Property Inspection Report

Client(s):  Teddy Clunie
Property address:  1010 Morningside Drive
Lebanon, IN 46052
Inspection date:  Friday, May 22, 2015

This report published on Friday, May 22, 2015 8:14:09 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeDamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings


General Information
Return to table of contents

Report number: 20150522
Time started: 12:00
Time finished: 3:00
Present during inspection: Client
Client present for discussion at end of inspection: Yes
Inspector: Martin Price
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool, 58
Ground condition: Dry
Recent weather: Dry (no rain)
Overnight temperature: Cool, 46
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1979
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: Yes
Source for additions and modifications: Client
1) Many areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Photo
Photo 1-1
Photo
Photo 1-2
Photo
Photo 1-3

2) The front window was found open by the inspector when he arrived at the home.
Photo
Photo 2-1

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Concrete
3) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 3-1

4) Mulch was seen around the A/C unit on the right side of the home. It appeared to have been washed there by water by the way it was placed on the sidewalk. Recommend you ask the owner about water problems on this side of the home. The ground may need to be regraded to slope away from the home.
Photo
Photo 4-1

5) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
Photo
Photo 5-4

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Concrete block
Footing material (under foundation stem wall): Poured in place concrete
6) Damage Fungal rot was found at one or more fascia. Conducive conditions for rot should be corrected (e.g. wood-soil contact, reverse perimeter slope). Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo
Photo 6-1
Photo
Photo 6-2
Photo
Photo 6-3

7) Conducive conditions The masonry (brick or stone) veneer was deteriorated or damaged in some areas. Where cracks or openings are exposed, water may enter the wall structure causing mold, fungal growth and structural damage. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by repointing mortar or replacing broken or missing masonry.
Photo
Photo 7-1
Photo
Photo 7-2
Photo
Photo 7-3
Photo
Photo 7-4

8) One or more exhaust duct end caps were damaged. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
Photo
Photo 8-1

9) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 9-1
Photo
Photo 9-2
Photo
Photo 9-3
Photo
Photo 9-4

10) Conducive conditions Trees were in contact with or were close to the building at one or more locations. Damage to the building may occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 10-1
Photo
Photo 10-2

11) Conducive conditions The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 11-1
Photo
Photo 11-2

12) Conducive conditions Caulk was deteriorated in some areas. For example, around windows. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK
Photo
Photo 12-1
Photo
Photo 12-2

13) Some foundation walls below the house were obscured by insulation. The inspector was unable to evaluate these areas. They are excluded from this inspection.
Photo
Photo 13-1

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Garage
Crawl space access points that were opened and viewed, traversed or partially traversed: A
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Concrete block
Beam material: Built-up wood
Floor structure above: Engineered wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Insulation material underneath floor above: None visible
Condition of vapor barrier: Not applicable, none installed
Vapor barrier present: None visible
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: Unconditioned space, with vents
14) Conducive conditions Microbial growths were found at one or more locations in the crawl space. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit:
http://www.reporthost.com/?MOLDCDC
http://www.reporthost.com/?MOLDEPA
Photo
Photo 14-1
Photo
Photo 14-2

15) Damage Fungal rot was found on the band board on the north wall of the crawlspace. Located below the kitchen area. The area in question did not have any water lines or drain lines in the immediate area. I was unable to determine the source of the moisture to this area. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 15-1
Photo
Photo 15-2
Photo
Photo 15-3

16) Conducive conditions Evidence of prior water intrusion or accumulation was found in one or more sections of the crawl space. For example, sediment stains on the vapor barrier or foundation, and/or efflorescence on the foundation. Accumulated water is a conducive condition for wood-destroying organisms and should not be present in the crawl space. Recommend that the client review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space. The crawl space should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, gravity drains and/or sump pump(s) in the crawl space.
Photo
Photo 16-1
Photo
Photo 16-2

17) Conducive conditions No vapor barrier was installed in the crawl space. This is a conducive condition for wood-destroying organisms due to the likelihood of water evaporating from the soil below up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified contractor install a vapor barrier per standard building practices.
Photo
Photo 17-1
Photo
Photo 17-2
Photo
Photo 17-3

18) Conducive conditions One or more exhaust ducts (e.g. bathroom fan, clothes dryer) in the crawl space have come apart or were loose. This can result in increased moisture levels inside the structure and is a conducive condition for wood-destroying organisms. Recommend that a qualified person make permanent repairs as necessary.
Photo
Photo 18-1
Photo
Photo 18-2

19) Conducive conditions Cellulose material such as scrap wood, insulation and old sump pumps were found in the crawl space. This is a conducive condition for wood-destroying organisms. Recommend removing all cellulose-based debris or stored items.
Photo
Photo 19-1
Photo
Photo 19-2

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Hipped
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full
20) Conducive conditions One or more rubber or neoprene pipe flashings were split or cracked. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor replace flashings where necessary.
Photo
Photo 20-1

21) Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 21-1

22) Conducive conditions Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 22-1
Photo
Photo 22-2
Photo
Photo 22-3

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Location of attic access point #A: Garage
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): R-19
Vermiculite insulation present: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Box vents (roof jacks)
23) The pull-down attic stairs had loose, missing or otherwise substandard hardware such as bolts, screws, hinges or brackets. This is a potential fall hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 23-1
Photo
Photo 23-2

24) The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
25) Both Bath exhaust fans in the attic had no duct to route the exhaust air outside. As a result, conditioned air will enter the attic when the fan is operated. This can result in excessive moisture in the attic. Recommend that a qualified contractor install ducting per standard building practices. Typically, this includes a duct with R-4 rated insulation permanently attached to a vent hood or cap installed on the roof or at an exterior wall.
Photo
Photo 25-1
Photo
Photo 25-2

26) The ceiling insulation in one or more areas of the attic was compacted or uneven and/or missing. Heating and cooling costs may be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).
Photo
Photo 26-1

27) What appeared to be past water stains were visible on the roof structure at one or more locations in the attic. However, no elevated levels of moisture were found at these stains during the inspection. The stains may have been caused by a past leak. Recommend asking the property owner about past leaks. Monitor these areas in the future, especially after heavy rains to determine if active leaks exist. If leaks are found, recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 27-1
Photo
Photo 27-2

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Metal
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
28) Some floor areas were obscured by vehicles and/or stored items and couldn't be fully evaluated.
Photo
Photo 28-1

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil, Cold water supply pipes
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Circuit breakers that were in the "off" position: Large 220 breaker
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
Smoke alarm power source(s): Battery
29) Panel(s) #A were manufactured by the Federal Pacific Electric company and used "Stab-Lok" circuit breakers. There is significant evidence that both double and single pole versions of these circuit breakers fail by not tripping when they are supposed to. However, in 2011 the Consumer Products Safety Commission (CPSC) closed an investigation into this product because they did not have enough data to establish that the circuit breakers pose a serious risk of injury to consumers. Regardless, and due to other evidence of safety issues, recommend that a qualified electrician carefully evaluate all Federal Pacific panels and make repairs as necessary. Consider replacing Federal Pacific panels with modern panels that offer more flexibility for new, safer protective technologies like ground fault circuit interrupters (GFCls) and arc fault circuit interrupters (AFCls). For more information, visit:
http://www.reporthost.com/?FP1
http://www.reporthost.com/?FP2
http://www.reporthost.com/?FP3
Photo
Photo 29-1
Photo
Photo 29-2
Photo
Photo 29-3
Photo
Photo 29-4
Photo
Photo 29-5
Photo
Photo 29-6

30) Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo
Photo 30-1
Photo
Photo 30-2

31) One or more wall switches were worn. The light or receptacle (outlet) controlled by the switch was powered intermittently and/or if the switch was wiggled. These switches can overheat or arc and spark due to loose connections. This is a potential fire hazard. Recommend that a qualified electrician replace worn switches as necessary.
Photo
Photo 31-1
closet light switch, middle bedroom

32) Light fixtures with fully or partially exposed incandescent bulbs were installed in one or more closets. This is a fire hazard. Flammable stored items can come into contact with hot bulbs, or hot fragments from broken bulbs can fall on combustible materials. Closet lighting should use fluorescent light fixtures or fully enclosed incandescent fixtures. Installing a compact fluorescent lamp in a lamp holder is not an acceptable practice. If globes or covers are missing, they should be replaced. Otherwise recommend that a qualified electrician replace closet lights per standard building practices.
Photo
Photo 32-1
Photo
Photo 32-2

33) One or more slots where circuit breakers are normally installed were open in panel(s) #A. Energized equipment was exposed and is a shock hazard. Recommend that a qualified person install closure covers where missing.
Photo
Photo 33-1

34) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.reporthost.com/?SMKALRMLS
Photo
Photo 34-1

35) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.reporthost.com/?COALRM
36) One or more energized conductors in panel(s) # A had white, gray or green insulation. Insulation on energized conductors should be black or red in color to identify them as energized wires. Recommend that a qualified electrician re-identify wires per standard building practices. For example, by wrapping in black vinyl tape or marking with a black permanent marker.
Photo
Photo 36-1
Photo
Photo 36-2

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water meter: By street
Location of main water shut-off: Not determined (obscured, inaccessible or none found)
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: Yes
Condition of sump pump: Appeared serviceable
Sewage ejector pump installed: No
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter
37) the liner was substandard, it was a 5 gallon bucket with holes drilled into it. Sediment can clog and damage the pump. Typical dimensions are 18 inches in diameter and 2-3 feet deep. Recommend that a qualified person repair per standard building practices.
Photo
Photo 37-1
Photo
Photo 37-2

38) The inspector did not determine the location of the main water shut-off valve, or verify that a readily accessible shut-off valve in the building exists. Recommend consulting with the property owner to determine if a main shut-off valve exists, locating it yourself, or that a qualified plumber find it if necessary. If no readily accessible main shut-off valve is found in the building, then recommend that a qualified plumber install one so the water supply can be quickly turned off in the event of an emergency, such as when a supply pipe bursts.
Photo
Photo 38-1
The yellow is the main line coming in from the meter pit in the yard. The red is the line connecting to the waterlines throughout the house.

39) The inspector was unable to determine the output location for the sump pump's discharge pipe. Consult with the property owner or evaluate further to determine the location of the sump pump discharge pipe. Discharge pipes should terminate well away from foundations to soil sloping down and away so water doesn't accumulate around the foundation or in crawl spaces or basements. If it does terminate close to the foundation, recommend that a qualified person repair per standard building practices.
40) No battery backup system was found for the sump pump. If the power goes out during heavy rains, the sump pump won't be able to eliminate accumulated water. Consider installing a battery backup system for the sump pump.
Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 2005
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Manufacturer: Rheem
Model number: 82V52-2
Serial number: 1005253480
Location of water heater: Garage
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 130
41) The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD
Photo
Photo 41-1

42) The water heater was installed in an unheated space on a concrete floor and was not resting on an insulated pad. The bottom of the casing is likely to rust, and energy efficiency may be reduced. Recommend installing an insulated pad under the water heater.
Photo
Photo 42-1
Photo
Photo 42-2

43) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be near this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 1995
Forced air heating system manufacturer: Armstrong
Forced air furnace model #: GCK100D14-2A
Forced air furnace serial number: 8495K24854
Location of forced air furnace: Garage
Condition of furnace filters: Required replacement
Condition of forced air ducts and registers: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
Condition of cooling system and/or heat pump: Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Estimated age: 1995
Manufacturer: Armstrong
Heat pump or air conditioner model number: SCU10A36A-2B
Heat pump or air conditioner serial number: 8495F29993
24 hour automatic ventilation system present: No
44) The last service date of the gas forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
Photo
Photo 44-1
Photo
Photo 44-2
Photo
Photo 44-3

45) The thermostat was inoperable. Recommend that a qualified person evaluate and repair or replace as necessary.
46) The electrical supply for the furnace was routed inside the cabinet to close to the burners. the electrical junction box was loose from the main cabinet. Recommend the wire be re-routed further from the open flame of the burner.
Photo
Photo 46-1
Photo
Photo 46-2

47) Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.
Photo
Photo 47-1

48) Furnace filter needs replaced.
Photo
Photo 48-1
Photo
Photo 48-2

49) The furnace heating system was not fully evaluated because the electricity supply was off and/or safety or serviceman's switch was off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that the inspector does not operate shut-off valves, pilot lights or circuit breakers, or any controls other than normal controls (thermostat).
Photo
Photo 49-1

50) The heat pump or air conditioner condensing unit was not fully evaluated because the electricity supply was turned off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that the inspector does not operate or replace overcurrent protection devices, or operate any controls other than normal controls (thermostat).
Photo
Photo 50-1
Photo
Photo 50-2
Photo
Photo 50-3

51) The furnace had signs of rust inside the cabinet around the burners. Recommend the furnace be evaluated by a qualified HVAC contractor. Repair or replacement as needed.
Photo
Photo 51-1
Photo
Photo 51-2
Photo
Photo 51-3
Photo
Photo 51-4

52) The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry
53) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 53-1
Photo
Photo 53-2
Photo
Photo 53-3
Photo
Photo 53-4
Photo
Photo 53-5
Photo
Photo 53-6

54) One or more masonry chimney crowns were cracked. Crowns are meant to keep water off of the chimney structure and prevent damage from freeze-thaw cycles. Chimney crowns are commonly constructed by mounding concrete or mortar on the top chimney surface, however this is substandard. A properly constructed chimney crown should:Recommend that a qualified contractor repair or replace crowns as necessary, and per standard building practices.
Photo
Photo 54-1
Photo
Photo 54-2
Photo
Photo 54-3

55) Mortar at the brick chimney was deteriorated (e.g. loose, missing, cracked). As a result, water is likely to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary. For example, by repointing the mortar.
Photo
Photo 55-1
Photo
Photo 55-2
Photo
Photo 55-3
Photo
Photo 55-4

56) Significant amounts of ash or fire materials were present in one or more fireplace or wood stove fireboxes. As a result, the inspector was unable to fully view or evaluate the firebox(es) and/or components inside (e.g. firebrick, metal liner, log lighter). These components are excluded from this inspection.
Photo
Photo 56-1

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Refrigerator, Under-sink food disposal, Microwave oven
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Condition of hot water dispenser: N/A (none installed)
Condition of trash compactor: N/A (none installed)
Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Location #B: Full bath, Master bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
57) The clothes dryer's flexible exhaust duct was routed through a wall, building substructure or attic. This type of duct is easily damaged, prone to clogging and not suitable for this purpose. Clothes dryers may overheat. This is a potential fire hazard. It is acceptable for a short length of corrugated, semi-rigid metal duct (not accordion flex-duct) be used between the dryer and the wall or floor fitting, but duct runs through walls, building substructures and attics should be made of rigid metal, and wrapped in R-4 insulation if routed through an unheated space. Recommend that a qualified person replace ducting per standard building practices.
Photo
Photo 57-1

58) The jetting system for the bathtub was inoperable. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 58-1
Photo
Photo 58-2

59) Conducive conditions The clothes dryer exhaust duct terminated in the crawl space. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person install, repair or replace the duct as necessary so it terminates outdoors, and per standard building practices. For more information, visit:
http://www.reporthost.com/?DRYER
Photo
Photo 59-1
Photo
Photo 59-2

60) The master bath tub/shower. Water dripped from shower head when filling the tub. Recommend a qualified plumbing contractor repair or replace as needed.
Photo
Photo 60-1

61) Conducive conditions Gaps, no caulk, or substandard caulking were found between the bathtub and the floor at location(s) #A and B. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 61-1
Photo
Photo 61-2

62) Gaps, no caulk, or substandard caulking were found between countertops and backsplashes at location(s) #B. Water can penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing or replacing caulk.
Photo
Photo 62-1

63) The sink drain stopper mechanism at location(s) #B was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 63-1

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl, Multi-pane, Single-hung, Casement
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Laminate
64) Crank handles at some windows were loose and/or broken. Recommend that a qualified person replace handles or make repairs as necessary.
Photo
Photo 64-1
Photo
Photo 64-2

65) One or more interior doors were sticking in the door jamb and were difficult to operate. Recommend that a qualified person repair as necessary. For example, by trimming doors.
Photo
Photo 65-1

66) Dirt staining was noted above the fireplace on the brick in the family room. The trim at the ceiling level was not caulked and appeared to be open to the attic. Dust and dirt from the attic appear to have stained the brick. Recommend you clean and caulk this gap.
Photo
Photo 66-1

67) Carpeting in one or more areas was significantly stained or soiled. Recommend having carpeting professionally cleaned as necessary.
Photo
Photo 67-1

68) Patches or evidence of prior repairs were found in one or more walls or ceilings. Recommend asking the property owner about the repairs (e.g. why necessary, whether prior leaks have occurred).
Photo
Photo 68-1
Photo
Photo 68-2

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: Yes
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: Yes
Visible evidence of conditions conducive to wood-destroying organisms: Yes
Evidence of prior treatment of wood-destroying insects: None
Location #A: North wall under kitchen
69) Damage Because of apparent structural damage at location(s) #A, recommend that a qualified contractor evaluate and repair as necessary. All wood significantly damaged by wood-destroying insects or fungal rot should be replaced or removed.
Photo
Photo 69-1
Photo
Photo 69-2
Photo
Photo 69-3