Price Property Services LLC

Website: http://www.pricepropertyservice.com
Email: martinp935@gmail.com
Inspector's email: martinp935@gmail.com
Phone: (317) 714-4143
Inspector's phone: (317) 714-4143
3029 Marquette Ct 
Indianapolis IN 46268-1339
Inspector: Martin Price
Indiana State Licensed Home Inspector
# HI 01400029
Indiana State Wood Destroying Pest Inspector
#F257434

 

Property Inspection Report

Client(s):  Troy Bradford
Property address:  1215 Pumpkinvine Road
Martinsville, IN 46151
Inspection date:  Monday, July 20, 2015

This report published on Monday, July 20, 2015 8:20:40 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeInfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.)
Concern typeDamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage and Barn
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings


General Information
Return to table of contents

Report number: 20150720
Time started: 1200
Time finished: 1510
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Inspector: Martin Price
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Hot, 78
Ground condition: Damp
Recent weather: Rain
Overnight temperature: Warm, 75
Type of building: Single family, Detached garage, Shop
Buildings inspected: One house, One detached garage
Number of residential units inspected: 1
Age of main building: 1990
Source for main building age: Municipal records or property listing
Front of building faces: South
Main entrance faces: South
Occupied: Yes, Furniture or stored items were present

1) Microbial growths were found at one or more locations in the crawl space. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials are cleaned with a mildewcide, enclosed affected spaces are allowed to dry thoroughly, and only then is the area covered with a mold resistant paint to encapsulate the effective areas . For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit:
http://www.reporthost.com/?MOLDCDC
http://www.reporthost.com/?MOLDEPA
Photo
Photo 1-1
Photo
Photo 1-2
Photo
Photo 1-3
Photo
Photo 1-4

2) Many areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Photo
Photo 2-1
Photo
Photo 2-2

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of fences and gates: Appeared serviceable
Fence and gate material: Chain link
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete, Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Masonry

3) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary. By garage concrete
Photo
Photo 3-1

4) The gravel driveway was in poor condition. Recommend that a qualified person repair as necessary. For example, by filling holes, grading and spreading new gravel.
Photo
Photo 4-1
Photo
Photo 4-2

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Vinyl
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Concrete block
Footing material (under foundation stem wall): Poured in place concrete
Anchor bolts or hold downs for seismic reinforcement: Installed

5) Some sections of siding and/or trim were loose and/or damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
Photo
Photo 5-4
Photo
Photo 5-5
Photo
Photo 5-6
Photo
Photo 5-7

6) One or more exhaust duct end caps were damaged. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
Photo
Photo 6-1

7) The crawl space access door area was substandard. the walls of the area had collapsed in. Recommend either the metal retaining well be bolted to the foundation or the Block wall be rebuilt properly being mortared in place and sealed.
Photo
Photo 7-1
Photo
Photo 7-2

8) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 8-1

9) Conducive conditions The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.

10) Caulk along the chimney was substandard. A high quality caulk should be used to seal all openings along masonry to siding joints.
Photo
Photo 10-1

11) Many foundation walls below the house were obscured by insulation. The inspector was unable to evaluate these areas. They are excluded from this inspection.
Photo
Photo 11-1
Photo
Photo 11-2

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Building exterior
Crawl space access points that were opened and viewed, traversed or partially traversed: A
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Built-up wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Insulation material underneath floor above: None visible
Condition of vapor barrier: Appeared serviceable
Condition of crawl space ventilation: Required repairs, replacement and/or evaluation (see comments below)
Ventilation type: Unconditioned space

12) Conducive conditions One or more crawl space vents were blocked by Plants and debris. This restricts ventilation in the crawl space and can result in increased levels of moisture inside. This is a conducive condition for wood-destroying organisms. Materials or items blocking vents should be removed as necessary.
Photo
Photo 12-1
Photo
Photo 12-2
Photo
Photo 12-3

13) One or more exhaust ducts (e.g. bathroom fan, clothes dryer) in the crawl space were not insulated. This can result in moisture forming inside the duct or "sweating" on the outside of the duct depending on the surrounding air temperature and the exhaust air temperature. Recommend that a qualified person install insulation on exhaust ducts per standard building practices (typically R-4 rating), or replace uninsulated ducts with insulated ducts.

14) Conducive conditions One or more exhaust ducts (e.g. bathroom fan, clothes dryer) in the crawl space have come apart or were loose. This can result in increased moisture levels inside the structure and is a conducive condition for wood-destroying organisms. Recommend that a qualified person make permanent repairs as necessary.
Photo
Photo 14-1

15) No vapor barrier was installed in the crawl space. This is a conducive condition for wood-destroying organisms due to the likelihood of water evaporating from the soil below up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified contractor install a vapor barrier per standard building practices.
Photo
Photo 15-1
Photo
Photo 15-2
Photo
Photo 15-3
Photo
Photo 15-4

16) One or more crawl space vents were intentionally blocked (e.g. removable panels, rigid foam). This restricts ventilation in the crawl space and can result in increased levels of moisture inside. This is a conducive condition for wood-destroying organisms. Such vents should be left open at all times except during severe freezing weather. Recommend removing materials or items blocking vents as necessary.
Photo
Photo 16-1
Photo
Photo 16-2

17) A pipe was found by the inspector in the crawl space. The pipe exited the east side of the crawl space and appeared to be a drain pipe to assist draining the crawl space if it was to flood. The exit of this pipe was not found but appeared to go to the ravine east of the home.
Photo
Photo 17-1

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Partially traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full

18) The gutter above the front door had a nail that was pulling free from the roof. If snow an ice build up in the gutter and it is not properly fastened to the home. It could cause the gutter to separate more or fall off the home. Recommend the gutter be reattached to prevent failure.
Photo
Photo 18-1

19) Normally the inspector attempts to traverse roof surfaces during the inspection. However, due to roof configuration (steep or very high), the inspector was unable to traverse the roof and wasn't able to fully evaluate the entire roof surface.
Photo
Photo 19-1
Photo
Photo 19-2
Photo
Photo 19-3
Photo
Photo 19-4
Photo
Photo 19-5
Photo
Photo 19-6

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Location of attic access point #A: Bedroom
Location of attic access point #B: Bedroom
Location of attic access point #C: Bedroom closet
Attic access points that were opened and viewed, traversed or partially traversed: A, B, C
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): R-30
Vermiculite insulation present: None visible
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Box vents (roof jacks)

20) One or more attic access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC

21) What appeared to be past water stains were visible on the roof structure at one or more locations in the attic. However, no elevated levels of moisture were found at these stains during the inspection. The stains may have been caused by a past leak. Recommend asking the property owner about past leaks. Monitor these areas in the future, especially after heavy rains to determine if active leaks exist. If leaks are found, recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 21-1

Garage and Barn
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Detached
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): No
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Condition of detached garage or carport structure: Appeared serviceable
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame, Pole
Condition of roof structure: Required repair, replacement and/or evaluation (see comments below)
Roof inspection method: Traversed
Roof type: Gable
Roof surface material: Asphalt or fiberglass composition shingles

22) No photoelectric sensors were installed for one or more garage vehicle doors' automatic opener. These have been required on all automatic door openers since 1993 and improve safety by triggering the door's auto-reverse feature without need for the door to come in contact with the object, person or animal that is preventing the door from closing. Recommend that a qualified contractor install photoelectric sensors where missing for improved safety. For more information on garage door safety issues, visit:
http://www.reporthost.com/?GDPES
Photo
Photo 22-1

23) The auto-reverse mechanism on one or more automatic openers for garage vehicle doors was inoperable. This is a potential safety hazard. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.reporthost.com/?NRGD
Photo
Photo 23-1

24) Conducive conditions The roof surface was significantly deteriorated and appeared to be at or beyond its service life. It needs replacing now. This is a conducive condition for wood-destroying organisms. Consult with a qualified contractor to determine replacement options. Note that some structural repairs are often needed after old roof surfaces are removed and the structure becomes fully visible. Related roofing components such as flashings and vents should be replaced or installed as needed and per standard building practices.
Photo
Photo 24-1
Photo
Photo 24-2
Photo
Photo 24-3
Photo
Photo 24-4

25) Conducive conditions Some composition shingles were damaged. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 25-1

26) Some sections of siding and/or trim were damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 26-1
Photo
Photo 26-2
Photo
Photo 26-3

27) One or more roof trusses were cut, damaged or modified. The roof structure has likely been weakened as a result. Trusses are engineered components and shouldn't be cut or modified by builders or homeowners. Repairs may involve restoring the trusses to their original condition or configuration. Recommend that a licensed structural engineer evaluate and prescribe repairs as necessary. A qualified contractor should perform repairs per the engineer's specifications.
Photo
Photo 27-1
Photo
Photo 27-2

28) Wood rot was found on the walk door of the barn. Recommend the trim be replaced and maintained.
Photo
Photo 28-1
Photo
Photo 28-2

29) Weatherstripping at the sides of the garage vehicle doors was damaged. Recommend replacing or installing weatherstripping where necessary to prevent water and/or vermin intrusion.
Photo
Photo 29-1
Photo
Photo 29-2

30) The floor drain in the garage was missing a drain grate. Someone could trip and injure themselves in this hole. Recommend a proper sized and secured drain grate be installed in the hole.
Photo
Photo 30-1

31) Conducive conditions The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.

32) Barn
Photo
Photo 32-1

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil, Cold water supply pipes
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Mechanical room
Location of sub-panel #C: Garage
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: No, recommend install

33) One or more electric receptacles (outlets) at the garage had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 33-1
Photo
Photo 33-2

34) One or more circuit breakers in panel(s) #C were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
Photo
Photo 34-1
Photo
Photo 34-2

35) One or more receptacle boxes were missing clamps. This is a potential safety hazard for shock or fire. Recommend that a qualified electrician repair as necessary.
Photo
Photo 35-1

36) One or more receptacles (outlets) were broken or damaged. This is a potential shock or fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.
Photo
Photo 36-1
Photo
Photo 36-2

37) One or more electric receptacles (outlets) had reverse-polarity wiring, where the hot and neutral wires were reversed. This is a shock hazard. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?RPR
Photo
Photo 37-1
Kitchen far left of Range

38) Smoke alarms were missing from one or more bedrooms. Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM

39) One or more bushings were missing from where wires enter holes in panel(s) #C. This is a potential safety hazard because the wiring insulation can be cut or abraded on the metal edge of the hole(s). Recommend that a qualified electrician install bushings where missing.
Photo
Photo 39-1

40) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.reporthost.com/?SMKALRMLS
Photo
Photo 40-1

41) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.reporthost.com/?COALRM

42) A live electrical wire was found in the garage and was taped off on the end. It ran to a switch and then into the sub panel to a 220V circuit. Recommend you ask current owner about it's purpose and have it terminated at the breaker and removed by a licensed electrician.
Photo
Photo 42-1
Photo
Photo 42-2

43) The garage propane furnace was powered by a flexible cord plugged into an outlet on the workbench. Recommend this be hard wired in with a safety switch to disconnect for service. Work should be completed by a licensed electrician.
Photo
Photo 43-1

44) One or more energized conductors in panel(s) # A and C had white, gray or green insulation. Insulation on energized conductors should be black or red in color to identify them as energized wires. Recommend that a qualified electrician re-identify wires per standard building practices. For example, by wrapping in black vinyl tape or marking with a black permanent marker.
Photo
Photo 44-1
Photo
Photo 44-2

45) One or more screws that attach the cover or dead front to panel(s) #A were missing or not installed. Recommend installing screws where missing so the cover or dead front is secure. Only screws with blunt tips approved for this purpose should be installed, so wiring inside the panel is not damaged. Because energized wires may be located directly behind screw holes, the client should consider having a qualified electrician replace missing screws.
Photo
Photo 45-1
Photo
Photo 45-2

46) Main Electrical Panel.
Photo
Photo 46-1
Photo
Photo 46-2

47) Garage sub-panel
Photo
Photo 47-1
Photo
Photo 47-2

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water meter: Not determined (obscured, inaccessible or none found)
Location of main water shut-off: In mechanical room, Crawl space
Service pipe material: Plastic
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Location(s) of plumbing clean-outs: Building exterior
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Sewage ejector pump installed: No
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground, propane tank
Location of main fuel shut-off valve: At propane tank

48) Conducive conditions Excess moisture was found in the crawlspace by the pipe coming from the kitchen drain. The band joist was wet. Further evaluation by a plumber is needed to locate the source of the moisture.
Photo
Photo 48-1
Photo
Photo 48-2

49) One or more drain pipes had a substandard slope. Clogging or leaks can occur as a result. Drain and waste pipes should be sloped 1/4 inch per foot of length if less than 3 inches in diameter, or 1/8 inch per foot of length for larger diameters. Recommend that a qualified plumber repair per standard building practices.
Photo
Photo 49-1
Kitchen sink drain in crawl space both directions sloped to clean-out.

50) The propane tank was unstable. It may tip or fall. Propane tanks should rest on sound and firm footing (not dirt or wood), and have additional support depending on local ordinances. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 50-1
Photo
Photo 50-2

51) The Hose bib located on the rear of the home was loose and pulled out when turning on and off. Recommend the pipe be secured inside the crawlspace as well as the exterior part of the hose bib be secured.
Photo
Photo 51-1

52) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC
Photo
Photo 52-1
Photo
Photo 52-2

53) The inspector did not determine the location of the water meter. Recommend consulting with the property owner to determine the meter location, that you locate it yourself, or consult with the local water municipality if necessary. It is especially important to find the meter if no main shut-off valve is found because the meter may be the only way to turn off the water supply in the event of an emergency, such as when a supply pipe bursts.

54) Main water shutoff was located in the crawlspace and a second one located in the mechanical room.
Photo
Photo 54-1

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 2010
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Manufacturer: Whirlpool
Model number: EE2H50RDO45V
Serial number: 1042T408995
Location of water heater: Mechanical room
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 110
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable

55) The temperature-pressure relief valve drain line terminated in a location that's not routinely accessed (e.g. crawl space). These valves often leak over time. If this valve leaks, significant amounts of water can accumulate where the drain line terminates. Recommend that a qualified plumber repair per standard building practices, and so the drain line terminates outside or in a readily accessible location. For more information, visit:
http://www.reporthost.com/?TPRVALVE
Photo
Photo 55-1
Photo
Photo 55-2

56) The water heater is an electric water heater and had a Energy smart control on it. It is beyond the scope of an inspection to test this type of device. You should ask the current owner for documentation on this unit or research it online to find out more information on it.
Photo
Photo 56-1
Photo
Photo 56-2
Photo
Photo 56-3
Photo
Photo 56-4

57) A water heater was installed in or over a finished living space or in an area where leaking can cause damage, and no catch pan or drain was installed. Catch pans and drains prevent water damage to finished interior spaces below if or when the water heater leaks or is drained. If concerned, consult with a qualified contractor about installing these. Note that drain lines for catch pans are usually installed below the floor level and are difficult at best to install in an existing home.
Photo
Photo 57-1

58) Hot water temperature
Photo
Photo 58-1

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Propane
Estimated age of forced air furnace: 2012
Forced air heating system manufacturer: Goodman
Forced air furnace model #: GCH950703BXAC
Forced air furnace serial number: 1204578390
Location of forced air furnace: Mechanical room
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At top of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Required repair, replacement and/or evaluation (see comments below)
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Type of combustion air supply: Vented door
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Estimated age: 2012
Manufacturer: Goodman
Heat pump or air conditioner model number: GSX130241DA
Heat pump or air conditioner serial number: 1204541221
Condition of controls: Appeared serviceable

59) Significant amounts of debris, dirt and/or dust were visible in one or more sections of supply and/or return air ducts for the heating or cooling system. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers." At a minimum, the visible debris should be thoroughly cleaned. Recommend that a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit:
http://www.reporthost.com/?DUCTCLEAN
Photo
Photo 59-1

60) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
Photo
Photo 60-1
Photo
Photo 60-2
Photo
Photo 60-3
Photo
Photo 60-4
Photo
Photo 60-5
Photo
Photo 60-6

61) The furnace did not respond to normal controls (thermostat). It appeared to be inoperable. The inspector was only able to perform a limited evaluation. If possible, consult with the property owner and/or review documentation on this system. Recommend that a qualified HVAC contractor evaluate and repair as necessary.
Photo
Photo 61-1
Photo
Photo 61-2

62) One or more heating or cooling ducts have come apart, or had significant gaps at junctions. This can result in reduced energy efficiency and increased moisture in surrounding spaces. Recommend that a qualified HVAC contractor make permanent repairs as necessary. For example, by securely supporting ducts and installing approved tape or mastic at seams.
Photo
Photo 62-1
Photo
Photo 62-2

63) One or more heating or cooling ducts in an unconditioned space (e.g. crawl space, attic or basement) were not insulated, or the insulation was damaged or deteriorated. This can result in reduced energy efficiency, moisture inside heating ducts, and/or "sweating" on cooling ducts. Recommend that a qualified person repair per standard building practices. For example, by wrapping ducts in insulation with an R-value of R-8.
Photo
Photo 63-1
Photo
Photo 63-2
Photo
Photo 63-3

64) Some heating or cooling ducts had significant amounts of corrosion or rust. Holes may develop and result in reduced energy efficiency or return air being drawn in from locations other than intended. Recommend that a qualified HVAC contractor repair as necessary. For example, by replacing ducts or sections of ducts.
Photo
Photo 64-1
Photo
Photo 64-2

65) Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.
Photo
Photo 65-1

66) The garage propane heater gas was turned off. It is beyond the scope of this inspection to turn on valves and light pilot lights. Recommend a qualified HVAC contractor turn on unit and service before heating season.
Photo
Photo 66-1
Photo
Photo 66-2

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Metal
Wood-burning stove type: Insert
Fan or blower installed in wood-burning fireplace or stove: Yes
Condition of chimneys and flues: Required repair, replacement and/or evaluation (see comments below)
Wood-burning chimney type: Masonry, with metal liner
Gas-fired flue type: Masonry with metal liner

67) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 67-1
Photo
Photo 67-2
Photo
Photo 67-3
Photo
Photo 67-4
Photo
Photo 67-5

68) The blower for the wood stove insert made excessive noise. The inspector did not determine why. Recommend that the client consult with the property owner and review documentation for such devices. If necessary, a qualified specialist should evaluate and repair.
Photo
Photo 68-1

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Permanently installed kitchen appliances present during inspection: Range, Dishwasher, Refrigerator, Microwave oven
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
Condition of hot water dispenser: N/A (none installed)
Condition of trash compactor: N/A (none installed)

69) The refrigerator had minor rust spots on the doors.
Photo
Photo 69-1

70) The microwave hood lights did not activate when switched on. This may be to a burnt out bulb. Recommend you replace bulbs and if they still do not function to have a qualified appliance repair person evaluate.
Photo
Photo 70-1

71) An exhaust hood was installed over the cook top or range, but the fan recirculated the exhaust air back into the kitchen. This may be due to no duct being installed, baffles at the front of the hood not being installed, or a problem with the duct. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. Recommend that a qualified contractor evaluate and repair as necessary so exhaust air is ducted outdoors.
Photo
Photo 71-1

72) Kitchen photos
Photo
Photo 72-1
Photo
Photo 72-2
Photo
Photo 72-3
Photo
Photo 72-4
Photo
Photo 72-5
Photo
Photo 72-6
Photo
Photo 72-7
Photo
Photo 72-8

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Full bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

73) The clothes dryer's flexible exhaust duct was routed through a wall, building substructure or attic. This type of duct is easily damaged, prone to clogging and not suitable for this purpose. Clothes dryers may overheat. This is a potential fire hazard. It is acceptable for a short length of corrugated, semi-rigid metal duct (not accordion flex-duct) be used between the dryer and the wall or floor fitting, but duct runs through walls, building substructures and attics should be made of rigid metal, and wrapped in R-4 insulation if routed through an unheated space. Recommend that a qualified person replace ducting per standard building practices.
Photo
Photo 73-1

74) Conducive conditions The clothes dryer exhaust duct terminated in the crawl space. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person install, repair or replace the duct as necessary so it terminates outdoors, and per standard building practices. For more information, visit:
http://www.reporthost.com/?DRYER
Photo
Photo 74-1

75) The bathtub drain stopper mechanism at location(s) #A and B was missing. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 75-1
Photo
Photo 75-2

76) The clothes dryer exhaust duct was routed through an unheated space (e.g. crawl space, basement, attic) and was not insulated. Condensation can accumulate inside the duct. In extreme cases ducts can be blocked by pooled water. Recommend that a qualified person permanently install R-4 insulation around the duct per standard building practices.

77) Gaps, no caulk, or substandard caulking were found between countertops and backsplashes / around the sink on the second floor. Water can penetrate these areas and cause damage. Recommend that a qualified person repair as necessary. For example, by installing or replacing caulk.
Photo
Photo 77-1

78) No access or only limited access was available to the back of the clothes washer and dryer, and to utility hook-ups located behind the appliances. The inspector normally attempts to determine the presence of a gas vs. electric power supply, the configuration of the stand pipe, whether the dryer exhaust duct is serviceable, etc. Because of the lack of access, the inspector was unable to fully evaluate and/or describe the hook-ups and appliances.
Photo
Photo 78-1
Photo
Photo 78-2

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Wood, Double-hung
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products, Laminate, Tile
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)

79) Handrails at one or more flights of stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.
Photo
Photo 79-1
Photo
Photo 79-2

80) One or more handrails had no "returns" installed, where ends of handrails turn and connect to adjacent walls so objects or clothing will not catch on the open ends. This is a safety hazard. Recommend that a qualified person install returns per standard building practices.
Photo
Photo 80-1
Photo
Photo 80-2

81) One or more interior doors were missing. Recommend that a qualified person replace or repair doors as necessary.
Photo
Photo 81-1
Second floor closet to right of stairs

82) Floor guides were missing at one or more sliding closet doors.
Photo
Photo 82-1

83) Several window screens were damaged. Recommend these be repaired or replaced.
Photo
Photo 83-1
Photo
Photo 83-2

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: Yes
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: Yes
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: Yes
Evidence of prior treatment of wood-destroying insects: None
Location #A: South West corner of crawlspace - bandboard

84) Damage Because of apparent structural damage at location(s) #A, recommend that a qualified contractor evaluate and repair as necessary. All wood significantly damaged by wood-destroying insects or fungal rot should be replaced or removed.

85) Infestation Evidence of past infestation of subterranean termites was found at location(s) #A in the form of frass and/or galleries or holes in wood with visible wood damage. Recommend the following:
  • Correct any conducive conditions for wood-destroying organisms mentioned in this report.
  • Consult with the property owner about any history of infestation.
  • Have a state-licensed pest control operator evaluate further and treat as necessary.
Photo
Photo 85-1
Photo
Photo 85-2
Photo
Photo 85-3
Photo
Photo 85-4
Photo
Photo 85-5
Photo
Photo 85-6
Photo
Photo 85-7
Photo
Photo 85-8

Your default report footer here...