HOME INSPECTION REPORT

Client(s):  Jack and Jill Homebuyer
Property address:  7212 - 111th ST E, Lake Stevens WA 98193
Inspection date:  Friday, January 10, 2014

This report published on Wednesday, January 06, 2016 9:01:58 PM PST

[b] Rainier Inspections, Inc. (RII) provides visual inspections which comply with WAC 308-408C, licensing law which regulates Washington home inspectors. The Washington Home Inspector Standards can be viewed at www.prwebworks.com/rainspect/files/WashingtonSOP.pdf Our inspections also meet the current standards of the American Society of Home Inspectors (ASHI). The ASHI standards can be viewed at www.ashiww.com/standards.htm

This report has been prepared for the sole and exclusive use of the client indicated above and is limited to an impartial opinion which is not a warranty that the items inspected are defect-free, or that latent or concealed defects may exist as of the date of this inspection, or which may have existed in the past, or may exist in the future. The report is limited to the components of the property which were visible to the inspector on the date of the inspection and his or her opinion of their condition at the time of the inspection. This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Safety HazardAny item that is identified as a safety hazard is to be considered harmful or dangerous to its occupants due to its presence or absence in the structure.
Minor ConcernA minor concern does not significantly affect habitability and can be considered an inexpensive repair. The baseline repair cost used in this report is $500.00 or less.
Repair/ReplaceRecommend repairing or replacing the noted concern as soon as possible.
Repair/MaintainRecommend repairing or replacing the noted concern in the near future.
Maintenance ItemAny item identified as a maintenance item is considered routine repairs for a house. These items can become larger concerns if not corrected.
Further InvestigateAn item which requires further investigation by a specialist. This includes, but is not limited to, destructive testing, engineering evaluations or cost estimates by licensed and bonded contractors.
CommentAdditional information, upgrade items or excluded items.

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior
Roof
Garage or Carport
Heating, Ventilation and Air Condition (HVAC)
Plumbing / Fuel Systems
Water Heater
Electric
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Fireplaces, Stoves, Chimneys and Flues
Attic and Roof Structure
Foundation Type
Crawl Space


General Information
Return to table of contents

Report number: 140103
Time started: 10:00 AM
Time finished: 12:40 PM
Present during inspection: Realtor
Client present during inspection: No
Weather conditions during inspection: Windy and overcast
Temperature during inspection: 40 Degrees Fahrenheit
Ground condition: Wet
Recent weather: Heavy rain and windy
Overnight temperature: Cool
Inspection fee: $450
Payment method: Check from real estate agent
Type of building: Two Story
Age of main building: New
Front of building faces: South
Main entrance faces: South
Occupied: No

1) Comment - The client should be aware that a break-in period occurs during the first year or two after a building is constructed. Some amount of settlement and shrinkage is inevitable as temperature and humidity varies during the seasons. Systems may need adjustment or repair after experiencing constant, prolonged and/or heavy usage. Overall performance of the building exterior has not yet been tested by a wide variety of weather conditions. Also, it is beyond the scope of this inspection to determine if all permits have been approved or signed off. Consult with the builder and/or municipality to determine if all necessary permits have been approved.

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment.
Condition of fences and gates: Appeared serviceable
Fence and gate material: Wood
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Concrete

Exterior
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation.
Condition of siding: Appeared serviceable
Apparent wall structure: Wood frame
Siding: Cement fiber, Stone or faux stone veneer

2) Minor Concern, Repair/Maintain - Some areas of the exterior paint are incomplete and/or substandard (e.g. primed only, too few coats) on the north side siding, hose faucets, downspouts and vent hoods. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint the exterior where necessary and per standard building practices.
Photo
Photo 2-1
Photo
Photo 2-2
Photo
Photo 2-3
 

3) Minor Concern, Repair/Maintain - Caulk was missing in some areas. For example, at the front hose faucet. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used.
Photo
Photo 3-1
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Age of roof surface(s): New
Roof inspection method: Viewed from ground with binoculars
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Aluminum
Gutter and downspout installation: Full

4) Minor Concern, Repair/Maintain - No storm covers were observed on the roof safety anchors. The roof safety anchors are located at the ridges of the roof. The metal anchors protrude through the roof surface and are flashed at the base to prevent water leakage during construction. The base flashing of these anchors will leak after a few years of exposure to the weather. These anchors also come with a permanent plastic storm cover to protect the anchors after the house is complete. The permanent storm covers should be installed to prevent future roof leakage.
Photo
Photo 4-1
 

5) Comment - Normally the inspector attempts to traverse roof surfaces during the inspection. However, due to safety concerns about the height of the structure, the inspector was unable to traverse the roof. The roof was inspected with binoculars from the ground.

Garage or Carport
Return to table of contents

Type: Attached, Garage
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core, Wood
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 2
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: None

6) Safety Hazard, Repair/Replace, Further Investigate - One or more gas-fired appliances (water heater) were installed in the garage, and no combustion air vent was visible. This can result in inadequate combustion air for the appliance(s), reduced efficiency, and possible safety issues related to carbon monoxide poisoning. Recommend that a qualified person evaluate further and repair per standard building practices. For example, by installing one or more vents to the exterior.
Photo
Photo 6-1
 

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
General heating system type(s): Forced air furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: New
Forced air heating system manufacturer: Bryant
Location of forced air furnace: Attic
Condition of furnace filters: Appeared serviceable, Required replacement
Location for forced air filter(s): Hallway ceiling
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Condition of controls: Appeared serviceable
Condition of whole house fan: Appeared serviceable
24 hour automatic ventilation system present: Yes, fan in full bathroom, but not timer

7) Repair/Replace, Repair/Maintain, Further Investigate - The control for the whole house ventilation system system is located in the full bathroom. The system is supposed to operate automatically for three, two hour periods per day. No timer control exists, therefore, the system can only be operated manually. A timer should be installed for proper air flow inside of the house. Recommend that a qualified person evaluate further and repair per standard building practices.
Photo
Photo 7-1
 

8) Repair/Replace, Repair/Maintain - Recommend replacing HVAC filters. Regardless of the type, recommend checking filters monthly in the future and replacing them as necessary. How frequently they need replacing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 8-1
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 60
Location of main water meter: By sidewalk in front of house
Location of main water shut-off: Garage
Service pipe material: Copper, Plastic
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter on east side of garage

9) Minor Concern, Repair/Maintain - Water supply pipes at the garage hose faucet piping are not insulated. Recommend insulating pipes per standard building practices to prevent them from freezing during cold weather.
Photo
Photo 9-1
 

10) Comment - A fire suppression system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. These systems normally require periodic inspection by a specialist to ensure correct operation. For example, checking for possible backflow contamination of the potable water system, or correct operation of valves and gauges. Recommend that a qualified specialist inspect this system in accordance with National Fire Prevention Association (NFPA) 25 standards.

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: New
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Manufacturer: Rheem
Location of water heater: Garage
Hot water temperature tested: No
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil, Concrete encased electrode, Gas pipe
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested
Smoke alarm power source(s): Hard wired

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Under-sink food disposal, Microwave oven
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas
Condition of built-in microwave oven: Appeared serviceable

11) Safety Hazard, Minor Concern - The range tips forward then stops. The anti-tip bracket may not be installed properly. This is a potential safety hazard since the range can tip forward when weight is applied to the open door, such as when a small child climbs on it or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free-standing ranges since 1985. Recommend installing an anti-tip bracket to eliminate this safety hazard. For more information, visit:
http://www.reporthost.com/?ATB

12) Repair/Replace, Repair/Maintain - Gaps, no caulk, or substandard caulking were found between countertops and backsplashes. Water may penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing caulk.
Photo
Photo 12-1
 

13) Maintenance Item - Recommend cleaning and sealing the countertops now and in the future as necessary to prevent staining and to improve waterproofing.

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Master bath
Location #B: Full bath
Location #C: Half bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom ventilation type: Spot fans
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

14) Safety Hazard, Further Investigate - No tempering valve is installed at master bathtub , but the plumbing exists for the valve. This valve is an extra safety device to prevent hot water scalding. A tempering valve does exist at the water heater, but does not directly regulate the bathtub water temperature. Recommend that a qualified person evaluate further and repair per standard building practices.
Photo
Photo 14-1
Photo
Photo 14-2

15) Maintenance Item - Recommend cleaning and sealing the grout at countertops at location(s) #A now and in the future as necessary to prevent staining and to improve waterproofing.

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Fiberglass or vinyl
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Sliding
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: CarpetHardwood
Condition of stairs, handrails and guardrails: Appeared serviceable

16) Minor Concern, Repair/Maintain - Condensation or staining was visible between multi-pane glass in one or more in the east side bedroom. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo
Photo 16-1
 

17) Minor Concern, Repair/Maintain - One or more walls in the master closet above the door were cracked. Recommend that a qualified person repair as necessary.
Photo
Photo 17-1
 

18) Comment - No window screens were installed. Windows may not provide ventilation during months when insects are active.

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device.
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Gas fireplace or stove type: Metal pre-fab fireplace
Fan or blower installed in gas-fired fireplace or stove: No
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: Direct vent

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Location of attic access point #A: Garage
Location of attic access point #B: Bedroom
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Cellulose loose fill
Approximate attic insulation R value (may vary in areas): R-38
Vapor retarder: None
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Box vents (roof jacks), Open soffit vents

19) Repair/Replace, Repair/Maintain - The ceiling insulation in one or more areas of the attic was compacted or uneven at trails through the insulation created by construction workers. Heating and cooling costs may be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).
Photo
Photo 19-1
 

Foundation Type
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior and crawl space. Items excluded from this inspection include below-grade foundation walls and footings; foundations. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
Anchor bolts or hold downs for seismic reinforcement: Installed

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing. The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Hall closet
Crawl space access points that were opened and viewed, traversed or partially traversed: A
Condition of floor substructure above crawl space: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: Solid wood joists and OSB sheathing
Condition of insulation underneath floor above: Appeared serviceable
Insulation material underneath floor above: Fiberglass roll or batt
Condition of vapor barrier: Appeared serviceable
Vapor barrier present: Yes
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: Unconditioned space

20) Minor Concern, Repair/Maintain, Further Investigate - Concrete-to-wood contact was observed at the floor posts. Moisture breaks where not installed at any of the concrete-to-wood contact locations. This condition is conducive to wood rot, even if the posts are treated wood. Moisture breaks should be installed. The picture shows a properly installed moisture break at the bottom of the post. Recommend that a qualified person evaluate further and repair per standard building practices.
Photo
Photo 20-1
 

Signature
Brad Albin, LWHI #239, Rainier Inspections. Inc. inspectorbrad@frontier.com 206-682-8968 / Text 206-948-6415