RAM Home Inspections


18 Stardust Ct 
Fairfield OH 45014-4930
Inspector: Michael Skimmerhorn

Property Inspection Report

Client(s):  Lance & Constance McMullins
Property address:  1517 Covered Bridge Rd
Cincinnati Ohio
Inspection date:  Monday, May 04, 2015

This report published on Tuesday, May 05, 2015 10:57:16 AM CDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeServiceableItem or component is in servicable condition
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings


General Information
Return to table of contents

Report number: 150305
Time started: 130pm
Present during inspection: Property owner
Client present for discussion at end of inspection: Yes
Temperature during inspection: Warm, 75
Inspection fee: Mock
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1959
Source for main building age: Property owner
Front of building faces: East
Main entrance faces: East
Occupied: No
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC
Photo
Photo 1-1
Front of property
 

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Gravel
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Condition of deck, patio and/or porch covers: Appeared serviceable
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Concrete, Stone
2) Handrails at one or more flights of stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.

Loose concrete blocks are currently being used as steps to the rear patio from the driveway area. This is a safety issue & trip hazard. Recommend they be removed and/or replaced with permanent stairs suitable for the application.
Photo
Photo 2-1
Handrail may be required.
Photo
Photo 2-2
Loose concrete blocks are currently being used as steps to the rear patio from the driveway area. This is a safety issue & trip hazard. Recommend they be removed and/or replaced with permanent stairs suitable for the application.

3) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 3-1
Sunken sidewalk.
Photo
Photo 3-2
Short step.
Photo
Photo 3-3
Broken threshold tile.
 

4) Cracks, holes, settlement, heaving and/or deterioration were found in sidewalks and/or patios. Recommend that qualified contractor repair as necessary.
Photo
Photo 4-1
Photo
Photo 4-2
Photo
Photo 4-3
Photo
Photo 4-4

5) Sidewalk(s) and/or patios were undermined in one or more areas, where soil has eroded out from beneath. Recommend that a qualified person repair as necessary to prevent further erosion and undermining.
Photo
Photo 5-1
Photo
Photo 5-2

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Concrete block
Wall covering: Vinyl, Brick veneer
Condition of foundation and footings: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Apparent foundation type: Finished basement
6) Some sections of siding and/or trim were deteriorated and/or loose. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 6-1
Photo
Photo 6-2
Photo
Photo 6-3
Note loose gutter nails in red circles.
 

7) Cement stucco finish deteriorated. Corner of poured foundation deteriorated and/or damaged. Recommend that a qualified person repair, replace as necessary.
Photo
Photo 7-1
Photo
Photo 7-2
Photo
Photo 7-3
Photo
Photo 7-4

8) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 8-1
Photo
Photo 8-2

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal, Sliding glass
Condition of floor substructure above: Finished ceiling, unable to inspect.
Pier or support post material: Masonry
Beam material: Finished ceiling, unable to inspect.
Floor structure above: Finished ceiling, unable to inspect.
Condition of insulation underneath floor above: Not applicable, none installed
9) The inspector was unable to verify that the glass used in one or more exterior doors was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a safety hazard. Approved safety glass should be used in all swinging doors except where "art glass," jalousie windows or glazing smaller than 3 inches is used. Recommend that a qualified contractor evaluate further to determine if glazing is approved safety glass, and replace glass if necessary, and per standard building practices.
Photo
Photo 9-1
Basement entry. Appeared serviceable. Please note short threshold/step. May be a trip hazard.
 

10) Handrails at one or more flights of stairs were loose. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 10-1
 

11) Sealant or water-proofing coating was found on basement walls and/or floors. This may indicate that water has infiltrated or accumulated in the basement previously. Monitor the basement for excessive moisture conditions in the future, and review any disclosure statements related to accumulated moisture in the basement. Note that the inspector does not guarantee or warrant that water will not accumulate in the basement in the future.
Photo
Photo 11-1
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Viewed from eaves on ladder
Condition of roof surface material: Near, at or beyond service life
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: Multiple
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
12) Multiple layers of asphalt shingles. Near, at or beyond service life.
Photo
Photo 12-1
Multiple layers
Photo
Photo 12-2
Worn & missing shingles.

13) Flashings at the base of one or more chimneys were loose. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 13-1
 

14) One or more gutters and/or downspouts were loose and/or damaged. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 14-1
Gutter nails loose throughout roof/gutter system.
Photo
Photo 14-2
Damaged gutter @ rear.
Photo
Photo 14-3
Downspout disconnected @ rear.
 

15) Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
16) Stains were found on one or more gutters that indicate past leaks have occurred. However, the inspector was unable to verify that the gutters do or don't leak because of lack of recent rainfall. Monitor the gutters in the future while it's raining to determine if gutters leak. If they do, then recommend that a qualified person repair as necessary to prevent water from coming in contact with the building or accumulating around the building foundation.
Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Cellulose loose fill
Approximate attic insulation R value (may vary in areas): R=21.6 (estimated @ approximately 6 inches of insulation)
Vapor retarder: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Gable end vents, Open soffit vents
Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached, Garage, Unable to inspect 
17)   Unable to inspect. Garage was inaccessible at time of inspection.
Photo
Photo 17-1
 

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 125
System ground: Not determined, not readily apparent
Condition of main service panel: Appeared serviceable
Condition of branch circuit wiring: Serviceable
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: No, recommend install
Carbon monoxide alarms installed: No, recommend install
18) Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo
Photo 18-1
Photo
Photo 18-2

19) One or more receptacles (outlets) were broken or damaged. This is a potential shock or fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.
Photo
Photo 19-1
 

20) No smoke alarms were visible. This is a potential safety hazard. A qualified electrician should install smoke alarms per standard building practices (e.g. in hallways leading to bedrooms, in each bedroom, on each floor and in attached garages). For more information, visit:
http://www.reporthost.com/?SMKALRM
21) One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 21-1
Open junction box behind furnace.
 

22) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.
23) 2-slot receptacles (outlets) rather than 3-slot, grounded receptacles were installed in one or more areas. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits.
Photo
Photo 23-1
Adapter @ water conditioner. Electrical hazard!
Photo
Photo 23-2
Photo
Photo 23-3
 

24) Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 24-1
Photo
Photo 24-2

25)   Test
Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: Not determined (obscured, inaccessible or none found)
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Not determined (inaccessible or obscured)
Vent pipe condition: Appeared serviceable
Vent pipe material: Not determined (inaccessible or obscured)
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Below ground, oil tank, in yard, None visible
Location of main fuel shut-off valve: Not applicable
26) A water softener system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Water softeners typically work by removing unwanted minerals (e.g. calcium, magnesium) from the water supply. They prevent build-up of scale inside water supply pipes, improve lathering while washing, and prevent spots on dishes. Recommend consulting with the property owner about this system to determine its condition, required maintenance, age, expected remaining life, etc. For more information, visit:
http://www.reporthost.com/?WTRSFT
http://www.reporthost.com/?HRDWTR

27) The inspector did not determine the location of the main water shut-off valve, or verify that a readily accessible shut-off valve in the building exists. Recommend consulting with the property owner to determine if a main shut-off valve exists, locating it yourself, or that a qualified plumber find it if necessary. If no readily accessible main shut-off valve is found in the building, then recommend that a qualified plumber install one so the water supply can be quickly turned off in the event of an emergency, such as when a supply pipe bursts.
28)   Test
Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: 2008
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 110
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Oil
Location of forced air furnace: Basement
Condition of furnace filters:
Location for forced air filter(s): None visible
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location: Rear
Condition of controls: Appeared serviceable
29)   HVAC systems
Photo
Photo 29-1
Photo
Photo 29-2

Kitchen
Return to table of contents


30) Kitchen not evaluated. Currently under renovation.
Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Location #B: Half bath
Location #C: Full bath in basement. Toilet water supply off. Unable to evaluate.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
31) The shower head at location(s) #A was dripping when the shower was turned on. Recommend that a qualified person repair as necessary.
Photo
Photo 31-1
 

32)   Test
Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of interior doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of windows and skylights: Appeared serviceable (one (1) cracked pane in basement window)
Type(s) of windows: Single-pane, Jalousie
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Plaster
Ceiling type or covering: Plaster
Condition of flooring: Appeared serviceable
Flooring type or covering: Wood or wood products
33) Handrails at one or more flights of stairs were loose. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 33-1
 

34) Wood flooring in one or more areas was significantly worn, deteriorated or damaged. Recommend that a qualified contractor refinish wood flooring as necessary.
35) One or more interior doors were sticking in the door jamb and were difficult to operate. Recommend that a qualified person repair as necessary. For example, by trimming doors.

One or more hollow core doors were damaged. Recommend that a qualified person repair as necessary
Photo
Photo 35-1
Photo
Photo 35-2
Photo
Photo 35-3
Photo
Photo 35-4
Note peeling paint in bathroom A ceiling.
Photo
Photo 35-5
Photo
Photo 35-6
Photo
Photo 35-7
 

36) Minor cracks & holes in plaster walls & ceiling were found in various rooms throughout the property. Recommend that a qualified person repair as necessary.
Photo
Photo 36-1
Basement.
Photo
Photo 36-2
Basement.
Photo
Photo 36-3
Basement. Note cracked window pane (red arrow).
Photo
Photo 36-4
Master bedroom

37) No window screens were installed. Windows may not provide ventilation during months when insects are active.
Photo
Photo 37-1
Photo
Photo 37-2

Wood Destroying Organism Findings
Return to table of contents

Limitations: Evaluating for the presence of wood destroying organisms is beyond the scope of this inspection. Any mention of these in this report is made as a courtesy only, and meant to refer the client to a specialist.
38) Insect bait traps were installed in the perimeter soil of the exterior of property. Recommend contacting the service provider for findings & evaluations.
Photo
Photo 38-1
Photo
Photo 38-2


Photo
Photo X-1
Minor crack in sidewalk.
Photo
Photo X-2
Steel lintels in windows require painting. Caulking appeared serviceable.
Photo
Photo X-3
200A Service entrance
Photo
Photo X-4
Bay window & panes appeared serviceable. Paint required.
Photo
Photo X-5
Basement ceiling (Plaster)
Photo
Photo X-6
Basement bath w/shower
Photo
Photo X-7
Basement bath w/ shower
Photo
Photo X-8
Water heater installed 2008
Photo
Photo X-9
Photo
Photo X-10
Photo
Photo X-11
Attic view from hatch.
Photo
Photo X-12
Photo
Photo X-13
Bathtub & tile in good condition
Photo
Photo X-14
Minor mold @ arrow
Photo
Photo X-15
Peeling ceiling paint @ bathroom A
Photo
Photo X-16
Digital thermostat

Please do not hesitate to contact me with questions or concerns regarding this report. I am available most anytime @ 513 814 4387 or mskimmerhorn@gmail.com. Thank you for your confidence in RAM Home Inspections and the opportunity to be of service to you.

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.