near, at or beyond the end of the normal useful life of such a structural element, system or subsystem is not by itself a material defect.

1.3. An Inspection Report shall describe and identify, in written format, the inspected systems, structures, and components of the dwelling, and shall identify material defects observed. Inspection reports may contain recommendations regarding conditions reported or recommendations for correction, monitoring or further evaluation by professionals, but this is not required.

This inspection was performed in accordance with the current Standards of Practice and Code of Ethics of the International Association of Certified Home Inspectors (InterNACHI). The Standards contain certain and very important limitations, exceptions, and exclusions to the inspection. A complete copy of the STANDARDS OF PRACTICE we adhere to can be found at the following link: http://www.nachi.org/sop.htm