How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary


General Information
Return to table of contents

Report number: 1003
Present during inspection: Client, Property owner
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: 55
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 19 yrs
Front of building faces: North
Main entrance faces: North
Occupied: No

1) This is a safety concern an as such needs to be address as soon as possible. Furnace and venting in attic.
Dryer vent obstruction.
Trusses in attic.
Bucket Chemical?
Photo
Photo 1-1
Dryer vent twisted and constricted. Recommend correcting and cleaning. This can cause a fire (gas supply line in direct contact with vent this is not safe).
Photo
Photo 1-2
The red arrow shows a 4 inch exhaust fan from bathroom venting into attic along with all bathroom exhaust installed the same way. Recommend correction by qualified HVAC contractor.
Photo
Photo 1-3
Trusses appear to have had boards nailed to them or possible cut. Recommend evaluation by qualified contractor and structural engineer. Remove bucket.
 

2) Many areas and items at this property were obscured by . This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground with binoculars
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable

3) Flashings at the base of one or more chimneys were . Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 3-1
No apparent leaks at time of inspection from chimney flashing. Recommend inspection by roofing contractor
 

4) Some composition shingles were loose. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 4-1
Shingle tiles raising, this will allow rain blown by wind to penetrate under shingle creating a possible leak. Recommend roofing contractor investigate.
 

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass loose fill
Roof ventilation type: Ridge vent(s)

5) One or more roof trusses were cut, damaged or modified. The roof structure has likely been weakened as a result. Trusses are engineered components and shouldn't be cut or modified by builders or homeowners. Repairs may involve restoring the trusses to their original condition or configuration. Recommend that a licensed structural engineer evaluate and prescribe repairs as necessary. A qualified contractor should perform repairs per the engineer's specifications.
Photo
Photo 5-1
The red arrow shows a 4 inch exhaust fan from bathroom venting into attic along with all bathroom exhaust installed the same way. Recommend correction by qualified HVAC contractor.
Photo
Photo 5-2
Trusses appear to have had boards nailed to them or possible cut. Recommend evaluation by qualified contractor and structural engineer. Remove bucket.

6) One or more soffit vents were blocked by insulation. This can reduce air flow through the roof structure or attic and result in reduced service life for the roof surface materials because of high temperatures. Moisture from condensation is also likely to accumulate in the roof structure and/or attic and can be a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary so air flows freely through all vents. For example, by moving or removing insulation and installing cardboard baffles.
Photo
Photo 6-1
 

Garage or Carport
Return to table of contents

Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 2
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes

7) The auto-reverse mechanism on one or more automatic openers for garage vehicle doors was inoperable. This is a potential safety hazard. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.reporthost.com/?NRGD

8) One or more garage vehicle doors were damaged or deteriorated. Recommend that a qualified contractor door(s) as necessary.

Safety eye north door inoperable, auto reverse not operating on either door.
Photo
Photo 8-1
Brick corner broken on north garage. Possibly due to small crack in brick at time of installation allowing water to freeze and expand breaking the brick. Consider sealing the exterior brick.
Photo
Photo 8-2
Damage to north garage door trim and molding. This need to be water tight to prevent storm water entering garage.

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Not determined (components inaccessible or obscured)
Main disconnect rating (amps): 200
System ground: Not determined, not readily apparent
Location of main service panel #A: Basement

9)   Service panel location
Photo
Photo 9-1
Electrical service panel in basement 200 amp.
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic

10) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC
Photo
Photo 10-1
Discoloration of ground around septic tank. Possible indication of issue with tank.
Photo
Photo 10-2
Ground around septic tank vent sinking. Possible indication of ground water (rain) entering into tank or settling of tank.

11) The sump pump pit was sealed (typically with bolts). As a result, the inspector was unable to determine if the pump was operable by lifting the float mechanism. Its condition is unknown. It may need repairs. If concerned, have a qualified contractor evaluate further to determine if it's serviceable.
Photo
Photo 11-1
Sump pump in basement unable to verified operation. Disassembly required. recommend verification by qualified plumper.
 

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 19yrs.
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace, Wood-burning fireplace or stove
General heating distribution type(s): Ducts and registers, Pipes, in-floor
Last service date of primary heat source: unknown
Condition of forced air heating/(cooling) system: Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 19 yrs
Location of forced air furnace: Basement
Condition of furnace filters: N/A (none visible)
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Circulating pump
Hydronic or steam heat fuel type: Natural gas
Condition of burners: Not determined (inaccessible, obscured, or gas or oil service off)
Type of combustion air supply: Vent(s) to exterior
Condition of venting system: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: east
Type: Split system

12) Because of the age and/or condition of the forced air furnace, recommend that a qualified HVAC contractor inspect the heat exchanger and perform a carbon monoxide test when it's serviced. Note that these tests are beyond the scope of a standard home inspection.
Photo
Photo 12-1
Heating and A/C unit. Evidence of condensate from A/C coil not draining properly. Recommend Service by HVAC contractor As soon as possible. Potential serious damage to unit will result.
Photo
Photo 12-2
90% furnace unable to determine age due to requiring removing bolts. Recommend servicing by HVAC contractor. As soon as possible.

13) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo
Photo 13-1
AC condenser recommend cleaning and maintenance on annual basis.
Photo
Photo 13-2

14) The last service date of the forced air heating/cooling system appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor service this system and make repairs if necessary. Because this system has a compressor and refrigerant system, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the contractor when it's serviced.

15) The heating system was not fully evaluated because the . Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that the inspector does not operate shut-off valves, pilot lights or circuit breakers, or any controls other than normal controls (thermostat).

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry with metal liner

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Range, cooktop, oven type: Natural gas
Type of ventilation: None visible
Condition of refrigerator: Near, at or beyond service life

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Condition of counters: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans
Gas supply for laundry equipment present: Yes

16) The clothes dryer exhaust duct was kinked, crushed or damaged. Air flow will be restricted as a result and the clothes dryer may overheat. This is a safety hazard due to the risk of fire. Recommend that a qualified person replace or repair the duct as necessary. For more information, visit:
http://www.reporthost.com/?DRYER
Photo
Photo 16-1
Dryer vent twisted and constricted. Recommend correcting and cleaning. This can cause a fire (gas supply line in direct contact with vent this is not safe).
 

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No


Photo
Photo X-1
Photo
Photo X-2
Domestic H/W (right) heater and Radiant water heater (left) 50% gallon capacity.
Photo
Photo X-3
Basement walkout door showing signs of water penetration. Recommend cleaning and sealing.
Photo
Photo X-4
Rust stains in tub in basement bath. Leaking faucet and high rust content in water.
Photo
Photo X-5
Photo
Photo X-6
Ceiling tiles in basement bath sagging on both side of room. This is due to moisture not being removed by exhaust also poor installation.
Photo
Photo X-7
Exterior storm door in master bedroom seal needs replace to prevent water penetration.
Photo
Photo X-8
Exterior door threshold in master bedroom showing signs of water penetration. Recommend cleaning and sealing
Photo
Photo X-9
Corrosion at supply line on half bath toilet. Recommend replacement.
Photo
Photo X-10
Water spots on ceiling in living room. Appear to be a old and show no evidence at this time of moisture.
Photo
Photo X-11
Water spots on ceiling in living room. Appear to be a old and show no evidence at this time of moisture.
Photo
Photo X-12
Red circle shows B-vent on H/W heater surrounded by insulation, this vent requires a one inch clearance from combustible materials.
The red arrow shows a 4 inch exhaust fan from bathroom venting into attic along with all bathroom exhaust installed the same way. Recommend correction by qualified HVAC contractor.
Photo
Photo X-13
The circle arrow shows a 4 inch exhaust fan from bathroom venting into attic along with all bathroom exhaust installed the same way. Recommend correction by qualified HVAC contractor.
Photo
Photo X-14
Front door needs cleaning and painting.
Photo
Photo X-15
Recommend cleaning deck and applying sealant.
Photo
Photo X-16
Exterior outlet missing cover on front porch, local may require ground fault interrupt (GFI) be installed.
Photo
Photo X-17
Photo
Photo X-18
Front porch stair uneven tread, settling on right. Tripping hazard.
Photo
Photo X-19
Electrical service 200 amp disconnect located on east side of home.
Photo
Photo X-20
Staining on roof due to chimney repair.
Photo
Photo X-21
Support joist setting on double joist only a few inches. Recommend evaluation by qualified contractor.
Photo
Photo X-22
Photo
Photo X-23
Support joist hanging from strap. Unusual installation recommend evaluation by qualified contractor.
Photo
Photo X-24
Crack in retaining wall. Recommend sealing to prevent water penetration an rusting if reinforcement bar in wall.
Photo
Photo X-25
Support post setting on edge and corner of post not on wall.
recommend evaluation by qualified contractor.
Photo
Photo X-26
Recommend cleaning deck and applying sealant.
Photo
Photo X-27
Remove all vegetation in contact with wood. This will prevent damage to wood due to moisture.
Photo
Photo X-28
Stairs and landing from rear deck uneven treads, landing slabs shifted and settling.
Tripping hazard.
Photo
Photo X-29
Stairs and landing from rear deck uneven treads, landing slabs shifted and settling.
Tripping hazard and winter ice billed up.
Photo
Photo X-30
Remove all vegetation in contact with wood. This will prevent damage to wood due to moisture.
Photo
Photo X-31
Remove all vegetation in contact with exterior wall. This will prevent damage to mortar.
Photo
Photo X-32
Vegetation over grow.
Photo
Photo X-33
Gas regulator on west side of house.
Photo
Photo X-34
Remove all vegetation in contact with exterior wall. This will prevent damage to mortar.
Photo
Photo X-35
Remove all vegetation in contact with wood. This will prevent damage to wood due to moisture.
Photo
Photo X-36
Remove all vegetation in contact with exterior wall. This will prevent damage to mortar.
Photo
Photo X-37
Recommend cleaning porch and applying sealant.
Photo
Photo X-38
Door bell wire hanging loose.

Thank you for you choosing Professional Home Inspections for your inspection needs. We will always provide quality inspections for a fare price, and take pride in doing so.

Timothy W. Patrick