HOME INSPECTION REPORT |
| Client(s): |
Sample Report - Updated |
| Property address: |
4321 W. Any Valley Drive Phoenix, AZ 85432 |
| Inspection date: |
Friday, June 25, 2010 |
This report published on Monday, July 19, 2010 4:09:13 PM MST
View summary page
This report is the exclusive property of QualCheck Home Inspections LLC and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
PURPOSE AND SCOPE
This inspection was conducted in accordance with the Standards of Professional Practice and the Rules of Professional Conduct as specified by the State of Arizona Board of Technical Registration. Additional information as to inspection standards is included at the end of the report.
A standard Home Inspection Report is based on a visual assessment of the condition of the accessible features of the residence at the time of inspection. The inspection and inspection report are offered as an opinion only. Although every reasonable effort is made to discover and correctly interpret indications of previous or ongoing defects that may be present, no guarantee is implied nor responsibility assumed by the inspector or inspection company, for the actual condition of the building or property being examined.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types: | Safety | Safety hazards posing a risk of injury or death |
 | Major Defect | Correction likely involves a significant expense |
 | Repair/Replace | Recommend repairing or replacing |
 | Repair/Maintain | Recommend repair and/or maintenance |
 | Maintain | Recommend maintenance |
 | Evaluate | Recommend evaluation by a specialist |
 | Serviceable | Item or component is in serviceable condition |
 | Comment | For your information |
Click here for a glossary of building construction terms.
Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp
Structures inspected: House, attached garage, pool
Seller's name: John Doe
Report number: Sample
Time started: 9 am
Time finished: 12 noon
Present during inspection: Buyer, Owner, Buyer's Realtor
Occupied: Yes
Approx. square footage: 1738
Approx. year built: 1993
Type of building: Single family
Bedrooms: 4
Bathrooms: 2
Weather conditions: Sunny
Temperature: Approx. 85F
Ground condition: Dry
Front of structure faces: South
Foundation type: Slab-on-grade
The following items are excluded from this inspection: Irrigation system, Low voltage outdoor lighting
Introduction: The structure section describes the basic characteristics of the house. Components covered are the foundation, floor structure, wall structure, columns, ceiling structure and roof structure. Observations of certain areas such as crawlspace and attic conditions are documented elsewhere in this report.
Foundation material: Poured in place concrete slab
Apparent wall structure: Wood frame
Wall sheathing: Foam secured directly to studs, Stucco
Wall studs: 2 x 4
On center: 16"
Roof assembly type: Manufactured truss
Rafter support: 2 x 4
On center: 24"
Ceiling joist: 2 x 4
On center: 24"
Roof sheathing: Oriented strand board
1)



Damaged/sawn manufactured roof trusses were noted in the attic. Manufactured truss members must not be cut or modified, unless such modification has been explicitly approved and designed by a qualified truss engineer. It is recommended that the client(s) determine from the seller whether this modification was properly approved and designed and whether documentation of such approval exists. If not, these modifications should be evaluated by a qualified truss engineer, who can either approve them in writing or prescribe a proper repair method to be undertaken by a reputable contractor.

Photo 20
|

Photo 21
|
2)
On some areas of the home's stem wall the paint has blistered and peeled off. Recommend scraping, priming and painting as appropriate to protect the concrete from further erosion.

Photo 12
|

Photo 19
|
3)
Soil is in contact with or less than 4" from siding and/or trim. This can allow moisture to wick up into the framing, and is also a conducive condition for wood destroying insects and organisms. Recommend re-grading soil to provide at least 4" of space between the siding and trim and the soil below.

Photo 13
|

Photo 14
|
Introduction: Landscaping and lot topography are examined during a residential house inspection as they can have a significant impact on the building structure. It is important that surface runoff water is adequately diverted away from the building, especially in areas that have expansive soil characteristics. Low spots or depressions in the topography can result in ponding water that may exert hydrostatic pressure against the foundation. This pressure can cause a variety of effects on the building. It is a standard recommendation that the lot grading slopes away from the building. Grading should fall a minimum of one inch every foot for a distance of six feet around the perimeter of the building.
Lot slope: Relatively flat
Driveway material: Poured in place concrete, Satisfactory condition
Walkway material: Poured in place concrete, Satisfactory condition
Patio: Concrete, Satisfactory condition
Gutters/downspouts drain: Onto grade
Fence: Concrete block
Gate(s): Wrought iron with wood slats
4)

One or more trip hazards were found in the sidewalk due to cracks and/or settlement. Recommend having a qualified paving contractor repair or replace sidewalk section(s) as necessary to eliminate trip hazards.

Photo 11
|
|
5)
Tree branches overhang the roof or are in contact with the roof. This condition can cause damage to gutters, paint and roofing. Accumulated leaves and/or organic debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Branches can allow insects to reach and penetrate the roof. Recommend pruning of branches away from structure.

Photo 15
|

Photo 16
|
6)
There are various plants and bushes in contact with the exterior wall(s). It is recommended that all vegetation be trimmed or pruned in such a way as to allow a minimum of six inches of clearance between the plant and the exterior wall. This is necessary in order to prevent damage to the exterior and to inhibit the ability of insects to migrate into the building structure.

Photo 17
|
|
Introduction: The exterior section identifies wall cladding, flashings and trim, eaves, soffits and fascias. Also included are entryway doors, a representative number of windows, and porches, stairs, decks and balconies.
Wall surface material: Portland cement stucco
Exterior door types: Metal Clad Insulated, Sliding glass aluminum frame
Window type: Aluminum, Single pane, Double pane
Downspouts type: Aluminum, Satisfactory condition
Gutters Type: Aluminum
7)

Condensation was noted in one or more double pane window(s). This indicates a break or deterioration in the seal(s). Recommend evaluation by a qualified window contractor and replacing panes where necessary.
Note that evidence of broken seals may be more or less visible from one day to the next depending on the weather (temperature, humidity, sunlight, etc.) and it is possible that more windows than the ones identified may have bad seals and need replacement too.

Photo 60
Note water stains between panes at bottom of window.
|

Photo 61
Location: windows at rear of home
|
8)

One of the main entry doors has a double-sided dead bolt lock set. This type of lock requires a key to unlock the door from the inside and represents an obstacle to egress in the event of fire. Replacement of a single sided lock set is recommended.

Photo 44
|
|
9)
Wood trim at the east side of the patio cover has deteriorated and is rotting. Recommend having a qualified carpenter or competent handyman remove and replace rotten wood, and repaint/re-seal surface and joints.

Photo 52
|
|
10)
One or more window(s) broken, cracked, or missing. Location(s): master bathroom. Recommend replacing glass.

Photo 23
|
|
11)
Portions of the exterior woodwork and painted surfaces are showing deterioration to the paint/stain finish. It is important that these surfaces are kept well protected to ensure a maximum service life. Affected areas should be re-painted now, and subsequently as the usual signs of failure such as cracking, peeling or blistering of the painted surface become evident.

Photo 26
|
|
12)
The building has a number of flashing details where various building features intersect adjacent surfaces. Gaps and/or cracks at trim intersections should be sealed with a polyurethane caulking to protect against damp and weather penetration.

Photo 53
Garage door trim
|

Photo 54
Kitchen window
|
13)
One or more gutters are clogged with debris (leaves, mud, etc. or granular roofing material). Recommend cleaning gutters so rainwater will freely run to downspout(s) and away from the structure.
14)
Eaves, soffits, and fascias appear to be in good condition.
15)
The main exterior entry and exit doors were examined. Except as noted, all doors appeared operational, in satisfactory condition, equipped with functioning deadbolts (except for sliding glass doors, where fitted) and adequately weather stripped. As air leakage is a significant factor in the insulative and energy efficient properties of buildings, it is a standard recommendation that all doors are well adjusted and fitted with appropriate, good quality weather stripping.
Introduction: The inspection includes the covering, penetration seals, skylights (if present) and flashing. The condition of roof felt paper or membranes below roof tiles, shingles, or wood shakes is unknown and cannot be inspected without possible damage to the roof coverings. Inspectors do not access roof if roof is too high or steep or could be damaged by accessing it. Antennas, solar systems, and other attachments are not inspected in the scope of this report. No guarantee or warranty is made by this inspection as to whether the roof leaks at the time of the inspection or is subject to future leaking.
Roof inspection method: Traversed
Roof type: Cross gable
Roof covering: Concrete tile
Drip edge: Yes
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
Material Condition: Good with minor corrections needed
Flashing type: Galvanized steel
Flashing locations: Penetrations, Roof valleys, Roof to wall intersections, Chimney base
Chimney(s): Multiwall metal vent in framed chase
Skylight(s): Fixed lens, Plastic, Raised curb type
Patio Cover: The patio is covered by a wood roof, and weather protection is provided by rolled roofing material.
16)
One or more roof tiles are broken with part of the tile displaced or missing. Recommend replacement/repair by licensed roofing contractor.

Photo 34
|

Photo 35
|
17)
One or more mortar caps were observed to be cracked or broken. Recommend repair by a licensed roofing contractor as appropriate.

Photo 33
|
|
18)
Rolled roofing on the patio cover has rippled and formed one or more "fishmouths" at the edge. This condition can allow rainwater to penetrate beneath the roofing and /or the covering, causing water damage to the patio cover and ceiling (where present). Recommend sealing edges and repair of rolled roofing as appropriate by a licensed roofing contractor.

Photo 49
|

Photo 55
|
19)
One or more bird nests were observed in the roof valley(s) and significant amounts of bird droppings are present. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. It is not known if the nest(s) are active at the time of the inspection, but we recommend nest(s) and debris be cleared away and the affected portions of the roof thoroughly cleaned to prevent damage to the roof.

Photo 39
|

Photo 40
|

Photo 41
|
|
Garage vehicle door type: Metal insulated sectional roll-up
Garage walk-through door: Fire-rated, Weather-stripped
20)


The garage vehicle door does not appear to "auto-reverse" as required. When closing, the door should reverse if it either strikes something or when something passes through a photo sensor at the base of the door. This is a safety hazard, especially for small children. Recommend having a qualified garage door contractor evaluate and repair or replace opener as necessary.

Photo 36
|
|
21)

The garage-house door poses a fire risk because a pet door has been installed in it, eliminating its fire rating. Recommend having a qualified contractor replace this door with a fire-rated door.

Photo 18
|
|
22)
Added cabinets on the west wall of the garage are covering vents intended to provide combustion air to the gas water heater. When cabinet doors are closed this may reduce air supply. (See water heater section of this report.) Recommend cutting holes in the north side of the cabinet (suggest trimming with register grilles) to facilitate free flow of combustion air.

Photo 58
|

Photo 59
Contents of cabinet appear to block vent.
|
Introduction: The inspection includes identifying the type and capacity of the service, and evaluating service panels, over-current protection, wiring, system ground, and a representative number of switches and outlets. Determination of adequacy of electrical panels and current capacity are not within the scope of this report. Low voltage systems, stereos, intercoms, vacuum systems, security systems or other low voltage systems are not inspected.
Location of main disconnect: Breaker at top of main panel
Primary service type: Underground service lateral
Compatibility: Breakers and wire sizes are compatible.
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200
Service voltage (volts): 120-240
Location of main service panel: Western exterior
Location of main disconnect: Breaker at top of main panel
Service conductor material: Copper
Service Earth Ground Conductor: Copper
Earth Ground Location: Water Heater
Main disconnect rating (amps): 200
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: No
Room for expansion: Yes
Ground fault circuit interrupters functioning in: Master Bathroom, Hall Bathroom
Smoke detectors present: Yes, Functioning (see note)
23)


One or more circuit breakers are "double tapped", where 2 or more wires are clamped in a circuit breaker terminal, and the circuit breaker is only designed for 1 wire. This is a safety hazard since wires may loosen and cause arcing, sparking and fires. Recommend having a qualified, licensed electrician evaluate and repair.

Photo 31
|
|
24)


One or more electric receptacles has reversed polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard and poses a risk of shock. Recommend further evaluation and repair as appropriate by a licensed electrician.

Photo 43
Location: east wall of master bedroom
|
|
25)


Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. Location(s): Attic. Recommend installation of junction boxes with cover plates where needed by a licensed electrician.

Photo 28
|

Photo 32
|
26)

Outlets in the garage are not GFCI protected. Ground fault circuit interrupters (GFCI's) are safety devices which sense a ground fault in an electrical system and cut power to a circuit instantly. Modern codes require outlets at kitchen counters, in bathrooms, basements, garages and exterior outlets to be GFCI protected. The code at the time this home was built may not have required GFCI protection at some of these circuits. Nonetheless, we recommend they be added at these locations as an extra preventive safety measure.
27)

One or more electric receptacle boxes have damaged or missing cover plates. Cover plates are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard and poses a risk of both fire and shock. Recommend replacing cover plates over receptacle boxes where needed.

Photo 47
|
|
28)

Appliances or systems which are constantly in use are plugged into one or more exterior receptacles not equipped with "in-use" receptacle covers for wet locations. This is a safety hazard and poses a risk of both fire and shock. Recommend installing "in use" covers where necessary.

Photo 25
Power to outdoor lighting system
|
|
29)

An minimal number of smoke detectors are installed. Modern codes require a functioning smoke detector in each bedroom and one in each hallway leading to bedrooms. The code at the time this home was built may not have required that many, but nonetheless it is our standard recommendation that additional smoke detectors be installed to the level described. For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html
30)

The electrical service panel box has one or more open holes in the bottom. Box holes no longer in use should be plugged in order to keep out dust, insects and small rodents.

Photo 63
|

Photo 64
|
31)

Unsecured wiring for the kitchen's under-sink waste disposal. The plastic grommet used to secure the flexible appliance cord is loose/displaced or missing . Repeated movement of the wire can result in damaged insulation and broken conductors. This is a safety hazard and poses a risk of shock and/or fire. Recommend having a qualified electrician repair as necessary.

Photo 45
|
|
32)

A representative number of fixtures, electrical outlets and switches were found and tested. Receptacles were tested for polarity and grounding. System is serviceable with the exception of defects noted in this and/or other sections of the report.
33)
Please note: The inspection of smoke alarms is not required by the State of Arizona. Inspection of alarms consists of testing the individual alarm by depressing the test button to determine if the alarm will sound. The sounding of the alarm is no guarantee that the alarm will work in the event of a real fire. The only way to accurately test the alarm is by the introduction of smoke next to the alarm. Due to the damage that can be caused, no smoke was introduced in the test. Further testing of the alarms by the client is at the client's own risk.
Introduction: The inspection includes the evaluation of functional flow and drainage. Description of pipe material type noted in the report refers to visible portions only. There is no non-invasive way to determine what is behind a closed wall. Concealed piping will not be evaluated or identified for size or type during this inspection.
Please note: Inspectors are not required to determine the source of water supply, operate any valve except water closet flush valves, fixture faucets, and hose bibs. Water stop valves and overflows are not checked. Fixtures and trim are checked for function only and not for cosmetic value. Evaluation of solar systems, wells, filters, conditioners, yard watering systems and fire sprinklers is not required of home inspectors by state regulations
Water supply: Public
Waste type: Public
Location of main water shut-off: Eastern exterior
Location of main water meter: At street
Location of gas meter and main shut-off: Eastern exterior
Water pressure (psi): 78
Service pipe material: Copper
Branch pipe material: Copper
Drain pipe material: ABS Plastic
Waste pipe material: ABS Plastic
Waste clean-out location: Southern exterior
34)
The main water stop valve is missing its handle. In the event of an emergency, such as when a supply pipe bursts, it will be difficult (using pliers or a wrench) or impossible to shut off the water supply. Recommend having a qualified plumber or competent handyman install a handle as appropriate.

Photo 50
|
|
35)
The dishwasher drain loop is installed incorrectly. This condition allows water to flow backward from the drain into the dishwasher floor pan. Drain line should be raised and bracketed to the cabinet at a point higher than the bottom of the sink. Recommend repair as appropriate.

Photo 56
|
|
36)
Faucet at the hall bathroom sink is leaking. Water leaks from handle when faucet is turned on. Recommend repair or replacement by licensed plumber.

Photo 48
|
|
37)
Stop valve under left hand master bathroom sink is stuck open and will not easily shut off (hot water supply line). This will necessitate turning off the water supply to the whole house in the event of maintenance or repairs to individual faucet. Recommend repair or replacement of faulty stop valve(s) by licensed plumbing contractor.

Photo 57
|
|
38)
The drain under the kitchen sink is leaking. Recommend repair as appropriate.

Photo 51
|
|
39)

All faucets inside and outside the home were operated and checked for functional flow, leaks and cross connections. All drains were checked for visible leaks and flow. System is functional with the exception of noted defects.
Location: Garage
Gas lines: Every effort is made to inspect the gas lines within the dwelling. This effort, however, is often hampered by inaccessible attics and by pipe being enclosed within walls. We recommend contacting the gas company to request a complete check of the supply system. The gas company has specialized equipment and will generally conduct inspections either at no charge or for a nominal fee.
Location: Garage
Estimated age: 7 years
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 50
Manufacturer: Reliance
Model Number: FG -132-052-654
Serial Number: 2598009653
Water temperature (degrees Fahrenheit): 104
Flue type: Multi-wall
Exits through: Roof
40)


Based on the location of the water heater and the visible venting, the water heater may have an inadequate source of combustion and/or dilution air. All gas appliances require adequate air (approximately 50 cubic feet per 1000 BTU) for combustion, dilution and ventilation. This is a potential safety hazard, and may result in combustion fumes entering living spaces. Recommend further evaluation by a qualified contractor for repairs as necessary, such as installing exterior vents, or grills in walls or doors. (See garage section of this report.)
41)

Temperature-pressure relief valve drain line is missing. This is a safety hazard. Recommend having a qualified plumber install a drain line extending to within 6" from the floor, or routed so as to drain outside.

Photo 42
|
|
Introduction: The inspection describes heating equipment, distribution type and energy source. Normal operating controls are checked, and we observe automatic safety controls and the presence in each room of an installed heat source.
We inspect only installed air conditioning units and we are required to operate the system using normal controls and to describe the energy source and equipment type. We are not required to determine whether the system is adequately sized for the home, pressure-test the system or inspect for leaking refrigerant, program digital thermostats or controls or operate the setback features of thermostats or controls.
Heating system energy source: Natural gas
Heat system type: Forced air
Heating system location: Attic
Flue exits through: Roof
Access: Ceiling hatch in:, Hall
Location of electrical safety switch: Within sight of unit
Thermostat: Non-programmable
Location of thermostat: Main floor hall
Heat source in each room: Yes
Cool source in each room: Yes
A/C energy source: Electric
Air conditioning type: Split system
Air handler location: Attic
Coil condition: Good condition
Distribution system: Flexible ducts
Make: Trane
Filter type: Pleated cartridge
Filter size(s): 200 x 30 x 1
Filter location(s): Return intake(s) in, hallway
42)
Insulation on a section of the flex-poly heating and cooling ductwork was found to have split. Recommend repair or replacement as appropriate by a licensed HVAC contractor.

Photo 46
|
|
43)
The insulation on the condenser suction line is damaged or missing. This can effect the efficiency of the air conditioning system. Recommend repair as appropriate by a licensed HVAC contractor or competent handyman..

Photo 37
|
|
44)
There is debris/insulation in the condensate drain pan. This condition can lead to a plugged condensate drain line. Recommendation: Clean pan of all foreign material as appropriate and test drain line for obstruction.

Photo 38
|
|
45)

The heating system was tested using normal operating controls. No obvious defects were noted.
46)

The cooling system was tested using normal operating controls. No obvious defects were noted.
47)

Thermometer readings at checked registers and the air return were within accepted tolerances.
48)
Every effort is made to inspect the gas lines within the dwelling. This effort, however, is often hampered by inaccessible attics and by pipe being enclosed within walls. We recommend contacting the gas company to request a complete check of the supply system. The gas company has specialized equipment and will generally conduct inspections either at no charge or for a nominal fee.
Introduction: The inspection includes the visually accessible areas of walls, floors, ceilings, cabinets and counters, and includes a representative number of windows and doors. We do not evaluate window treatments, move furniture, lift carpets and rugs, nor empty closets and cabinets. Condition of floor under floor coverings, furnishings and appliances can not be verified and is therefore excluded from the scope of this inspection. The detection of environmental pollutants such as asbestos, carbon monoxide, radon, molds and fungi require specialized equipment which is beyond the scope of this service.
wall surface type: Drywall
Ceiling surface type: Drywall
Flooring types: Wall to wall carpet, Ceramic tile, Sheet vinyl.
Kitchen cabinet type: Face frame
Bathroom cabinet type: Face frame
Kitchen counter type: Laminate
Bathroom counter type: Cultured marble
Interior door type(s): Hollow core wood panel
Walls, ceilings, doors OK: Walls, ceilings, floors, interior doors, windows, counters and cabinetry, and (where present) stairs, balconies and railings were inspected with no defects observed except where noted.
Built-in appliances: Built in appliances such as range/oven, dishwasher, under-sink waste disposal and microwave were examined (where present), with no defects observed except as noted.
49)

One or more ceramic floor tiles is loose. This can be a safety hazard. Recommend having the tile(s) re-installed and grouted as appropriate.

Photo 27
Location: hallway
|
|
50)
The dishwasher mechanism leaks when the machine is running. Water appears to have lifted a portion of the vinyl flooring adjacent to the cabinet wall at the left of the dishwasher. Recommend having the dishwasher leak repaired by a qualified appliance service technician, and repairs to or replacement of (as may be necessary) the affected portion of the vinyl flooring by a qualified flooring contractor.

Photo 22
|

Photo 24
|
51)
The countertop in the kitchen to the left of the range is loose on the cabinetry. Recommend securing top to cabinet as appropriate.

Photo 2
|
|
52)
One or more gaps were noted at the joint between the wall and the top of the shower surround in the master bathroom. To prevent water intrusion which can damage wall materials, we recommend the joints be caulked/re-sealed.

Photo 7
|

Photo 8
|
Introduction: The inspection of the insulation, vapor retarders and ventilation systems of this home was limited to only unfinished, accessible areas that are exposed to view. No invasive inspection methods were used, therefore the presence of required vapor retarders or the type and density of insulation installed behind finished surfaces could not be verified. Even if the type of materials used could be determined, no declarations have been made here as to the installed density or adequacy of concealed materials.
Should the client(s) wish detailed information concerning the existence/condition of any vapor retarders and insulation concealed in the walls, ceiling cavities or other inaccessible and/or un-viewable areas, we suggest consulting an insulation contractor or certified energy auditor. Many have thermal imaging equipment that can aid in determining the overall effectiveness of installed insulation systems and identify areas needing improvement.
Insulation on perimeter walls is unknown. The inspector has no way of visually verifying insulation behind perimeter walls without utilizing invasive techniques. Perimeter wall insulation is therefore excluded from the scope of this inspection.
Inspection method: Traversed
Insulation material: Fiberglass roll or batt, Cellulose loose fill
Insulation depth: +/- 9"
Insulation rating: R30 (certificate posted
Attic ventilation: Passive
Attic ventilation intake: Frieze vents
Attic ventilation exhaust: Gable louvre vents
Exhaust fans: Kitchen, Laundry, Master Bathroom, Bathroom 2, Not all operational
53)
Dryer exhaust duct is not sealed at the roof vent cap . This condition allows lint and moist air to enter the attic space which can be a conducive condition for wood destroying insects and organisms. Recommend repairs as necessary so the exhaust air is vented outside.

Photo 65
Lint build-up on truss and roof sheathing
|
|
Fireplace location: Living room
Fireplace type: Zero-Clearance gas burning
Liner: Metal
Chimney type: Metal
Supply air: Scavenging from room
Damper: No
Hearth style: Raised hearth
54)

The fireplace was examined and tested for function and appeared to be in satisfactory condition.

Photo 4
|
|
Pool type: in ground
Pool material: Pebble-Tec
Filter type: Sand filter
Cleaning system: Vacuum
Water feature: Water fall
Pump grounded: Yes
Outlets(s) GFCI protected: Yes
Light(s): Yes, Functioning
Auto-fill: Yes, Not functioning
55)

Level of water in pool is too high. Float mechanism in auto fill feature appears to be non-functional. Recommend further evaluation by licensed pool contractor for repair or replacement as necessary.

Photo 1
|

Photo 5
|
56)
Cracks were noted in one or more areas of the deck . Recommend repair to prevent intrusion of water into ground around pool structure and potential for damage from soil expansion.

Photo 29
|

Photo 30
|
57)
Pressure on filter gauge is excessive, indicating need for backwashing or possible replacement of filter medium. Recommend further evaluation and service as necessary by licensed pool equipment contractor.

Photo 10
|
|
58)
Secondary leaf catcher basket at pump is clogged and should be cleaned.

Photo 3
|
|
59)
Areas of the kooldeck coating are chipped at the pool edge. Recommend repair as appropriate.

Photo 6
|

Photo 9
|
This concludes the Inspection Report
STANDARDS OF PROFESSIONAL PRACTICE
TABLE OF CONTENTS
Section Description
1. Introduction
2. Purpose and Scope
3. General Limitations & Exclusions
4. Structural Components
5. Exterior
6. Roofing
7. Plumbing
8. Electrical
9. Heating
10. Central Air Conditioning
11. Interiors
12. Insulation & Ventilation
13. Pools and Spas
Glossary NOTE: Italicized words are defined in the Glossary
1. INTRODUCTION
1.1 These Standards define the practice of Home Inspection in the State of Arizona.
1.2 These Standards of Practice
A. provide inspection guidelines.
B. make public the services provided by private fee-paid inspectors.
2. PURPOSE AND SCOPE
Inspections performed to these Standards shall provide the client with a better understanding of the property conditions, as observed at the time of the inspection.
2.2 Inspectors shall:
A. before the inspection report is delivered, enter into a written agreement with the client or their authorized agent that includes:
1. the purpose of the inspection.
2. the date of the inspection.
3. the name address and certification number of the inspector.
the fee for services.
4. a statement that the inspection is performed in accordance with these Standards.
limitations or exclusions of systems or components inspected.
B. Observe readily accessible installed systems and components listed in these Standards.
C. submit a written report to the client, which shall:
1. describe systems and components identified in sections 4-12 of these Standards.
2. state which systems and components designated for inspection in these Standards have been inspected and any systems and components designated for inspection in these Standards, which were present at the time of the inspection and were not inspected and a reason why they were not inspected.
3 state any systems and components so inspected which were found to be in need of immediate major repair and any recommendations to correct, monitor or evaluate by appropriate persons.
2.3 These Standards are not intended to limit inspectors from:
A. reporting observations and conditions in addition to those required in Section 2.2.
B. excluding systems and components from the inspection if requested by the client.
3. GENERAL LIMITATIONS AND EXCLUSIONS
3.1 General limitations:
A. Inspections done in accordance with these Standards are visual, not technically exhaustive and will not identify concealed conditions or latent defects.
These Standards are applicable to buildings with four or less dwelling units and their garages or carports.
3.2 General exclusions:
A. Inspectors are NOT required to report on:
1. life expectancy of any component or system.
2. the causes of the need for a major repair.
3. the methods, materials and costs of corrections.
4. the suitability of the property for any specialized use.
5. compliance or non-compliance with applicable regulatory requirements.
6. the market value of the property or its marketability.
7. the advisability or inadvisability of purchase of the property.
8. any component or system, which was not observed.
9. the presence or absence of pests such as wood damaging organisms, rodents, or insects.
10. cosmetic items, underground items, or items not permanently installed.
B. Inspectors are NOT required to:
1. offer warranties or guarantees of any kind.
2. calculate the strength, adequacy, or efficiency of any system or component.
3. enter any area or perform any procedure, which may damage the property or its components or be dangerous to the inspector or other persons.
4. operate any system or component, which is shut down or otherwise inoperable.
5. operate any system or component, which does not respond to normal operating controls.
6. disturb insulation, move personal items, furniture, equipment, plant life, soil, snow, ice, or debris, which obstructs access or visibility.
7. determine the presence or absence of any suspected hazardous substance including but not limited to toxins, fungus, molds, mold spores, carcinogens, noise, and contaminants in soil, water, and air.
8. determine the effectiveness of any system installed to control or remove suspected hazardous substances.
9. predict future conditions, including but not limited to failure of components.
10. project operating costs of components.
11. evaluate acoustical characteristics of any system or component.
3.3 Limitations and exclusions specific to individual systems are listed in following sections.
4. SYSTEM: STRUCTURAL COMPONENTS
4.1 The inspector shall observe:
A. structural components including:
1. foundation.
2. floors.
3. walls.
4. columns.
5. ceilings.
6. roofs.
4.2 The Inspector shall:
A. describe the type of:
1. foundation.
2. floor structure.
3. wall structure.
4. columns.
5. ceiling structure.
6. roof structure.
B. probe structural components where deterioration is suspected. However, probing is NOT required when probing would damage any finished surface.
C. enter under floor crawl spaces and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected.
D. report the methods used to inspect under floor crawl spaces and attics.
E. report signs of water penetration into the building or signs of abnormal or harmful condensation on building components.
5. SYSTEM: EXTERIOR
5.1 The inspector shall observe:
A. wall cladding, flashings and trim.
B. entryway doors and representative number of windows.
C. garage door operators.
D. decks, balconies, stoops, steps, areaways, and porches including railings.
E. eaves, soffits and fascias.
F. vegetation, grading, drainage, driveways, patios, walkways and retaining walls with respect to their effect on the condition of the building.
5.2 The inspector shall:
A. describe wall-cladding materials.
B. operate all entryway doors and representative number of windows including garage doors, manually or by using permanently installed controls of any garage door operator.
C. report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing.
5.3 The inspector is NOT required to observe:
A. storm windows, storm doors, screening, shutters, awnings and similar seasonal accessories.
B. fences.
C. safety glazing.
D. garage door operator remote control transmitters.
E. geological conditions.
F. soil conditions.
G. recreational facilities.
H. outbuildings other than garages and carports.
6. SYSTEM: ROOFING
6.1 The inspector shall observe:
A. roof coverings.
B. roof drainage systems.
C. flashings.
D. skylights, chimneys and roof penetrations.
E. signs of leaks or abnormal condensation on building components.
6.2 The inspector shall:
A. describe the type of roof covering materials.
B. report the methods used to inspect roofing.
6.3 The inspector is NOT required to:
A. walk on the roofing.
B. observe attached accessories including but not limited to solar systems, antennae, and lightning arresters.
7. SYSTEM: PLUMBING
7.1 The inspector shall observe:
A. interior water supply and distribution system including:
1. piping materials, including supports and insulation.
2. fixtures and faucets.
3. functional flow.
4. leaks.
5. cross connections.
B. interior drain, waste and vent system, including:
1. traps; drain, waste, and vent piping; piping supports and pipe insulation.
2. leaks.
3. functional drainage.
C. hot water systems including:
1. water heating equipment.
2. normal operating controls.
3. automatic safety controls.
4. chimneys, flues and vents.
D. fuel storage and distribution systems including:
interior fuel storage equipment, supply piping, venting and supports.
leaks.
E. sump pumps.
7.2 The inspector shall:
A. describe:
1. water supply and distribution piping materials.
2. drain, waste and vent piping materials.
3. water heating equipment.
B. operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house.
7.3 The inspector is NOT required to:
A. state the effectiveness of anti-siphon devices.
B. determine whether water supply and waste disposal systems are public or private.
C. operate automatic safety controls.
D. operate any valve except water closet flush valves, fixture faucets and hose faucets.
E. observe:
1. water conditioning systems.
2. fire and lawn sprinkler systems.
3. on-site water supply quantity and quality.
4. on-site waste disposal systems.
5. foundation irrigation systems.
6. spas, except as to functional flow and functional drainage.
8. SYSTEM: ELECTRICAL
8.1 The inspector shall observe:
A. service entrance conductors.
B. service equipment, grounding equipment, main over-current device, and main and distribution panels.
C. amperage and voltage ratings of the service.
D. branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages.
E. the operation of a representative number of installed lighting fixtures, switches and receptacles located inside the house, garage, and on its exterior walls.
F. the polarity and grounding of all receptacles within six feet of interior plumbing fixtures and all receptacles in the garage or carport, and on the exterior of inspected structures.
G. the operation of ground fault circuit interrupters.
8.2 The inspector shall:
A. describe:
1. service amperage and voltage.
2. service entry conductor materials.
3. service type as being overhead or underground.
4. location of main and distribution panels.
B. report any observed aluminum branch circuit wiring.
8.3 The inspector is NOT required to:
A. insert any tool, probe or testing device inside the panels.
B. test or operate any over current device except ground fault interrupters.
C. dismantle any electrical device or control other than to remove covers of the main and auxiliary distribution panels.
D. observe
1.smoke detectors.
2. telephone, security, cable TV, intercoms or other ancillary wiring that is not a part of the primary electrical distribution system.
9. SYSTEM: HEATING
9.1 The inspector shall observe:
A. permanently installed heating systems including:
1. heating equipment.
2. normal operating controls.
3. automatic safety controls.
4. chimneys, flues and vents.
5. solid fuel heating devices.
6. heat distribution systems including fans, pumps, ducts and piping, with supports, dampers, insulation, air filters, registers, radiators, fan coil units, convectors.
7, the presence of an installed heat source in each room.
9.2 The inspector shall:
A. describe:
1. energy source.
2. heating equipment and distribution type.
B. operate the systems using normal operating controls.
C. open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance.
9.3 The inspector is NOT required to:
A. operate heating systems when weather conditions or other circumstances may cause equipment damage.
B. operate automatic safety controls.
C. ignite or extinguish solid fuel fires.
D. observe:
1. the interior of flues.
2. fireplace insert flue connections.
3. humidifiers.
4. electronic air filters.
5. the uniformity or adequacy of heat supply to the various rooms.
10. SYSTEM: CENTRAL AIR CONDITIONING
10.1 The inspector shall observe:
A. central air conditioners including:
1. cooling and air handling equipment.
2. normal operating controls.
B. distribution systems including:
1. fans, pumps, ducts and piping, with supports, dampers, insulation, air filters, registers, fan-coil units.
2. the presence of an installed cooling source in each room.
10.2 The inspector shall:
A. describe:
1. energy sources.
2. cooling equipment type.
B. operate the systems using normal operating controls.
C. open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance.
10.3 The inspector is NOT required to:
A. operate cooling systems when weather conditions or other circumstances may cause equipment damage.
B. observe non-central air conditioners.
C. observe the uniformity or adequacy of cool-air supply to the various rooms.
11. SYSTEM: INTERIORS
11.1 The inspector shall observe:
A. walls, ceiling and floors.
B. steps, stairways, balconies and railings.
C. counters and a representative number of cabinets.
D. a representative number of doors and windows.
E. separation walls, ceilings, and doors between a dwelling unit and an attached garage or another dwelling unit.
F. sumps.
11.2 The inspector shall:
A. operate a representative number of primary windows and interior doors.
B. report signs of water penetration into the building or signs of abnormal or harmful condensation on building components.
11.3 The inspector is NOT required to observe:
A. paint, wallpaper and other finish treatments on the interior walls, ceilings, and floors.
B. carpeting.
C. draperies, blinds or other window treatments.
D. household appliances.
E. recreational facilities or another dwelling unit.
12. SYSTEM: INSULATION & VENTILATION
12.1 The inspector shall observe:
A. insulation and vapor retarders in unfinished spaces.
B. ventilation of attics and foundation areas.
C. kitchen, bathroom, and laundry venting systems.
12.2 The inspector shall describe:
A. insulation and vapor retarders in unfinished spaces.
B. absence of same in unfinished space at conditioned surfaces.
12.3 The inspector is NOT required to report on:
A. concealed insulation and vapor retarders.
B. venting equipment, which is integral with household appliances.
13. Pools and Spas
The inspector may examine the following at his/her discretion, as agreed with client:
A. Items to be identified and reported:
1. Location and type of pool or spa examined.
2. Conditions limiting or otherwise inhibiting inspection.
3. Enclosure and related gates.
4. Hardscaping and drainage related to the inspected pool or spa.
5. Condition of visible portions of systems, structures, or components.
6. Normally necessary and present equipment such as lights, pumps, heaters, filters, and related mechanical and electrical connections.
B. The inspector is not required to:
1. Examine any above-ground, movable, freestanding, or otherwise non-permanently installed pool or spa, or self-contained equipment.
2. Come into contact with pool or spa water to examine the system, structure, or components.
3. Determine adequacy of spa jet water force or bubble effect.
4. Determine structural integrity or leakage of any kind.
5. Evaluate thermostat(s) or their calibration, heating elements, chemical dispensers, water chemistry or conditioning devices, low voltage or computer controls, timers, sweeps or cleaners, pool or spa covers, and related components.
6. Operate or evaluate filter backwash systems.
7. Examine accessories, such as, but not limited to, aerators or air-blowers, diving or jump boards, ladders, skimmers, slides, or steps.
GLOSSARY
Automatic Safety Controls:
Devices designated and installed to protect systems and components from high or low pressures and temperatures, electrical current, loss of water, loss of ignition, fuel leaks, fire, freezing, or other unsafe conditions.
Central Air Conditioning:
A system, which uses ducts to distribute, cooled and/or dehumidified air to more than one room or uses pipes to distribute chilled water to heat exchangers in more than one room, and that is not plugged into an electrical convenience outlet.
Client:
A customer who contracts with a home inspector for a home inspection.
Component:
A readily accessible and observable aspect of a system, such as a floor, or wall, but not individual pieces such as boards or nails where many similar pieces make up the system.
Cross Connection:
Any physical connection or arrangement between potable water and any source of contamination.
Dangerous or Adverse Situations:
Situations, which pose a threat of injury to the inspector, and those situations that require the use of special protective clothing or safety equipment.
Describe:
Report in writing a system or component by its type, or other observed characteristics, to distinguish it from other components used for the same purpose.
Dismantle:
To take apart or remove any component, device or piece of equipment that is bolted, screwed, or fastened by other means and that would not be taken apart or removed by a homeowner in the course of normal household maintenance.
Engineering:
Any professional service or creative work requiring education, training, and experience and the application of special knowledge of the mathematical, physical and engineering sciences
Evaluation by Appropriate Persons:
Examination and analysis by a qualified professional, tradesman, or service technician beyond that provided by the home inspector.
Functional Drainage:
A drain is functional when it empties in a reasonable amount of time and does not overflow when another fixture is drained simultaneously.
Functional Flow:
A reasonable flow at the highest fixture in a dwelling when another fixture is operated simultaneously.
Immediate Major Repair:
A major defect, which if not quickly addressed, will be likely to do any of the following:
worsen appreciably
cause further damage
be a serious hazard to health and/or personal safety
Inspector:
A person certified as a home inspector by the Arizona Board of Technical Registration
Installed:
Attached or connected such that the installed item requires tools for removal.
Major Defect:
A system or component that is unsafe or not functioning
Normal Operating Controls:
Homeowner operated devices such as a thermostat, wall switch or safety switch.
Observe:
The act of making a visual examination of a system or component and reporting on its condition.
On-site Water Supply Quality:
Water quality is based on the bacterial, chemical, mineral and solids content of the water.
On-site Water Supply Quantity:
Water quantity is the rate of flow of water.
Primary Windows and Doors:
Windows and/or exterior doors, which are designed to remain in their respective openings year round.
Readily Accessible
Available for visual inspection without requiring moving of personal property, dismantling, destructive measures, or any action which will likely involve risk to persons or property.
Readily Openable Access Panel:
A panel provided for homeowner inspection and maintenance that has removable or operable fasteners or latch devices in order to be lifted off, swung open, or otherwise removed by one person, and its edges and fasteners are not painted in place. Limited to those panels within normal reach or from a 4-foot stepladder, and which are not blocked by stored items, furniture, or building components.
Recreational Facilities:
Spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities.
Representative Number:
For multiple identical components such as windows and electrical outlets, the inspection of one such component per room. For multiple identical exterior components, the inspection of one such component on each side of the building.
Roof Drainage Systems:
Gutters, downspouts, leaders, splash blocks, and similar components used to carry water off a roof and away from a building.
Safety Glazing:
Tempered glass, laminated glass, or rigid plastic.
Shut Down:
A piece of equipment whose safety switch or circuit breaker is in the "off" position, or its fuse is missing or blown, or a system that cannot be operated by the device or control that a home owner should normally use to operate it.
Solid Fuel Heating Device:
Any wood, coal, or other similar organic fuel-burning device, including but not limited to fireplaces whether masonry or factory built, fireplace inserts and stoves, woodstoves (room heaters), central furnaces, and combinations of these devices.
Structural Component:
A component that supports non-variable forces or weights (dead loads) and variable forces or weights (live loads). For purposes of this definition, a dead load is the fixed weight of a structure or piece of equipment, such as a roof structure on bearing walls, and a live load is a moving variable weight added to the dead load or intrinsic weight of a structure.
System:
A combination of interacting or interdependent components, assembled to carry out one or more functions.
Technically Exhaustive:
An inspection is technically exhaustive when it involves the use of measurements, instruments, testing, calculations, and other means to develop scientific or engineering findings, conclusions, and recommendations.
Under floor Crawl Space:
The area within the confines of the foundation and between the ground and the underside of the lowest floor structural component.
Unsafe:
A condition in a readily accessible, installed system or component, which is judged to be a significant risk of personal injury during normal, day-to-day use. The risk may be due to damage, deterioration, improper installation or a change in adopted residential construction standards.